Professional Documents
Culture Documents
Wang 2017
Wang 2017
Abstract—The well-known active power-frequency and distributed generators and loads are interconnected separately.
reactive power-voltage amplitude droop scheme is widely used in Droop control strategy and its variants have appealed to a large
islanded microgrids to automatically share load power and number of researchers in the last decade. Considerable efforts
regulate output voltage of parallel voltage-controlled inverters were made to improve performance of droop controlled parallel
(VCIs) in microgrids. However, droop controlled VCIs tend to inverters operating in islanded microgrids. For example, virtual
lose stability as droop slopes increasing. Meanwhile, parameter impedance is introduced to the conventional droop controller,
discrepancies extend synchronization time between VCIs which providing better active and reactive power decoupling and
degrade system dynamic performance. In order to compensating accurate reactive power sharing [4-6]. The concept of robust
above limitations of traditional method, this paper proposed a
droop controller is developed to manage the inherent trade-off
droop based hybrid control strategy by exploiting advantages
from both voltage-controlled and current-controlled inverters.
between power sharing accuracy and voltage deviation. [7-8].
Capturing the detail of inner control loops, a small-signal state- The stability issues are also discussed detailedly in [9-10].
space model is derived to analyze characteristics of the overall However, almost without exception only VCIs are focused.
parallel system. Comparing to traditional method, eigenvalues of Actually, a significant number of inverters belonging to
the hybrid control strategy indicate better stability and dynamic renewable energy generation operate in current-controlled
performance. In agreement with theoretical analysis, both mode, like photovoltaic or wind power systems in microgrids
simulation and experimental results are presented to validate the
[11]. Besides stable voltage sources like large synchronous
advantages of this proposed strategy.
generators, current sources like wind turbines could also
Keywords—active and reactive power droops; voltage-controlled participate in the regulation of grid voltage in conventional
and current-controlled inverters; state-space model power systems [12]. As for microgrids, the potential grid-
supporting ability of CCIs were also noticed by authors in [13].
The basic control structure of grid-supporting inverter
I. INTRODUCTION operating as current source was defined. In grid-connected
When it comes to coordinative control strategies of parallel mode, this kind of inverter could contribute to the regulation of
inverters in standalone ac supply systems, two dominant grid frequency and voltage by delivering proper values of
schemes are master-salve control and droop control methods active and reactive power, yet no further investigations were
[1]. In master-slave control structure, one voltage-controlled made. Comparing to voltage controlled mode, inverter
inverter (VCI) acts as master voltage source to maintain operating as current source has simpler control structure, faster
constant voltage on ac bus while other current-controlled dynamic response and more independence in power flow
inverters (CCIs) act as slave current sources to track control [14]. If these advantages were properly introduced to a
distributive current references. It is easy to implement this parallel system, there would exist a chance to improve the
control strategy and achieve tight current sharing [2]. Owing to overall performance.
limit flexibility brought by critical intercommunication links,
master-slave control is confined to centralized applications like This paper initiates the idea of developing a droop based
uninterruptible power supply (UPS) systems. The droop control hybrid control strategy for parallel inverters which exploits
method is also called peer to peer control, which is based on advantages from both VCI and CCI. Firstly, the basic structure
the active power-frequency (P-ω*) and reactive power-voltage of hybrid control is established. Secondly, capturing the detail
amplitude (Q-V *) droop mechanism to realize automatic power of inner control loops, a small-signal state-space model is
sharing and voltage regulation between parallel inverters [3]. derived to analyze the operation of the parallel system.
The independency of communication make droop control Comparing to traditional droop method where only VCIs are
method become the most suitable choice for microgrids, where considered, the eigenvalues of the hybrid control strategy
indicate better stability and dynamic performance. Finally,
simulation and experimental results are presented to validate
This work was supported by the National Natural Science Foundation of
the advantages of this proposed strategy.
China under Grant 51437007, and the Power Electronics Science and
Education Development Program of Delta Environmental & Educational
Foundation under Grant DREM2014002.
