Temp R-Tron 612 version 2.

2 U Operation Manual

Temp R-Tron 612


OPERATION MANUAL
Version 2.2 U 26/05/2016

E-mail : tmcc_cn@163.com Page1


Temp R-Tron 612 version 2.2 U Operation Manual
Product Warranty & Limitation of Liability
The product warranty is in accordance with the following regulations:
1. The manufacturer should take responsibility for below specific elements:
• In domestic use (as calculated from the date of invoice)
- Invoice within one month should accept replacement and repair.
- Invoice within twelve months should accept repair.
• Goods exported overseas (excluding China) and invoice within fifteen months, the local seller is responsible for repair.
2. All the distributors, agency or production place of Temp Control in whole China can provide after-sales service for Temp Control product, their
conditions of service as follows:
• We provide inspection service on the local selling place (including troubleshooting).
• All services comply with the related after-sale service terms and conditions stated on the agency agreement between Siam Water Flame and
distributors.
• Buyers can pay to any Temp Control agent if need any after-sales services (whether or not the warranty).
3. The product,s warranty period is one year from the date of invoice. The product shall be free of defects in materials or workmanship and will conform
To technical specification.
4. Siam Water Flame will not be responsible for any labor costs or expenses associated with repair and replacement of defective.
5. In the case of the following causes of failure, even in the warranty period is also a paid repair:
• Incorrect operation (depending on the use of manual), or misuse, alteration, neglect, improper, abuse, accident, or unauthorized maintenance or repair.
• The problems caused by using the control beyond its standard specifications requirement.
• Damage caused by drop down or improper handling.
• Controller components aged or failure caused by improper environment.
• Due to an earthquake, fire, wind and water disasters, lightning strikes, abnormal voltage, electrical power surge, interruption of electricity,
electrical power surge or other natural disasters and disasters, accompanied by the damage caused.
• The damage during transport (Note: The mode of transport designated by the customer, the company's help on behalf of the procedures for
handling the transfer of goods).
• When the manufactures brand, trademark, serial number, nameplate and other damage or cannot be recognized.
• If the buyer has not paid full money according to purchase agreement.
• The installation, wiring, operation, maintenance or other use of objective reality cannot be described to the company's service office.
6. Concerning replacement and repair services, goods shall be returned Temp Control to company, after confirmed the attribution of responsibility then
they are allowed to be returned or repaired.
The user should be aware and alert that something may fail beyond our control exists. Since farm condition and livestock environment may cause
controller damage, the user should provide adequate back up and alarm system. These are to operate critical system even in case of Temp Controller
system failure. Neglecting to provide such a backup will be regarded as the user,s willingness to accept the risk of loss, injury and financial damage.
In no event will Siam Water Flame be liable to user or any third party for any direct, indirect, special, consequential or incidental damages, including but
not limited to any damage or injury to business earnings, lost profits or goodwill, personal injury, costs of delay, any failure of delivery, costs of lost or
damaged data or documentation, lost or damaged products or goods, lost sales, lost orders, lost income. Except of the above express warranty,
Siam Water Flame makes no other warranties, express or implied, relating to the products. Siam Water Flame disclaims and excludes the implied
warranties of merchantability and fitness for a particular purpose. No person is authorized to make any other warranty or representation concerning the
performance of the products other than as provided by Siam Water Flame.

E-mail : tmcc_cn@163.com Page2


Temp R-Tron 612 version 2.2 U Operation Manual
1. INSTALLATION
Open the front panel
1. Connect the Temp R Tron 612 to the wall in a dry place approximately 1 meter away from the electrical
Cabinet and Connect a 220V cable to the unit.
2. Connect the Analog Input (Temperature Sensor, Humidity Sensor), Analog Output, Digital Input as below:
2.1Analog Input Connections
2.1.1 Temperature sensors
T1 is used for indoor temperature sensor 1. Use a two wire cable.
Connect one wire (Brown) to T1 terminal and second wire (White and Black) to the 0V terminal
T2 is used for indoor temperature sensor 2. Use a two wire cable.
Connect one wire (Brown) to T2 terminal and second wire (White and Black) to the 0V terminal
T3 is used for outdoor temperature sensor 3. Use a two wire cable.
Connect one wire (Brown) to T3 terminal and second wire (White and Black) to the 0V terminal
T4 is used for indoor temperature sensor 4. Use a two wire cable.
Connect one wire (Brown) to T4 terminal and second wire (White and Black) to the 0V terminal
The sensors can be placed up to 180 meters from the main unit with an ordinary two-wire cable.

