Professional Documents
Culture Documents
Lecture Obstruction Ceiling
Lecture Obstruction Ceiling
OBSTRUCTIONS
137
CHAPTER 6
8' SPRINKLER
4'
18"
4'
PROTECTION
OCCUPANCY MAXIMUM DISTANCE AREA
BETWEEN
SPRINKLERS FROM WALL SQ. FT.
† For hydraulically calculated systems with design densities below 0.25 gpm per sq. ft.,
a maximum 15 ft. distance is allowed between sprinklers and a maximum 130 sq. ft. of
protection area per sprinkler is allowed.
** For pipe schedule systems the maximum protection area per sprinkler is:
For light combustible framing members spaced less than 3' on centers for light
hazard occupancies, the maximum protection area is 130 sq. ft.
2. Exception: Sprinklers can be more than 15' apart when listed for a greater
spacing.
L2 L1 L1 L3
W2
TYPICAL PENDENT
SPRINKLER
15'
MAX W1
7 1 2'
MAX 15'
MAX
11 5L
7 1 2'
M .25'
W3
.7
MAX
AX
Note:
1. W2 1/2W1
2. L2 1/2L1
L2 L1 L1 L3
W2
TYPICAL PENDENT
SPRINKLER
W1
1
2L
MAX
1
W 2
5L
W3
MAX
.7
Note:
1. W2 1/2W1
2. L2 1/2L1
a. Light Hazard
b. Light Hazard
3. ½ L1 = 7' , ½ W 1 = 7'.
c. Ordinary Hazard
3. ½ L1 = 5', ½ W 1 = 6.5'.
d. Ordinary Hazard
3. ½ L1 = 6', ½ W 1 = 5'.
d. Do not exceed the maximum area coverage per sprinkler of 200 sq.
ft. for non-calculated systems or 225 sq. ft. for calculated systems.
(Table 8.6.2.2.1(a))
e. The small room rule is used in areas where there are ceiling
obstructions such as lighting fixtures and HVAC diffusers.
6'-0"
TYPICAL PENDENT
SPRINKLER
9'-0"
7'-6"
TYPICAL PENDENT
SPRINKLER 7'-6"
OI ST
BA RJ
70% OPEN
a. Locate the sprinkler deflector 1" to 12" below the roof or ceiling. If
a concealed, recessed, or flush sprinkler is used, install it per it’s
listing. See NFPA 13, A.3.7.2 for examples.
a. smooth ceilings.
SPRINKLERS
CONCRETE
SPRINKLER
ROOF OR FLOOR
M
BEA
SPRINKLER
7 1/2' OR GREATER
ON CENTER
4" OR
LESS
FLOOR OR ROOF
20"
OR GREATER
SPRINKLER
150 Automatic Sprinkler Plan Review
CEILING / ROOF
7'-6" MAXIMUM
CEILING / ROOF
22" MAXIMUM
WEB
LEGS 1" MAX ABOVE
1" MAX BELOW
2. Solid wood members less than 4" wide and up to 14" deep
that are spaced more than 3' on center are also considered
wood joist construction.
b. Ceiling changes that are greater than 36" are considered a wall for
sprinkler spacing.
1. x < 36"
SPRINKLER
BRANCHLINE
CEILING
SPRINKLER
BRANCHLINE x < 36"
S
S = Maximum allowable distance between sprinklers
SPRINKLER
BRANCHLINE
CEILING
1/2 S
MAX
SPRINKLER
BRANCHLINE
x > 36"
a. Sprinklers shall be located not more than 3' vertically down from
the roof peak.
