Professional Documents
Culture Documents
A To Q Transition Manual (Intelligent Function Modules)
A To Q Transition Manual (Intelligent Function Modules)
(Communications)
When exported from Japan, this manual does not require application to the
Ministry of Economy, Trade and Industry for service transaction permission.
Before using this product, please read this handbook and the relevant manuals introduced in this
handbook carefully and pay full attention to safety to handle the product correctly.
In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
Note that the CAUTION level may lead to a serious consequence according to the circumstances.
Always follow the instructions of both levels because they are important to personal safety.
Please save this handbook to make it accessible when required and always forward it to the end user.
A-1
[Design Precautions]
DANGER
z Install a safety circuit external to the PLC that keeps the entire system safe even when there are
problems with the external power supply or the PLC module. Otherwise, trouble could result from
erroneous output or erroneous operation.
(1) Outside the PLC, construct mechanical damage preventing interlock circuits such as emergency
stop, protective circuits, positioning upper and lower limits switches and interlocking forward/
reverse operations.
(2) When the PLC detects the following problems,
it will stop calculation and turn off all output in the case of (a).
In the case of (b), it will hold or turn off all output according to the parameter setting.
Note that the AnS series module will turn off the output in either of cases (a) and (b).
(b) The CPU module self-diagnosis functions, such Hold or turn off all output
as the watchdog timer error, detect problems. according to the parameter Output OFF
setting.
In addition, all output will be turned on when there are problems that the PLC CPU cannot
detect, such as in the I/O controller. Build a fail safe circuit exterior to the PLC that will make sure
the equipment operates safely at such times.
Refer to "LOADING AND INSTALLATION" in this manual for example fail safe circuits.
(3) Output could be left on or off when there is trouble in the outputs module relay or transistor. So
build an external monitoring circuit that will monitor any single outputs that could cause serious
trouble.
A-2
[Design Precautions]
DANGER
z When overcurrent which exceeds the rating or caused by short-circuited load flows in the output
module for a long time, it may cause smoke or fire. To prevent this, configure an external safety
circuit, such as fuse.
z Build a circuit that turns on the external power supply when the PLC main module power is turned
on.
If the external power supply is turned on first, it could result in erroneous output or erroneous
operation.
z When there are communication problems with the data link, refer to the corresponding data link
manual for the operating status of each station.
Not doing so could result in erroneous output or erroneous operation.
z When connecting a peripheral device to the CPU module or connecting a personal computer or the
like to the intelligent function module / special function module to exercise control (data change) on
the running PLC, configure up an interlock circuit in the sequence program to ensure that the whole
system will always operate safely.
Also before exercising other control (program change, operating status change (status control)) on
the running PLC, read the manual carefully and fully confirm safety.
Especially for the above control on the remote PLC from an external device, an immediate action
may not be taken for PLC trouble due to a data communication fault.
In addition to configuring up the interlock circuit in the sequence program, corrective and other
actions to be taken as a system for the occurrence of a data communication fault should be
predetermined between the external device and PLC CPU.
CAUTION
z Do not bunch the control wires or communication cables with the main circuit or power wires, or
install them close to each other.
They should be installed 100 mm (3.94 inch) or more from each other.
Not doing so could result in noise that would cause erroneous operation.
z When controlling items like lamp load, heater or solenoid valve using an output module, large current
(approximately ten times greater than that present in normal circumstances) may flow when the
output is turned OFF to ON.
Take measures such as replacing the module with one having sufficient rated current.
A-3
[Installation Precautions]
CAUTION
z Use the PLC in an environment that meets the general specifications contained in this manual.
Using this PLC in an environment outside the range of the general specifications could result in
electric shock, fire, erroneous operation, and damage to or deterioration of the product.
z While pressing the installation lever located at the bottom of module, insert the module fixing tab into
the fixing hole in the base unit until it stops. Then, securely mount the module with the fixing hole as
a supporting point.
Incorrect loading of the module can cause a malfunction, failure or drop.
When using the PLC in the environment of much vibration, tighten the module with a screw.
Tighten the screw in the specified torque range.
Undertightening can cause a drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to damage to the screw or module.
z When installing extension cables, be sure that the base unit and the extension module connectors
are installed correctly.
After installation, check them for looseness.
Poor connections could cause an input or output failure.
z Securely load the memory card into the memory card loading connector.
After installation, check for lifting.
Poor connections could cause an operation fault.
z Completely turn off the externally supplied power used in the system before mounting or removing
the module. Not doing so could result in damage to the product.Note that the module can be
changed online (while power is on) in the system that uses the CPU module compatible with online
module change or on the MELSECNET/H remote I/O station.
Note that there are restrictions on the modules that can be changed online(while power is on), and
each module has its predetermined changing procedure.
For details, refer to this manual and the online module change section in the manual of the module
compatible with online module change.
A-4
[Wiring Precautions]
DANGER
z Completely turn off the externally supplied power used in the system when installing or placing
wiring.
Not completely turning off all power could result in electric shock or damage to the product.
z When turning on the power supply or operating the module after installation or wiring work, be sure
that the module's terminal covers are correctly attached.
Not attaching the terminal cover could result in electric shock.
[Wiring Precautions]
CAUTION
z Be sure to ground the FG terminals and LG terminals to the protective ground conductor.
Not doing so could result in electric shock or erroneous operation.
z When wiring in the PLC, be sure that it is done correctly by checking the product's rated voltage and
the terminal layout.
Connecting a power supply that is different from the rating or incorrectly wiring the product could
result in fire or damage.
z External connections shall be crimped or pressure welded with the specified tools, or correctly
soldered.
Imperfect connections could result in short circuit, fires, or erroneous operation.
z Be sure there are no foreign substances such as sawdust or wiring debris inside the module.
Such debris could cause fires, damage, or erroneous operation.
z The module has an ingress prevention label on its top to prevent foreign matter, such as wire offcuts,
from entering the module during wiring.
Do not peel this label during wiring.
Before starting system operation, be sure to peel this label because of heat dissipation.
A-5
[Startup and Maintenance precautions]
DANGER
z Do not touch the terminals while power is on.
Doing so could cause shock or erroneous operation.
z Switch off all phases of the externally supplied power used in the system when cleaning the module
or retightening the terminal or module mounting screws.
Not doing so could result in electric shock.
Undertightening of terminal screws can cause a short circuit or malfunction.
Overtightening of screws can cause damages to the screws and/or the module, resulting in fallout,
short circuits, or malfunction.
A-6
[Startup and Maintenance precautions]
CAUTION
z The online operations conducted for the CPU module being operated, connecting the peripheral
device (especially, when changing data or operation status), shall be conducted after the manual has
been carefully read and a sufficient check of safety has been conducted.
Operation mistakes could cause damage or problems with of the module.
z Use any radio communication device such as a cellular phone or a PHS phone more than 25cm
(9.85 inch) away in all directions of the PLC.
Not doing so can cause a malfunction.
z Completely turn off the externally supplied power used in the system before mounting or removing
the module. Not doing so could result in damage to the product.
Note that the module can be changed online (while power is on) in the system that uses the CPU
module compatible with online module change or on the MELSECNET/H remote I/O station.
Note that there are restrictions on the modules that can be changed online (while power is on), and
each module has its predetermined changing procedure.
For details, refer to this manual and the online module change section in the manual of the module
compatible with online module change.
z Do not mount/remove the module onto/from base unit more than 50 times (IEC61131-2-compliant),
after the first use of the product. Failure to do so may cause the module to malfunction due to poor
contact of connector.
z Before touching the module, always touch grounded metal, etc. to discharge static electricity from
human body, etc.
Not doing so can cause the module to fail or malfunction.
[Disposal Precautions]
CAUTION
z When disposing of this product, treat it as industrial waste.
A-7
[Transportation Precautions]
CAUTION
z When transporting lithium batteries, make sure to treat them based on the transport regulations.
(Refer to QCPU User’s Manual (Hardware Design, Maintenance and Inspection) for details of the
controlled models.)
A-8
REVISIONS
* The handbook number is given on the bottom left of the back cover.
Print Date * Handbook Number Revision
Apr., 2005 L(NA)-08050ENG-A First edition
This handbook confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this handbook.
A-9
CONTENTS
A - 10
CHAPTER 4 EXTERNAL DIMENSIONS 4-1~4-6
4.1 External Dimensions for A Series •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 1
4.2 External Dimensions for QnA Series •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 3
4.3 External Dimensions for Q Series ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 5
A - 11
Memo
1 INTRODUCTION
1 INTRODUCTION
1
This manual outlines replacement of the following communication modules when A series PLCs or QnA
series PLCs are replaced with Q series PLCs.
(1) Replacement of A series computer link modules and QnA series serial communication
modules
(a) A series computer link module
QJ71C24N
Communications on the RS-232 QJ71C24N RS-232 :1ch
interface or RS-422/485:1ch
QJ71C24N-R2
QJ71C24N-R2
RS-232 :2ch
AJ71UC24
QJ71C24N
AJ71UC24 QJ71C24N RS-232 :1ch
RS-232 :1ch
RS-422/485 :1ch or RS-422/485 :1ch
QJ71C24N-R4
Communications on the RS-422/485 QJ71C24N-R4
RS-422/485 :2ch
interface
Communications on QJ71C24N
AJ71QC24N the RS-232 interface QJ71C24N RS-232 :1ch
or or RS-422/485:1ch
AJ71QC24N-R2 QJ71C24N-R2 QJ71C24N-R2
RS-232 :2ch
AJ71QC24N
RS-232 :1ch
RS-422/485 :1ch
AJ71QC24N-R2
RS-232 :2ch
Communications on QJ71C24N
AJ71QC24N the RS-422/485 interface QJ71C24N RS-232 :1ch
or or RS-422/485 :1ch
AJ71QC24N-R4 QJ71C24N-R4
QJ71C24N-R4
RS-422/485 :2ch
AJ71QC24N
RS-232 :1ch
RS-422/485 :1ch
AJ71QC24N-R4
RS-422 :1ch
RS-422/485 :1ch
POINT
Q series communication modules do not have a function equivalent to the multidrop link function of the
A series communication module AJ71UC24.
Consider replacement to a CC-Link system, MELSECNET/H data link system or other systems.
1-1
1 INTRODUCTION
(2) Replacement of an A series Ethernet interface module and QnA series Ethernet
interface module
(a) A series Ethernet interface module
AJ71E71N3-T
Communications on 10BASE-T QJ71E71-100
or QJ71E71-100 10BASE-T/100BASE-TX:1ch
AJ71E71N-T
AJ71E71N3-T
10BASE-T:1ch
AJ71E71N-T
10BASE-T:1ch
AJ71QE71N3-T
Communications on 10BASE-T QJ71E71-100
or QJ71E71-100 10BASE-T/100BASE-TX:1ch
AJ71QE71N-T
AJ71QE71N3-T
10BASE-T:1ch
AJ71QE71N-T
10BASE-T:1ch
1-2
2 SERIAL COMMUNICATION MODULE REPLACEMENT
REPLACEMENT
2-1
2 SERIAL COMMUNICATION MODULE REPLACEMENT
(1) A series
:Compatible, :Partial change required, :Incompatible
Specifications
QJ71C24N Compat-
Item Precautions for replacement
AJ71UC24 QJ71C24N-R2 ibility
QJ71C24N-R4
RS-232 compliant RS-232 compliant The connector on the connec-
(D-Sub 25P) (D-Sub 9P) tion cable must be changed.
