COOLING LOAD ESTIMATE SHEET

0
C to 0 F 42 108 Inside 0 F
FLOOR & ROOF
Length Width Area sq.ft U factor
Floor 25 40 9000 0.8
Roof 25 40 9000 0.2
WALLS
Length Height Area sq.ft U factor
North 25 2 450 0.3
Norht East 0 0 0 0
East 40 2 720 0.3
South East 0 0 0 0
South 25 4 900 0.3
South West 0 0 0 0
West 40 4 1440 0.3
North West 0 0 0 0
SUB-TOTAL HEAT GAINED
GLASS
Length Height Area sq.ft Solar Gain
North 25 2 450 20
North East 0 0 0 0
East 40 2 720 200
South East 0 0 0 0
South 0 0 0 0
South West 0 0 0 0
West 0 0 0 0
North West 0 0 0 0
SUB-TOTAL HEAT GAINED
LIGHTING
Wattage No. Lamps Utl. Factors F
Incandiscent Lamps 100 100 3.4
Florscent lamps 0 0 3.4
TOTAL LIGHTING
OCCUPANTS
No. Occup Quantity of Heat
Sensible 200 200
Latent 200 250
APPLIANCES
ELECTRIC APPLIANCES Wattage No. App Utilization Factor
1 500 1 3.4
2 0 0 3.4
3 0 0 3.4
SUB-TOTAL ELECTRIC APP COOLING LOAD ESTIMATE SHEET Copy Right Dr. A
HEAT APPLIANCES Number Area sq.ft Total Sensible & Latent
1 1 2 1000
2 0 0 0
3 0 0 0
4 0 0 0
5 0 0 0
6 0 0 0
SUB-TOTAL HEAT APP COOLING LOAD ESTIMATE SHEET Copy Right Dr. A
TOTAL APPLIANCES

SUB-TOTAL QUANTITY OF HEAT GAI


QUANTITY OF HEAT GAINED FOR VENTELA
CFM / Person # Persons Tota
VENTILATION CFM 25 200
Temperature Diff
Factor C.F.M.v T. outside T. inside
SENSIBLE HEAT 1.08 5000 104 80
Specific Humidity D
Latent Heat Co. Vapour Reduction
LATENT HEAT 4840 0.006
FAN LOAD
Heat Gained Ventilation Fan HP
RECIRCULATED AIR 325144 12960 25

TOTAL AIR CONDITIONING ESTIMATED


Total load
TOTAL TON REFREGERATION 713544

Total C.F.M
Area of Duct (cm )
2 19576

Number of Units 1 2
Ton Refregiration, TR 60 30
Total Air Change, CFM 19576 9788
Area of Duct, sq.ft. 14.0 7.0
Area of Duct, sq.cm. 12990 6495
Circular Duct
Diameter, cm 129 91
Rectangular Duct 1:2
Height, cm 85 60
Width, cm 169 120
Rectangular Duct 1:3
Height, cm 71 50
Width, cm 212 150
# of Diffusers (Air Speed > ) 700 27 13
TIMATE SHEET
Analysis % of Total
80 Outside 0 F 104
OOF
EQV.T. Out Temp. In Temp. Diff Total btu/hr.
80 80 0 0 0%
145 80 65 117000 16%

EQV.T. Out Temp. In Temp. Diff Total btu/hr.


106 80 26 3510
106 80 26 0
112 80 32 6912
114 80 34 0
114 80 34 9180
110 80 30 0
108 80 28 12096
106 80 26 0
31698 4%

Heat Trans Shading Coefficient Total btu/hr.


