Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/339023847

Cross Connected Source based Reduced Switch Count Multilevel Inverter


Topology with Fault Tolerance

Conference Paper · October 2019


DOI: 10.1109/GCAT47503.2019.8978379

CITATIONS READS

0 41

3 authors, including:

S Nagaraja Rao Pranupa . S


M. S. Ramaiah University of Applied Sciences M. S. Ramaiah University of Applied Sciences
28 PUBLICATIONS   123 CITATIONS    6 PUBLICATIONS   1 CITATION   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Power Electronics View project

All content following this page was uploaded by S Nagaraja Rao on 26 April 2020.

The user has requested enhancement of the downloaded file.


2019 Global Conference for Advancement in Technology (GCAT)
Bangalore, India. Oct 18-20, 2019

Cross Connected Source based Reduced Switch


Count Multilevel Inverter Topology with Fault
Tolerance
Nagaraja Rao Sulake Pranupa S. Indira M.S.
Assistant Professor Assistant Professor Professor
Department of Electrical Engineering, Department of Electrical Engineering, Department of Electrical Engineering,
Ramaiah University of Applied Sciences, Ramaiah University of Applied Sciences, Ramaiah University of Applied Sciences,
Bangalore, India Bangalore, India Bangalore, India
nagarajarao.ee.et@msruas.ac.in pranupa.ee.et@msruas.ac.in indira.ee.et@msruas.ac.in

Abstract— Abstract—In this paper, topology of a Cross switching for identical voltage levels [5, 6]. These states are
Connected Source based Reduced Switch Count (CCS-RSC) termed as ‘redundant states’. The availability of redundant
Multilevel Inverter (MLI) has been analyzed with fault states is apparently due to large number of power switches.
tolerance for a 7-level fed ‘R’ load. The proposed CCS-RSC There is a decrease in the redundant states as the number of
MLI generates higher voltage levels with optimum number of
power switches. The configuration results in an improved
power switches are reduced in RSC MLIs. Hence, RSC
power quality by due to reduction in the harmonic content, MLIs are restricted with respect to FT operation. This paper
compared to traditional Multilevel Inverters (MLIs). The CCS- presents an approach to deal with FT capability of RSC-
RSC MLI requires only ‘m+1’ power switches for ‘m’ levels, MLIs by reconfiguring the switching tables for a single
whereas the traditional MLIs require ‘(2m-1)’ switches. power switch under open circuit [7, 8].
Therefore, CCS-RSC inverter requires only eight power Off late, multilevel DC link inverter topologies are
switches and three DC sources to generate 7-levels in the proposed to decrease the number of power switches in
output voltage. The redundant switch combinations get limited comparison to traditional MLIs. However these topologies
due to the decrease in power switches. Consequently, the require more power switches to increase the levels in the
possibility of fault tolerant capability gets effected for a few
particular faulty switches. The proposed inverter is analyzed
output voltage. In the present work CCS-RSC MLI topology
by reconfiguring the switching tables for fault tolerant is suggested with reduced number of power switches. Also,
procedure for an open circuited single switch. Also, the FT analysis has been done by reconfiguring the switching
proposed inverter with sine wave reference and inverted sine combinations with faulty power switches. The proposed
carrier modulation strategy has a lower %Voltage THD CCS-RSC MLI topology can be effectively adopted with a
compared to traditional MLI. The effective performance of the sine wave reference and inverted sine carrier modulation
suggested topology for a 7-level single-phase CCS-RSC strategy [9, 10]. This control scheme results in higher output
inverter with fault tolerance is validated with voltage with less THD. In addition, the modulation index for
MATLAB/SIMULINK for open circuit fault on each of the the proposed topology can be modified to maintain good
power switches.
power quality when fault occurs on power switches [11, 12].
Keywords— CCS-RSC MLI, PWM, Fault tolerant, THD The principle of CCS-RSC MLI is characterized in
Section II. Section III deals with the reconfiguration of
I. INTRODUCTION switching tables under fault conditions. Pulse generation
methodology for the proposed 7-level CCS-RSC MLI is
Multilevel Inverters (MLIs) use controlled power
discussed in Section IV. Section V deals with the simulation
switches along with several DC voltage levels by
results for CCS-RSC MLI topology with ‘R’ load. The CCS-
synthesizing a stepped voltage waveform to maintain good
RSC MLI topology is compared with traditional MLI in
power quality in conversion from DC to AC [1]. In addition,
Section VI.
MLIs are techno-economically viable for both high and
medium power applications. Circuit setup for a given MLI II. CROSS CONNECTED SOURCE BASED REDUCED SWITCH
[2] that characterizes the mode of interconnection between COUNT MULTILEVEL INVERTER
single/multiple sources, active/passive components and the
The circuit configuration of a 7-level single phase, CCS-
load is defines the “topology.” Over the years both industry
RSC MLI topology for single-phase is shown in Fig.1. The
and academia have evinced interest in“traditional topologies” topology consists of ‘8’ IGBT power switches and ‘3’
(i.e., diode clamped, capacitor clamped and cascaded H- symmetrical DC sources/batteries with a resistive load. The
bridge MLI topologies. The increased number of power circuit produces ‘7’ voltage levels (i.e., -3Vdc, -2Vdc, -Vdc, 0,
switches has been referred as one of the most significant +Vdc, +2Vdc, and +3Vdc,) across the load. The ‘8’ IGBTs are
limitations of traditional MLIs. Off late this limitation has grouped in two legs, with ‘4’ IGBTs in each leg. The
been overcome, in various Reduced Switch Count (RSC) possible switching states/combinations is given by (1).
MLI topologies [3, 4]. These RSC MLI topologies have
reduced gate driver circuits, heat sinks, protection circuits, Ns = 2N (1)
control complexity, cost and area. Where, Ns is the number of possible switching states,
MLIs offer significant improvement in Fault Tolerant
N is the number of IGBTs in each leg.
(FT) procedure due to accessibility of several states of