Interface
RS-422/485 compliant
RS-422/485 compliant Wiring must be changed.
(2-piece terminal block)
Communica-
tion using
Half-duplex communication
dedicated pro-
Communi- tocol
cation Non-proce-
method dural/bidirec-
Full duplex communication (1:1 connection)/
tional
Half-duplex communication (1:n, m:n connection)
communica-
tion
Synchronization method Start stop synchronization (asynchronous method)
Transmission speed 300 to 19200 bps 50 to 230400 bps
Start bit 1
Data bit 7 or 8
Data format
Parity bit 1(vertical parity)/none
Stop bit 1 or 2
Communica-
tion using One request is processed when the mounted station PLC CPU
dedicated pro- executes END processing.
tocol
Access
cycle Non-proce-
dural/bidirec-
Transmission can be executed at each send request,
tional
and reception is available at all times.
communica-
tion
Error Parity check Performed (odd/even)/none
detection Sum check Performed (MC protocol/Bidirectional)/none
RS-232 RS-422/485
Communica-
tion using 1:1, 1:n, m:n
dedicated pro- (n:max.32, m+n:max.32)
Line config- tocol
For details on linked operation
uration Non-proce-
between interfaces, refer to the
(data com- dural commu- 1:1, 1:n (n:max.32) 1:1, 1:n, n:1 (n:max.32)
manual.
munication) nication
Bidirectional
communica- 1:1
tion
Transmis- RS-232 Max.15m
sion dis- Max.500m Max.1200m
tance RS-422/485
(overall distance) (overall distance)
(Continued on next page)
2-2
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Specifications
QJ71C24N Compat-
Item Precautions for replacement
AJ71UC24 QJ71C24N-R2 ibility
QJ71C24N-R4
No. of E2PROM writes Max. 100,000 times on same Max. 100,000 times on same
No. of flash ROM writes area in E2PROM area in flash ROM
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment: special 32 (I/O assignment: intelli. 32
points) points)
2-3
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Specifications
AJ71QC24N QJ71C24N Compat-
Item Precautions for replacement
AJ71QC24N-R2 QJ71C24N-R2 ibility
AJ71QC24N-R4 QJ71C24N-R4
RS-232 compliant RS-232 compliant The connector on the connec-
RS-232
(D-Sub 25P) (D-Sub 9P) tion cable must be changed.
RS-422/485 compliant
RS-422 compliant
RS-422 (2-piece plug-in connector
(D-Sub 25P)
socket block)
RS-422/485 compliant Wiring must be changed.
RS-422/485 compliant (2-piece terminal block)
RS-422/485
(2-piece terminal block) (2-piece plug-in connector
socket block)
Interface Communica-
tion using
Half-duplex communication
dedicated pro-
tocol
Non-proce-
dural protocol
Full duplex communication/Half-duplex communication
communica-
tion
Bidirectional
protocol com- Full duplex communication/Half-duplex communication
munication
Synchronization method Start stop synchronization (asynchronous method)
Transmission speed 300 to 230400 bps 50 to 230400 bps
Start bit 1
Data bit 7 or 8
Data format
Parity bit 1 (vertical parity)/none
Stop bit 1 or 2
Communica-
tion using Processing when the mounted station PLC CPU performs END
dedicated pro- processing
tocol
Non-proce-
Access
dural protocol
cycle
communica-
tion Transmission can be executed at each send request,
and reception is available at all times.
Bidirectional
protocol com-
munication
Parity check Performed (odd/even)/none
Error
detection Select at parameter/user
Sum check Performed / none
frame.
Line config- RS-232 1:1 The Q series does not have the
uration RS-422 1:1 RS-422 interface.
(connec- 1:1, 1:n, m:n 1:1, 1:n, n:1, m:n The interface to be used must
tion) RS-422/485 be changed.
(n:max.32, m+n:max.32) (n:max.32, m+n:max.32)
(Continued on next page)
2-4
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Specifications
AJ71QC24N QJ71C24N Compat-
Item Precautions for replacement
AJ71QC24N-R2 QJ71C24N-R2 ibility
AJ71QC24N-R4 QJ71C24N-R4
Communica-
tion using 1:1, 1:n, m:n
dedicated pro- (n:max.32, m+n:max.32)
tocol
line config-
Non-proce- For details on linked operation
uration
dural protocol between interfaces, refer to the
(data com- 1:1, 1:n (n:max.32) 1:1, 1:n, n:1 (n:max.32)
communica- manual.
munication)
tion
Bidirectional
protocol com- 1:1
munication
RS-232 Max.15m The Q series does not have the
Transmis-
RS-422 Max.1200m RS-422 interface.
sion dis-
The interface to be used must
tance RS-422/485 Max.1200m (overall distance) be changed.
No. of E2PROM writes Max. 100,000 times on same Max. 100,000 times on same
No. of flash ROM writes area in E2PROM area in flash ROM
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment: special 32 (I/O assignment: intelli. 32
points) points)
2-5
2 SERIAL COMMUNICATION MODULE REPLACEMENT
(1) A series
:Compatible, :Partial change required, :Incompatible
Specifications
QJ71C24N Compat-
Item Precautions for replacement
AJ71UC24 QJ71C24N-R2 ibility
QJ71C24N-R4
Cable Use a cable that is compliant with the RS-232 standard. *1
Cable length Max.15m
Applicable
connector for
RS-232 external wiring
(side of con- D-Sub 25P D-Sub 9P *2 The connector must be
nection cable (male, screw type) (male, screw type) changed.
for connect-
ing to the
module)
Item Description
Number of pairs 3P
*1
Max.500m Max.1200m
Cable length
(overall distance) (overall distance)
External wir-
ing (side of
connection For details on the connection
Connected to terminal block
cable for con- method, refer to the manual.
necting to the
module)
*1 The RS-232 and RS-422/485 recommended cables are listed in the Q series serial communication module manual.
*2 Use the exclusive products listed in the Q series serial communication module manual as the connector shell of the cable to
connect to the Q series serial communication module.
2-6
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Specifications
AJ71QC24N QJ71C24N Compat-
Item Precautions for replacement
AJ71QC24N-R2 QJ71C24N-R2 ibility
AJ71QC24N-R4 QJ71C24N-R4
Cable Use a cable that is compliant with the RS-232 standard. *1
Cable length Max.15m
Applicable
connector for
RS-232 external wiring
(side of con- D-Sub 25P D-Sub 9P *2 The connector must be
nection cable (male, screw type) (male, screw type) changed.
for connect-
ing to the
module)
Cable (Same as RS-422/485)
Applicable
connector for The Q series does not have the
external wiring RS-422 interface.
RS-422 (side of con- D-Sub 25P Connected to the RS-232 or The interface to be used must
nection cable (male, screw type) RS-422/485 interface. be changed.
for connect-
ing to the
module)
Item Description
Number of pairs 3P
*1
*1 The RS-232 and RS-422/485 recommended cables are listed in the Q series serial communication module manual.
*2 Use the exclusive products listed in the Q series serial communication module manual as the connector shell of the cable to
connect to the Q series serial communication module.
2-7
2 SERIAL COMMUNICATION MODULE REPLACEMENT
(1) A series
:Compatible, :Partial change required, :Incompatible
Description
QJ71C24N Compat- Reference
Item Precautions for replacement
AJ71UC24 QJ71C24N-R2 ibility section
QJ71C24N-R4
The available commands,
accessible device range, and
access to another station are
Communi- Device memory PLC CPU data is read/written to and from exter-
restricted.
cation read/write nal devices.
The program on the external
using dedi- device side must be
cated pro- changed.
tocol *1
Change to a sequence pro-
Data is transmitted to external devices from the
On-demand gram that uses the dedicated
PLC CPU.
instruction (ONDEMAND).
Data transmission Data is transmitted to external devices from the Change to a sequence pro-
Non-proce- PLC external device PLC CPU. gram that uses the dedicated Section
dural com-
Data reception instructions (OUTPUT/ 2.6.1
munication Data is transmitted from external devices.
PLC external device INPUT).
Data transmission Data is transmitted to external devices from the
Bidirec- PLC external device PLC CPU. Change to a sequence pro-
tional com- gram that uses the dedicated
munication Data reception instructions (BIDOUT/BIDIN).
Data is transmitted from external devices.
PLC external device
Change to a sequence pro-
gram that uses the dedicated
Transmits messages (character strings) to the instruction (PRR).
Transmission using printer function
printer from the PLC CPU. Transmitted by nonproce-
dural protocol using user
frames.
DTR/DSR control Data transmission/reception with external
CD signal control devices is controlled by RS-232 control signals.
Transmis-
sion control DC codes (including Xon/Xoff) are sent/
DC code control received to control data transmission/reception
with external devices.
*1 On the Q series, this is called "MELSEC communication protocol" (abbrev. "MC protocol").
2-8
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Description
AJ71QC24N QJ71C24N Compat- Reference
Item Precautions for replacement
AJ71QC24N-R2 QJ71C24N-R2 ibility section
AJ71QC24N-R4 QJ71C24N-R4
Communications in Communications in dedicated protocol is per-
ASCII mode formed using ASCII data.
Communications in Communications in dedicated protocol is per-
binary mode formed using binary data.
Communi-
Device memory PLC CPU data is read/written to and from exter-
cation
read/wite nal devices.
using dedi-
cated pro- The program on the PC side
tocol *1 Access to another sta- Data is read/written to another station's PLC sometimes must be changed
tion CPU on the network system. according to the network to
pass through.
Data is transmitted to external devices from the
On-demand
PLC CPU.
Data transmission/
reception Data is transmitted/received between the PLC
PLC CPU and external devices.
Non-proce- external device
dural proto- Data transmission/ Data is transmitted or received using the data
col reception in user (user frames) registered to the serial communi-
communi- frames cation module.
cation Binary data is converted to ASCII data before it
Data transmission/
is transmitted.
reception by ASCII
Received ASCII data is converted to binary
binary conversion
data.
Data transmission/
reception Data is transmitted/received between the PLC
Bidirec- PLC CPU and external devices.
tional proto- external device
col
communi- Binary data is converted to ASCII data before it
Data transmission/
cation is transmitted.
reception by ASCII
Received ASCII data is converted to binary
binary conversion
data.
Data is transmitted/
received with another
Communication by dedicated link Study the method for com-
station's PLC CPU on Section
instruction municating via MELSEC-
a multidrop connec- 2.6.2
(SEND/RECV, READ/WRITE, REQ) NET/H.
tion by link instruc-
tions.