25 1 20448
25 0 0
25 0.5 81158
25 0 0
25 0 0
25 0 0
25 0 0
25 0 0
101606 14%
G
FACTOR Total btu/hr.
1 34000
1.25 0
34000 5%
TS
Quantity of Heat btu/hr. Total btu/hr.
200 40000 6%
250 50000 7%
ES
Utilization Factor Usage Factor Total btu/hr.
3.4 0.2 340
3.4 0.2 0
3.4 0.2 0
SHEET Copy Right Dr. Ali Faramawy 340
Hooded Total btu/hr.
0.25 500
0 0
0 0
0 0
0 0
0 0
SHEET Copy Right Dr. Ali Faramawy 500
840 0%

NTITY OF HEAT GAINED 325144 46%

GAINED FOR VENTELATION


Total C.F.M.v
5000
Temperature Difference
T. inside Temp diff. Total btu/hr.
80 24 129600 1.8% 16.3%
Specific Humidity Difference
C.F.M.v Total btu/hr.
5000 145200 20%
AN LOAD
Fan CFM Supply Total btu/hr.
63600 19576 401704 9%

IONING ESTIMATED LOAD 713544 100%

Total load / 1200 BTU = 1TR


713544 / 12000 326
60
Total C.F.M. Air Speed (ft/m)
19576 1400
15537

3 4 5 6
20 15 12 10
6525 4894 3915 3263
4.7 3.5 2.8 2.3
4330 3248 2598 2165

74 64 58 53

49 42 38 35
98 85 76 69

41 35 32 29
122 106 95 86
9 6 5 4
nalysis % of Total

Floor
Roof

Wall

Glass

Lighting

Occ. Sen.
Occ. Lat.
Appliance

Subtotal

Sensible

Latent

Fan

Total

Check
CFM/TR
Total Equivalent Summer Temperature Difference 0 F for Walls & Roo
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
300 Latitude N NE E SE
Bricks 20 cm thick, Light Color 26 26 32 34

