ATV303 complete parameters list ENGLISH

S1B4488905
Reference mode F006 Current measurement circuit 203 Logic inputs type 217 Speed Template 407 Command channel 1
Reference menu

menu
F007 Internal thermal sensor fault [00]* positive [00]* Standard [01]* Terminals

I/O
402 External reference value
403 Analog input virtual F008 Internal CPU [01] negative [02] DeadBand [02] Local
801 Speed reference F009 Overbraking 204- AI1 CONFIGURATION MENU 300- MOTOR CONTROL MENU [03] Remote display

Control menu (cont.)


59.11 Internal PID reference F010 Overcurrent 204.0 AI1 type 301 Standard motor frequency [10] Modbus
806 PID reference value F011 Drive overheat [5U]* Voltage: 0-5Vdc [00]* 50Hz 408 Forced local assignment
F012 Process overload [10U] Voltage: 0-10Vdc [01] 60Hz [00]* No: Function inactive
Monitoring mode F013 Motor overload [0A] Current: x-y mA 302 Rated motor power [L1H] LI1 active High
402 External reference value F014 1 Output phase loss [LIU] Logic inputs Drive power (-5 to +2) depending on drive rating [L2H] LI2 active High
403 Analog input virtual F015 3 Output phases loss 204.1 AI1 current scaling parameter of 0% 303 Rated motor cos phi [L3H] LI3 active High
Monitoring parameter

801 Speed reference F016 Main overvoltage 0-20mA (4mA*) 0.5 to 1 (depending on drive rating) [L4H] LI4 active High

Detected fault codes


802 Output frequency F017 Input phase loss 204.2 AI1 current scaling parameter of 100% 304 Rated motor voltage [LUH] LIU active High
803 Motor current F018 Motor short-circuit 0-20mA (20mA*) 360 to 460V (380V*) 409 Forced local reference
804 PID error F019 Ground short-circuit 205 R1 assignment 305 Rated motor current [00]* Not assigned
805 PID Feedback F020 IGBT short circuit [00] Not assigned 0.25 to 1.5In (depending on drive rating) [01] Terminal
806 PID reference F021 Load short circuit [01]* No error detected 306 Rated motor frequency [163] Remote display
807 Main voltage F022 Modbus interruption [02] Drive run 10 to 400Hz (50Hz*) [183] Integrated jog dial
808 Motor thermal state F024 HMI communication [04] Frequency threshold reached 307 Rated motor speed 500- FUNCTION MENU
809 Drive thermal state F025 Overspeed [05] HSP reached 0 to 24000rpM (depending on drive rating) 501- RAMP MENU
810 Output power F026 PI feedback fault [06] I threshold reached 308 Maximum frequency 501.0 Acceleration

3
[07] Frequency reference reached

1
811 Product status F027 IGBT overheat 10 to 400Hz (60Hz*) 0.0 to 999.9s (3.0s*)
[00] Drive ready F028 Autotuning fault [08] Motor thermal reached 309 Motor control type 501.1 Deceleration
[01] Drive running F029 Process underload [21] Underload alarm [00] Performance: Vector control 0.0 to 999.9s (3.0s*)

Motor control menu


[02] Acceleration [22] Overload alarm [03]* Standard: U/F 2 points 501.2 Ramp shape assignment
F030 Undervoltage [123] Loss of 4-20mA signal
[03] Deceleration F031 Incorrect configuration [06] Pump: U²/F [00]* Linear
[04] DC injection braking in progress F032 Invalid configuration 206- LO1 CONFIGURATION MENU 310 IR compensation [01] S shape
Drive status

[05] Current limitaion state F033 AI1 current loss 206.0 LO1 Assignment 25 to 200% (100%*) [02] U shape

Function / Ramp menu


[06] Freewheel stop control or freewheel state F034 Download invalid configuration [00]* Not assigned 311 Slip compensation 501.3 Ramp switching commutation
[07] Auto-adatated deceleration [01] No error detected 0 to 150% (100%*) [00]* Not assigned
[08] Controlled stop on mains phase loss Configuration mode [02] Drive run 312 Frequency loop stability [L1H] LI1 active High
[09] Auto-tuning in progress 301 Standard motor frequency [04] Frequency threshold reached 0 to 100% (20%*) [L2H] LI2 active High
[10] Fast stop state [00] 50Hz IEC [05] HSP reached 313 Frequency loop gain [L3H] LI3 active High
[11] No line power state [01] 60Hz NEMA [06] I threshold reached 0 to 100% (20%*) [L4H] LI4 active High
[12] Drive in back state 401 Reference channel 1 [07] Frequency reference reached 314 Flux Profil [LUH] LIU active High
[13] Remote control mode [01] Terminal [08] Motor thermal reached 0 to 100% (20%*) [L1L] LI1 active low
[14] Local control mode [163] Remote display [21] Underload alarm 315 Switching frequency [L2L] LI2 active low

I/O menu (cont.)