DTR/DSR control
Data transmission/reception with external
RS/CS control
devices is controlled by RS-232 control signals.
Transmis- CDsignal control
sion control
DC codes (including Xon/Xoff) are sent/
DC code control received to control data transmission/reception
with external devices.
*1 On the Q series, this is called "MELSEC communication protocol" (abbrev. "MC protocol").
2-9
2 SERIAL COMMUNICATION MODULE REPLACEMENT
(1) A series
:Compatible, :Partial change required, :Incompatible
Description
2 - 10
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Description
2 - 11
2 SERIAL COMMUNICATION MODULE REPLACEMENT
(1) A series
There is no compatibility in the I/O signal assignments between the A series and the Q series.
Make a new sequence program.
:Compatible, :Partial change required, :Incompatible
AJ71UC24 Compat-
Precautions for replacement
Input signal Signal name ibility
On the Q series, Xn0, Xn1, Xn7, and Xn8 are used as the transmission com-
Xn0 Transmission complete
plete signals.
On the Q series, Xn3, Xn4, XnA, and XnB are used as the read request,
Xn1 Receive data read request
receive data, and read request signals.
Xn2 Global signal On the Q series, X(n+1)A and X(n+1)B are used as global signals.
Transmission complete of on-demand data is confirmed by the complete
Xn3 On-demand in execution
device of the ONDEMAND instruction.
Xn4
Computer link module The status is confirmed by the transmission sequence state storage area
Xn5
Transmission sequence status (addresses: 597(256H), 613(265H)) in buffer memory.
Xn6
Xn7 Computer link module ready On the Q series, X(n+1)E is used as the ready signal.
On the Q series, Xn8 is used as the abnormal completion of transmission
Xn8 Use prohibited
signal.
Xn9 Mode switching complete On the Q series, Xn6 is used as the mode switching complete signal.
XnA Use prohibited On the Q series, XnA and XnB are used as signals for various applications.
XnB Use prohibited (Refer to (2).)
XnC Use prohibited
XnD Watchdog timer On the Q series, X(n+1)F is used as the watchdog timer signal.
XnE Use prohibited
On the Q series, XnE to X(n+1)F are used as signals for various applica-
to to
tions. (Refer to (2).)
X(n+1)F Use prohibited
AJ71UC24 Compat-
Precautions for replacement
Output signal Signal name ibility
Yn0 Use prohibited
On the Q series, Yn0 to YnF are used as signals for various applications.
to to
(Refer to (2).)
YnF Use prohibited
Y(n+1)0 Send request On the Q series, Yn0 and Yn7 are used as the send request signals.
On the Q series, Yn1 and Yn8 are used as the receive data read complete
Y(n+1)1 Receive data read complete
signals.
Y(n+1)2 Use prohibited
On the Q series, Y(n+1)2 to Y(n+1)8 are used as signals for various applica-
to to
tions. (Refer to (2).)
Y(n+1)8 Use prohibited
On the Q series, Yn2 and Yn9 are used as the mode switching request sig-
Y(n+1)9 Mode switching request
nals.
Y(n+1)A Use prohibited
Y(n+1)B Use prohibited
On the Q series, Y(n+1)C is used as the system setting default request sig-
Y(n+1)C Use prohibited
nal.
Y(n+1)D Use prohibited
Y(n+1)E Use prohibited
Y(n+1)F Use prohibited
2 - 12
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Signal name
AJ71QC24N QJ71C24N Compat- Precautions for
Input signal
AJ71QC24N-R2 QJ71C24N-R2 ibility replacement
AJ71QC24N-R4 QJ71C24N-R4
Normal completion of Normal completion of
Xn0
transmission transmission
Abnormal completion of Abnormal completion of
Xn1
transmission transmission
CH1 CH1
Transmission processing in Transmission processing in
Xn2
progress progress
Xn3 Receive data read request Receive data read request
Xn4 Receive error detection Receive error detection
Xn5 (System use) (System use)
Xn6 CH1 mode switching CH1 mode switching
Normal completion of Normal completion of
Xn7
transmission transmission
Abnormal completion of Abnormal completion of
Xn8
transmission transmission
CH2 CH2
Transmission processing in Transmission processing in
Xn9
progress progress
XnA Receive data read request Receive data read request
XnB Receive error detection Receive error detection
XnC (System use) (System use)
XnD CH2 mode switching CH2 mode switching
XnE CH1 ERR.LED ON CH1 error.
XnF CH2 ERR.LED ON CH2 error.
X(n+1)0 Modem initialization completion Modem initialization completion
X(n+1)1 Dialing Dialing
X(n+1)2 Connecting Line connection
Abnormal completion of initialization/
X(n+1)3 Initialization, line connection failure
connection
X(n+1)4 Modem disconnection completion Line disconnection completion
X(n+1)5 Normal completion of notification Normal completion of notification
X(n+1)6 Abnormal completion of notification Abnormal completion of notification
X(n+1)7 E2PROM read complete Flash ROM read complete
X(n+1)8 E2PROM write complete Flash ROM write complete
X(n+1)9 E2PROM system setting write complete Flash ROM system setting completion
X(n+1)A CH1 global signal CH1 global signal
X(n+1)B CH2 global signal CH2 global signal
X(n+1)C System setting default completion System setting default completion
X(n+1)D (System use) (System use)
X(n+1)E QC24N ready signal (accessible) C24 ready signal
X(n+1)F Watchdog timer Watchdog timer
2 - 13
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Signal name
AJ71QC24N QJ71C24N Compat- Precautions for
Output signal
AJ71QC24N-R2 QJ71C24N-R2 ibility replacement
AJ71QC24N-R4 QJ71C24N-R4
Yn0 Send request Send request
Yn1 CH1 Receive data read complete CH1 Receive data read complete
Yn2 Mode switching request Mode switching request
Yn3 Use prohibited Use prohibited
to to to
Yn6 Use prohibited Use prohibited
Yn7 Send request Send request
Yn8 CH2 Receive data read complete CH2 Receive data read complete
Yn9 Mode switching request Mode switching request
YnA Use prohibited Use prohibited
to to to
YnD Use prohibited Use prohibited
CH1 side error information initialization
YnE CH1 ERR.LED OFF request
request
CH2 side error information initialization
YnF CH2 ERR.LED OFF request
request
Y(n+1)0 Modem initialization request Modem initialization request
Y(n+1)1 Connection request Line connection request
Y(n+1)2 Modem disconnection request Line disconnection request
Y(n+1)3 Use prohibited Use prohibited
Y(n+1)4 Notification issue request Notification issue request
Y(n+1)5 Use prohibited Use prohibited
Y(n+1)6 Use prohibited Use prohibited
Y(n+1)7 E2PROM read request Flash ROM read request
Y(n+1)8 E2PROM write request Flash ROM write request
Y(n+1)9 E2PROM system setting write request Flash ROM system setting reqnest
Y(n+1)A Use prohibited Use prohibited
Y(n+1)B Use prohibited Use prohibited
Y(n+1)C System setting default request System setting default request
Y(n+1)D Use prohibited Use prohibited
Y(n+1)E Use prohibited Use prohibited
Y(n+1)F Use prohibited Use prohibited
2 - 14
2 SERIAL COMMUNICATION MODULE REPLACEMENT
(1) A series
There is no compatibility in the buffer memory assignments between the A series and the Q series.
Make a new sequence program.
The table below shows the main assignment areas for the initial settings and for transmission/reception.
:Compatible, :Partial change required, :Incompatible
AJ71UC24
Compat-
Buffer memory address Precautions for replacement
Buffer memory name ibility
HEX DEC
Non-procedural send data count On the Q series, the area of address 400H, 800H (1024, 2048) is
0H 0
storage area used as the send data count specification area.
1H 1
On the Q series, the area from address 401H, 801H (1025, 2049)
to to Send data storage area
is used as the send data specification area.
7FH 127
Non-procedural receive data count On the Q series, the area of address 600H, A00H (1536, 2560) is
80H 128
storage area used as the receive data count specification area.
81H 129
On the Q series, the area from address 601H, A01H (1537, 2561)
to to Receive data storage area
is used as the receive data storage area.
FFH 255
Non-procedural receive end code On the Q series, the area of address A5H, 145H (165, 325) is
100H 256
specification used as the receive end code specification area.
On the Q series, the area from address 101H (257) onward is
to to to
used for various applications.
Non-procedural word/byte On the Q series, the area of 96H, 136H (150, 310) is used as the
103H 259
specification area word/byte unit specification area.*1
On the Q series, the area of address A2H, 142H (162, 322) is
Non-procedural send buffer memory
104H 260 used as the send buffer memory head address specification
head address specification area
area.*1
Non-procedural send buffer memory On the Q series, the area of address A3H, 143H (163, 323) is
105H 261
length specification area used as the send buffer memory length specification area.*1
On the Q series, the area of address A6H, 146H (166, 326) is
Non-procedural receive buffer memory
106H 262 used as the receive buffer memory head address specification
head address specification area
area.*1
On the Q series, the area of address A7H, 147H (167, 327) is
Non-procedural receive buffer memory
107H 263 used as the receive buffer memory buffer memory length specifi-
length specification area
cation area.*1
Non-procedural receive end data On the Q series, the area of address A4H, 144H (164, 324) is
108H 264
count specification area used as the receive end data count specification area.*1
On the Q series, the area of address A0H, 140H (160, 320) is
On-demand buffer memory
109H 265 used as the on-demand buffer memory head address specifica-
head address specification area
tion area.*1
On the Q series, the area of address A1H, 141H (161, 321) is
10AH 266 On-demand length specification area
used as the on-demand data length specification area.*1
RS-232 CD terminal check setting On the Q series, the area of 97H, 137H (151, 311) is used as the
10BH 267
area CD terminal check specification area.*1
to to to On the Q series, the area from address 10CH (152) onward is
DFFH 3583 used for various applications.
2 - 15
2 SERIAL COMMUNICATION MODULE REPLACEMENT
2 - 16
2 SERIAL COMMUNICATION MODULE REPLACEMENT
2 - 17
2 SERIAL COMMUNICATION MODULE REPLACEMENT
The following shows a description of how to reuse programs for A series computer link module for use
on a Q series serial communication module at replacement of modules.
2 - 18
2 SERIAL COMMUNICATION MODULE REPLACEMENT
*2 The following devices in special relays (M9000 onwards) and special registers (D9000 onwards) are accessed:
• SD1000 to SD1255 are accessed by specifying D9000 to D9255.
• SM1000 to SM1255 are accessed by specifying M9000 to M9255.
*3 In the same way as when an A series computer link module is used, any receive end code can be registered to a Q series
serial communication module, and data can be transmitted to external devices as a result of this.
*4 Messages that are handled by an A series computer link module become user frames on a Q series serial communication
module.
