Design Notes for Structural Analysis

Project Name Propsoed Two-Storey Residential Building

Location Municipality of Sto. Niño, South Cotabato


Client

A. Software/s Used

1. STAAD Pro V8i SS6


2. MIDAS Design+ 2015

B. Reference Codes

1. National Structural Code of the Philippines


2. American Institute for Steel Construction (AISC-05) with Supplementary Seismic Provisions
3. American Concrete Institute (ACI 318-14M)
4. American Society of Civil Engineers (ASCE/SEI 7-10)

C. Loadings Specifications and Provisions

C.1. Dead Loads


Loading Value Unit
Concrete 23.54 kN/cu.m.
Steel 76.93 kN/cu.m.
Mechanical, Electrical, Plumbing Utilities 0.10 kN/sq.m.
Self-Weight of Truss (includes Purlins) 0.08 kN/sq.m.
Rib-Type Roofing Pre-Painted 0.05 kN/sq.m.
Ceiling 0.20 kN/sq.m.
Partition Load 1.00 kPa

C.2. Live/Occupancy Loads


Loading Value Unit
Roof Live Load 1.00 Unit
Basic Floor Area 1.90 Unit
Balcony 2.90 Unit
Design Notes for Structural Analysis
Project Name Propsoed Two-Storey Residential Building

Location Municipality of Sto. Niño, South Cotabato


Client

C.3. Wind Provisions


Basic Wind Speed 270 kph
Importance Factor 1
Exposure Category Exposure B
Building Classification Category Category II
Structure Type Building Structure
Building Height 7.9 m
Enclosure Classification Partially Enclosed

C.4. Seismic Provisions


Occupancy Category IV
Seismic Zone 0.4
Importance Factor 1
Ductility Factor 8.5
Soil Profile Type 4
Distance to the Nearest Fault Line (*Faultfinder, 2019 ) 3.1 km
Near Source Factor, Na 1.2
Near Source Factor, Nv 1.6
Ct Value 0.0731
Design Notes for Structural Analysis
Project Name Propsoed Two-Storey Residential Building

Location Municipality of Sto. Niño, South Cotabato


Client

D. Design Stresses
Materials Value Unit
Concrete
Compressive Strength @ 28 days 20.7 MPa
Reinforcing Bars
For bars 16mm. diameter and greater 275 MPa
For bars less than 16mm. diameter 230 MPa
Structural Steel (ASTM-A36)
For trusses, bracings, and struts 248 MPa
Structural Steel (ASTM-A36)
Cold formed light gauge shapes 248 MPa
Masonry Units
Non-Load Bearing CHB Walls 3.45 MPa
Load Bearing CHB Walls 6.89 MPa

E. Provisions on Foundations

Assume soil bearing capacity of 96 kPa


1. In case the actual location of the structure is less than the assumed distance from the seismic
source of 3.1 km, notify the structural engineer, bureau of design for proper revision of the design.
Refer to the seismic source map provided in the NSCP or PHIVOLCS Seismic Source Map

2. Soil test shall be conducted prior to start of the construction.

3. In case the actual soil bearing capacity is found to be less than the assumed, 96 kPa, notify the
structural engineer, bureau of design for proper revision of foundation.

4. No footing shall rest on fill.

5. Bottom of footing shall be at least 1.0 meter below natural grade line, unless otherwise specified.

6. Soil bearing capacity shall be increased by 33% when in combination with seismic or wind load.