Professional Documents
Culture Documents
Protection Relay: REF 542 Plus Manufacturer: ABB Relay Description: Bay Control and Protection Unit Protection Functions
Protection Relay: REF 542 Plus Manufacturer: ABB Relay Description: Bay Control and Protection Unit Protection Functions
Protection Relay: REF 542 Plus Manufacturer: ABB Relay Description: Bay Control and Protection Unit Protection Functions
Manufacturer: ABB
Relay description: Bay control and protection unit
Protection functions:
Current Protection Functions:
Inrush (68)
Overcurrent instantaneous (50)
Overcurrent definite time and IDMT (51High, 51 Low, 51 IDMT)
Directional Overcurrent protection (67High, 67 Low)
Earthfault protection definite time and IDMT (51N High, 51N Low, 51N IDMT)
Directional earth fault protection (67N High, 67N Low, 67N sensitive, 67N sector)
fault high
V.I. (Very inverse) K = 11 KV feeders
current
current
instantan
IDMT- over Over Earth Unde
setting
voltag
e low r
eous
g settin
I/I K ID St Ti St Ti S T
In * e lu va art
In * e lu va art
pe ty T M
(s) e m
(s) e m
n
e u l a v t r a t
) s ( e mi
*
n I
0. 0. 0. 0. 0. 0. 0 0
0 :4 05
5 :1. 05
00 :3 02
0 :4 05
00 :1 07
40 1:
2 . 1 : 1 .
0 0 3 : 5 0 .
CT GCT
Ratio Ratio K
e at tiv ac e-
e at tiv ac e-
e at tiv ac e-
0 1 0 1 - S E
100/1 50/1 K5 1.3 0.9 .E.I 21.3 0.02 0.2 0.1 0.4 2
500/1 50/1 K6 1 0.25 .N.I 15.2 0.02 0.2 0.1 0.4 2
100/1 50/1 K7 1.3 0.9 .E.I 21.3 0.02 0.2 0.1 0.4 2
200/1 50/1 K8 1 0.7 .E.I 15.1 0.02 0.2 0.1 0.4 2
200/1 50/1 K9 1 0.7 .E.I 15.1 0.02 0.2 0.1 0.4 2
200/1 50/1 K10 1 0.7 .E.I 15.1 0.02 0.2 0.1 0.4 2
250/1 50/1 K11 0.82 0.65 .V.I 19 0.02 0.2 0.1 0.4 2
200/1 50/1 K12 1 0.7 .E.I 15.1 0.02 0.2 0.1 0.4 2
200/1 50/1 K13 1 0.7 .E.I 15.1 0.02 0.2 0.1 0.4 2
200/1 50/1 K14 1 0.9 .E.I 21.5 0.02 0.2 0.1 0.4 2
1 1500/1 K3 0.7 0.3 .N.I De-activate De-activate 0.4 5
1600/1 K4 0.9 0.38 .N.I De-activate 0.08 0.7 0.4 5
3 1 0
1421/1511/1521/1611/1621And1TC-1411-M-10
1P-1601B - M-01BAnd1P-1601A - M-01A
1P-1202B -M-01Band1P-1202A -M-01A
B/C/D/E/F/G/HAnd1P-2401A -M-01A
1C-2401 -M-01
1C-1301 -M-01
1421/1511/1521/1611/1621And2TC-1411-M-10
2PK-3502B-CM-01BAnd2PK-3502 A-CM-01A
2P-1601B - M-01BAnd2P-1601A - M-01A
2P-1202B -M-01BAnd2P-1202A -M-01A
2C-1301 -M-01
Inspection Frequency:
According to the manufacturer’s recommendations the relay should be submitted to
secondary testing at seven years’ intervals.
Inspection activities:
1) Visual inspection:
- Signs of mechanical damage on relay case and terminals.
- Dust accumulated inside the relay cover or case; remove carefully with compressed
Air blower or a soft brush.
- Signs of corrosion on terminals, case or components inside the relay
This test applied for all REF 542plus with the following procedure
1- Make sure that the load/feeder which its relay under test is electrically
isolated.
2- Make sure that all REF settings are the same settings in the above tables
(record any changes).
