The vendor must provide supporting Procedure Qualification Records (PQRs) for several Welding Procedure Specifications (WPS). Several PQRs are missing required test results or have test coupon thicknesses that do not support the thickness ranges in the corresponding WPS. Additional corrections are needed for F numbers, bend tests, thickness ranges, and base metal thicknesses in some WPS and PQRs. Finally, no WPS are available to cover several welds, and some WPS are missing inspection company representative stamps.
The vendor must provide supporting Procedure Qualification Records (PQRs) for several Welding Procedure Specifications (WPS). Several PQRs are missing required test results or have test coupon thicknesses that do not support the thickness ranges in the corresponding WPS. Additional corrections are needed for F numbers, bend tests, thickness ranges, and base metal thicknesses in some WPS and PQRs. Finally, no WPS are available to cover several welds, and some WPS are missing inspection company representative stamps.
The vendor must provide supporting Procedure Qualification Records (PQRs) for several Welding Procedure Specifications (WPS). Several PQRs are missing required test results or have test coupon thicknesses that do not support the thickness ranges in the corresponding WPS. Additional corrections are needed for F numbers, bend tests, thickness ranges, and base metal thicknesses in some WPS and PQRs. Finally, no WPS are available to cover several welds, and some WPS are missing inspection company representative stamps.
Vendor must provide supporting PQRs for the following WPS;
o 03B-2021, 03-2021, 03FW-2021
o 05-2021 o 06-2021 o 07-2021 o 08-2021 F Number for E 16.8.2-15 is 5 as per AMSE Section IX (QW-432). Correction needed in following documents: o PQR no. 04-2020 o WPS no 04-2020, 4B-2020 and 4FW-2020. As per ASME section IX (QW-451.1), 04 side bend tests are required for PQR no. 04- 2020. Tensile and Bend test results are missing in the PQR no. 02-2021 and PQR no. 03-2021. Test coupon thickness of PQR no. 04-2021 (i.e. 13mm) doesn’t support the thickness range to be qualified in the following WPS. o 04B-2021, 04-2021, 04FW-2021 (i.e. 1,5÷17,12 mm) Supporting PQRs for the WPS nos. 04B-2020, 04FW-2020 are 04-2020 (04-2021) Max weld deposit thickness (2+38.88 mm max.) as per WPS no 04-2020 and WPS no 04B-2020 is not in concurrence with Thickness Range qualified (42.88mm max.). WPS no. 06-2021 must be qualified for the base metal thickness of 11.13mm (10.97mm) WPS no. 07-2021 must be qualified for the base metal thickness of 6.02mm & 11.13mm (13mm) No WPS is available to cover the welds W-438, W-439, W-444, W-445, W-447, W-448, W-453, W-454, W-457, W-456, W-464, W-465, W-467, W-468, W-473, W-474 Inspection company representative stamp is missing on few WPS.