900- MAINTENANCE MENU [164] Modbus [22] Overload alarm 2 to 12kHz (4kHz*) [L3L] LI3 active low
901 State of logic inputs LI1 to LI4 [183] Integrated display with Jog dial [123] AI1 alarm 4-20mA 317 Motor noise reduction [L4L] LI4 active low
902 State of the logic output LO1 and relay R1 501.0 Acceleration [126] Auxiliary pump active [00]* No [LUL] LIU active low
903 Display of high speed value 0.0 s to 999.9s (3.0s*) 206.1 LO1 status (output active level) [01] Yes 501.4 Acceleration 2
904 Drive Power rating 501.1 Deceleration [00]* Positive : hight activation level 318 Auto-tuning 0.0 to 999.9s (5.0s*)
037 0.0 s to 999.9s (3.0s*) [01] Negative : low activation level [00]* No: When factory paramameters of stan- 501.5 Deceleration 2
075 512.0 Low speed 207 Application Overload time delay dard motors 0.0 to 999.9s (5.0s*)
U15 0.0Hz to High speed (0Hz*) 0 to 100 s (0 s*) [01] Yes: Launches auto-tuning 501.6 Decel Ramp Adaptation assignment
U22 512.2 High speed 208 Application Overload threshold [02] Done: If auto-tuning has already been [00] Function deactivated
Short menu

U30 Low speed to max. frequency (mot. frequency*) 70 to 150% of nominal motor current (90%*) performed [01]* Function activated
U40 302 Rated Motor Power 209 Overload fault duration 319 Motor parameter choice [02] Motor brake
U55 NCV -5 to NCV +2 (according to drive rating*) 0 to 6 min (0 min*) [00]* Nominal motor power 502- STOP CONFIGURATION MENU
U75 305 Rated motor current 210 Application underload time delay [01] Nominal motor cos phi 502.0 Type of stop
D11 (0.25-1.5In) (In*) 0 to 100 s (0 s*) 320 Vector control 2 points [00]* Ramp stop

2 4
905 Drive voltage rating

Function / Stop configuration menu


204.0 AI1 type 211 Application Underload threshold [00]* No [01] Fast stop
N4 [5U]* 0-5V 20 to 100% of nominal motor current (60%*) [01] Yes [02] Free wheel stop
906 Specific Product Number [10U] 0-10V 212 Underload fault duration 321 Max voltage of constant power 502.1 Freewheel stop assignment
Maintenance menu

907 Card 1 Software Version [0A] x-y mA 0 to 6min (0min*) 360 to 460V (380V*) [00]* Not assigned
908 Card 2 Software Version [LIU] Logic inputs 213 Motor frequency threshold 322 Max frequency of constant power [L1L] LI1 active Low to stop
909 Run elapsed time display 101 Store customer parameter set 0 to 400Hz (50Hz* or 60Hz) 50 to 400Hz (50Hz*) [L2L] LI2 active Low to stop
910 Power On time display [00]* Disabled 214 Motor current threshold 400- CONTROL MENU [L3L] LI3 active Low to stop
911 Fan time display [01] Stores current configuration 0 to 1.5In (In*) 401 Reference channel 1 [L4L] LI4 active Low to stop
912 Process Elapsed time 102 Factory / recall customer parameter set 215 Motor thermal state threshold [01] Terminal [LUL] LIU active Low to stop
913 Modbus communication status [00]* Disabled 0 to 118% (100%*) [163] Remote display 502.2 Fast stop assignment
914 Last fault 1 [02] Customer configuration 216.0 AOI assignment [164] Modbus [00]* Not assigned
915 State of drive at fault 1 [64] Factory set configuration [00]* Not assigned [183] Integrated display with Jog dial [L1L] LI1 active Low to stop
[129] Motor current [L2L] LI2 active Low to stop

Control menu
916 Last fault 2 COMPLETE MENU 402 External reference value
917 State of drive at fault 2 100 Macro-configuration [130] Output frequency -400 to 400Hz [L3L] LI3 active Low to stop
Macro