3- Make sure that the REF input signals from CT’s are connected to terminals
X6/216, X6/221, X6/226 and X6/251) and the relay output signals are
connected to terminals:
Generator case:
1. Trip MAN C.B X5/63 and X5/62
2. To F86 X5/65 and X2/32
3. To differential protection X5/66 and X5/67
4. U/V of generator (X10/342, X10/343 and X10/344)
5. DCS common alarm X5/120 and X5/121
Transformer feeder case:
1. To close C.B X3/40 and X1/4
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/65 and X2/32
4. To differential protection X5/66 and X5/67
5. To block close X2/32 and X3/41
6. DCS common alarm X5/120 and X5/121
11 KV feeder case:
1. Trip MAN C.B X5/63 and X5/62
2. To F86 X5/65 and X2/32
3. To differential protection X5/66 and X5/67
4. U/V of generator V.T X10/352 and X10/353
5. U/V of generator V.T X10/356 and X10/357
6. DCS common alarm X5/120 and X5/121
3.3 KV feeder case:
1. To YC close X1/4 and X3/41
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/67 and X2/32
4. U/V trip X2/32 and X5/66
5. Not start protection X10/360 and X10362
6. DCS common alarm X5/99 and X5/100
Motor feeder case:
1. Trip MAN C2 X2/32 and X5/95
2. To C3 trip protection X2/32 and X5/96
3. DCS common alarm X5/99 and X5/100
4- Disconnect all input and output terminals.
5- Cover the wires of input and output with isolating tape.
6- Connect tester current output signals to terminals of REF input.
7- Connect the REF output terminals to the tester proper terminals.
8- Set the test current Itest at a value slightly under the set start current of the over
current protection.
9- Apply test current on the REF by turned the tester on.
10- Take the reading of REF displays for I1, I2 and I3.
(Record any changes between tester displays and REF displays for the
Currents).
11- Increase the current of relay tester until trip state occurs.
12- Record the value of current and time at which the trip occurs.
13- Compare the tripping values with REF settings.
14- Repeat the test with tester current 2 Itest and 4 Itest.
15- Reconnect the input and output wires to the REF terminals (after removing the
isolating tape).
16- Make sure all settings, switches and wires are proper.
This test applied for all transformer feeders REF 542plus with the following
procedure
1- Make sure that the load/feeder which its REF under test is electrically isolated.
2- Make sure that all REF settings are the same settings in the above tables
(record any changes).
3- Make sure that the REF input signals from CT’s are connected to terminals
X6/216, X6/221, X6/226 and X6/251) and the REF output signals are
connected to terminals:
Transformer feeder case:
1. To close C.B X3/40 and X1/4
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/65 and X2/32
4. To differential protection X5/66 and X5/67
5. To block close X2/32 and X3/41
6. DCS common alarm X5/120 and X5/121
4- Disconnect all input and output terminals.
5- Cover the wires of input and output with isolating tape.
6- Connect tester current output signals to terminals of REF input.
7- Connect the REF output terminals to the tester proper terminals.
8- Set the test current Itest at a value slightly under the set start current of the
instantaneous over current protection.
9- Apply test current on the REF by turned the tester on.
10- Take the reading of REF displays for I1, I2 and I3.
(Record any changes between tester readings and relay readings for the
Currents).
11- Increase the current of relay tester until trip state occurs.
12- Record the value of current and time at which the trip occurs.
13- Compare the tripping values with REF settings.
14- Reconnect the input and output wires to the REF terminals (after removing the
isolating tape).
15- Make sure all settings, switches and wires are proper.
This test applied for all REF 542plus with the following procedure
1- Make sure that the load/feeder which its REF under test is electrically isolated.
2- Make sure that all REF settings are the same settings in the above tables
(record any changes).