+
+
- -
Master Cf_M iload Cf_S Slave
VCI PLL CCI
θ_M θ_M Rload voq_S θ_S
PWM
abc
iodq_M PWM
abc Power kp+ki /s abc
*
vi _ M vodq_M vod_S
Cal
Lload
ωff dq v*i _S
+
dq vodq_M dq
+
ω
ildq_M PM QM
θ_S
iodq_S
abc v *id _ M
Dual-loop * *
vd = v* , vq* ≡ 0 ω * = ω0 − m p _ M ( PM − P0 _ M )
*
PS* = P0 _ S + (ω 0 − ωS ) / m p _ S id = PS vod _ S v *id _S abc
Control
dq v * Current v *
iq _ M
θ_M ω* (
v* = V0 − nq _ M QM − Q0 _ M ) QS* = Q0 _ S + (V0 − vod _ S ) / nq _ S *
iq = QS* vod _ S Control iq _S dq
θ_M Droop for Master Droop for Slave θ_S
PS* = P0 _ S + (ω0 − ωS ) / m p _ S
II. HYBRID CONTROL STRUCTURE (2)
In a conventional droop controlled parallel inverter system, QS* = Q0 _ S + (V0 − vod_S ) / nq _ S
all modules are equally treated as peer to peer voltage sources. where PS* and QS* are calculated output active and reactive
Different inverters coordinate with each other by regulating
power reference. P0 _ S and Q0 _ S are the initial active and
their own output frequency and voltage amplitude based on the
P-ω* and Q-V *droop mechanism. In steady state, the overall reactive power references when ωS=ω0, vod_S=V0. ωS is the
frequency is synchronized and load power proportionally estimated PCC frequency tracked by a synchronous reference
shared at the same time. However, parallel droop controlled frame phase-locked loop. Through a feedback control loop, the
VCIs tend to lose stability if the value of droop slopes angular position of this dq reference frame is controlled to
increased [10]. Meanwhile, the synchronization between drive the voq_S component to zero. Therefore, the value of vod_S
different VCIs take relatively long time especially there exists equals to the estimated PCC voltage amplitude. mp_S and nq_S
discrepancies in line inductance, which degrade the dynamic are the active and reactive power inverse droop slopes.
response [15]. Unlike VCIs, CCIs do not generate frequency In steady state, the CCI synchronized with VCI which
references individually. A well-designed phase-locked loop can means ωS=ω*, the active output power reference for CCI is:
ensure fast and precise tracking of the frequency at the point of
common coupling (PCC) [16]. Comparing to VCIs, CCIs have PS* = P0 _ S + [ω0 − (ω0 − m p _ M ( PM − P0 _ M ))] / mp_S
faster dynamic response and more independence in power flow (3)
control [14], which may compensate the limitations of VCIs m p _ M PM − m p _ M P0 _ M =m p _S PS* − m p _S P0 _ S
and improve the overall system performance.
If mp_M and mp_S for master and slave inverters are designed
In order to introduce CCIs into the parallel system, the proportional to their nominal output power set points, the
master-salve structure is an ideal choice considering the actual output active power of two inverters will be
absence of utility voltage support in islanded microgids. Fig.1 automatically proportional shared based on their ratings as (4).
shows a basic structure of the hybrid control strategy which
consists of a master VCI and a slave CCI. The VCI adopts m p _ M P0 _ M = m p _S P0 _ S
conventional P-ω* and Q-V* droop control, operating as a (4)
m p _ M PM = m p _S PS*
master voltage source to set up PCC voltage. As the left-hand
side blue equations shown in Fig.1: If line impedance Lc_M and Lc_S are identical (only inductive
component is included in Fig.1), the value of vod_S will equal to
ω = ω0 − m p _M ( PM − P0 _M )
*
v* of master inverter. Like active power in (3) and (4), there is
(1)
v* = V0 − nq _M (QM − Q0 _M ) also similar relationship between reactive power of two
where ω* and v* are calculated output frequency and voltage inverters: nq _ M QM = nq _SQS* . However, when Lc_M ≠ Lc_S the
amplitude references. ω0 and V0 are nominal values of PCC reactive power cannot be proportional shared because of the
voltage. mp_M and nq_M are frequency and amplitude droop discrepancy between vod_S and v*.
slopes. P0 _M and Q0 _M are ideal operating set points for master
In conclusion, this hybrid control strategy could realize the
inverter. same steady-state power sharing function as traditional droop
According to the control diagram of current-controlled method where only VCIs are considered. After introducing the
grid-supporting inverter proposed in [13], the slave CCI adjusts inverse droop controlled slave CCI, the improvements on
its output power with voltage amplitude and frequency system stability and dynamic performance will be analyzed via
deviation following an inverse ω-P* and V-Q* droop small-signal state-space modeling, simulation and experimental
relationship. As the right-hand side blue equations shown in results comparison in following sections.