978-1-7281-3694-3/19/$31.00 ©2019 IEEE 1


9 S11, S2, S3, S4
10 S1, S2, S31, S41 - Vdc
11 S11, S21, S31, S4
12 S11, S2, S31, S41
- 2Vdc
13 S1, S2, S31, S4
14 S11, S2, S31, S4 - 3Vdc
15 S1, S21, S31, S4
0
16 S11, S2, S3, S41

TABLE II. SWITCHING COMBINATIONS FOR CCS-RSC MLI BY


EXCLUDING REDUNDANT STATES UNDER NORMAL/HEALTHY
CONDITION

Switching Output
S. No. Combinations/ Voltage (Vo)
Functions
1 S1, S21, S3, S41 +3Vdc
2 S1, S21, S3, S4 +2Vdc

3 S1, S21, S31, S41 +Vdc

Fig. 1. Single-phase 7-level CCS-RSC MLI topology


4 S11, S21, S31, S41 0

The 16 possible switching states/combinations in a 5 S11, S2, S3, S4 - Vdc


single-phase 7-level CCS-RSC MLI with redundant states
are given in Table I. It can be observed that there are both 6 6 S11, S2, S31, S41 - 2Vdc
positive, and negative with 4 zero output voltage levels,
7 S11, S2, S31, S4 - 3Vdc
indicated by the states 1, 2, 15 and 16. Zero voltage can be
achieved by short circuiting the main switches or
complementary switches or in combination through DC
sources. The total output voltage ‘Vo’ of CCS-RSC MLI in III. RECONFIGURATION OF SWITCHING TABLES FOR CCS-
terms of DC sources/batteries and power switches under RSC MLI UNDER FAULTY CONDITIONS
normal/healthy condition is given by (2). The switching
The proposed CCS-RSC MLI topology is analyzed under
states excluding redundant states are given in Table II.
open circuit, as these are most predominant faults in
semiconductor based power switches. During a fault on any
Vo = (S1 – S2) Vdc1 + (S3 – S2) Vdc2 + (S3 – S4) Vdc3 (2)
power switch, it is bypassed to obtain a symmetrical output
TABLE I. VALID SWITCHING STATES FOR CCS-RSC MLI voltage wave to maintain good power quality [6, 7].