Wiring Diagram Temp R-Tron 612 Temperature sensor

TEMP 3-4 ANALOG OUT D-IN 3-4


INV

DIM

T3 0V T4 0V X3 X4 CM2

TEMP 1-2 HUMIDITY D-IN 1-2


HUM

T1 0V T2 +V 0V X1 X2 CM1
BROWN
WHITE/BLACK
WHITE/BLACK

WHITE/BLACK

WHITE/BLACK
BROWN

BROWN

BROWN
T3 Temperature Sensor Outside

T1 Temperature Sensor Inside

T2 Temperature Sensor Inside

T4 Temperature Sensor Inside

E-mail : tmcc_cn@163.com Page3


Temp R-Tron 612 version 2.2 U Operation Manual
2.1.2 Humidity sensors
HUM is used for humidity sensor. Use a three wire cable. Brown to +V terminal,
White to HUM terminal. and Green to 0V terminal
The sensors can be placed up to 180 meters from the main unit with an ordinary three-wire cable.

Wiring Diagram Temp R-Tron 612 Humidity sensor

TEMP 3-4 ANALOG OUT D-IN 3-4

INV

DIM
T3 0V T4 0V X3 X4 CM2

TEMP 1-2 HUMIDITY D-IN 1-2

HUM
T1 0V T2 +V 0V X1 X2 CM1

BROWN

GREEN
WHITE
Humidity Sensor Inside

2.2 Analog Output Connections


2.2.1 Analog Output 1 is used for the variable speed fan inverter (0-10VDC). Use a two wire cable.
Connect one wire to INV terminal and second wire to the 0V. terminal.
2.2.2Analog Output 2 is used for the Dimmer Light or variable speed fan 2 (0-10VDC) see code 78.
Use a two wire cable. Connect one wire to DIM terminal and second wire to the 0 V. terminal.
2.3 Digital Input Connections
2.3.1 X1 is used for the water meter dry contact signal. Use a two wire cable.
Connect one wire to X1 terminal and the seconds wire to CM1 terminal.
The signal from the water meter should be wired in such a way that when the water meter sends a pulse
( 1 pulse per 10 Liters), the dry contact will be in a normally closed state (shorted).
( See Water meter wiring diagram page 40)

E-mail : tmcc_cn@163.com Page4


Temp R-Tron 612 version 2.2 U Operation Manual
2.3.2 X2 is used for the Feed counter dry contact signal. Use a two wire cable.
Connect one wire to X2 and The second wire to CM1.
The signal from Feed counter should be wired in such a way that when the feed counter send a pulse
( 1 pulse user can set weight kilogram or by time user can set in 10 second by kilogram),
the dry contact will be in a normally closed state (shorted). ( See Feed counter wiring diagram page 40)
2.3.3 X3 is used for the Curtain control feedback dry contact signal. Use a two wire cable.
Connect one wire to X3 and The second wire to CM2.
The signal from Curtain control feedback should be wired in such a way that when the curtain moves,
the dry contact will be in a normally closed state (shorted). ( See Curtain control wiring diagram page 40)
2.3.4 X4 is used for the Inlet control feedback dry contact signal. Use a two wire cable.
Connect one wire to X4 and The second wire to CM2.
The signal from Inlet control feedback should be wired in such a way that when the Inlet moves,
the dry contact will be in a normally closed state (shorted). ( See Inlet control wiring diagram page 40)
3. Connect the relay’s outputs to the various systems. All outputs are dry contacts, maximum 4 Amp/220V
(see drawing page 36 -39) Note that there is no breaker (fuse) inside and it must be installed externally.