918 Last fault 3 [00] Start/stop [131] Ramp output 403 Analog input virtual [L4L] LI4 active Low to stop
919 State of drive at fault 3 [04] PID regulation [135] PID reference 0 to 100% [LUL] LIU active Low to stop
920 Last fault 4 [09] Speed [136] PID feedback 404 Reverse inhibition 502.3 Ramp divider
921 State of drive at fault 4 200- I/O MENU [137] PID error [00]* No 1 to 10 (4*)
999 HMI Password 201 Type of control [139] Output power [01] Yes 503 Reverse direction
[140] Motor thermal state [00]* Not assigned

reverse direction
F000 Fault menu [00]* 2-wire control 405 Stop key priority
F001 Precharge [141] Drive thermal state [00] No: Stop inactive [L1H] LI1 active High
I/O menu

[01] 3-wire control

Function
F002 Unknown drive rating 202 2-wire type control 216.1 AOI type [01]* Yes: Stop active [L2H] LI2 active High
F003 Unknown or incompatible power board [00] level [10U] Voltage: 0-10 Vdc 406 Channel configuration [L3H] LI3 active High
F004 Internal serial link [01]* transition [0A]* Current: 0-20 mA [01]* Not separate mode [L4H] LI4 active High
F005 Invalid industrialization zone [02] Forward priority [4A] Current: 4-20 mA [02] Separate mode [LUH] LIU active High

The (*) indicates a parameter factory setting.

www.schneider-electric.com 1/2
ATV303 complete parameters list
504- AUTO DC INJECTION MENU 59- PID MENU 59.25 PID feedback supervision 512.4 4 High speed assignment 610 Detected fault inhibition assignment

Degr. Modbus Det. fault inhibit.


DC injection function

Speed limitation function (cont.)


504.0 Automatic DC injection 59.00 PID feedback assignment [00]* Not assigned [00]* Not assigned [00]* Function inactive
[00] Function inactive, no DC injected current. [00]* Not assigned [01] Free wheel [L1H] LI1 active High [L1H] LI1 active High
[01]* Time limited DC injection [01] Terminal [04] Fallback speed [L2H] LI2 active High [L2H] LI2 active High
[02] Continuous DC injection 59.01 PID proportional gain 59.26 Fallback speed [L3H] LI3 active High [L3H] LI3 active High
504.1 Automatic DC injection current 0.01 to 100 (1*) 0 to High speed (0Hz*) [L4H] LI4 active High [L4H] LI4 active High
0 to 120% of nominal motor current (70%*) 59.02 PID integral gain 510- PUMP SUB-MENU [LUH] LIU active High [LUH] LIU active High
512.5 High speed 2 611 Modbus detected fault management

line interrup.
504.2 Automatic DC injection time 0.01 to 100 (1*) 207 Overload time delay
0.1 to 30s (0.5s*) 59.03 PID derivative gain 0 to 100 s (0 s*) Low speed to Max frequency (50 or 60Hz*) [00]* Detected fault ignored
505 Jog assignment 0.00 to 100.0 (0*) 208 Overload threshold 512.6 High speed 3 [01] Freewheel stop
[00]* Not assigned 59.04 PID feedback scale factor Low speed to Max frequency (50 or 60Hz*) 612 Degraded line supply operation
Jog function

70 to 150% of nominal motor current (90%*)


[L1H] LI1 active High 0.1 to 100.0 (1.0*) 209 Overload fault duration 512.7 High speed 4 [00]* No
[L2H] LI2 active High 59.05 Activation internal PID reference 0 to 6 min (0 min*) Low speed to Max frequency (50 or 60Hz*) [01] Yes
[L3H] LI3 active High [00]* No 210 Underload time delay 513 Cooling fan control 613 Reset power run

Fan
[L4H] LI4 active High [01] Yes 0 to 100 s (0 s*) [00] Fan runs when drive runs [00]* No

Reset power run


[LUH] LIU active High 59.06 2 preset PID assignment 211 Underload threshold [01]* Thermal control [03] Reset drive running time
506- Speed up and down [00]* Not assigned 20 to 120% of nominal motor current (60%*) 600- FAULT DETECTION MANAGEMENT MENU [04] Reset power-on time

Detected fault reset


506.0 Up speed command [L1H] LI1 active High 212 Underload fault duration 601 Detected fault reset assignment [07] Reset fan operation time

