Professional Documents
Culture Documents
DET Summary 1 03 11-1
DET Summary 1 03 11-1
The following is intended to be a brief summary and is not considered an official document or interpretation of the DET
requirements of the 2011 Georgia State Energy Code. For additional information, please refer to the 2009 IECC and the
2011 GA Amendments to the 2009 IECC for all code requirements. The Georgia State Supplements and Amendments to the
2009 IECC can be found at the following DCA link:
http://www.dca.state.ga.us/development/constructioncodes/programs/codeAmendments.asp
403.2.2 Sealing (Mandatory). All ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed. Joints
and seams shall comply with section 403.2.4 of these Georgia State Supplements and Amendments. Duct tightness shall be
verified by any of the following and comply with the testing protocol in Appendix B.
Exceptions:
1. Duct tightness testing is not required if the air handler and all ducts are located within conditioned space.
2. Duct tightness testing is not required for existing duct systems unless more than 50% of the duct system is modified.
3. If the air handler, furnace or evaporator coil is replaced on an existing system, all joints, seams and connections from
equipment to duct system and duct system connections to plenums shall meet the sealing requirements of this code and
be verified by a visual inspection by the state licensed conditioned air contractor or by a DET Verifier.
The majority of energy contractors in Georgia will either have a HERS Certification OR a BPI Certification. Where
most HERS Raters focus on the new construction market and BPI Analysts focus on the existing home market. There
are a growing number of energy contractors that will have all three certifications to be able to provide home energy
certifications for both markets.
How does a Builder locate a DET Verifier?
• The DET Verifier certification training is under development and will be available beginning January 2011
• The Builder may also hire a verifier that holds at least one of the approved certifications listed above
CLARIFICATION – The DET Verifier is not required to be an independent third party in order to meet the requirements
sections 402 and 403 of the State Energy Code. The Builder is allowed to hire any DCA certified DET Verifier which may
include, but not limited to, an employee of the Builder, trade contractor, home inspector, energy contractor, etc.