Relay number Output Type 1 Output Type 2 Output Type 3 Output Type 4 Output Type 5 Output Type 6 Output Type 7
Analog Curtain Analog Inlet Analog All
No use all Use Curtain Use Inlet Use All
Code 55 = 1 Code 55 = 2 Code 55 = 3 Code 55 = 4 Code 55 = 5 Code 55 = 6 Code 55 = 7
1 Fan group 1 Fan group 1 Fan group 1 Fan group 1 Fan group 1 Fan group 1 Fan group 1
2 Fan group 2 Fan group 2 Fan group 2 Fan group 2 Fan group 2 Fan group 2 Fan group 2
3 Fan group 3 Fan group 3 Fan group 3 Fan group 3 Fan group 3 Fan group 3 Fan group 3
4 Fan group 4 Fan group 4 Fan group 4 Fan group 4 Fan group 4 Fan group 4 Fan group 4
5 Fan group 5 Fan group 5 Fan group 5 Curtain open Fan group 5 Fan group 5 Fan group 5
6 Fan group 6 Fan group 6 Fan group 6 Curtain close Fan group 6 Fan group 6 Fan group 6
7 Fan group 7 Curtain open Inlet open Inlet open Fan group 7 Fan group 7 Fan group 7
8 Fan group 8 Curtain close Inlet close Inlet close Fan group 8 Fan group 8 Fan group 8
9 Cooling Cooling Cooling Cooling Cooling Cooling Cooling
10 Heating Heating Heating Heating Heating Heating Heating
11 Lighting Lighting Lighting Lighting Lighting Lighting Lighting
12 Alarm Alarm Alarm Alarm Alarm Alarm Alarm

E-mail : tmcc_cn@163.com Page5


Temp R-Tron 612 version 2.2 U Operation Manual
2. OPERATION
The Temp R-Tron 612 will display the average temperature of the connected in house temperature sensors.
It is possible to display each sensor separately.
Turn on power.
1. Each time power is connected to the unit “2.2” will appear on the right display. This number is version number,
and the controller will count down for Delay System ( Code82 ) normally is 3 seconds.
2. The left red display indicates the indoor temperature. The center green display shows the indoor humidity.
and the right red display shows the code.
3. To display temperature, Press on button “ 1 ”
The right red display shows “ ” the left red display shows present temperature of sensor 1.
If user want to calibrate temperature sensor 1 Press “Enter”
The left red display shows flashing indicates “ 0 “ and the center green display shows 
User must key user password (3digit). If have not password. key “ 0 ” three time.
The left red display shows flashing present temperature. User can key new temperature value and press “Enter”.
New temperature will be updated. Press “Next”
The right red display shows “ ” the left red display show temperature of sensor 2.
If user want to calibrate temperature sensor 2. please following the process same  Then press “Next”
The right red display shows “ ” the left red display show temperature of sensor 3.
If user want to calibrate temperature sensor 3. Please following the process same  Then press “Next”
The right red display shows “ ” the left red display show temperature of sensor 4.
If user want to calibrate temperature sensor 4. Please following the process same 
4. To display humidity, Press on button “ 2 ”
The right red display shows “” the center green display show humidity
If user want to calibrate humidity sensor. Please following the process same 
5. To display percentage of Speed Fan (0-100%), Press on button “ 3 ”
The right red display shows “” the left red display show for percentage of Speed Fan (0-100%)
6. To display percentage of Dimmable Light (0-100%), Press on button “ 4 ”
The red right display shows “ ” the left red display show for Dimmable Light (0-100%)
7. To display percentage of Curtain (0-100%), Press on button “ 5 ”
The right red display shows “ ” the left red display show for percentage of Curtain (0-100%)

