Tower Water
Temperature. . .
Control It How??!
1
'As cold as possible!
2
“always nun it hot — at design,
possile.
3
"We always use wet bulb plus &
degrees.
‘Where should you run your tower
‘sump controler? I's an often-asked
‘question that's been answered various
ways, as evidenced above. With the
advent of new technology, i's time to
think each ofthese conclusions.
1 —As Cold As Possible
Half-Tuth: "The chilis the largest
ower consumer of the HVAC
system..."
Fallacy: "... so, one way to minimize
chiller energy consumption isto supply
the chiller withthe coldest tower water
possible,
Fact: I's commonly known that
lowering condensing ternperature
increases a chiler's efficiency. As long
Figure 1: Chiller efficiency at various loads and tower Is
temperatures.
066 KW -
5 the evaporator temperature is
constant, a reduced condenser
temperature wil yield a lower pressure
aifference between the evaporator and
condenser, and ease the burden on the
‘compressor
VON ‘v2 tonsge6
However it's important to recognize that
the efficiency improvements intially
‘gained through lower condense
temperatures are limited. From a
system perspective, improved chiler
efficiency may be offset by increased
tower fan and pumping costs. Consider,
100, that not every condenser
temperature reduction necessary
results in improved chiler efficiency, As
Figure 1 ilustrate, chiler consumption
(ewton) eventually “bottoms aut" and
actually begins to increase as
‘condensing pressure fals,
In shor, though chilers are stil a
significant power consumer within the
HVAC system, they are also the most
efficient part of that system, Centrifugal
chillers, for example, are available at
(0.50 kwiton at ARI rating conditions,
That's performance unheard of ust a
‘ew years ago, With that in mind, don’
‘overlook the potential energy savings.
possible in other areas ofthe system;
the air handler may be a good place to
start.
osaKw [Ss
062 kw
0.60 KW
osakw
0.56KW | Chiter Loading
EB con
PORE CIUC) VESEI Lal)
OSH con
osekw | Ml e0%
0.50 KW
esr OF 15F
70F osF oF2 — Always Run It Hot.
Hoalf-tth: "Fan power is proportional to
the airflow rate cubed (0°), 50 when
variable-speed ckves are
used.
Fallacy: "t's 8 good idea to produce
the warmest possible tower water if
‘you want 10 obtain a considerable
eduction in tower fan eneray
‘consumption.
Fact I's possible to have too much of a
good thing, Although the chiller may stil
perform sfficienty, operating at elevated
{ower water ternperetures may cause
adverse effects over time. The “higher:
than-normal " pressure differential,
between the evaporator and condenser
‘or example, places a greater burden on
the compressor. Put simply, while
reducing fan consumption a worthy
oa, achieving it snot without cost
3 — We Always Use Wet Bull
Plus § Degrees
Half-Ruth: "Maintaining the tower sump
design temperature means excess
chiller energy consumption, but lowering
the termperature makes the fans work
too hard..."
Fallacy: "... therefore, since the
leaving water temperature the tower
can produce is a function of ambient
‘wet bulb temperature, the tower control
‘setpoint should be reduced as the wet
bulb temperature fal.”
Fact: Tower performance is @ function
of ambiont wet bulb temperature, but
it's also influenced by the amount of
heat being rejected, le. the cooling load
‘So How Should Tower Water
‘Temperature Be Controlled?
(EGitors note: The following aiscussion
assumes that the only variable systern
‘design condition isthe tower leaving
water temperature setpoint al other
parameters are constant. Given that
‘scenavo, only the power consumption
(of the chil and tower fans) changes)
Fact: At sorne point in the tower control
band, between design and "as cold as
eee
Figure 2: Chiller + tower energy consumption at various loads and condenser
water temperatures.
Loving Tower Water Temperate
0010 | — Balser Posse a
Hl ovsinas
asoxw | 25 Design a
Hi vere ss
200 KW
ssoKW
ookw
soKW
oKw
possible,” the total power consumption
ofthe chile pls the tower is minimized,
Fact: Crilers are rated in accordance
‘with Air-Conditioning & Refrigeration
Institute (AR) standards, simian,
cooling towers are rated in accordance
with Cooling Tower institute (CT
standards. This practice assures
dependable, repestabie performance for
both types of equinrent.
temperature needed to minimize the
taral energy consumpion of the cooling
‘wer and chiler can be calculated using
rated tower and chilsr performance data,
Fact: Tracer Summit” wil soon provide
the control algorithm needed to optimize
tower water temperature for minimum
rower/chiler energy consumption,
How Much Does Tower Water
Control Optimization Save?