PID / Pump mangement function


[00]* Not assigned [L2H] LI2 active High 0 to 6min (0min*) [00]* Not assigned 614 Reset all previous detected faults via Run key
[L1H] LI1 active High [L3H] LI3 active High 510.0 Selecting operating mode [L1H] LI1 active High of HMI
[L2H] LI2 active High [L4H] LI4 active High [00]* Deactivated

7
[00]* Single frequency conversion mode [L2H] LI2 active High

5
[L3H] LI3 active High [LUH] LIU active High [01] Single frequency conversion combined [L3H] LI3 active High [01] Active
[L4H] LI4 active High 59.07 4 preset PID assignment with auxiliary pump mode [L4H] LI4 active High 700- COMMUNICATION MENU
[LUH] LIU active High [00]* Not assigned 510.1 Starting frequency of the auxiliary pump [LUH] LIU active High 701 Modbus address
506.1 Down speed command [L1H] LI1 active High 0 to 60Hz (50Hz*) 602- AUTOMATIC RESTART MENU Off to 247 (off*)
[00]* Not assigned [L2H] LI2 active High 510.2 Time delay before starting auxiliary pump 602.0 Automatic restart 702 Modbus baud rate
Motor potentiometer function

[L1H] LI1 active High [L3H] LI3 active High 0 to 999.9s (2s*) [00]* No [24] 4.8 kbps

after a etected fault


[L2H] LI2 active High [L4H] LI4 active High

Automatic restart
510.3 Auxiliary pump ramp reaching [01] Yes [28] 9.6 kbps
[L3H] LI3 active High [LUH] LIU active High 0 to 999.9s (2s*) 602.1 Max. automatic restart [32]* 19.2 kbps
[L4H] LI4 active High 59.08 2 preset PID reference 510.4 Auxiliary pump stop frequency [00]* 5 min [36] 38.4 kbps
[LUH] LIU active High 0 to 100% (25%*) 0 to 60Hz (0Hz*) [01] 10 min 703 Modbus format
506.2 Store 59.09 3 preset PID reference 510.5 Auxiliary pump stop time delay [02] 30 min [02] 8o1
[00]* No 0 to 100% (50%*) 0 to 999.9s (2s*) [03] 1 hour [03]* 8E1
[01] RAM 59.10 4 preset PID reference 510.6 Auxiliary pump stop ramp [04] 2 hours [04] 8n1
[02] ROM 0 to 100% (75%*) 0 to 999.9s (2s*) [05] 3 hours [05] 8n2
PID Control function

506.3 Clear the function 59.11 Internal PID reference 510.7 Zero flow detection period [06] Infinite 704 Modbus time out
[00]* Not assigned 0 to 100% (0%*) 0 to 20min (0min*) 603 Catch on the fly 0.1 to 30s (10s*)

Catch on
the fly
[L1H] LI1 active High 59.12 PID reference ramp 510.8 Zero flow detection activation threshold [00]* Function inactive 705- INPUT SCANNER MENU
[L2H] LI2 active High 0 to 100% (0%*) 0 to 400Hz (0Hz*) [01] Function active 705.0 Com scanner read adress parameter 1
[L3H] LI3 active High 59.13 PID min value reference 510.9 Zero flow detection offset 604- MOTOR THERMAL PROTECTION MENU 0C81*
[L4H] LI4 active High 0 to 100% (0%*) 0 to 400Hz (0Hz*) 604.0 Motor thermal current 705.1 Com scanner read adress parameter 2
[LUH] LIU active High

Motor thermal protection


59.14 PID max value reference 511- CURRENT LIMITATION MENU 0.2-1.5In (According to drive rating*) 219C*
[159] Acceleration and deceleration with 0 to 100% (100%*) 511.0 2nd current limitation commutation 604.1 Motor protection type 705.2 Com scanner read adress parameter 3
command active high 59.15 PID predictive speed [00]* Not activated [01]* Self-ventilated 0000

PID / Pump mangement function


506.4 Reactivity of +/- speed around ref. 0.1 to 400Hz (0.0*) [L1H] LI1 active High [02] Motor-ventilated 705.3 Com scanner read adress parameter 4
0 to 100% (0%*) 501.4 Acceleration 2 604.2 Overload fault management 0000