Switching Output Fault on power switch S1: The switching states of the CCS-
State Voltage
Combinations/ RSC MLI under normal or healthy mode of operation are
Number (Vo)
Functions shown in Table II. If fault occurs on the power switch S1, the
1 S1, S2, S3, S4 switching combinations given in Table II cannot be used as
0 voltage levels +3Vdc, +2Vdc and +Vdc cannot be generated.
2 S11, S21, S31, S41 Alternate redundant paths from Table I can be selected to
generate the required voltage levels. However, +3Vdc voltage
3 S1, S21, S31, S41 level cannot be generated since there is no redundant path for
+3Vdc. Thus, the proposed CCS-RSC MLI generates an
4 S11, S21, S3, S4 +Vdc asymmetrical output waveform across the load due to
difference in the number of levels in the positive (two) and
5 S1, S2, S3, S41 negative half cycles (three) along with a zero level. A
symmetrical waveform can be obtained by modifying
6 S1, S21, S3, S4 Modulation Index (MI) to a value between >0.33 and ≤0.633
+2Vdc
7 S11, S21, S3, S41 for the power switch S1 under fault. Therefore, switching
combinations given in Table III can be followed for power
8 S1, S21, S3, S41 +3Vdc switch S1 under fault.

2
TABLE III. SWITCHING STATES FOR CCS-RSC MLI BY SELECTING compared with the sine wave reference (i.e., Vref) at a
REDUNDANT STATES WITH POWER SWITCH S1 UNDER FAULT
CONDITION fundamental frequency of 50Hz. The proposed control
scheme is divided into three phases to generate switching
Switching Output pulses [13, 14].
State Voltage
Combinations/
Number (Vo) Phase 1: Appropriate selection of reference and carrier
Functions
signals allows the control scheme proposed to adopt any
1 S11, S21, S3, S41 +2Vdc
modulation strategy. The carrier arrangement with reference
2 S11, S21, S3, S4 +Vdc signal is shown in Fig. 3. In this phase, at every instant, a
comparison is made between all the inverted carriers and the
3 S11, S21, S31, S41 0 sine wave reference. Resultant signals based on (3) and (4)
4 S11, S2, S3, S4 - Vdc are generated. (3) and (4).

5 S11, S2, S31, S41 - 2Vdc (3)


= 0, otherwise
Fault on power switch S2: Similarly, when the fault occurs
on switch S2, the levels -3Vdc, -2Vdc and -Vdc cannot be (4)
generated. Therefore alternate redundant paths from Table I = -1, otherwise
can be selected to generate required voltage levels. However,
-3Vdc and -2Vdc voltage levels cannot be generated as there Phase 2: In the second phase, the waveform obtained using
are no redundant paths available. Thus the proposed MLI (3) and (4) are added to synthesize a signal known Vexp (t)
generates an asymmetrical output waveform across the load given by (5). The output Vexp (t) is shown in Fig.3.
due to difference in the number of levels in the positive
(three) and negative half cycles (one) along with a zero level. (5)
A symmetrical waveform can be obtained by modifying MI
to a value between >0 and ≤0.333 for power switch S2 under It is observed that Vexp (t) has the wave shape as expected
fault. Therefore, switching combinations given in Table IV across the load.
can be followed with power switch S2 under fault.
Furthermore, reconfigured switching states are listed in Phase 3: Switching table can be formed based on the MLI
Table IV with power switches S3, S4, S11, S21, S31 and S41 topology. The proposed control method is valid to for all
under fault conditions to generate required output voltage topologies of MLI. Furthermore, based on Vexp (t) and the
levels using redundant paths. switching table, the MLI can be operated under normal and
open circuit FT conditions using any of the redundant
TABLE IV. SWITCHING STATES FOR CCS-RSC MLI BY SELECTING combination. Therefore, in Phase 3, switching pulses to be
REDUNDANT STATES WITH DIFFERENT FAULTY POWER
SWITCHES used in CCS-RSC MLI can be derived.