E-mail : tmcc_cn@163.com Page6


Temp R-Tron 612 version 2.2 U Operation Manual
If user want to calibrate Curtain timing Press “Enter”
The left red display shows flashing indicates “ 0 “ and the center green display shows 
User must key user password (3digit). If have not password. key “ 0 ” three time.
Then key “1” for confirm to calibrate Curtain timing and press “Enter”
The left red display shows  The controller will close the curtain until 0 % then will count timer from
curtain close to curtain open 100%. If controller finished calibration then it will open at position of control.
Before calibration please check code 55 for choose output type 2 or 4
8. To display percentage of Inlet (0-100%) , Press on button “ 6 ”
The right red display shows “” the left red display show for percentage of Inlet (0-100%)
If User wants calibrate Inlet timing Press “Enter”. Please following the process same curtain.
Before calibration please check code 55 for choose output type 3 or 4
9. To display Total water consumption and Total Feed consumption, Press on button “ 7 ”
The Left red display The center green display Water consumption
Example :   
Total water consumption 012580(Pulse) X 10 liter(1 Pulse=10Liter) = 125,800 Liter
Press “Next”
The Left red display The center green display Feed consumption
Example :   
Total Feed consumption 074693(Pulse) X 10 Kg.(1 Pulse=10Kg.) = 746,930 Kg.
10. To display water consumption in today and Total Feed consumption in today, Press on button “ 8 ”
The right red display shows “” the left red display and center green display shows for
water consumption in today. Press “Next”
The right red display shows “ ” the left red display and center green display shows for
feed consumption in today.

E-mail : tmcc_cn@163.com Page7


Temp R-Tron 612 version 2.2 U Operation Manual
11. To display Alarm Even, Press on button “ 9 ”
The right red display shows “” ” the left red display show Type of Alarm

 Sensor disconnect


 Sensor damage or short circuit
 Sensor problem (Incase use more than one Temperature sensor)
  Absolute High Temperature Alarm
  Differential High Temperature Alarm
  Absolute Low Temperature Alarm
  Differential Low Temperature Alarm
  Differential Temperature Alarm (T1 and T2)
  Absolute High Humidity Alarm
  Differential Humidity Alarm
  Current Timing in controller have problem. Need to Re-Program
  Temperature sensor 1 have problem
  Temperature sensor 2 have problem
  Temperature sensor 3 have problem
  Temperature sensor 4 have problem
  Humidity sensor have problem

3. READING SET POINT


It is possible to read all the information on the Temp R-Tron 612 display.
The right red display indicates the function code. The left red display shows the set point for each function code.
Each function code has a set point. (see menu on the front panel)
By pressing on the “Code” button, the Code number display on the right side of the panel will show ”00”
(Required Fan Temp). The preset information will appear on the data display on the left side of the panel.
Example:
If you would like to see function code 01; Press on the “Code” button then Press on “01” On the function display will
appear 01 and on the data display will appear the information. If you would like to see next function no.02; press on the
“Next” button or press on “02”On the function display will appear 02 and on the data display will appear the information.
Some functions have more information in one code
Example:
Press on the “Code” button then press on “31”. On the function display will appear “31” and on the data display will appear
the information. If you would like to see next function; Press on the “Next” button or press on “d2” (Function 31-d2)
On the function display will appear d2 and on the data display will appear the information.

E-mail : tmcc_cn@163.com Page8


Temp R-Tron 612 version 2.2 U Operation Manual
4. CHANGE OF SET POINT
It is possible to change each set point.
1. Go into the desired function as explained above.
2. Press on “Enter” button. The function display will start to flash.
3. Use the keyboard to enter the desired data. The new data will appear on the data display.
4. Check the display to see if the information is correct. If yes, press on the “Enter” button again. The function
display will stop flashing to indicate that the new information has been stored into the unit’s memory.
5. SET POINTS
Function
00. Required Fan Temp
The required fan temperature is the requested fan temperature for the house. All set points (except the Required Heat Temp
and Required Cool Temp set point) are set as a differential above or below the required fan temperature.
The required fan temperature will be reduced daily according to the stage table (see hidden Code 31 T-Curve)
01. Fan1
Fan 1 set point is the temperature differential above the required fan temperature at which time fan 1 will operate nonstop.
Fan group 1 alone may be used as a minimum ventilation fan group or it may be used together in a rotating manner together
with the other 8 fan groups (see Code 61 Select Fan Vent.).
02. Fan2
Fan 2 set point is the temperature differential above the required fan temperature at which time fan 2 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.).
03. Fan3
Fan 3 set point is the temperature differential above the required fan temperature at which time fan 3 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.).
04. Fan4 or Spray
See code 79 for select Fan4 mode or Spray mode before setting.
Fan 4 set point is the temperature differential above the required fan temperature at which time fan 4 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.).
Spray set point is the humidity differential below the required Humidity off cooling pump curve (code 47)
If humidity in the house is lower than set point of humidity differential. Spray will On and Off until reach the set point.