Communication menu
[L2H] LI2 active High
507- PRESET SPEED MENU 0.0 to 999.9s (5s*) [L3H] LI3 active High [00] Detected fault ignored 706- OUTPUT SCANNER MENU
507.0 2 Preset speeds 59.16 PID correction reverse [L4H] LI4 active High [01]* Free wheel stop 706.0 Com scanner write adress parameter 1
[00]* Not assigned [00]* No [LUH] LIU active High 604.3 Motor thermal state memo 2135*
[L1H] LI1 active High [01] Yes [L1L] LI1 active Low [00]* thermal state not stored at power off 706.1 Com scanner write adress parameter 2

6 8
[L2H] LI2 active High 59.17 PID auto/manual assignment [L2L] LI2 active Low [01] thermal state is stored at power off 219A*
[L3H] LI3 active High [00]* Not assigned [L3L] LI3 active Low 605 Output Phase loss 706.2 Com scanner write adress parameter 3
[L4H] LI4 active High [L1H] LI1 active High [L4L] LI4 active Low [00] Deactivated

Phase loss
0000
[LUH] LIU active High [L2H] LI2 active High [LUL] LIU active Low [01]* Tripping then freewheel stop 706.3 Com scanner write adress parameter 4
507.1 4 Preset speeds [L3H] LI3 active High 511.1 Current limitation 606 Input Phase loss 0000
same as 2 Preset speeds [L4H] LI4 active High 0.25 to 1.5In (1.5In*) [00] Detected fault ignored 707- INPUT SCANNER ACCESS MENU
Maintenance menu

507.2 8 Preset speeds [LUH] LIU active High 511.2 Current limitation 2 [01]* Detected fault with freewheel stop 707.0 Com scanner read adress value 1
same as 2 Preset speeds 59.18 PID manual reference 0.25 to 1.5In (1.5In*) 607- UNDERVOLTAGE MENU
[00]* No 0C81*
507.3 Preset speed 2 512- SPEED LIMIT MENU 607.0 Undervoltage detected fault management 707.1 Com scanner read adress value 2
0 to 400Hz (10Hz*) [01] Yes [00]* Detected fault and R1 relay open
512.0 Low speed 219C*

Phase loss
507.4 Preset speed 3 [183] Integrated jog dial [01] Detected fault and R1 relay closed
512.1 Low speed operating time 0Hz to high speed (0Hz*) 707.2 Com scanner read adress value 3
0 to 400Hz (15Hz*) 512.1 Low speed operating time 607.1 Undervoltage prevention 0000
507.5 Preset speed 4 0.1 to 999.9s (0s*) [00]* No action (freewheel)
0.1 to 999.9s (0s*) 707.3 Com scanner read adress value 4
Speed limitation function

0 to 400Hz (20Hz*) 59.19 PID: wake up level [02] Stop following an adjustable ramp
0 to 100% (0%*) 512.2 High speed 0000
507.6 Preset speed 5 Low speed to maximum frequency (50 or 60Hz 607.2 Undervoltage ramp deceleration time
0 to 400Hz (25Hz*) 59.20 PID: Wake up threshold 708- OUTPUT SCANNER ACCESS MENU
according to standard motor frequency*) 0.0 to 10.0s (1.0s*) 708.0 Com scanner write adress value 1
507.7 Preset speed 6 0 to 100% (0%*) 512.3 2 High speed assignment 608 IGBT test
59.21 Sleep offset threshold CMD value*

IGBT
0 to 400Hz (30Hz*) [00]* Not assigned [00]* No test
507.8 Preset speed 7 0 to High speed (0Hz*) 708.1 Com scanner write adress value 2
[L1H] LI1 active High [01] Starting test LFRD value*
0 to 400Hz (35Hz*) 59.22 PID feedback supervision threshold [L2H] LI2 active High 609 4-20mA loss Behaviour
507.9 Preset speed 8 0 to 100% (0%*) 708.2 Com scanner write adress value 3
[L3H] LI3 active High [00]* Detected fault ignored
4-20 mA loss
0 to 400Hz (40Hz*) 59.23 PID supervision function time delay 8000
[L4H] LI4 active High [01] Freewheel stop 708.3 Com scanner write adress value 4
508 Skip frequency 0 to 300s (0s*)
frequency

[LUH] LIU active High 8000


0 to 400Hz (0Hz*) 59.24 Maximum frequency detection Hysteresis
Jump

0 to 50Hz (0Hz*)

The (*) indicates a parameter factory setting.

www.schneider-electric.com 2/2 S1B44889 - 07/2014