Obvious, this depends on the loads
served. But here's an exarnpl,
Chiller
'500-ton (1758-4) capacity
(058 kwiton (606
100% Fu Load
85.95 F (29.4.35 condenser water =
temperature
78 F (25.6 C) design wet bulb
1600 gom (9462 \ps} condenser water
fow
Tower
(One 25 hp (18.6 ke) fan
Economics
a
sare
fees
11% of time at 25% loadu
)
Figures 2, 3 and 4 show the energy Figure 3: Excess energy purchased at various loads when compared to an
‘optimal tower leaving water temperature.
‘consumption of each control ation and
the savings possible when optimized
control is used instead. (As a basis for
‘comparison, the estmated cost of
‘operating the preceding system is about 4,
$848,000, so savings range between four
‘and five percent) 10%
While these savings aren't astronomical,
‘they are easily obtainable with a soo"
to-be-avallable Tacer Summit control eS
algorithm.
Let’s Go A Little Further ad
Suppase the cooling tower isn't just oS
Contalled to provide the coldest water
possibe, buts actualy designed to do Gg
0, Such a strategy isn't unheard of
Some utiies even offer incentives 10 5
fenoourage this practice, but ist
‘advantageous for ether the buicing am
‘owner out? The story you are about
to read s true o%
Using an incentive program, ausity
encourages buling sesignes 0
achieve low cooling tower approach
temperatures withthe folowing resuts
Shier 2000
450-10n (1582-kw) capacity
2200
(052 kwiton (6.76 COP} @ ARI
‘conditions
6 $2,100
75-85 F (239-294 C) condenser water
temperature re
71 F (256 G design wet bulo samo
11295 gpm (817 ips)
flow
$1900
Tower
ei 1700
Two 25 hp (186 kw fans
Economics
$0.08 / kwh
$12.00 / kw
1900 equivalent ful-loed hours
Lenina Tower Var Teneeaue |
Hil cone rceave
Bil onion 4
Hi vero 65
25% Load 0% Load 75% Load
strategies.
[ieeeeeeeeee
100% (Ful Laas
Figure 4: Energy savings comparison of tower leaving water control
Optimal ws Coldest Possible
‘pina ve Design
(Optra ve Wet Bub + 5ARI Unloading
Figure 5: Chiller + tower energy consumption at various loads and condenser
water temperatures.
179% of time at full load
2 s0KW
39% of time at 75% load
Leaving Tower Water Temporture |
33% of time at 50% load 200% |— Bh catsest Posse
s optimal
114% of time at 25% load me
250 Kw f— elon
‘As Figures 5, 6 and 7 indicate, @ HH veroun +s
potential eperating cost savings of 14
percent can be obtained by optimizing "00 KW ‘
the tower water control instead of
‘making the coldest water possible. More gow a
intriguing is this: Even at ful-ioad design y fe
conditions, power can be saved by
resetting the tower water control 1oKW eee
temperature upward! At ful load, the
‘ower can produce 75 F water and the
tower and chiler, together, consume soKw Pat
264 ko I, nstead, the tower control i E
temperature is 8! F, the tower and qo dl
chiler consume only 240 kw (While this aaa ay eee eee
teas the questo, “Should he seem
igned at this higher temperature?”
‘we won't attempt to answer it here)
Caveats
It's important to remember thatthe
‘optimal tower control temperatures.
shown here are appliation-specific
and are not meant for general use.
Load, ambient conditions and the part
load operating characteristics of the
chiller and tower ultimately determine
the optimum tower contro!
temperatures for a given instalation.
Note, too, that helcabrotary (screw)
compressor energy consumption drops
quickly wity reduce head press
(condenser water temperature), so the
‘optimal tower water setpoint control for
these compressors may be lower than
for centefugal compressors.
20%
25%
20%
15%
10%
Leaving Towor Water Temperature
Hi Coldest Posstie
BB Dosen
Mi vers +5
Figure 6: Excess energy purchased at various loads when compared to an
‘optimal tower leaving water temperature.
25% Load
‘0% Load
75% Load
|__|
|
|
|
|
i
100% (Ful LoadFigure 7: Energy savings comparison of tower leaving water control
strategies,
7000
+8000
$5000
$4000
‘Optimaivs ColdestPossbie Optinalve Design Optmalvs Wet ub +5
So...
{0 obtain the greatest possible
{energy cost savings through HVAC
system optimization, each subsystem
ot ust the chiller... must be
operated in the mast efficient manner
possible while continuing to satisfy the
current buiding load. Key to successful
‘optimization are inforrnation-sharing
controls capable of monitoring and
governing all areas of the HVAC
system. Equaly important, however,
is an awareness... .and periodic
re-examination... -of our design
paradigms if we're to provide building
owners with added value, @
By Mick Schwedler, applications
‘engineer, and Brenda Bradley,
information designer, The Tane
Company.