E-mail : tmcc_cn@163.com Page9


Temp R-Tron 612 version 2.2 U Operation Manual
05. Fan5
Fan 5 set point is the temperature differential above the required fan temperature at which time fan 5 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.).
06. Fan6
Fan 6 set point is the temperature differential above the required fan temperature at which time fan 6 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.)
07. Fan7
Fan 7 set point is the temperature differential above the required fan temperature at which time fan 7 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.).
08. Fan8
Fan 8 set point is the temperature differential above the required fan temperature at which time fan 8 will operate nonstop.
it may be used together in a rotating manner together with the other 8 fan groups (see Code 61 Select Fan Vent.)..
09. Fan On Time
Fan on time is set in minutes and seconds (0.1=10sec. / 0.2=20sec./ 0.3=30sec./0.4=40sec./0.5=50sec.)
This is the length of time the minimum ventilation fans will run during minimum ventilation cycle.
Example: Fan On Time = 1.3This means fan will be on 1 minute and 30 seconds.
Fan On Time = 2.5 This means fan will be on 2 minutes and 50 seconds.
Fan on time is possible to set a required on a table automatically as stage 1-8 (    )
The day stage is use same as Fan stage.
10. Fan Off Time
Fan off time is set in minutes and seconds (0.1=10sec. / 0.2=20sec./ 0.3=30sec./0.4=40sec./0.5=50sec.)
This is the length of time the minimum ventilation fans will be off during minimum ventilation cycle.
The Fan LED will be flashing during off time period.
Example: Fan Off Time = 5.2 This is mean fan will be off 5 minutes and 20 seconds.
Fan Off Time = 4.1 This is mean fan will be on 4 minutes and 10 seconds.
Fan Off time is possible to set a required on a table automatically as stage 1-8 (    )
The day stage is use same as Fan stage.
11. Fan Humidity Set
Fan humidity set is set in percentage. If the humidity reading in the house reaches the set humidity as set here, the unit
will automatically reduce require fan temperature 1C down then the unit will open more fan group.
Note: Fan Humidity Set = 0 It means off this function. Maximum reduce require fan temperature = 3 C
E-mail : tmcc_cn@163.com Page10
Temp R-Tron 612 version 2.2 U Operation Manual
Example:
Code # Setting
00. Requested Fan Temperature 30° C
01. Fan 1 1.0
02. Fan 2 2.0
03. Fan 3 3.0
04. Fan 4 4.0
05. Fan 5 5.0
09. Fan on time (minutes. Seconds) 2.3
10. Fan off time (minutes. Seconds) 5.0
If the current average temperature in the house is 30°C or less, then the unit will be working in the minimum
ventilation mode.
Fan 1 will be working in minimum ventilation cycle. Fan 1will be run 2 minute 30 seconds and be off
5 minutes (Code 09 and 10)
If the temperature reaches 31°C (Code 00 + Code 01). Fan 1 will be run continuously. The unit will no
longer be in the minimum ventilation cycle.
When the temperature reaches 32°C (Code 00 + Code 02). Fan 2 will be start. Now both Fans 1 and Fan 2 will be
operating nonstop.
This procedure will continue with Fan 3, 4 and 5 as the temperature raises. The reverse procedure will
apply when the temperature starts to drop.
12. Required Heat Temp
The required heat temperature is the requested heat temperature for the house.
The required heat temperature will be reduced daily according to the stage table (see hidden Code 32H-Curve)
13. Required Cool Temp
The required cool temperature is the requested cool temperature for the house.
The required cool temperature will be reduced daily according to the stage table (see hidden Code 33C-Curve)
14. Humidity Off Cooling Pump
Humidity off cooling pump set is set for high humidity cut off cooling pump. If humidity reading in the house reaches the
set high humidity as set here, the unit will automatically cut off cooling pump. If humidity reduced as below diff humidity
set point (see Code 37). The cooling pump will come back to operate.
15. Cool ON Time
This is the cooling pump ON time period, set in minutes and seconds,
(0.1=10sec. / 0.2=20sec./ 0.3=30sec./0.4=40sec./0.5=50sec.)which the cooling system will run.
16. Cool OFF Time
This is the cooling pump off time period, set in minutes and seconds,
(0.1=10sec. / 0.2=20sec./ 0.3=30sec./0.4=40sec./0.5=50sec.)which the cooling system will be off during the cooling system
cycle.The Cool LED will be flashing during off time period.
E-mail : tmcc_cn@163.com Page11
Temp R-Tron 612 version 2.2 U Operation Manual
Example:

Code # Setting
13 Requested Cool Temperature 30° C
14 Humidity off cooling pump 80 %
15 Cool ON Time (minutes. Seconds) 2.1
16 Cool OFF Time (minutes. Seconds) 4.2
37 Diff Humidity 2%
If the house temperature reaches 30oC the cooling system will be start to operate. The cooling system will be run for
2 minutes and 10 seconds (code 15), and be off for 4 minutes and 20 seconds (code 16)
If humidity reading in the house reaches 80% the cooling system will be off. If humidity reduced as 78%
(see Code 37). The cooling pump will be come back to operate.
17. High Temp Alarm and Different High Temp Alarm
High Temp Alarm is set point the high temperature alarm. If the house temperature reaches to set point then the
Alarm relay will be activated.
Different High Temp Alarm is set point high temperature differential above the required fan temperature (code 00).
18. Low Temp Alarm and Different Low Temp Alarm
Low Temp Alarm is set point the low temperature alarm. If the house temperature reduced to set point then the
Alarm relay will be activated.
Different Low Temp Alarm is set point low temperature differential reduce the required fan temperature (code 00).
19. High Humidity Alarm and Different High Humidity Alarm
High Humidity Alarm is set point the high humidity alarm. If the house humidity reaches to set point then the
Alarm relay will be activated.
Different High Humidity Alarm is set point high humidity differential above the required humidity (code 47).
20. Growth Days
This is the current grow day of the flock. At the beginning of the flock enter 0 here
The required fan temperature (code 00) will automatically receive the value as entered in Growth day 0.
21. Data Recording
 : Maximum Temperature Inside House Today with time recoding.
 : Minimum Temperature Inside House Today with time recoding.
 : Maximum Temperature Outside House Today with time recoding.
 : Minimum Temperature Outside House Today with time recoding.
 : Maximum Humidity Inside House Today with time recoding.
 : Minimum Humidity Inside House Today with time recoding.

E-mail : tmcc_cn@163.com Page12


Temp R-Tron 612 version 2.2 U Operation Manual
22. Data Recording for Yesterday
 : Maximum Temperature Inside House Yesterday with time recoding.
 : Minimum Temperature Inside House Yesterday with time recoding.
 : Maximum Temperature Outside House Yesterday with time recoding.
 : Minimum Temperature Outside House Yesterday with time recoding.
 : Maximum Humidity Inside House Yesterday with time recoding.
 : Minimum Humidity Inside House Yesterday with time recoding.
23. Data Recording for 2 Days ago
 : Maximum Temperature Inside House 2 days ago with time recoding.
 : Minimum Temperature Inside House 2 days ago with time recoding.
 : Maximum Temperature Outside House 2 days ago with time recoding.
 : Minimum Temperature Outside House 2 days ago with time recoding.
 : Maximum Humidity Inside House 2 days ago with time recoding.
 : Minimum Humidity Inside House 2 days ago with time recoding.
28. Over Outside temperature for compensation time on-off minimum ventilation
It is set point for over outside temperature for compensation 100% of minimum ventilation.
29. Lower Outside temperature for compensation time on-off minimum ventilation
It is set point for lower outside temperature for compensation min. percentage (code 30) of minimum ventilation.
30. Minimum percentage for compensation time on-off minimum ventilation
It is set point of minimum percentage for compensation time on-off minimum ventilation at lower outside temperature
Example:

Code # Setting
09 Fan On-Time 10 min.
10 Fan Off-Time 10 min.
28 Over outside Temp for compensation 10 C
29 Lower outside Temp for compensation -15 C
30 Min. percentage for compensation 60 %

