Professional Documents
Culture Documents
0004 - GCAT2019 - Cross Connected Source Based Reduced Switch Count Multilevel Inverter Topology With Fault Tolerance
0004 - GCAT2019 - Cross Connected Source Based Reduced Switch Count Multilevel Inverter Topology With Fault Tolerance
net/publication/339023847
CITATIONS READS
0 41
3 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by S Nagaraja Rao on 26 April 2020.
Abstract— Abstract—In this paper, topology of a Cross switching for identical voltage levels [5, 6]. These states are
Connected Source based Reduced Switch Count (CCS-RSC) termed as ‘redundant states’. The availability of redundant
Multilevel Inverter (MLI) has been analyzed with fault states is apparently due to large number of power switches.
tolerance for a 7-level fed ‘R’ load. The proposed CCS-RSC There is a decrease in the redundant states as the number of
MLI generates higher voltage levels with optimum number of
power switches. The configuration results in an improved
power switches are reduced in RSC MLIs. Hence, RSC
power quality by due to reduction in the harmonic content, MLIs are restricted with respect to FT operation. This paper
compared to traditional Multilevel Inverters (MLIs). The CCS- presents an approach to deal with FT capability of RSC-
RSC MLI requires only ‘m+1’ power switches for ‘m’ levels, MLIs by reconfiguring the switching tables for a single
whereas the traditional MLIs require ‘(2m-1)’ switches. power switch under open circuit [7, 8].
Therefore, CCS-RSC inverter requires only eight power Off late, multilevel DC link inverter topologies are
switches and three DC sources to generate 7-levels in the proposed to decrease the number of power switches in
output voltage. The redundant switch combinations get limited comparison to traditional MLIs. However these topologies
due to the decrease in power switches. Consequently, the require more power switches to increase the levels in the
possibility of fault tolerant capability gets effected for a few
particular faulty switches. The proposed inverter is analyzed
output voltage. In the present work CCS-RSC MLI topology
by reconfiguring the switching tables for fault tolerant is suggested with reduced number of power switches. Also,
procedure for an open circuited single switch. Also, the FT analysis has been done by reconfiguring the switching
proposed inverter with sine wave reference and inverted sine combinations with faulty power switches. The proposed
carrier modulation strategy has a lower %Voltage THD CCS-RSC MLI topology can be effectively adopted with a
compared to traditional MLI. The effective performance of the sine wave reference and inverted sine carrier modulation
suggested topology for a 7-level single-phase CCS-RSC strategy [9, 10]. This control scheme results in higher output
inverter with fault tolerance is validated with voltage with less THD. In addition, the modulation index for
MATLAB/SIMULINK for open circuit fault on each of the the proposed topology can be modified to maintain good
power switches.
power quality when fault occurs on power switches [11, 12].
Keywords— CCS-RSC MLI, PWM, Fault tolerant, THD The principle of CCS-RSC MLI is characterized in
Section II. Section III deals with the reconfiguration of
I. INTRODUCTION switching tables under fault conditions. Pulse generation
methodology for the proposed 7-level CCS-RSC MLI is
Multilevel Inverters (MLIs) use controlled power
discussed in Section IV. Section V deals with the simulation
switches along with several DC voltage levels by
results for CCS-RSC MLI topology with ‘R’ load. The CCS-
synthesizing a stepped voltage waveform to maintain good
RSC MLI topology is compared with traditional MLI in
power quality in conversion from DC to AC [1]. In addition,
Section VI.
MLIs are techno-economically viable for both high and
medium power applications. Circuit setup for a given MLI II. CROSS CONNECTED SOURCE BASED REDUCED SWITCH
[2] that characterizes the mode of interconnection between COUNT MULTILEVEL INVERTER
single/multiple sources, active/passive components and the
The circuit configuration of a 7-level single phase, CCS-
load is defines the “topology.” Over the years both industry
RSC MLI topology for single-phase is shown in Fig.1. The
and academia have evinced interest in“traditional topologies” topology consists of ‘8’ IGBT power switches and ‘3’
(i.e., diode clamped, capacitor clamped and cascaded H- symmetrical DC sources/batteries with a resistive load. The
bridge MLI topologies. The increased number of power circuit produces ‘7’ voltage levels (i.e., -3Vdc, -2Vdc, -Vdc, 0,
switches has been referred as one of the most significant +Vdc, +2Vdc, and +3Vdc,) across the load. The ‘8’ IGBTs are
limitations of traditional MLIs. Off late this limitation has grouped in two legs, with ‘4’ IGBTs in each leg. The
been overcome, in various Reduced Switch Count (RSC) possible switching states/combinations is given by (1).
MLI topologies [3, 4]. These RSC MLI topologies have
reduced gate driver circuits, heat sinks, protection circuits, Ns = 2N (1)
control complexity, cost and area. Where, Ns is the number of possible switching states,
MLIs offer significant improvement in Fault Tolerant
N is the number of IGBTs in each leg.