Faulty Reconfigured Output


power state numbers voltage
switches from Table1 levels
S1 1,4,7,9,12 5
S2 1,3,10 3
S3 2,3,10 3
S4 2,4,7,10,13 5
S 11 1,3,6,10,13 5
S 21 1,5,9 3
S 31 1,4,9 3
Fig. 2. Signal generation using sine wave reference with inverted sine
S 41 1,4,6,9,13 5 carriers

IV. PULSE GENERATION CONTROL SCHEME FOR


CCS-RSC MLI
The proposed CCS-RSC MLI topology using sine wave
reference with inverted sine carrier modulation control
scheme is analyzed for 7-level under normal and FT
operating conditions. The schematic diagram of inverted sine
carrier modulation control is shown in Figure 4 [11].
Inverted sine carriers are incorporated into sine wave
reference to generate switching pulses. For a m-level CCS-
RSC MLI (m-1/2) carriers are required to generate
switching pulses in a 7-level CCS-RSC inverter. Six
inverted sine carrier signals (V+inv1, V+inv2, V+inv3, V-inv1, V- Fig. 3. Resultant output voltage Vexp (t)
-
inv2 and V inv3) with a 5 kHz switching frequency are

3
Fig. 4. Schematic diagram of proposed control scheme for CCS-RSC MLI topology

V. SIMULATION RESULTS
CCS-RSC MLI topology for a single-phase 7-level fed
resistive load under normal operation and open circuit FT
conditions is simulated using MATLAB for the parameters
chosen listed in Table V.
Simulation results are presented for CCS-RSC MLI
topology with sine wave reference and inverted sine carrier
modulation control.

TABLE V. SIMULATION PARAMETERS OF CCS-RSC MLI

Parameter Value
Fig. 6. %Voltage THD of CCS-RSC MLI topology under normal operation
Voltage (Vdc1= Vdc2 = Vdc3) 76.66V
The output voltage and the corresponding %Voltage THD
Switching frequency 5kHz during normal operation using switching combinations
listed in Table II are shown Fig.5 and Fig.6 respectively.
Resistive load 10 Ω
From Fig. 5, it can be seen that the voltage levels obtained
Modulation index 0 to 1 during normal operation and %Voltage THD found to be
21.02% for the fundamental value of 226.8V.
A. Under normal operating conditions

Fig. 7. Output current of CCS-RSC MLI topology under normal mode


Fig. 5. Output voltage of CCS-RSC MLI topology under normal operation

4
Fig. 11. Output voltage of CCS-RSC MLI topology under fault on power
switch S1 using redundant paths

Fig. 8. %Current THD of CCS-RSC MLI topology under normal mode

Furthermore, the output current and its %THD of CCS-


RSC MLI are shown in Fig. 7 and Fig. 8 respectively. It can
be observed that, the fundamental current value is 22.68A
and %Current THD is 21.02%. It can be noticed that %THD
of current and voltage remains the same for a resistive load.
B. Fault on power switch S1
The simulation results of CCS-RSC MLI with power Fig. 12. %Voltage THD of CCS-RSC MLI topology under fault on power
switch S1 under fault has been analyzed by reconfiguring switch S1 using redundant paths
switching combinations.
Fig. 11 and Fig. 12 shows the output voltage and %THD
with fault on power switch S1. As discussed in Section 3, it
can be observed that the +3Vdc voltage level is not generated
since there is no redundant path and the output voltage
waveform is asymmetrical. Therefore, the %Voltage THD
of 60.19% with redundant paths, is very high when
compared to normal mode or during fault on power switch
S1. Hence, symmetrical voltage waveform can be obtained
appropriately by defining the range of MI as shown in Fig.
13.
Fig. 9. Output voltage of CCS-RSC MLI topology with fault on switch S1

Fig. 13. Output voltage of CCS-RSC MLI topology under fault on power
switch S1 with modified MI

Fig. 10. %Voltage THD of CCS-RSC MLI topology with fault on power
switch S1

Fig. 9 and Fig. 10 shows the output voltage and %THD


with fault on power switch S1. As discussed in Section III it
can be observed that the three positive voltage levels are not
generated. Also, the %Voltage THD is 51.77% that is very
high when compared to normal mode of operation.
Therefore, it is necessary to reconfigure the switching
combinations using redundant paths listed in Table I. Fig. 14. %Voltage THD of CCS-RSC MLI topology under fault on power
switch S1 with modified MI

5
Fig. 13 and Fig. 14 shows the output voltage and %THD
with fault on power switch S1 after updating MI. The
voltage waveform is symmetrical with %Voltage THD of
34.62%. Hence %Voltage THD value can be reduced
drastically by maintaining symmetrical voltage with
modified MI.
C. Fault on power switch S2
The simulation results of CCS-RSC MLI with fault on
power switch S2 has been analyzed by reconfiguring
switching combinations.
Fig. 18. %Voltage THD of CCS-RSC MLI topology with fault on power
switch S2 using redundant paths

The resultant asymmetrical waveform and %THD is


shown in Fig. 17 and Fig. 18 respectively. Symmetrical
voltage waveform can be obtained by modifying the range
of MI as shown in Fig. 19.