BACK TO BACK
SPRINKLER CEILING
SPRINKLER
CEILING
4'
2'
MIN
3' MAX
PITCHED ROOF
SPRINKLER
CEILING
157
SPRINKLER SPRINKLER
OBSTRUCTION
4' WIDE MAX LESS THAN 18"
Beam Rule
158 Automatic Sprinkler Plan Review
Standard Sprinklers
SPRINKLER
BRANCHLINE
CEILING
B C =DISTANCE
NOT TO EXCEED THE MAX
BELOW THE CEILING
PER THE SPRINKLERS LISTING
OBSTRUCTION A
c. Workshop Example
CEILING SPRINKLER
OBSTRUCTION b
d a
WALL
7'-6" MAX
OR PER SPRINKLER LISTING
2. d < 30"
SPRINKLER
SOFFIT
d a
S
OBSTRUCTION
SPRINKLER
1/2 S
161
c. Workshop Example
1. d is 24", b is 8".
3. a > (d - 8") + b
a > (24 - 8) + 8
a > 16 + 8
a > 24"
162 Automatic Sprinkler Plan Review
3X RULE
OBSTRUCTION
C
SPRINKLER
D A
PLAN VIEW OF COLUMN
c. A > 3C or 3D
A < 24"
e. When A is greater than 24" the 3 times rule is not applicable and
there is no obstruction. When A is less than 12" another sprinkler
is required.
g. Workshop Example:
1. A is 20".
3. A > 3C or 3D.
CEILING
d. When A is greater than 24" the 3 times rule is not applicable and
there is no obstruction.
g. Workshop Example:
1. A is 24"
3. A > 3C or 3D
5. A > 18"
1/2 1/2
4" OR LESS
20" OR GREATER
SPRINKLER CENTERED
BETWEEN TRUSS
c. Workshop Example:
1. “A” is 24".
d. Workshop Problem #1
1. “A” is 36"
2. “B” is 24"
QUICK RESPONSE
SPRINKLER
168 Automatic Sprinkler Plan Review
ROOF ROOF
PENDENT PENDENT
LESS THEN 18"
SPRINKLER SPRINKLER
IS ALLOWED
18"
MINIMUM
TOYS
SHELVING
SHELVING
FLOOR FLOOR
CORRECT CORRECT
169
ROOF
CEILING
BAR JOIST SPRINKLER
14'
14'
OVER
14' OR 14'
LESS
OUTLINE OF
OVERHEAD DOOR
OVER 14' OVER 14'
STANDARD SIDEWALL
SPRINKLER
14' OR 14'
170 Automatic Sprinkler Plan Review
TYPICAL SPRINKLER
WITH WATER SHIELD TYPICAL SPRINKLER PIPING
171
1. The maximum area of coverage shall not exceed 100 sq. ft. per sprinkler.
The minimum area of protection shall not be less than 80 sq. ft. per
sprinkler. (8.12.2.2.2)
5'-0"
10'-0" 1'-0"
MIN
11'-0"
5'-0" 10'-0" 10'-0" 5'-0"
10'-0"
10'-0"
Table 8.12.2.2.1 indicates that ESFR sprinklers cannot be used under obstructed
combustible construction. However paragraph 8.4.6.3 identifies construction that
can be considered in this category.
ESFR SPRINKLERS
ROOF
BAR JOIST
36"
MINIMUM
FLOOR
173
5. ESFR’s are only permitted with the following construction types (8.4.6.3):
6. ESFR’s cannot be used in buildings with roof slopes greater than 2" per ft.
(8.4.6.2)
7. ESFR’s are only permitted for wet systems unless specifically listed for dry
system application. (8.4.6.1)
8. The allowable ESFR sprinkler deflector distances below the ceiling are as
follows for pendent ESFR sprinklers: (8.12.4.1)
9. For obstructions located at the ceiling, the same rules apply as for
standard upright and pendent sprinklers. However, ESFR’s must be
installed a minimum of 1' horizontally from the nearest edge of any bottom
chords at open trusses or open bar joists. (8.12.5.3.1)
10. For obstructions over 2' wide and located entirely below the sprinklers, the
sprinkler location must meet the requirements of NFPA 13,
Figure 8.12.5.2 – beam rule.