* Total Equivelant Tenperature Difference are processed in Calculation sheet


nce 0 F for Walls & Roofs *
Right Dr. Ali Faramawy
S SW W NW Roofs
34 30 28 26 65
S.R.F. - Factors for Sensible Heat Gain through Glass (btu/sq.ft.)
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
300 Latitude N NE E SE S SW
Morning 20 150 200 125 16 16
Afternoon 20 15 15 16 16 125
rough Glass (btu/sq.ft.)
Right Dr. Ali Faramawy
W NW Horizontal
15 15 270
200 150 270
Solid Masonary Walls
Outside Surface
Outside surface (15 mph wind) 0.17 0.17
Exterior Finishing
Plaster 1 in. (sand agg.) 0.18 0.18
Brick
Brick 5 in. 1.00
Brick 10 in. 2.00
Brick 15 in. 3.00
Stone
Stone 8 in. 0.64
Stone 12 in. 0.96
Stone 16 in. 1.28
Concrete
Concrete 6 in. 2.40
Concrete 8 in. 3.20
Concrete 10 in. 4.00
Concrete 12 in. 4.80
Concrete Block
Concrete Block 8 in. 1.11
Concrete Block 12 in. 1.28
Air Space
Air Space 0.97
Fibrous Insulation 1/2 in. 1.85
Fibrous Insulation 1 in. 3.70
Fibrous Insulation 2 in. 7.41
Fibrous Insulation 3 in. 11.11
Interior Finish
Plaster 5/8 in. 0.11
Metal lath & Plas. 3/4 in. 0.13
Gypsum lath & Plas. 1/2 in. 0.41
Insul. Brd. Lath 1/2 in. & Plas. 1/2 in. 1.52
Inside Surface
Inside surface (still air) 0.68 0.68
Total Resistance 53.91 1.03
U value 0.97
U-value Calculator for Solid and Composit Masonary Walls, F
COO
Composite Masonary Walls
Outside Surface
Outside surface (15 mph wind) 0.17 0.17
Exterior Finish
Face Brick 4 in. 0.44
Stone 4 in. 0.32
Precast Concrete 4 in. 0.32
Precast Concrete 6 in. 0.48
Precast Concrete 8 in. 0.64
Cavity
Cavity 0.97
Fibrous Insulation 1/2 in. 1.85
Fibrous Insulation 1 in. 3.70
Fibrous Insulation 2 in. 7.41
Fibrous Insulation 3 in. 11.11
Backing
Hollow clay tile 4 in. 1.11
Hollow clay tile 8 in. 1.85
Hollow clay tile 12 in. 2.50
Concrete block 4 in. 0.71
Concrete block 8 in. 1.11
Concrete block 12 in. 1.28
Concrete 4 in. 0.32
Concrete 8 in. 0.48
Concrete 12 in. 0.64
Air Space
Air space 0.97
Interior Finish
Plaster 5/8 in. 0.11
Metal lath & 3/4 in. plas. 0.13
Gypsum lath & 1/2 in. plas. 0.41
Insul. brd. Lath (1/2 in.) & 1/2 in. plas. 1.52
Inside Surface
Inside surface (still air) 0.68 0.68
Total Resistance 41.23 0.85
U value 1.18
or for Solid and Composit Masonary Walls, Frame Walls, Interior Walls, Concrete Floor-Ceiling Constructi
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
Frame Walls
Outside Surface
Outside surface (15 mph wind) 0.17 0.17
Exterior
Stucco 1in. 0.15
Plywood 3/4 in. 0.44
Face-brick veneer 0.47
Wood siding 1in. X 8 in. 0.85
Wood Sshingles over insul. 1.40
Asphalt insul. shingles 1.45
Air Space
Air space 0.97
Fibrous Insulation 1/2 in. 1.85
Fibrous Insulation 1 in. 3.70
Fibrous Insulation 2 in. 7.41
Fibrous Insulation 3 in. 11.11
Sheething
No sheething 0.06
Gypsum Board 1/2 in. 0.45
Plywood 5/16 in. 0.39
Insulation Board 1/2 in. 1.32
Interior
Metal lath & Plas. 3/4 in. (sand) 0.13
Plywood 1/4 in. 0.31
Gypsum Board 3/8 in. 0.32
Gypsum Lath 3/8 in. & Plas. (sand) 0.41
Wood Pannels 3/4 in. 0.94
Insul. Board 1/2 in. 1.43
Insul. Board 1/2 in. & Plas. 1/2 in. (sand) 1.52
Inside Surface
Inside surface (still air) 0.68 0.68
Total Resistance 37.93 0.85
U value 1.18
ior Walls, Concrete Floor-Ceiling Constructions, and Wooden Frame Ceilings and Floors
TE SHEET Copy Right Dr. Ali Faramawy
Partitions or Interior Walls
Outside Surface
Outside surface (still air) 0.68 0.68
One side
Metal Lath & Plas 3/4 in. (sand) 0.13
Plywood 1/4 in. 0.31
Gypsum board 3/8 in. 0.32
Gypsum lath 3/8 in. & Plas. (sand) 0.41
Wood pannels 3/4 in. 0.94
Insul. Board 1/2 in. 1.43
Insul. Board 1/2in. & Plas. 1/2 in. (sand) 1.52
Hollow concrete block 8 in. 1.11
Hollow concrete block 12 in. 1.28
Hollow clay tile 6 in. 1.52
Hollow clay tile 8 in. 1.85
Air Space
Air space 0.97 0.97
Other side
Metal lath & 3/4 in. plas (sand) 0.13
Plywood 1/4 in. 0.31
Gypsum board 3/8 in. 0.32
Gypsum lath 3/8 in. & plas. (sand) 0.41
Wood pannels 3/4 in. 0.94
Insul. Board 1/2 in. 1.43
Insul. Board 1/2in. & Plas. 1/2 in. (sand) 1.52
Hollow concrete block 8 in. 1.11
Hollow concrete block 12 in. 1.28
Hollow clay tile 6 in. 1.52
Hollow clay tile 8 in. 1.85
Inside surface (still air) 0.68 0.68
Total Resistance 23.97 2.33
U value 0.43
Frame Ceilings and Floors