Fig. 15. Output voltage of CCS-RSC MLI topology under fault on power
switch S2

Fig. 19. Output voltage of CCS-RSC MLI topology under fault on power
switch S2 with modified MI

Fig.16. %Voltage THD of CCS-RSC MLI topology under fault on power


switch S2

Fig. 15 and Fig. 16 shows the output voltage and %THD


with fault on power switch S2. As discussed in Section III, it
can be observed that the three negative voltage levels are not
generated. Also, the %Voltage THD of 51.63% is very high
when compared to normal mode of operation. Therefore, it
is necessary to reconfigure the switching combinations
using redundant paths listed in Table I. However, the Fig. 20. %Voltage THD of CCS-RSC MLI topology under fault on power
voltage levels -2Vdc and -3Vdc cannot be generated, since switch S1 with modified MI
there are no redundant paths available. Hence, asymmetrical
voltage waveform can be generated by reconfiguring the Fig. 19 and Fig. 20 shows the output voltage and %THD
switching combinations. for fault on power switch S2 with modified MI. It can be
observed that the voltage waveform is symmetrical and
%Voltage THD is 63.39%. Also, form Fig. 19 it can be
observed that voltage levels have reduced from 7 to 3 with
increase in %Voltage THD.

D. Fault on any single power switch ( S3/ S4/S11/S21/S31/S41)


Further, FT analysis has been carried out for open circuit
fault on single power switch and results are listed in Table
VI. It can be observed that %THD during fault on any
power switch is higher than that of healthy condition.
Fig. 17. Output voltage of CCS-RSC MLI topology under fault on power Therefore, it can be improved by reconfiguring switch
switch S2 using redundant paths combinations using Table I and modifying MI to maintain

6
a symmetrical waveform. Also, it can be noticed that the by reconfiguring switch combinations and modified
%THD decreases with increase in number of levels. modulation index.