Fig.1:
3463
III. SMALL-SIGNAL STATE-SPACE MODELING 0 0 − nq _M
CPω _ M = 0 − m p _M 0 CPv _ M = (10)
The modeling approach to the two inverter parallel system
0 0 0
in Fig.1 divides into several sub-modules: master VCI, slave
CCI, output LC filter and line impedance, and loads at PCC.
* *
ildq_M
The reference frame of master VCI is chosen as the common vdq_M
reference frame to construct the complete system model. kpv_M+kiv_M /s
vodq_M
A. Master VCI
1) Power Controller: For small-signal state space Fig. 2. Voltage controller of master VCI.
modelling of traditional droop controlled parallel VCIs, authors
2) Voltage Controller: The block diagram of voltage
from [10] have provided a well-established demonstration. The
controller in master VCI is shown in Fig.2. To simplify the
modeling procedures of master VCI in the hybrid control
calculation, no decoupling nor feed-forward terms are included.
strategy are conducted in accordance with [10]. In “Power Cal”
Defining intermediate state variables as:
block of Fig.1, firstly instantaneous active and reactive power
p and q are calculated as (5). d φd _ M d φq _ M
= vd* _ M − vod _ M , = vq* _ M − voq _ M (11)
p M = vod_M iod_M + voq_M ioq_M dt dt
(5) The small-signal state-space equation of ϕdq_M and ildq *
_M is:
qM = vod_M ioq_M − voq_M iod_M
Through a one order low-pass filter whose cut-off frequency is Δildq _ M
ωc, the average active and reactive power are obtained.
Δφdq _ M = [ 0] Δφdq _ M + BV 1 Δv + BV 2 Δvodq _ M
*
dq _M
ωc ωc Δi (12)
PM = p M , QM = qM (6) odq _ M
s + ωc s + ωc 1 0 0 0 − 1 0 0 0
According to droop expression in (1), the small-signal equation BV 1 = , BV 2 =
of frequency and voltage amplitude references are: 0 1 0 0 0 − 1 0 0
Δildq _ M
ΔωM = −m p _M ΔPM
Δi = CV Δφdq _ M + DV 1 Δv + DV 2 Δvodq _ M
* *
* *
(7) ldq _ M dq _M
Δvod _M = − nq _M ΔQM , Δvoq ≡0 Δi
odq _ M
Representing the angle between individual dq frame and the
common reference DQ frame, δ is defined in (8). kiv _ M 0 k pv _ M 0
CV = , DV 1 = (13)
0 kiv _ M 0 k pv _ M
δ = (ωi − ωcom ) Δδ = Δωi − Δωcom (8)
0 0 − k pv _ M 0 0 0
where ωi and ωcom are rotating frequency of individual inverter DV 2 =
and common reference frame. After linearizing and simplifying 0 0 0 k pv _ M 0 0
(5) to (8), the small-signal state-space model of power
controller can be written in (9) and (10). *
ildq_M v*idq_M
kpc_M+kic_M /s
Δδ M Δδ M Δildq _ M ildq_M
ΔP = A ΔP + B
M P _M M P _ M Δvodq _ M + BPω com _M Δωcom
Fig. 3. Current controller of master VCI.
ΔQM ΔQM Δi
odq _ M 3) Current Controller: Fig.3 shows the block diagram of
Δδ inner current control loop of master VCI. Similarly,
ΔωM CPω _ M M
* = ΔPM intermediate state variables γdq_M are defined.
Δvodq _ M CPv _ M dγ d _ M * dγ q _ M *
ΔQM = ild _ M − ild _ M , = ilq _ M − ilq _ M (14)
(9) dt dt
0 − m p _M 0 −1
0 BPωcom _M = 0
*
AP _M = 0 − ωc The small-signal state-space equation of γdq_M and vidq_M is:
0 − ωc 0 Δildq _ M
0
0 0 0 0 0 0 Δγ dq _ M = [ 0] Δγ dq _ M + BC1_ M Δi
*
+ BC 2 _ M Δvodq _ M
ldq _M
Δi
BP _M = 0 0 ωc I od _M ωc I oq _M ωcVod _M ωcVoq _M odq _ M (15)
1 0 −1 0 0 0 0 0
0 0 ωc I oq _M − ωc I od _M − ωcVoq _M ωcVod _M BC 1_ M = , BC 2 _ M =
0 1 0 − 1 0 0 0 0
3464
Δildq _ M Δid* Δvod _ S
* = D1ΔPLL + D2
Δv = CC_M Δγ dq _ M + DC1_M Δi + DC 2_M Δvodq _ M
* *
idq _ M ldq _M
Δiq Δvoq _ S
Δiodq _ M PS* kp
kic _ M 0 k pc _ M 0 ki − 2 − (23)
CC_M = (16) − Vod _ S Vod _ S m p _ S
, DC1_M = D1 = Vod _ S m p _ S D2 =
0 k
ic _ M 0 k pc _ M *
0 − Vod _ S + nq _ SQS 0
− k pc _ M 0 0 0 0 0
DC 2_M = nq _ SVod2 _ S
0 − k pc _ M 0 0 0 0
Fig.4 shows the block diagram of current controller of slave
B. Slave CCI CCI. Like γdq_M in (14), intermediate state variables γdq_S are
1) PLL Controller: For salve CCI, as Fig.1 shows, the PLL defined.