*5 Messages (user frames) can be registered on the utility package (GX Configurator-SC).
Messages are transmitted by the dedicated instruction (PRR).
2 - 19
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Data communications between PLC CPUs and external devices, and between PLC CPUs that was per-
formed by the QnA series serial communication module can also be performed using Q series serial
communication modules.
The following shows a description of how reuse programs for a QnA series serial communication mod-
ule for use on a Q series serial communication module at replacement of module.
Item Relevant device Description Remarks
[Data communications by link instructions]
Link instructions are not provided with a function for per-
forming data communications with another stations PLC
Communication using link CPU on a multidrop connection.
PLC CPU
instruction The communications method must be changed (e.g. com-
munications via MELSECNET/H).
Delete the data communications program using the link
instruction.
[Data communications on the RS-422/485 interface]
The precautions during data communications are the same
as when a QnA series serial communication module is
Communication Refer to the User's Manual
Others used.
target device (Basic).
First check operation of the RS-422/485 interface on the
PLC CPU side, and then insert a wait time, etc. to adjust the
data transmission/reception timing.
2 - 20
2 SERIAL COMMUNICATION MODULE REPLACEMENT
The following shows the precautions relating to Q series serial communication modules when A series/
QnA series PLCs are replaced with Q series PLCs.
2 - 21
2 SERIAL COMMUNICATION MODULE REPLACEMENT
The following shows an example of how to change the nonprocedural communications program on the
A series computer link module for use on a Q series serial communication module when replacing an A
series PLC with a Q series PLC.
When applying the program examples introduced in this section to an actual program, sufficiently study
if there will be any problem in control on the target system.
Send completion
Read request
X1 Buffer memory
FROMP Data reading Address
80H
Y11
Data receiving
Read completion
2 - 22
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Transmission processing
Writes No. of send data.
Send Module Transmis- Send
enable ready sion com- request
flag signal plete
2 - 23
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Transmission processing
(Instruction execution)
Receive
data read
(Instruction execution)
2 - 24
2 SERIAL COMMUNICATION MODULE REPLACEMENT
OUTPUT Personal
Send request computer
Send completion
M0
Read request
X3 Buffer memory
Address
X4
Data reading 600H
INPUT
Read completion Data receiving
M20
2 - 25
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Transmission processing
Specifies channel No. for data
Send Interface transmission.
enable No.
flag
(Instruction execution)
Interface Send Transmis- Data stored in the area starting
No. data sion com- D11 from are sent.
plete
Transmis-
(Flag control at reception
Transmission Transmission normal
sion com- complete flag completion)
normal/abnormal
plete
Transmission Transmission
normal/abnormal failed flag
Transmission
failed flag
2 - 26
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Reception processing
Specifies channel No. for data
CH1 read Interface
No.
reception.
request
(Instruction execution)
Interface Reception Receive data are stored in the
No. complete
area starting from D30.
Reception Reception
normal/abnormal failed flag
Reception
failed flag
2 - 27
2 SERIAL COMMUNICATION MODULE REPLACEMENT
Memo
2 - 28
3 ETHERNET INTERFACE MODULE REPLACEMENT
REPLACEMENT
3-1
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
(a) 10BASE-T
: Compatible, : Partial change required, : Incompatible
Specifications Compat-
Item Precautions for replacement
AJ71E71N3-T, AJ71E71N-T QJ71E71-100 ibility
Transmission speed 10Mbps 100Mbps/10Mbps
Communication mode Half-duplex Full duplex/Half-duplex
Transmission method Base band
Trans-
mission Maximum segment
100m*1
specifi- length
cations Up to two modules can be
Maximum number of connected in a cascade
Cascade connection: Up to 4
nodes/connection connection when using at 100
Mbps.
Number of allowable
simultaneously open 8 connections 16 connections
Trans- connections
fer data
storage Fixed buffer 1k word 8 1k word 16 Change the sequence program
memory as buffer memory
Random access buffer 3k words 2 6k words 1 assignments differ.
(Refer to 3.6.2.)
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment special 32 (I/O assignment intelli 32
points) points)
(b) 10BASE5
: Compatible, : Partial change required, : Incompatible
Specifications Compat-
Item Precautions for replacement
AJ71E71N-B5 QJ71E71-B5 ibility
Transmission speed 10Mbps
Communication mode Half-duplex
Transmission method Base band
Trans- Max. distance between
2500m
mission nodes
specifi- Maximum segment
cations 500m
length
Maximum number of
100/segment
nodes/connection
Minimum node interval 2.5m
Number of allowable
simultaneously open 8 connections 16 connections
Trans- connections
fer data
storage Fixed buffer 1k word 8 1k word 16 Change the sequence program
memory as buffer memory
Random access buffer 3k words 2 6k words 1 assignments differ.
(Refer to 3.6.2.)
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment special 32 (I/O assignment intelli 32
points) points)
12V DC external power supply
Use a transceiver and AUI cables that satisfy specifications.
capacity (Transceiver)
3-2
3 ETHERNET INTERFACE MODULE REPLACEMENT
(c) 10BASE2
: Compatible, : Partial change required, : Incompatible
Specifications Compat-
Item Precautions for replacement
AJ71E71N-B2 QJ71E71-B2 ibility
Transmission speed 10Mbps
Communication mode Half-duplex
Transmission method Base band
Trans- Max. distance between
925m
mission nodes
specifi- Maximum segment
cations 185m
length
Maximum number of
30/segment
nodes/connection
Minimum node interval 0.5m
Number of allowable
simultaneously open 8 connections 16 connections
Trans- connections
fer data
storage Fixed buffer 1k word 8 1k word 16 Change the sequence program
memory as buffer memory
Random access buffer 3k words 2 6k words 1 assignments differ.
(Refer to 3.6.2.)
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment special 32 (I/O assignment intelli 32
points) points)
3-3
3 ETHERNET INTERFACE MODULE REPLACEMENT
Specifications
Compat-
Item AJ71QE71N3-T, Precautions for replacement
QJ71E71-100 ibility
AJ71QE71N-T
Transmission speed 10Mbps 100Mbps/10Mbps
Communication mode Half-duplex Full duplex/Half-duplex
Transmission method Base band
Trans-
mission Maximum segment
100m*1
specifi- length
cations Up to two modules can be
Maximum number of connected in a cascade
Cascade connection: Up to 4
nodes/connection connection when using at 100
Mbps.
Number of allowable
Trans- simultaneously open 8 connections 16 connections
fer data connections
storage
Fixed buffer 1k word 8 1k word 16
memory
Random access buffer 6k words 1
Max. 100,000 times on
No. of E2PROM writes No E2PROM (Refer to 3.8.)
same area in E2PROM
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment special 32 (I/O assignment intelli 32
points) points)
(b) 10BASE5
: Compatible, : Partial change required, : Incompatible
Specifications Compat-
Item Precautions for replacement
AJ71QE71N-B5 QJ71E71-B5 ibility
Transmission speed 10Mbps
Communication mode Half-duplex
Transmission method Base band
Trans- Max. distance between
2500m
mission nodes
specifi- Maximum segment
cations 500m
length
Maximum number of
100/segment
nodes/connection
Minimum node interval 2.5m
Number of allowable
Trans- simultaneously open 8 connections 16 connections
fer data connections
storage
Fixed buffer 1k word 8 1k word 16
memory
Random access buffer 6k words 1
Max. 100,000 times on
No. of E2PROM writes No E2PROM (Refer to 3.8.)
same area in E2PROM
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment special 32 (I/O assignment intelli 32
points) points)
12V DC external power supply
Use a transceiver and AUI cables that satisfy specifications.
capacity (Transceiver)
3-4
3 ETHERNET INTERFACE MODULE REPLACEMENT
(c) 10BASE2
: compatible, : partial change required, : Incompatible
Specifications Compat-
Item Precautions for replacement
AJ71QE71N-B2 QJ71E71-B2 ibility
Transmission speed 10Mbps
Communication mode Half-duplex
Transmission method Base band
Trans- Max. distance between
925m
mission nodes
specifi- Maximum segment
cations 185m
length
Maximum number of
30/segment
nodes/connection
Minimum node interval 0.5m
Number of allowable
Trans- simultaneously open 8 connections 16 connections
fer data connections
storage
Fixed buffer 1k word 8 1k word 16
memory
Random access buffer 6k words 1
Max. 100,000 times on
No. of E2PROM writes No E2PROM (Refer to 3.8.)
same area in E2PROM
32 points/slot 32 points/slot
No. of occupied I/O points (I/O assignment special 32 (I/O assignment intelli 32
points) points)
3-5
3 ETHERNET INTERFACE MODULE REPLACEMENT
*1 When connecting a hub that does not have the auto-negotiation function
On a connection with a hub that does not have the auto-negotiation function,
set the hub side to the half-duplex communication mode.
*2 About wiring of the external power supply terminal (for the transceiver) on the QJ71E71-B5
An FG terminal is not provided for the external power supply terminal on the QJ71E71-B5.
When handling the FG terminal on the external power supply (for the transceiver),
ground the FG signal on the external power supply side.
3-6
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
: Compatible, : Partial change required, : Incompatible
Description
AJ71E71N3-T Compat-
Item QJ71E71-100 Precautions for replacement
AJ71E71N-T ibility
QJ71E71-B5
AJ71E71N-B5
QJ71E71-B2
AJ71E71N-B2
Delete the sequence program of
the section corresponding to the
The state in which data communications with an external device
Initial processing function, and set in the GX
is possible is set.
Developer network parameters.
*1 (Refer to 3.9.)
Change to a sequence program
The communications line for performing data communications that uses the dedicated
Open processing
with external devices is connected. instructions (OPEN, CLOSE).*5
(Refer to 3.9.)
Change to a sequence program
Communications using fixed The fixed buffer on the Ethernet interface module is used to
that uses the dedicated
buffer send/receive the desired data between the PLC CPU and
instructions (BUFSND,
(procedural, nonprocedural) external devices.
BUFRCV). (Refer to 3.9.)
Change the sequence program
Communications using Data is read/written to the random access buffer of the Ethernet
as buffer memory assignments
random access buffer interface module from multiple external devices.
differ. (Refer to 3.6.2.)
Some of the commands and
Read/write communications of
PLC CPU data is read/written to and from external devices. device ranges are restricted.
PLC CPU internal data
(Refer to 3.7.)
Data is sent/received to all external devices on the same
Broadcast communication Ethernet network as the Ethernet interface module
by UDP/IP-based data communications. (broadcast)
Delete the sequence program of
the section corresponding to the
Communications while the Data communications can be continued when the PLC CPU
function, and set in the GX
PLC CPU is stopped enters a stop state. (during passive open processing)
Developer network parameters.
*2
Delete the sequence program of
the section corresponding to the
Router relay function Data communications is performed via a router and a gateway. function, and set in the GX
Developer network parameters.