Concrete Floor-Ceiling Constructions


Outside Surface
Top surface (still air) 0.92 0.92
Finished Floor
Tile Shingles & Building Paper 0.11
Floor tile or linoleum 1/8 in. 0.05
Wood block 13/16 in. on slab 0.74
Floor on sleepers 0.89
Wood subfloor, felt and hard wood 1.72
Insulation
Roof insulation 1.39
Fibrous Insulation 1/2 in. 1.85
Fibrous Insulation 1 in. 3.70
Fibrous Insulation 2 in. 7.41
Fibrous Insulation 3 in. 11.11
Floor material
Concrete 4 in. 0.32
Concrete 6 in. 0.48
Concrete 8 in. 0.64
Concrete 10 in. 0.80
Air Space
Air space 1.25 1.25
Type of Ceiling
Plaster 1/8 in. (sand) on ceiling 0.02
Acoustic tile 1/2 in. glued to ceiling 1.19
Acoustic tile 3/4 in. glued to ceiling 1.78
Gypsum Board 3/4 in. and plaster 1/2 in. 0.41
Metal lath and plaster 3/4 in. 0.13
Acoustic tile 1/2 in. on gypsum brd. 3/8 in. 1.51
Acoustic tile 3/4 in. on gypsum brd. 3/8 in. 2.10
Acoustic tile 1/2 in. on furring 1.19
Acoustic tile 3/4 in. on furring 1.78
Bottom Surface
Bottom surface (still air) 0.92 0.68
Total Resistance 1.03 2.85
U value 0.35
Wooden Frame Ceiling and Floors
Outside Surface
Top surface (still air) 0.92 0.92
Floor - Roof Finish
Tile Shingles & Building paper 0.11
Ceramic tiles 1/2 in. & Cement 11/2 in. 1.38
Tile or Linoleum 0.05
Felt 0.06
Plywood 5/8 in. 0.78
Insulation
Roof insulation 1.39
Fibrous Insulation 1/2 in. 1.85
Fibrous Insulation 1 in. 3.70
Fibrous Insulation 2 in. 7.41
Fibrous Insulation 3 in. 11.11
Wood Floor
Flat metal roof deck 0.00
Wood sheething 25/32 in. 0.98
Hardwood floor 3/4 in. 1.72
Wooed deck 1 in. 0.98
Wooed deck 2 in. 2.03
Wooed deck 3 in. 3.28
Wood sub-floor 25/32 in. 0.98
Air Space
Air space 1.25 1.25
False Ceiling
Metal lath & Plas 3/8 in. (sand) 0.13
Gypsum board 3/8 in. 0.32
Gypsum lath 3/8 in. & Plas. (sand) 0.41
Wood pannels 3/4 in. 0.94
Insul. Board 1/2 in. 1.43
Insul. Board 1/2in. & Plas. 1/2 in. (sand) 1.52
Acoustic tile 1/2 in. on Gypsum brd. 3/8 in. 1.51
Acoustic tile 1/2 in. on furring 1.19
Bottom Surface
Bottom surface (still air) 0.92 0.68
Total Resistance 2.41 2.85
U value 0.35
Heat Gain From Occupants
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
Activity Latent Heat (BTU/HR)
Seated Relaxed 250
Light work 250
Active office work 250
Hard work (gym) 300

The above values are based on 80F room dry-bulb temp.


cupants
Copy Right Dr. Ali Faramawy
Sensible Heat (BTU/HR)
200
250
250
350
Heat Gain From Appliances BTU/sq.ft.
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
Appliance Electrical Gas
Coffee brewer, 1/2 gallon 1120 1700
Coffee brewer, unit, 4and 1/2 gallon 6000 9000
Coffee Urn, 3 gallon 3700 5000
Coffee Urn, 5 gallon 5700 7800
Coffee Warmer, 1/2 gallon 290 500
Food and Plate Warmer, per sq ft of top surface 700 -
Food Warmer, per sq ft of top surface - 1300
Fry kattle, per sq ft of fry area 8500 10000
Griddle, per sq ft of fry area 4600 -
Grill, meat, per sq ft of fry area 7200 12500
Grill, sandwich, per sq ft of fry area 3400 -
Hair Dryer, Blower 2700 -
Hair Dryer, Helmet 2200 -
Sterilizer for physicians' instruments 1850 -
Toaster, belt-driven, 4 slices wide 8700 17000