model is firstly derived. Define a state variable PLL as: dγ d _ S dγ q _ S
d PLL = id* − iod _ S , = iq* _ S − ioq _ S (24)
= voq _ S (17) dt dt
dt
Then the small signal form of synchronized frequency ωs is: *
The small-signal state-space equation of γdq_S and vidq_S is:
3465
Similarly, as the input variable for inverters, PCC voltage
Δildq _ i Δildq _ i on common reference frame ∆vPCCDQ should be converted to
Δv =A individual reference frames using reverse transformation. Since
odq _ i LCL _ i Δvodq _ i + BLCL1_ i Δvidq _ i
the reference frame of master VCI is chosen as the common
Δ
odq _ i
i Δ
odq _ i
i reference frame, ∆ωcom =∆ωM, δ0M=0. The steady state angle
+ BLCL 2 _ i [ΔvPCCdq _ i ] + BLCL 3 _ i Δωi difference between slave CCI and the common reference frame
−1 δ0S is determined by the output of PLL.
0 ω0 0 0 0
Lf _i ΔvPCCdq _ i = TS−__1 i ΔvPCCDQ + TV−_1i Δδ i
−ω −1
0 0 0 L 0 0 −VPCCD sin (δ 0i ) + VPCCQ cos (δ 0i ) (30)
f _i
TV−_1i =
1 −1 VPCCD cos (δ 0i ) − VPCCQ sin (δ 0i )
0 0 ω0 0
C C f _i
ALCL _ i = f _ i Combing (9), (12), (13), (15), (16), (28), (29) and (30), the
0 1 −1 sub-model of master VCI is obtained in (31). There are totally
− ω0 0 0
C f _i C f _i 13 states, three inputs and three outputs.
0 1
0 0 ω0
0
Lc _ i [ Δ xM ] = AM [ Δ xM ] + BM Δ vPCCDQ + Bωcom_M [ Δωcom ]
1
0 0 0 − ω0 0 ΔωM CINVω _ M
Lc _ i Δi = [ Δ xM ] (31)
oDQ _ M CINVc _ M
1 0 0
where, [ Δ xM ] = [Δδ M ΔPM ΔQM Δφdq _ M
L 0 0
0
f _i 0 0 Δγ dq _M Δildq _ M Δvodq _ M Δiodq _ M ]13
T
0 1 ×13
L 0 0 (28) Combing (20), (23), (25), (26), (28), (29) and (30), the sub-
BLCL _ i = f _i
BLCL 2 _ i = −1 model of slave CCI is obtained in (32). There are totally 10
0 0 L 0 states, three inputs and two outputs.
0 0 c_i
0 0 −1
3466
diloadD − Rload 1
= iloadD + ωcom iloadQ + vPCCD
dt Lload Lload
(34)
diloadQ − Rload 1
= iloadQ − ωcomiloadD + vPCCQ
Imaginary ——>
dt Lload Lload
− Rload 1 − I loadD
−ω0 L 0 L
load load
In (33) and (35), ∆vpccDQ are regarded as inputs to each sub-
model. To ensure the PCC voltage is well defined, authors Fig. 6. Traces of eigenvalues as mp increasing.
from [10] come up with a solution which assume a sufficiently
large virtual resistor rN (1000 Ω) to be connected between PCC
and ground. Hence, the PCC voltage could be expressed as:
3467
keep staying in left half plane. It suggests that this hybrid 2.3k
P_A P_B
O utput power W
2.0k
increase than traditional method.