*3
Change to a sequence program
Existence check of external Whether or not the external device is operating normally after
that uses the dedicated
device the connection is established (in open processing) is checked
instructions (OPEN).*5
The connection is opened with connection for reception and Change to a sequence program
Communications using pairing
connection for transmission as a single pair. (for fixed buffer that uses the dedicated
open
communications) instructions (OPEN).*4*5
Delete the sequence program of
Unit of timer set values for Set the unit (500 ms/2 s) of the section corresponding to the
data communications timer values function.
Fixed to 500 ms
*1 Initial Processing
The Q series performs initial processing by setting the following items in the GX Developer network parameters.
• "Network parameters setting the number of MNET/10H Ethernet cards"
• "Operational settings"
• "Initial settings"
There is no need for a sequence program for initial processing/end processing.
3-7
3 ETHERNET INTERFACE MODULE REPLACEMENT
3-8
3 ETHERNET INTERFACE MODULE REPLACEMENT
Description
AJ71QE71N3-T Compat- Precautions for
Item QJ71E71-100
AJ71QE71N-T ibility replacement
QJ71E71-B5
AJ71QE71N-B5
QJ71E71-B2
AJ71QE71N-B2
Sequence Some communications
program are restricted.*1
Initial The state in which data communications with an external device is
processing GX Developer possible is set.
network
parameters
The communications line for performing data communications with
Open processing
external devices is connected.
Communications using fixed The fixed buffer on the Ethernet interface module is used to
buffer send/receive the desired data between the PLC CPU and external
(procedural, nonprocedural) devices.
Communications using random Data is read/written to the random access buffer of the Ethernet
access buffer interface module from multiple external devices.
Some of the commands
Read/write communications of
PLC CPU data is read/written to and from external devices. and device ranges are
PLC CPU internal data
restricted. (Refer to 3.7.)
Communications using data link Use data link instructions to read/write LPC CPU data of other stations
instructions via Ethernet
The default log-in name
and password have been
File transfer Use FTP commands to read/write individual files from external changed from
(FTP server functions) devices. "AJ71QE71" to
"QJ71E71", so set the
log-in name again.
Data is sent/received to all external devices on the same Ethernet
Broadcast communication network as the Ethernet interface module by UDP/IP-based data
communications. (broadcast)
Delete the sequence pro-
gram of the section cor-
Communications while the PLC Data communications can be continued when the PLC CPU enters a responding to the
CPU is stopped stop state. (during passive open processing) function, and set in the
GX Developer network
parameters. *2
On a network system comprising a mixture of Ethernet and
MELSECNET/H,
MELSECNET/H or MELSECNET/10, or a network system that relays Some communications
MELSECNET/10 relay
through multiple Ethernets, data communications is performed via are restricted.*3
exchange
these multiple networks.
Router relay function Data communications is performed via a router and a gateway.
Existence check of external Whether or not the external device is operating normally after the
device connection is established (in open processing) is checked
The connection is opened with connection for reception and
Communications using pairing Some communications
connection for transmission as a single pair. (For fixed buffer
open are restricted.*4
communications)
Parameter registration to No E2PROM
Saves parameters to E2PROM.
E2PROM (Refer to 3.8.)
3-9
3 ETHERNET INTERFACE MODULE REPLACEMENT
3 - 10
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
: Compatible, : Partial change required, : Incompatible
Description
AJ71E71N3-T Compat- Precautions for
Switch name QJ71E71-100
AJ71E71N-T ibility replacement
QJ71E71-B5
AJ71E71N-B5
QJ71E71-B2
AJ71E71N-B2
Selects the operation mode.
0: Online
1: Offline Set in GX Developer net-
Operation mode setting switch 2: Test 1 work parameters.
(self-loopback test) (1) in *1)
3: Test 2 (RAM test)
4: Test 3 (ROM test)
Selection
of line
Selects line processing when a
process- Closes the line when a
TCP ULP timeout error occurs.
SW1 ing at a TCP ULP timeout error
OFF: Closes the line.
TCP occurs.
ON : Does not close the line.
timeout
error
Selects the communications data
Set in GX Developer
Exchan Data code code type.
SW2 network parameters.
ge con- setting OFF: Binary code
(2) in *1)
dition ON : ASCII code
setting Selects write during RUN
switch CPU com-
enable/disable.
munica- Set in GX Developer
OFF: Write during RUN
SW7 tions network parameters.
disabled
timing (3) in *1)
ON : Write during RUN
setting
enabled
Selects the initial processing A quick start is
Initial startup timing. performed (Initial
SW8
timing OFF: Quickstart processing starts up with
ON : Normal start no delay time.)
2)
1)
3)
3 - 11
3 ETHERNET INTERFACE MODULE REPLACEMENT
Description
AJ71QE71N3-T Compat- Precautions for
Switch name QJ71E71-100
AJ71QE71N-T ibility replacement
QJ71E71-B5
AJ71QE71N-B5
QJ71E71-B2
AJ71QE71N-B2
Selects the operation mode.
0: Online
1: Offline Set in GX Developer
Operation mode setting switch 2: Test 1 (self-loopback test) network parameters.
3: Test 2 (RAM test) (1) in *1)
4: Test 3 (ROM test)
5: Test 4 (E2PROM test)
Selection
of line
Selects line processing when a
process- Closes the line when a
TCP ULP timeout error occurs.
SW1 ing at a TCP ULP timeout error
OFF: Closes the line.
TCP occurs.
ON : Does not close the line.
timeout
error
Selects the communications data
Set in GX Developer
Data code code type.
SW2 network parameters.
setting OFF: Binary code
(2) in *1)
ON : ASCII code
Exchan
Selects the startup method when
ge con- Automatic
a module is started.
dition startup Operation follows the
SW3 OFF: Operation follows Y19.
setting mode setting of Y19.*2
ON : Operation regardless of
switch setting
Y19
Selects write during RUN
CPU
enable/disable.
communi- Set in GX Developer
OFF: Write during RUN
SW7 cations network parameters.
disabled
timing (3) in *1)
ON : Write during RUN
setting
enabled
Selects the initial processing A quick start is
Initial startup timing. performed (Initial
SW8
timing OFF: Quickstart processing starts up with
ON : Normal start no delay time.)
2)
1)
3)
*2 When performing initial processing using GX Developer network parameters, initial processing is executed automatically.
(There is no need for a sequence program for initial processing/end processing.)
3 - 12
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
The Q series is not compatible as parameters that were set in buffer memory are set
in GX Developer network parameters.
Set new parameters.
Description
AJ71QE71N3-T Compat- Precautions for
Parameter name QJ71E71-100
AJ71QE71N-T ibility replacement
QJ71E71-B5
AJ71QE71N-B5
QJ71E71-B2
AJ71QE71N-B2
Network type Network type
Start I/O No. Start I/O No.
Network No. Network No.
Group No. Group No.
Station No. Station No.
On the QnA series,
the mode was set on the
Mode
operation mode setting
Network parameter switch.
IP address setting Operational setting
Initial settings On the QnA series,
the setting was set in the
Open settings sequence program.
Station No. <-> IP information Station No. <-> IP information
FTP Parameters FTP Parameters
Router relay parameter Router relay parameter
Routing parameters Routing parameters
3 - 13
3 ETHERNET INTERFACE MODULE REPLACEMENT
Signal name
AJ71E71N3-T Compat- Precautions for
Input signal QJ71E71-100
AJ71E71N-T ibility replacement
QJ71E71-B5
AJ71E71N-B5
QJ71E71-B2
AJ71E71N-B2
Transmission normal end or reception Transmission normal end or reception
Xn0
end (For connection No.1) end (For connection No.1)
Transmission error detection or Transmission error detection or
Xn1 reception error detection reception error detection
(For connection No.1) (For connection No.1)
Transmission normal end or reception Transmission normal end or reception
Xn2
end (For connection No.2) end (For connection No.2)
Transmission error detection or Transmission error detection or
Xn3 reception error detection reception error detection
(For connection No.2) (For connection No.2)
Transmission normal end or reception Transmission normal end or reception
Xn4
end (For connection No.3) end (For connection No.3)
Transmission error detection or Transmission error detection or
Xn5 reception error detection reception error detection
(For connection No.3) (For connection No.3)
Transmission normal end or reception Transmission normal end or reception
Xn6
end (For connection No.4) end (For connection No.4)
Transmission error detection or Transmission error detection or
Xn7 reception error detection reception error detection
(For connection No.4) (For connection No.4)
Transmission normal end or reception Transmission normal end or reception
Xn8
end (For connection No.5) end (For connection No.5)
Transmission error detection or Transmission error detection or
Xn9 reception error detection reception error detection
(For connection No.5) (For connection No.5)
Transmission normal end or reception Transmission normal end or reception
XnA
end (For connection No.6) end (For connection No.6)
Transmission error detection or Transmission error detection or
XnB reception error detection reception error detection
(For connection No.6) (For connection No.6)
Transmission normal end or reception Transmission normal end or reception
XnC
end (For connection No.7) end (For connection No.7)
Transmission error detection or Transmission error detection or
XnD reception error detection reception error detection
(For connection No.7) (For connection No.7)
Transmission normal end or reception Transmission normal end or reception
XnE
end (For connection No.8) end (For connection No.8)
Transmission error detection or Transmission error detection or
XnF reception error detection reception error detection
(For connection No.8) (For connection No.8)
X(n+1)0 Open end (For connection No.1) Open end (For connection No.1)
X(n+1)1 Open end (For connection No.2) Open end (For connection No.2)
X(n+1)2 Open end (For connection No.3) Open end (For connection No.3)
X(n+1)3 Open end (For connection No.4) Open end (For connection No.4)
X(n+1)4 Open end (For connection No.5) Open end (For connection No.5)
X(n+1)5 Open end (For connection No.6) Open end (For connection No.6)
X(n+1)6 Open end (For connection No.7) Open end (For connection No.7)
X(n+1)7 Open end (For connection No.8) Open end (For connection No.8)
X(n+1)8 Open error detection Open error detection
X(n+1)9 Initial normal end Initial normal end
X(n+1)A Initial error end Initial error end
X(n+1)B Use prohibited Use prohibited
X(n+1)C COM. ERR LED ON COM. ERR LED ON
X(n+1)D
Use prohibited Use prohibited
X(n+1)E
X(n+1)F Watchdog timer error detection Watchdog timer error detection
3 - 14
3 ETHERNET INTERFACE MODULE REPLACEMENT
Signal name
AJ71E71N3-T Compat- Precautions for
Output signal QJ71E71-100
AJ71E71N-T ibility replacement
QJ71E71-B5
AJ71E71N-B5
QJ71E71-B2
AJ71E71N-B2
Transmission request or reception end Transmission request or reception end
Yn0
check (For connection No.1) check (For connection No.1)
Transmission request or reception end Transmission request or reception end
Yn1
check (For connection No.2) check (For connection No.2)
Transmission request or reception end Transmission request or reception end
Yn2
check (For connection No.3) check (For connection No.3)
Transmission request or reception end Transmission request or reception end
Yn3
check (For connection No.4) check (For connection No.4)
Transmission request or reception end Transmission request or reception end
Yn4
check (For connection No.5) check (For connection No.5)
Transmission request or reception end Transmission request or reception end
Yn5
check (For connection No.6) check (For connection No.6)
Transmission request or reception end Transmission request or reception end
Yn6
check (For connection No.7) check (For connection No.7)
Transmission request or reception end Transmission request or reception end
Yn7
check (For connection No.8) check (For connection No.8)
Yn8 Open request (For connection No.1) Open request (For connection No.1)
Yn9 Open request (For connection No.2) Open request (For connection No.2)
YnA Open request (For connection No.3) Open request (For connection No.3)
YnB Open request (For connection No.4) Open request (For connection No.4)
YnC Open request (For connection No.5) Open request (For connection No.5)
YnD Open request (For connection No.6) Open request (For connection No.6)
YnE Open request (For connection No.7) Open request (For connection No.7)
YnF Open request (For connection No.8) Open request (For connection No.8)
Y(n+1)0
Y(n+1)1
Y(n+1)2
Y(n+1)3 Use prohibited Use prohibited
Y(n+1)4
Y(n+1)5
Y(n+1)6
Y(n+1)7 COM. ERR LED OFF request COM. ERR LED OFF request
Y(n+1)8 Use prohibited Use prohibited
Y(n+1)9 Initial request Initial request
Y(n+1)A
Use prohibited
Y(n+1)B
Buffer memory channel
switching is not required.