When hooded and with adequate exhaust, use 50% of above values
Table 6.Ventilation
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
Outside Air
Application Smoking CFM Per Person
Apartment Some 20
Banking space Occasional 10
Barber shops Considerable 15
Beauty parlors Occasional 10
Cocktail bars Heavy 30
Stores None 7.5
Drug stores Considerable 10
Factories None 10
Funeral parlors None 10
Hospitals-private rooms None 30
Hospitals-wards None 20
Hotel rooms Heavy 30
Meeting Rooms Very Heavy 50
Offices-private None 25
Offices-general Some 15
Restaurants Considerable 15
Cafeterias Considerable 12
Theatres None 7.5
Table 1, Air Cooled Package Units Size (Carrier)
Performance Unit Length mm Length + Service Area mm
Model TR C.F.M. Length Width Hight Length Width Hight
55 5 2000 900 780 1605 2900 1780 1605
90 7 3000 1340 790 1830 3340 1790 1830
110 9 3500 1340 790 1830 3340 1790 1830
145 12 6000 1595 870 2145 3595 1870 2145
180 14 6000 1595 870 2145 3595 1870 2145
240 19 7000 2050 1080 2035 4050 2080 2035

Table 2, Central Air/Water Cooled Chillers Units Size


Performance Unit Length mm Length + Service Area mm
Model TR C.F.M. Length Width Hight Length Width Hight
XX 60-1000 Var 8000 2000 2000 9000 4000 2000

Table 3, Central Air Handeling Units Size (Saivez)


Performance Unit Length mm Length + Service Area mm
Model TR M3/H CFM Length Width Hight Length Width
ST 20-20 4 1800 1060 1350 1000 750 2350 3000
ST 25-25 5 2250 1330 1400 1100 750 2400 3100
ST 33-25 6 3000 1770 1400 1200 750 2400 3200
ST 44-29 8 4000 2360 1600 1400 800 2600 3400
ST 50-29 10 4600 2710 1600 1400 900 2600 3400
ST 59-33 11 5300 3120 1700 1400 950 2700 3400
ST 67-33 13 6100 3590 1700 1550 950 2700 3550
ST 79-37 15 7200 4240 1900 1500 1050 2900 3500
ST 89-37 16 8100 4770 1900 1650 1050 2900 3650
ST 100-41 18 9000 5300 1950 1750 1100 2950 3750
ST 111-41 20 10000 5890 1950 1850 1100 2950 3850
ST 122-45 23 11000 6480 1950 1750 1350 2950 3750
ST 138-45 26 12500 7360 1950 1950 1350 2950 3950
ST 154-49 28 14000 8240 2100 2000 1350 3100 4000
ST 177-49 32 16000 9420 2100 2150 1350 3100 4150
ST 200-58 36 18000 10590 2300 2200 1500 3300 4200
ST 233-58 43 21000 12360 2300 2500 1500 3300 4500
ST 264-66 50 24000 14120 2700 2500 1700 3700 4500
ST 303-66 56 27000 15890 2700 2750 1700 3700 4750
ST 346-74 63 31000 18240 2850 2750 1850 3850 4750
ST 373-74 66 34000 20000 2850 3050 1850 3850 5050
ST 420-82 68 37500 22060 3050 2900 2100 4050 4900
ST 470-82 86 42000 24710 3050 3250 2100 4050 5250
ST 555-92 95 48000 28240 3550 3150 2500 4550 5150
ST 625-92 114 56000 32950 3550 3550 2500 4550 5550
ST 715-104 128 64000 37650 3750 3750 2650 4750 5750
+ Service Area mm
Hight
750
750
750
800
900
950
950
1050
1050
1100
1100
1350
1350
1350
1350
1500
1500
1700
1700
1850
1850
2100
2100
2500
2500
2650
COOLING LOAD ESTIMATE SHEET
COOLING LOAD ESTIMATE SHEET Copy Right Dr. Ali Faramawy
SUPERVISION:
Prof. Dr. Ali Faramawy
Arch. Tarek Hassan
Working Drawing 1
3rd Year, 2002-2003
Department of Architectural Engineering
Ain Shams University

ADVISORS:
Prof. Dr. Ahmed El Assy, Mechanical

STUDENTS
Mohamed Hisham

You might also like