TABLE VI. FT ANALYSIS ON A SINGLE FAULTY POWER SWITCH


ACKNOWLEDGMENT
Analysis of output voltage
Authors would like to sincerely thank the Honorable
Faulty After reconfiguring Vice Chancellor and Management of RUAS for providing
power During fault switching table and all facilities required to carry out this research work.
switches updating MI
%Voltage Voltage %Voltage Voltage REFERENCES
THD levels THD levels [1] Rodriguez, J., Lai, J. S., & Peng, F. Z. (2002). Multilevel inverters: a
S3 78.59 4 63.39 3 survey of topologies, controls, and applications. IEEE Transactions
S4 99.37 4 34.62 5 on industrial electronics, 49(4), 724-738.
[2] Ebrahimi, J., Babaei, E., & Gharehpetian, G. B. (2011). A new
S11 51.89 4 34.62 5
multilevel converter topology with reduced number of power
S21 51.89 4 63.39 3 electronic components. IEEE Transactions on industrial electronics,
S31 99.37 4 63.39 3 59(2), 655-667.
S41 78.59 4 34.62 5 [3] Su, G. J. (2005). Multilevel DC-link inverter. IEEE Transactions on
Industry Applications, 41(3), 848-854.
[4] Rao, S. N., Kumar, D. A., & Babu, C. S. (2013, February). New
VI. COMPARISON OF CCS-RSC MLI TOPOLOGY WITH
multilevel inverter topology with reduced number of switches using
TRADITIONAL MLIS advanced modulation strategies. In 2013 International Conference on
Power, Energy and Control (ICPEC) (pp. 693-699). IEEE.
The number of components required in a CCS-RSC MLI
[5] Sabyasachi, S., Borghate, V. B., Maddugari, S. K., & Karasani, R. R.
topology and various traditional MLIs are listed in Table (2017, November). A reliable multilevel inverter with fault tolerance.
VII for m-level to highlight the significance of proposed In TENCON 2017-2017 IEEE Region 10 Conference (pp. 557-562).
MLI. As the number of level increases, the number of power IEEE.
[6] Jalhotra, M., Kumar, L., Gautam, S.P. and Gupta, S., (2018).
switches increases by ‘2(m-1)’ and ‘m+1’ respectively for Development of fault-tolerant MLI topology. IET Power Electronics,
traditional and proposed MLI topologies. This study 11(8), pp.1416-1424.
revealed that the CCS-RSC MLI topology requires less [7] Santosh Kumar, M., Borghate, V.B., Karasani, R.R., Sabyasachi, S.
number of power switches when compared to traditional and Suryawanshi, H.M., (2018). A fault‐tolerant modular multilevel
MLIs. inverter topology. International Journal of Circuit Theory and
Applications, 46(5), pp.1028-1043.
[8] Maddugari, S.K., Borghate, V.B., Karasani, R.R., Sabyasachi, S. and
TABLE VII. COMPONENTS COUNT OF TRADITIONAL MLIS Suryawanshi, H.M., (2019). A Three-phase Nine-level Fault Tolerant
AND PROPOSED CCS-RSC MLI Asymmetrical Inverter. Arabian Journal for Science and Engineering,
44(3), pp.1779-1790.
Traditional MLIs Proposed
[9] Rao, S.N., Kumar, D.A. and Babu, C.S., (2018). Implementation of
Topologies/ Diode- Capacitor- Cascaded CCS- Cascaded based Reversing Voltage Multilevel Inverter using Multi
Components clamped clamped H-bridge RSC Carrier Modulation Strategies. International Journal of Power
MLI MLI MLI MLI Electronics and Drive Systems, 9(1), pp. 220-230.
[10] Reddy, V. N. B., Rao, S. N., & Babu, C. S. (2013, February).
Main Switches 2 (m-1) 2 (m-1) 2 (m-1) m+1 Emphasis of modulated techniques for cascaded multilevel inverters
fed drive using FPGA. In 2013 International Conference on Power,
Main Diodes 2 (m-1) 2 (m-1) 2 (m-1) m+3 Energy and Control (ICPEC) (pp. 686-692). IEEE.
Clamping [11] Gupta, K. K., & Jain, S. (2018). Control of Multilevel Inverters With
2 (m-3) 0 0 0 Reduced Device Count. In Modeling and Control of Power
diodes
Electronics Converter System for Power Quality Improvements (pp.
Balancing 121-149). Academic Press.
0 (m-2) 0 0
capacitors [12] Ounejjar, Y., Al-Haddad, K., & Gregoire, L. A. (2010). Packed U
DC bus cells multilevel converter topology: theoretical study and
m-1 0 0 0 experimental validation. IEEE Transactions on Industrial Electronics,
capacitors
58(4), 1294-1306.
DC Sources 1 1 (m-1)/2 (m-1)/2 [13] Rao, S. N., Kumar, D. A., & Babu, C. S. (2018). Implementation of
Multilevel Boost DC-Link Cascade based Reversing Voltage Inverter
for Low THD Operation. Journal of Electrical Engineering &
VII. CONCLUSION Technology, 13(4), 1528-1538.
[14] Sulake, N., Devarasetty Venkata, A., & Choppavarapu, S. (2018).
The single-phase 7-level CCS-RSC MLI topology is FPGA Implementation of a Three-Level Boost Converter-fed Seven-
analyzed under both normal and FT conditions with Level DC-Link Cascade H-Bridge inverter for Photovoltaic
Applications. Electronics, 7(11), 282.
reconfiguration of switching combinations and modifying
the range of MI. Also, sine wave reference with inverted
sine carrier pulse generation methodology has been
discussed. The case of open circuit fault for a single power
switch has been considered. Due to reduced number of
power switches the proposed CCS-RSC MLI topology has
less number of redundant switch combinations to achieve
required number of levels. The simulation results for the
proposed CCS-RSC MLI topology, are presented and is
seen that they work reasonably well under fault conditions

View publication stats

You might also like