Delete the sequence
Y(n+1)C Buffer memory channel switching
Use prohibited program of the section
corresponding to the
function.
Y(n+1)D
Y(n+1)E Use prohibited
Y(n+1)F
3 - 15
3 ETHERNET INTERFACE MODULE REPLACEMENT
Signal name
AJ71QE71N3-T Compat- Precautions for
Input signal QJ71E71-100
AJ71QE71N-T ibility replacement
QJ71E71-B5
AJ71QE71N-B5
QJ71E71-B2
AJ71QE71N-B2
Transmission normal end or reception Transmission normal end or reception
Xn0
end (For connection No.1) end (For connection No.1)
Transmission error detection or Transmission error detection or
Xn1 reception error detection reception error detection
(For connection No.1) (For connection No.1)
Transmission normal end or reception Transmission normal end or reception
Xn2
end (For connection No.2) end (For connection No.2)
Transmission error detection or Transmission error detection or
Xn3 reception error detection reception error detection
(For connection No.2) (For connection No.2)
Transmission normal end or reception Transmission normal end or reception
Xn4
end (For connection No.3) end (For connection No.3)
Transmission error detection or Transmission error detection or
Xn5 reception error detection reception error detection
(For connection No.3) (For connection No.3)
Transmission normal end or reception Transmission normal end or reception
Xn6
end (For connection No.4) end (For connection No.4)
Transmission error detection or Transmission error detection or
Xn7 reception error detection reception error detection
(For connection No.4) (For connection No.4)
Transmission normal end or reception Transmission normal end or reception
Xn8
end (For connection No.5) end (For connection No.5)
Transmission error detection or Transmission error detection or
Xn9 reception error detection reception error detection
(For connection No.5) (For connection No.5)
Transmission normal end or reception Transmission normal end or reception
XnA
end (For connection No.6) end (For connection No.6)
Transmission error detection or Transmission error detection or
XnB reception error detection reception error detection
(For connection No.6) (For connection No.6)
Transmission normal end or reception Transmission normal end or reception
XnC
end (For connection No.7) end (For connection No.7)
Transmission error detection or Transmission error detection or
XnD reception error detection reception error detection
(For connection No.7) (For connection No.7)
Transmission normal end or reception Transmission normal end or reception
XnE
end (For connection No.8) end (For connection No.8)
Transmission error detection or Transmission error detection or
XnF reception error detection reception error detection
(For connection No.8) (For connection No.8)
X(n+1)0 Open end (For connection No.1) Open end (For connection No.1)
X(n+1)1 Open end (For connection No.2) Open end (For connection No.2)
X(n+1)2 Open end (For connection No.3) Open end (For connection No.3)
X(n+1)3 Open end (For connection No.4) Open end (For connection No.4)
X(n+1)4 Open end (For connection No.5) Open end (For connection No.5)
X(n+1)5 Open end (For connection No.6) Open end (For connection No.6)
X(n+1)6 Open end (For connection No.7) Open end (For connection No.7)
X(n+1)7 Open end (For connection No.8) Open end (For connection No.8)
X(n+1)8 Open error detection Open error detection
X(n+1)9 Initial normal end Initial normal end
X(n+1)A Initial error end Initial error end
X(n+1)B Use prohibited Use prohibited
X(n+1)C COM. ERR LED ON COM. ERR LED ON
X(n+1)D E2PROM read complete No E2PROM
Use prohibited
X(n+1)E E2PROM write complete (Refer to 3.8.)
X(n+1)F Watchdog timer error detection Watchdog timer error detection
3 - 16
3 ETHERNET INTERFACE MODULE REPLACEMENT
Signal name
AJ71QE71N3-T Compat- Precautions for
Output signal QJ71E71-100
AJ71QE71N-T ibility replacement
QJ71E71-B5
AJ71QE71N-B5
QJ71E71-B2
AJ71QE71N-B2
Transmission request or reception end Transmission request or reception end
Yn0
check (For connection No.1) check (For connection No.1)
Transmission request or reception end Transmission request or reception end
Yn1
check (For connection No.2) check (For connection No.2)
Transmission request or reception end Transmission request or reception end
Yn2
check (For connection No.3) check (For connection No.3)
Transmission request or reception end Transmission request or reception end
Yn3
check (For connection No.4) check (For connection No.4)
Transmission request or reception end Transmission request or reception end
Yn4
check (For connection No.5) check (For connection No.5)
Transmission request or reception end Transmission request or reception end
Yn5
check (For connection No.6) check (For connection No.6)
Transmission request or reception end Transmission request or reception end
Yn6
check (For connection No.7) check (For connection No.7)
Transmission request or reception end Transmission request or reception end
Yn7
check (For connection No.8) check (For connection No.8)
Yn8 Open request (For connection No.1) Open request (For connection No.1)
Yn9 Open request (For connection No.2) Open request (For connection No.2)
YnA Open request (For connection No.3) Open request (For connection No.3)
YnB Open request (For connection No.4) Open request (For connection No.4)
YnC Open request (For connection No.5) Open request (For connection No.5)
YnD Open request (For connection No.6) Open request (For connection No.6)
YnE Open request (For connection No.7) Open request (For connection No.7)
YnF Open request (For connection No.8) Open request (For connection No.8)
Y(n+1)0 E2PROM read request No E2PROM
Y(n+1)1 E2PROM write request (Refer to 3.8.)
Y(n+1)2
Y(n+1)3 Use prohibited
Y(n+1)4 Use prohibited
Y(n+1)5
Y(n+1)6
Y(n+1)7 COM. ERR LED OFF request COM. ERR LED OFF request
Y(n+1)8 Use prohibited Use prohibited
Y(n+1)9 Initial request Initial request
Y(n+1)A
Y(n+1)B
Y(n+1)C
Use prohibited Use prohibited
Y(n+1)D
Y(n+1)E
Y(n+1)F
3 - 17
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
There is no compatibility in the buffer memory assignments between the A series and the Q series.
Make a new sequence program.
: Compatible, : Partial change required, : Incompatible
3 - 18
3 ETHERNET INTERFACE MODULE REPLACEMENT
3 - 19
3 ETHERNET INTERFACE MODULE REPLACEMENT
3 - 20
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
: Compatible, : Partial change required, : Incompatible
Compatibility
Sequence program Precautions for
Item Program (Communication
(Ethernet Interface replacement
target device)
module)
[PLC side]
The sequence program is
not compatible as buffer
Communications using memory assignments
fixed buffer differ.
(procedural, nonprocedural) Change to a sequence
program that uses the
dedicated instructions
(BUFSND/BUFRCV).
[PLC side]
The sequence program is
not compatible as buffer
Communications using memory assignments
random access buffer differ.
Check the buffer memory
assignments and change
the sequence program.
[Communication target
device side]
Read/write of PLC CPU
Some of the command and
internal data
device ranges are
restricted. *1
(3) The following devices are accessed on special relays (M9000 onwards) and special registers (D9000 onwards):
• SD1000 to SD1255 are accessed by specifying D9000 to D9255.
• SM1000 to SM1255 are accessed by specifying M9000 to M9255.
3 - 21
3 ETHERNET INTERFACE MODULE REPLACEMENT
Compatibility
Sequence program Precautions for
Item Program (Communication
(Ethernet Interface replacement
target device)
module)
Communications using
fixed buffer
(procedural, nonprocedural)
Communications using
random access buffer
[Communication target
device side]
Read/write of PLC CPU
Some of the command and
internal data
device ranges are
restricted. *1
Communications using data
link instructions
[Communication target
device side]
The default log-in name
File transfer and password have been
(FTP server functions) changed from
"AJ71QE71" to
"QJ71E71", so set the
log-in name again.
(2) The program for accessing the PLC CPU in the data link system cannot be used.
The following devices cannot be accessed from external devices:
(The QCPU (Q mode) cannot be connected to MELSECNET (II) and MELSECNET/B.)
3 - 22
3 ETHERNET INTERFACE MODULE REPLACEMENT
3 - 23
3 ETHERNET INTERFACE MODULE REPLACEMENT
The following shows a program example at transition from the A series to the Q series.
When applying the program example introduced in this section to an actual program,
sufficiently study if there will be any problem in control on the target system.
(b) Q series
Ethernet interface module *1 External device
BUFSND instruction
Q25HCPU For connection No.1 fixed buffer transmission
3 - 24
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
The A series performs initial processing by writing parameters for initial processing
by the sequence program to buffer memory and turning the initial request signal (Y19) ON.
(a) Program conditions
The following shows a program example for performing initial processing
when the communication start instruction (X40) is turned ON.
Set the parameters for initial processing as follows. (Otherwise, use default values.)
Local station
IP address
Initial
request
Initial
request
3 - 25
3 ETHERNET INTERFACE MODULE REPLACEMENT
(2) Q series
The Q series performs initial processing by setting the following items
in the GX Developer network parameters.
• "Operational settings"
• "Initial settings"
3 - 26
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
[Open processing]
The A series performs open processing by writing communication parameters
by the sequence program to buffer memory and turning the open request signal (Y8) ON.
[Close processing]
The A series performs close processing by turning the open request signal (Y8) OFF,
or by the close request (FIN) from an external device.
(a) Program conditions
The following shows a program example for performing open processing (unpassive open)
on connection No.1 when initial normal end (X19) turns ON.
Set the communication parameters as follows. (Otherwise, use default values.)