1.8k
Fig. 8 plots the overall eigenvalue locations of two control 1.5k
schemes with the same parameters (mp, nq=1e-4, Lc_M =2.7 mH, 1.3k
Lc_S =1.4 mH). It could be clearly seen from cluster 3, 2 and 1 1.0k
that comparing to traditional method, the eigenvalues of hybrid f_A f_B
control at high, medium and low frequency range are all further 50.025
Frequency Hz
50.000
line inductance, this hybrid control could realize faster settling 49.975
speed and stronger damping on high frequency oscillation.
49.950
Output power W
1.8k
A. Simulation Results 1.5k
Simulations are conducted in PSCAD/EMTDC software. In 1.3k
hybrid control scheme, the master is drooped controlled voltage 1.0k
source and the slave is inverse droop controlled current source f_M f_PLL
50.025
whose parameters are listed in Table I. In traditional method, Frequency Hz
inverter A and B are both drooped controlled VCI whose 50.000
parameters are the same as master VCI in hybrid control 49.975
method.
49.950
P_A P_B
6.0k
49.925
5.0k t s 1.50 2.00 2.50 3.00 3.50 4.00
4.0k
Fig. 12. Hybrid controlled VCI and CCI with load step change.
Output power W
3.0k
Firstly, Fig. 9 and 10 shows the output active power
2.0k waveforms of two inverters. When droop gain mp increased
1.0k from 1e-4 to 1e-3 at 2s, the traditional droop controlled VCIs
0.0
lose stability immediately while master and slave inverters in
Fig.10 just experience a small oscillation within 0.1s then
-1.0k maintaining stable operation. Secondly, Fig. 11 and 12 shows
-2.0k the output active power and frequency waveforms of two
t s 1.50 2.00 2.50 3.00 3.50 inverters with mp, nq=1e-4, Lc_M/A =2.7 mH, Lc_S/B =1.4 mH.
When load power increased from 3kW to 4kW at 2s, the
Fig. 9. Traditional droop controlled VCIs with mp increasing.
settling time for traditional droop controlled VCIs in Fig. 11 is
P_M P_S about 1.5s while only 0.3s in Fig. 12. Furthermore, the
1.80k
waveforms of hybrid control strategy are smoother with less
1.70k
high frequency oscillations. Agree with eigenvalues from Fig.
6 to 8, the simulation results prove the validity of previous
Output Power W
1.50k
B. Experimental Results
1.40k The hardware experiments are conducted in a platform
consisting of two parallel three-phase inverters (Product Name:
1.30k MYINV-9R144), whose parameters are listed in Table I. The
real-time values of the output active power were recorded by
t s
1.20k
the HIOKI Power Analyzer 3390 and plot via Matlab in Fig. 13
1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50
and 14. Firstly, droop gain mp increased from 1e-4 to 1e-3 at
Fig. 10. Hybrid controlled VCI and CCI with mp increasing. 1.5s in Fig. 13. The traditional droop controlled VCIs in Fig.13
(a) lose stability and inverter B triggers protection then shuts
down. The hybrid controlled VCI and CCI maintaining stable
3468
operation in Fig.13 (b). In accordance with simulation results, VI. CONCLUSION
when line inductance of two inverters are different, the hybrid This paper proposed a droop based hybrid control strategy
control in Fig.14 (b) has shorter settling time and less by exploiting advantages from both voltage-controlled and
overshoot after load step changing from 1070W to 2750W. current-controlled inverters. A small-signal state-space model
is derived to analyze system properties. Both simulation and
experimental results are presented to validate that this hybrid
control strategy achieves better stability and dynamic
performance comparing to traditional method.
REFERENCES
[1] J. M. Guerrero, L. Hang, and J. Uceda, “Control of distributed
uninterruptible power supply systems,” IEEE Trans. Ind. Electron., vol.
55, no. 8, pp. 2845–2859, Aug. 2008.
[2] J. F. Chen and C.-L. Chu, “Combination voltage-controlled and current-
controlled PWM inverters for UPS parallel operation,” IEEE Trans.
Power Electron., vol. 10, no. 5, pp. 547–558, Sep. 1995.
(a) Traditional droop controlled VCIs [3] M. C. Chandorkar, D. M. Divan, and R. Adapa, “Control of parallel
connected inverters in standalone AC supply systems,” IEEE Trans. Ind.
Appl., vol. 29, no. 1, pp. 136–143, Jan./Feb. 1993.
[4] Y. W. Li and C. N. Kao, “An Accurate Power Control Strategy for
Power-Electronics-Interfaced Distributed Generation Units Operating in
Output Power W
3469