(FT) procedure due to accessibility of several states of
Switching Output
S. No. Combinations/ Voltage (Vo)
Functions
1 S1, S21, S3, S41 +3Vdc
2 S1, S21, S3, S4 +2Vdc
Switching Output Fault on power switch S1: The switching states of the CCS-
State Voltage
Combinations/ RSC MLI under normal or healthy mode of operation are
Number (Vo)
Functions shown in Table II. If fault occurs on the power switch S1, the
1 S1, S2, S3, S4 switching combinations given in Table II cannot be used as
0 voltage levels +3Vdc, +2Vdc and +Vdc cannot be generated.
2 S11, S21, S31, S41 Alternate redundant paths from Table I can be selected to
generate the required voltage levels. However, +3Vdc voltage
3 S1, S21, S31, S41 level cannot be generated since there is no redundant path for
+3Vdc. Thus, the proposed CCS-RSC MLI generates an
4 S11, S21, S3, S4 +Vdc asymmetrical output waveform across the load due to
difference in the number of levels in the positive (two) and
5 S1, S2, S3, S41 negative half cycles (three) along with a zero level. A
symmetrical waveform can be obtained by modifying
6 S1, S21, S3, S4 Modulation Index (MI) to a value between >0.33 and ≤0.633
+2Vdc
7 S11, S21, S3, S41 for the power switch S1 under fault. Therefore, switching
combinations given in Table III can be followed for power
8 S1, S21, S3, S41 +3Vdc switch S1 under fault.
2
TABLE III. SWITCHING STATES FOR CCS-RSC MLI BY SELECTING compared with the sine wave reference (i.e., Vref) at a
REDUNDANT STATES WITH POWER SWITCH S1 UNDER FAULT
CONDITION fundamental frequency of 50Hz. The proposed control
scheme is divided into three phases to generate switching
Switching Output pulses [13, 14].
State Voltage
Combinations/
Number (Vo) Phase 1: Appropriate selection of reference and carrier
Functions
signals allows the control scheme proposed to adopt any
1 S11, S21, S3, S41 +2Vdc
modulation strategy. The carrier arrangement with reference
2 S11, S21, S3, S4 +Vdc signal is shown in Fig. 3. In this phase, at every instant, a
comparison is made between all the inverted carriers and the
3 S11, S21, S31, S41 0 sine wave reference. Resultant signals based on (3) and (4)
4 S11, S2, S3, S4 - Vdc are generated. (3) and (4).
3
Fig. 4. Schematic diagram of proposed control scheme for CCS-RSC MLI topology
V. SIMULATION RESULTS
CCS-RSC MLI topology for a single-phase 7-level fed
resistive load under normal operation and open circuit FT
conditions is simulated using MATLAB for the parameters
chosen listed in Table V.
Simulation results are presented for CCS-RSC MLI
topology with sine wave reference and inverted sine carrier
modulation control.
Parameter Value
Fig. 6. %Voltage THD of CCS-RSC MLI topology under normal operation
Voltage (Vdc1= Vdc2 = Vdc3) 76.66V
The output voltage and the corresponding %Voltage THD
Switching frequency 5kHz during normal operation using switching combinations
listed in Table II are shown Fig.5 and Fig.6 respectively.
Resistive load 10 Ω
From Fig. 5, it can be seen that the voltage levels obtained
Modulation index 0 to 1 during normal operation and %Voltage THD found to be
21.02% for the fundamental value of 226.8V.
A. Under normal operating conditions
4
Fig. 11. Output voltage of CCS-RSC MLI topology under fault on power
switch S1 using redundant paths
Fig. 13. Output voltage of CCS-RSC MLI topology under fault on power
switch S1 with modified MI
Fig. 10. %Voltage THD of CCS-RSC MLI topology with fault on power
switch S1
5
Fig. 13 and Fig. 14 shows the output voltage and %THD
with fault on power switch S1 after updating MI. The
voltage waveform is symmetrical with %Voltage THD of
34.62%. Hence %Voltage THD value can be reduced
drastically by maintaining symmetrical voltage with
modified MI.
C. Fault on power switch S2
The simulation results of CCS-RSC MLI with fault on
power switch S2 has been analyzed by reconfiguring
switching combinations.
Fig. 18. %Voltage THD of CCS-RSC MLI topology with fault on power
switch S2 using redundant paths
Fig. 15. Output voltage of CCS-RSC MLI topology under fault on power
switch S2
Fig. 19. Output voltage of CCS-RSC MLI topology under fault on power
switch S2 with modified MI
6
a symmetrical waveform. Also, it can be noticed that the by reconfiguring switch combinations and modified
%THD decreases with increase in number of levels. modulation index.