3 - 27
3 ETHERNET INTERFACE MODULE REPLACEMENT
Local
Written to the connection No.1
station exchange address setting
port area.
No. -1
Open
request
-1
Open
Connection No.1 open error
Open Open Open WDT
error request comple- error error processing.
detection -1 tion detection code -1
CON-1
Open
error
code-1
Open Open
error error
code -1 code -1
Close
command
accept-
ance -1
3 - 28
3 ETHERNET INTERFACE MODULE REPLACEMENT
(2) Q series
[Open processing]
The Q series uses the dedicated instruction (OPEN) to perform open processing.
The communication parameters are set in the control data of the dedicated instruction (OPEN)
or at "Network parameter" - "Open settings" on GX Developer.
[Close processing]
The Q series performs close processing by either using the dedicated instruction (CLOSE),
or by the close request (FIN) from an external device.
(a) Program conditions
The following shows a program example for performing open processing (unpassive open)
on connection No.1 when initial normal end (X19) turns ON with the initial normal end
signal (M5000) ON.
Set the communication parameters at "Network parameters" - "Open settings" in GX Developer.
3 - 29
3 ETHERNET INTERFACE MODULE REPLACEMENT
\
Read the open request signal
Open Connection 1
request Open information from the connec-
signal request signal tion status information area.
CLOSE
instruction
executed
failed
POINT
When "Operational settings" - "Initial timing" in GX Developer is set to "Always wait for OPEN",
the sequence program for open processing/close processing is not required.
3 - 30
3 ETHERNET INTERFACE MODULE REPLACEMENT
(1) A series
[Transmission processing]
The A series performs data transmission processing to external devices from the fixed buffer
by writing the send data to the fixed buffer area by the sequence program, and turning the send
request signal (Y0) ON.
[Reception processing]
On the A series, the reception completion signal (X0) turns ON when data is received to
the fixed buffer area.
The A series performs data reception processing by reading received data
from the fixed buffer area by the sequence program, and turning the reception completion
confirmation signal (Y0) ON.
(a) Program conditions
The following shows a program example for performing transmission processing by fixed buffer No.1
when the fixed buffer transmission instruction (X43) is turned ON.
Fixed Send
BUF send command
command acceptance-1
BUF CH0
switch
request-1
BUF CH BUF CH
switch switch
3 - 31
3 ETHERNET INTERFACE MODULE REPLACEMENT
Send
Set the data length to 3
BUF CH0 Communi-
switch- cation ena- data words.
ing-1 ble-1 length
Send
data 2
Send
data 3
Send
Writes the data length
data and send data in the
length fixed buffer No.1 area.
Send
request
-1
BUF CH0
switch-
ing-1
Send
request
-1
3 - 32
3 ETHERNET INTERFACE MODULE REPLACEMENT
(2) Q series
[Transmission processing]
The Q series uses the dedicated instruction (BUFSND) to perform data transmission
from the fixed buffer to an external device.
[Reception processing]
On the Q series, the fixed buffer reception status signal (corresponding bit of address 5005H)
in buffer memory turns ON when data is received to the fixed buffer area.
The Q series uses the dedicated instruction (BUFRCV) to perform data reception.
(a) Program condition
The following shows a program example for performing transmission processing
by fixed buffer No.1 when the transmission instruction (M7000) is turned ON.
Send data
Send
data
setting
Send
data
setting
Send
data
setting
Transmission processing
Data length BUFSND
instruction
by the connection 1.
setting (No. of
words) complete
device
3 - 33
3 ETHERNET INTERFACE MODULE REPLACEMENT
Memo
3 - 34
4 EXTERNAL DIMENSIONS
4 4EXTERNAL DIMENSIONS
4.2(0.17)
(0.2)
5
RUN 2-C/N
2-SD 2-P/S
2-RD 2-PRO
2-SIO
2-NEU 4-C/N L4
L4
2-ACK 4-P/S L5
L5
2-NAK 4-PRO L6
L6
L 1 4-NEU
L1 4-SIO
L 2 4-ACK
L2
L3
L 3 4-NAK CPUR/W
4-SD COM
4-RD M.D.M
M.D.L
B0
B1
B2
MODE
STATION NO.
10
SW11 ON
12
240(9.45)
13
250(9.84)
14
15
16
17
18
21
22
23
24
RS-232-C
RS-422
RS-485
SDA
SG
SDB
FG
RDA
NC
RDB
(0.2)
5
106(4.17) 25 37.5
(0.98) (1.48)
4.2 131(5.16)
(0.17)
(When using connector) (When using terminal block)
Cable diameter 4 10 85
RS-422
RS-485
(3.35)
SG
R1 FG
r1 RDA
NC
RDB
R2
(Unit: mm (inch))
R1 (Bending radius near terminal block) : Cable diameter x 4 (reference value)
R2 (Bending radius near connector) : Cable diameter x 4 (reference value)
r1 (Bending radius near solderless terminal) : Connectable as long as not bended extremely
4-1
4 EXTERNAL DIMENSIONS
89A
EF 2
89A
EF 2
0:ONLINE
89A
EF 2
89A
EF 2
0:ONLINE
01
01
1:OFFLINE 1:OFFLINE
01
67
67
01
1:OFFLINE
67
1:OFFLINE
67
345 345
345
2:TEST1
345
2:TEST1 2:TEST1
2:TEST1 3:TEST2 3:TEST2
3:TEST2 3:TEST2 ON OFF ON
ON ON 4:TEST3 4:TEST3
4:TEST3 4:TEST3
SW1 SW1
SW1 SW1 SW2 SW2
SW2 SW2 SW3 SW3
SW3 SW3 SW4 SW4
SW4 SW4 SW5 SW5
SW5 SW5 SW6 SW6
SW6 SW6 SW7 SW7
SW7 SW7
250(9.84)
SW8 SW8
SW8 SW8
10BASE-T
EXT.PW
EXT.PW
(FG)
10BASE-T
10BASE5
56(2.20)
R1 R1
R1
14
(0.55)
(Unit: mm(inch))
4-2
4 EXTERNAL DIMENSIONS
23
23
STATION STATION
23
23
23
23
78 9
78 9
78 9
78 9
78 9
78 9
01 NO. 01 01 NO. NO.
01 01 01
ABCD
ABCD
ABCD
2345
ABCD
ABCD
2345
2345
2345
2345
MODE MODE MODE
EF01 EF01 EF01 EF01 EF01
SW SW SW
240(9.45)
250(9.84)
01 01 01
02 02 02
03 03 03
04 04 04
05 05 05
06 06 06
07 07 07
08 08 08
09 09 09
10 10 10
11 11 11
12 12 12
CH1
RS232C
CH1 CH1
RS232 RS422
CH2 CH2
RS422 RS422
RS485 RS485
SDA SDA
SG SG
RDA RDA
FG FG
RDB RDB
(0.2)
5
Cable diameter 4 10
R2
CH2
85 RS422
RS485
(Unit: mm (inch))
(3.35) SG
FG
4-3
4 EXTERNAL DIMENSIONS
89A
EF 2
89A
EF 2
0:ONLINE
89A
EF 2
89A
EF 2
0:ONLINE
01
01
1:OFFLINE 1:OFFLINE
01
67
67
01
1:OFFLINE
67
1:OFFLINE
67
345 345
345
2:TEST1
345
2:TEST1 2:TEST1
2:TEST1 3:TEST2 3:TEST2
3:TEST2 3:TEST2 ON OFF ON
ON ON 4:TEST3 4:TEST3
4:TEST3 4:TEST3 5:TEST4 SW1 5:TEST4 SW1
5:TEST4 SW1 5:TEST4 SW1
SW2 SW2
SW2 SW2 SW3 SW3
SW3 SW3 SW4 SW4
SW4 SW4 SW5 SW5
SW5 SW5 SW6 SW6
SW6 SW6 SW7 SW7
SW7 SW7
250(9.84)
SW8 SW8
SW8 SW8
10BASE-T
EXT.PW
EXT.PW
(FG)
10BASE-T
10BASE5
56(2.20)
R1 R1
R1
14
(0.55)
(Unit: mm (inch))
4-4
4 EXTERNAL DIMENSIONS
CH1
RS-422/485
SDA
CH1
SDB
98(3.86)
RS-232
RDA
CH1
RS-232 RDB
SG
(FG)
CH2
RS-422/485
SDA
SDA
1
SG SDB
SDB
2
RDA
(FG)
3 CH2 RDB
4 RS-232
RDA SG
(FG)
5
6 (FG)
RDB
CH2
7
RS-422
/485
Cable diameter 4 10
SDA
1
SG
SDB R3
(FG)
3
RDA
5
R1
(FG)
6
r2
r1 RDB
7
CH2
RS-422
/485
R2
(Unit: mm (inch))
4-5
4 EXTERNAL DIMENSIONS
10BASE 5
10BASE-T/100BASE-TX
12 12V
12G
EXT. POWER
23.65(0.43)
R1
R1
11.5
DC power supply (0.45)
for transceiver
(Unit: mm (inch))
4-6
APPENDIX
APPENDIX
APPENDIX
(2) A series
No. Manual name Manual No. Model code
1 Computer Link Module Guidebook SH-3510 13JE76
Computer Link Module User’s Manual
2 SH-3511 13JE77
(Com.link func./Print.func.)
3 For A Ethernet Interface Module User’s Manual SH-080192 13JR45
(4) Q series
No. Manual name Manual No. Model code
Q Corresponding Serial Communication Module User’s
1 SH-080006 13JL86
Manual (Basic)
Q Corresponding Serial Communication Module User’s
2 SH-080007 13JL87
Manual (Application)
Q Corresponding MELSEC Communication Protocol
3 SH-080008 13JF89
Reference Manual
Q Corresponding Ethernet Interface Module User’s Manual
4 SH-080009 13JL88
(Basic)
Q Corresponding Ethernet Interface Module User’s Manual
5 SH-080010 13JL89
(Application)
Q Corresponding Ethernet Interface Module User’s Manual
6 SH-080180 13JR40
(Web function)
GX Configurator-SC Version 2 Operating Manual
7 SH-080393E 13JU46
(Protocol FB support function)
App- 1
APPENDIX
Memo
App- 2
WARRANTY
Please confirm the following product warranty details before using this product.
3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center
may differ.
6. Product application
(1) In using the Mitsubishi MELSEC programmable logic controller, the usage conditions shall be that the application will not lead
to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and
fail-safe functions are systematically provided outside of the device for any problem or fault.
(2) The Mitsubishi programmable logic controller has been designed and manufactured for applications in general industries, etc.
Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by
respective power companies, and applications in which a special quality assurance system is required, such as for Railway
companies or Public service purposes shall be excluded from the programmable logic controller applications.
In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical applications,
incineration and fuel devices, manned transportation, equipment for recreation and amusement, and safety devices, shall also
be excluded from the programmable logic controller range of applications.
However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi representative
outlining the special requirements of the project, and providing that all parties concerned agree to the special circumstances,
solely at the users discretion.