3- Make sure that the REF input signals from PT’s are connected to terminals
X4/216, X4/221, X4/226 and X4/251) and the REF output signals are
connected to terminals:
Generator case:
1. Trip MAN C.B X5/63 and X5/62
2. To F86 X5/65 and X2/32
3. To differential protection X5/66 and X5/67
4. U/V of generator (X10/342, X10/343 and X10/344)
5. DCS common alarm X5/120 and X5/121
Transformer feeder case:
1. To close C.B X3/40 and X1/4
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/65 and X2/32
4. To differential protection X5/66 and X5/67
5. To block close X2/32 and X3/41
6. DCS common alarm X5/120 and X5/121
11 KV feeder case:
1. Trip MAN C.B X5/63 and X5/62
2. To F86 X5/65 and X2/32
3. To differential protection X5/66 and X5/67
4. U/V of generator V.T X10/352 and X10/353
5. U/V of generator V.T X10/356 and X10/357
6. DCS common alarm X5/120 and X5/121
3.3 KV feeder case:
1. To YC close X1/4 and X3/41
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/67 and X2/32
4. U/V trip X2/32 and X5/66
5. Not start protection X10/360 and X10362
6. DCS common alarm X5/99 and X5/100
Motor feeder case:
1. Trip MAN C2 X2/32 and X5/95
2. To C3 trip protection X2/32 and X5/96
3. DCS common alarm X5/99 and X5/100
4- Disconnect all input and output terminals.
5- Cover the wires of input and output with isolating tape.
6- Connect tester voltage output signals to terminals of REF input.
7- Connect the REF output terminals to the tester proper terminals.
8- Set the test voltage at a value slightly above the set start voltage of the under
voltage protection.
9- Apply test voltage on the REF by turned the tester on.
10- Take the reading of REF displays for U1, U2 and U3.
(Record any changes between tester displays and REF displays for the
Currents).
11- Reduce the voltage of relay tester until trip state occurs.
12- Record the value of voltage and time at which the trip occurs.
13- Compare the tripping values with REF settings.
14- Reconnect the input and output wires to the REF terminals (after removing the
isolating tape).
15- Make sure all settings, switches and wires are proper.
This test applied for all REF 542plus except (1ES-101 feeders and generators) with
the following procedure
1- Make sure that the load/feeder which its REF under test is electrically isolated.
2- Make sure that all REF settings are the same settings in the above tables
(record any changes).
3- Make sure that the REF input signals from Ring core are connected to
terminals:
Transformer feeder case X6/236 and X6/237.
3.3 KV feeders case X6/230 and X6/231.
Motor feeder case X6/230 and X6/231.
And the REF output signals are connected to terminals:
Transformer feeder case:
1. To close C.B X3/40 and X1/4
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/65 and X2/32
4. To differential protection X5/66 and X5/67
5. To block close X2/32 and X3/41
6. DCS common alarm X5/120 and X5/121
11 KV feeder case:
1. Trip MAN C.B X5/63 and X5/62
2. To F86 X5/65 and X2/32
3. To differential protection X5/66 and X5/67
4. U/V of generator V.T X10/352 and X10/353
5. U/V of generator V.T X10/356 and X10/357
6. DCS common alarm X5/120 and X5/121
3.3 KV feeder case:
1. To YC close X1/4 and X3/41
2. Trip MAN C.B X5/63 and X5/62
3. To F86 X5/67 and X2/32
4. U/V trip X2/32 and X5/66
5. Not start protection X10/360 and X10362
6. DCS common alarm X5/99 and X5/100
Motor feeder case:
1. Trip MAN C2 X2/32 and X5/95
2. To C3 trip protection X2/32 and X5/96
3. DCS common alarm X5/99 and X5/100
4- Disconnect all input and output terminals.
5- Cover the wires of input and output with isolating tape.
6- Connect tester current output signals to terminals of REF input.
7- Connect the REF output terminals to the tester proper terminals.
8- Set the test current at a value slightly under the set start current of the earth
fault protection.
9- Apply test current on the REF by turned the tester on.
10- Take the reading of REF displays for I1, I2 and I3.
(Record any changes between tester displays and REF displays for the
Currents).
11- Increase the current of relay tester until trip state occurs.
12- Record the value of current and time at which the trip occurs.
13- Compare the tripping values with REF settings.
14- Reconnect the input and output wires to the REF terminals (after removing the
isolating tape).
15- Make sure all settings, switches and wires are proper.
Required logistics:
- Manpower:
Electrical engineer
Electrician
- Tools:
- Air blower (cordless, variable speed blower – MAKITA)
- Relays tester
Inspection Report