Microsoft Windows, Microsoft Windows NT are registered trademarks of Microsoft Corporation in the United States and other
countries.
Pentium is a registered trademark of Intel Corporation in the United States and other countries.
Ethernet is a registered trademark of Xerox. Co., Ltd in the United States.
Other company and product names herein are either trademarks or registered trademarks of their respective owners.
MITSUBISHI ELECTRIC
MITSUBISHI ELECTRIC EUROPE GEVA AUSTRIA UAB UTU POWEL LITHUANIA Avtomatika Sever Ltd. RUSSIA
EUROPE B.V. Wiener Straße 89 Savanoriu pr. 187 Lva Tolstogo St. 7, Off. 311
German Branch AT-2500 Baden LT-2053 Vilnius RU-197376 St Petersburg
Gothaer Straße 8 Phone: +43 (0) 2252 / 85 55 20 Phone: +370 (0) 52323-101 Phone: +7 812 / 11 83 238
D-40880 Ratingen Fax: +43 (0) 2252 / 488 60 Fax: +370 (0) 52322-980 Fax: +7 812 / 11 83 239
Phone: +49 (0) 2102 / 486-0 e mail: office@geva.at e mail: powel@utu.lt e mail: as@avtsev.spb.ru
Fax: +49 (0) 2102 / 486-1120
e mail: megfamail@meg.mee.com TEHNIKON BELARUS INTEHSIS SRL MOLDOVA CONSYS RUSSIA
Oktjabrskaya 16/5, Ap 704 Cuza-Voda 36/1-81 Promyshlennaya St. 42
MITSUBISHI ELECTRIC FRANCE BY-220030 Minsk MD-2061 Chisinau RU-198099 St Petersburg
EUROPE B.V. Phone: +375 (0)17 / 22 75 704 Phone: +373 (0)2 / 562 263 Phone: +7 812 / 325 36 53
French Branch Fax: +375 (0)17 / 22 76 669 Fax: +373 (0)2 / 562 263 Fax: +7 812 / 147 20 55
25, Boulevard des Bouvets e mail: tehnikon@belsonet.net e mail: intehsis@mdl.net e mail: consys@consys.spb.ru
F-92741 Nanterre Cedex
Phone: +33 1 55 68 55 68 Getronics b.v. BELGIUM Getronics b.v. NETHERLANDS Electrotechnical RUSSIA
Fax: +33 1 55 68 56 85 Control Systems Control Systems Systems Siberia
e mail: factory.automation@fra.mee.com Pontbeeklaan 43 Donauweg 2 B Partizanskaya St. 27, Office 306
B-1731 Asse-Zellik NL-1043 AJ Amsterdam RU-121355 Moscow
MITSUBISHI ELECTRIC IRELAND Phone: +32 (0) 2 / 467 17 51 Phone: +31 (0) 20 / 587 67 00 Phone: +7 095/ 416-4321
EUROPE B.V. Fax: +32 (0) 2 / 467 17 45 Fax: +31 (0) 20 / 587 68 39 Fax: +7 095/ 416-4321
Irish Branch e mail: infoautomation@getronics.com e mail: info.gia@getronics.com e mail: info@eltechsystems.ru
Westgate Business Park, Ballymount
IRL-Dublin 24 TELECON CO. BULGARIA Beijer Electronics AS NORWAY Electrotechnical RUSSIA
Phone: +353 (0) 1 / 419 88 00 4, A. Ljapchev Blvd. Teglverksveien 1 Systems Siberia
Fax: +353 (0) 1 / 419 88 90 BG-1756 Sofia N-3002 Drammen Shetinkina St. 33, Office 116
e mail: sales.info@meir.mee.com Phone: +359 (0) 2 / 97 44 05 8 Phone: +47 (0) 32 / 24 30 00 RU-630088 Novosibirsk
Fax: +359 (0) 2 / 97 44 06 1 Fax: +47 (0) 32 / 84 85 77 Phone: +7 3832 / 22-03-05
MITSUBISHI ELECTRIC ITALY e mail: — e mail: info@beijer.no Fax: +7 3832 / 22-03-05
EUROPE B.V. e mail: info@eltechsystems.ru
Italian Branch INEA CR d.o.o. CROATIA MPL Technology Sp. z o.o. POLAND
Via Paracelso 12 Drvinje 63 ul. Sliczna 36 Elektrostyle RUSSIA
I-20041 Agrate Brianza (MI) HR-10000 Zagreb PL-31-444 Kraków ul. Garschina 11
Phone: +39 039 6053 1 Phone: +385 (0) 1 / 36 67 140 Phone: +48 (0) 12 / 632 28 85 RU-140070 Moscow
Fax: +39 039 6053 312 Fax: +385 (0) 1 / 36 67 140 Fax: +48 (0) 12 / 632 47 82 Phone: +7 095 / 514 9316
e mail: factory.automation@it.mee.com e mail: — e mail: krakow@mpl.pl Fax: +7 095 / 514 9317
e mail: info@estl.ru
MITSUBISHI ELECTRIC SPAIN AutoCont CZECH REPUBLIC Sirius Trading & Services srl ROMANIA
EUROPE B.V. Control Systems s.r.o. Str. Biharia No. 67-77 Elektrostyle RUSSIA
Spanish Branch Nemocnicni 12 RO-013981 Bucuresti 1 Krasnij Prospekt 220-1
Carretera de Rubí 76-80 CZ-702 00 Ostrava 2 Phone: +40 (0) 21 / 201 1146 Office No. 312
E-08190 Sant Cugat del Vallés Phone: +420 59 / 6152 111 Fax: +40 (0) 21 / 201 1148 RU-630049 Novosibirsk
Phone: +34 9 3 / 565 3131 Fax: +420 59 / 6152 562 e mail: sirius@siriustrading.ro Phone: +7 3832 / 10 66 18
Fax: +34 9 3 / 589 2948 e mail: consys@autocont.cz Fax: +7 3832 / 10 66 26
INEA d.o.o. SLOVENIA e mail: info@estl.ru
e mail: industrial@sp.mee.com louis poulsen DENMARK Stegne 11
MITSUBISHI ELECTRIC UK industri & automation SI-1000 Ljubljana ICOS RUSSIA
EUROPE B.V. Geminivej 32 Phone: +386 (0) 1-513 8100 Industrial Computer Systems Zao
UK Branch DK-2670 Greve Fax: +386 (0) 1-513 8170 Ryazanskij Prospekt 8a, Office 100
Travellers Lane Phone: +45 (0) 70 / 10 15 35 e mail: inea@inea.si RU-109428 Moscow
GB-Hatfield Herts. AL10 8 XB Fax: +45 (0) 43 / 95 95 91 Phone: +7 095 / 232 - 0207
e mail: lpia@lpmail.com Beijer Electronics AB SWEDEN Fax: +7 095 / 232 - 0327
Phone: +44 (0) 1707 / 27 61 00 Box 426 e mail: mail@icos.ru
Fax: +44 (0) 1707 / 27 86 95 UTU Elektrotehnika AS ESTONIA S-20124 Malmö
e mail: automation@meuk.mee.com Pärnu mnt.160i Phone: +46 (0) 40 / 35 86 00 NPP Uralelektra RUSSIA
MITSUBISHI ELECTRIC JAPAN EE-11317 Tallinn Fax: +46 (0) 40 / 35 86 02 ul. Sverdlova 11a
CORPORATION Phone: +372 (0) 6 / 51 72 80 e mail: info@beijer.se RU-620027 Ekaterinburg
Office Tower “Z” 14 F Fax: +372 (0) 6 / 51 72 88 Phone: +7 34 32 / 53 27 45
e mail: utu@utu.ee ECONOTEC AG SWITZERLAND Fax: +7 34 32 / 53 27 45
8-12,1 chome, Harumi Chuo-Ku Postfach 282 e mail: elektra@etel.ru
Tokyo 104-6212 Beijer Electronics OY FINLAND CH-8309 Nürensdorf
Phone: +81 3 6221 6060 Ansatie 6a Phone: +41 (0) 1 / 838 48 11 SSMP Rosgidromontazh Ltd. RUSSIA
Fax: +81 3 6221 6075 FIN-01740 Vantaa Fax: +41 (0) 1 / 838 48 12 23, Lesoparkovaya Str.
MITSUBISHI ELECTRIC USA Phone: +358 (0) 9 / 886 77 500 e mail: info@econotec.ch RU-344041 Rostov On Don
AUTOMATION Fax: +358 (0) 9 / 886 77 555 Phone: +7 8632 / 36 00 22
e mail: info@beijer.fi GTS TURKEY Fax: +7 8632 / 36 00 26
500 Corporate Woods Parkway Darülaceze Cad. No. 43 Kat. 2 e mail: —
Vernon Hills, IL 60061 UTECO A.B.E.E. GREECE TR-80270 Okmeydani-Istanbul
Phone: +1 847 / 478 21 00 5, Mavrogenous Str. Phone: +90 (0) 212 / 320 1640 STC Drive Technique RUSSIA
Fax: +1 847 / 478 22 83 GR-18542 Piraeus Fax: +90 (0) 212 / 320 1649 ul. Bajkalskaja 239, Office 2 - 23
Phone: +302 (0) 10 / 42 10 050 e mail: gts@turk.net RU-664075 Irkutsk
Fax: +302 (0) 10 / 42 12 033 Phone: +7 3952 / 24 38 16
e mail: sales@uteco.gr CSC Automation Ltd. UKRAINE Fax: +7 3952 / 23 02 98
MIDDLE EAST REPRESENTATIVE 15, M. Raskova St., Fl. 10, Office 1010 e mail: privod@irk.ru
Meltrade Automatika Kft. HUNGARY UA-02002 Kiev
TEXEL Electronics Ltd. ISRAEL 55, Harmat St. Phone: +380 (0) 44 / 238-83-16 STC Drive Technique RUSSIA
Box 6272 HU-1105 Budapest Fax: +380 (0) 44 / 238-83-17 Poslannikov Per. 9, str.1
IL-42160 Netanya Phone: +36 (0)1 / 2605 602 e mail: csc-a@csc-a.kiev.ua RU-107005 Moscow
Phone: +972 (0) 9 / 863 08 91 Fax: +36 (0)1 / 2605 602 Phone: +7 095 / 790-72-10
Fax: +972 (0) 9 / 885 24 30 e mail: office@meltrade.hu Fax: +7 095 / 790-72-12
e mail: texel_me@netvision.net.il e mail: info@privod.ru
SIA POWEL LATVIA
Lienes iela 28
LV-1009 Riga
Phone: +371 784 / 22 80 AFRICAN REPRESENTATIVE
Fax: +371 784 / 22 81
e mail: utu@utu.lv CBI Ltd. SOUTH AFRICA
Private Bag 2016
ZA-1600 Isando
Phone: +27 (0) 11/ 928 2000
Fax: +27 (0) 11/ 392 2354
e mail: cbi@cbi.co.za