10 mim 10 mim
If outside temperature >10 C
Compensation = 100% ON Time OFF Time

If outside temperature <-15 C 6 mim 14 mim


Compensation = 60%
ON OFF Time
Time

E-mail : tmcc_cn@163.com Page13


Temp R-Tron 612 version 2.2 U Operation Manual
31. Fan Stage and Required Fan Temperature Curve ( T-Curve)
It is possible to set a required fan temperature table to reduce automatically the required fan temperature
each day during the raising period. It is possible to set up to 8 Stage. Length of each group can be up to 999 days.
 : Required Fan Temperature of stage1 and Day of stage1
 : Required Fan Temperature of stage2 and Days of stage2
 : Required Fan Temperature of stage3 and Days of stage3
 : Required Fan Temperature of stage4 and Days of stage4
 : Required Fan Temperature of stage5 and Days of stage5
 : Required Fan Temperature of stage6 and Days of stage6
 : Required Fan Temperature of stage7 and Days of stage7
 : Required Fan Temperature of stage8 and Days of stage8
Example:
: Required Fan Temperature of stage 1 = 33oC and Day of stage 1= 0 day
: Required Fan Temperature of stage 2 = 30oC and Day of stage 2= 7 day
# 1 Differential between Required Fan Temperature of stage 1 and 2 = 33oC - 30oC = 3oC
# 2 Differential between Day of stage 1 and 2 = 6 day
#3 Required Fan Temperature will reduce automatically = 3/6 = 0.5oC per day
Day 1 Required Fan Temperature 33oC
Day 2 Required Fan Temperature 32.5oC
Day 3 Required Fan Temperature 32oC
Day 4 Required Fan Temperature 31.5oC
Day 5 Required Fan Temperature 31.0oC
Day 6 Required Fan Temperature 30.5oC
Day 7 Required Fan Temperature 30.0oC
32. Heat Stage and Required Heat Temperature Curve ( H-Curve)
It is possible to set a required heat temperature table to reduce automatically the required heat temperature
each day during the raising period. The day stage is use same as Fan stage.
 : Required Heat Temperature of stage1
 : Required Heat Temperature of stage2
 : Required Heat Temperature of stage3

E-mail : tmcc_cn@163.com Page14


Temp R-Tron 612 version 2.2 U Operation Manual
 : Required Heat Temperature of stage4
 : Required Heat Temperature of stage5
 : Required Heat Temperature of stage6
 : Required Heat Temperature of stage7
 : Required Heat Temperature of stage8
33. Cool Stage and Required Cool Temperature Curve ( C-Curve)
It is possible to set a required cool temperature table to reduce automatically the required cool temperature
each day during the raising period. The day stage is use same as Fan stage.
 : Required Cool Temperature of stage1
 : Required Cool Temperature of stage2
 : Required Cool Temperature of stage3
 : Required Cool Temperature of stage4
 : Required Cool Temperature of stage5
 : Required Cool Temperature of stage6
 : Required Cool Temperature of stage7
 : Required Cool Temperature of stage8
34. Differential temperature for Off Fan
Differential temperature for Off Fan is set point differential for off fan.
35. Differential temperature for ON Heat
Differential temperature for ON Heat is set point differential for ON Heater.
36. Differential temperature for Off cooling pump
Differential temperature for Off Cooling Pump is set point for differential Off Cooling Pump.
37. Differential humidity for ON cooling pump
Differential humidity for ON Cooling Pump is set point for differential ON Cooling Pump.
38. Light ON-OFF periods
It is set point for ON and Off times period of Light program with 8 periods per day.
 : Light Period 1 ON/OFF ( hh :m )
 : Light Period 2 ON/OFF ( hh :m )
 : Light Period 3 ON/OFF ( hh :m )
 : Light Period 4 ON/OFF ( hh :m )
 : Light Period 5 ON/OFF ( hh :m )
 : Light Period 6 ON/OFF ( hh :m )

E-mail : tmcc_cn@163.com Page15


Temp R-Tron 612 version 2.2 U Operation Manual
 : Light Period 7 ON/OFF ( hh :m )
 : Light Period 8 ON/OFF ( hh :m )
Example: ON 06 : 1 = Light will open at 6:10 / OFF 18:5 = Light will close at 18:50
39. Light Intensity
It is set point for minimum and maximum of percentage intensity with 0 to 100% by analog output Light intensity.
The user can connect to Dimmer controller for decrease or increase intensity of Light.
Example: minimum 20% = 2 VDC ; maximum 70% = 7 VDC
40.Light Delay
It is set point for delay time of intensity from 0% to maximum of intensity (Code 38)
Example:

Code # Setting
38Light ON-OFF L1 On 06:0
38 Light ON-OFF L1 Off 18:0
39 Min. Light Intensity 20%
39 Max. Light Intensity 70%
40 Light Delay 45 min.
The light system will open at 06:00 with intensity 20% and the light will increase intensity until 06:45 at 70%.
The light system will close at 17:15 with intensity 70% and the light will decrease intensity until 18:00 at 20%.
41.Start time Cooling Pump Period
It is set point for start and stop working time period of cooling pump with 8 Stage. The day stage is use same as Fan stage.
 : Start working time for Cooling Pump Stage 1.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 1.The set time is show on middle display (Green color)
 : Start working time for Cooling Pump Stage 2.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 2.The set time is show on middle display (Green color)
 : Start working time for Cooling Pump Stage 3.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 3.The set time is show on middle display (Green color)
 : Start working time for Cooling Pump Stage 4.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 4.The set time is show on middle display (Green color)
 : Start working time for Cooling Pump Stage 5.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 5.The set time is show on middle display (Green color)
 : Start working time for Cooling Pump Stage 6.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 6.The set time is show on middle display (Green color)
 : Start working time for Cooling Pump Stage 7.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 7.The set time is show on middle display (Green color)
E-mail : tmcc_cn@163.com Page16
Temp R-Tron 612 version 2.2 U Operation Manual
 : Start working time for Cooling Pump Stage 8.The set time is show on right display (Red color)
: Stop working time for Cooling Pump Stage 8.The set time is show on middle display (Green color)
42.Outdoor Temperature Control Cooling Pump Period
It is set point for outside temperature to control working cooling pump.
If outside temperature is lower than this point then cooling pump is not working.
 : Outdoor Temperature Control working Cooling Pump Period 1
 : Outdoor Temperature Control working Cooling Pump Period 2
 : Outdoor Temperature Control working Cooling Pump Period 3
 : Outdoor Temperature Control working Cooling Pump Period 4
 : Outdoor Temperature Control working Cooling Pump Period 5
43.Time On Cooling Pump Period
It is set point for time On and Off cooling pump for stage 1-8. The day stage is use same as Fan stage.
 : Time On Cooling Pump Stage 1 / Time Off Cooling Pump Stage 1
 : Time On Cooling Pump Stage 2 / Time Off Cooling Pump Stage 2
 : Time On Cooling Pump Stage 3 / Time Off Cooling Pump Stage 3
 : Time On Cooling Pump Stage 4 / Time Off Cooling Pump Stage 4
 : Time On Cooling Pump Stage 5 / Time Off Cooling Pump Stage 5
 : Time On Cooling Pump Stage 6 / Time Off Cooling Pump Stage 6
 : Time On Cooling Pump Stage 7 / Time Off Cooling Pump Stage 7
 : Time On Cooling Pump Stage 8 / Time Off Cooling Pump Stage 8
Example:
Code # Setting
31  0
 7
 14
41.  Start working time Stage 1 06:0
 Stop working time Stage 1 18:0
 Start working time Stage 2 07:0
 Stop working time Stage 2 19:0
43.  Time On Cooling Pump Stage 1 5.0
 Time Off Cooling Pump Stage 1 5.0
 Time On Cooling Pump Stage 2 10.0
 Time Off Cooling Pump Stage 2 10.0

Growth day between 0 – 7 day. The cooling pump will working in 06:00 to 18:00.
Then cool on time is 5.0 min. and cool off time is 5.0 min.
E-mail : tmcc_cn@163.com Page17
Temp R-Tron 612 version 2.2 U Operation Manual
Growth day between 8-14 day. The cooling pump will working in 07:00 to 19:00.
Then cool on time is 10.0 min. and cool off time is 10.0 min.
44.Cooling On / Off Time by High Humidity
It is set point for time ON and Off of cooling pump in case High Humidity.
Example: .
Code # Setting
44. Cooling On / Off Time by High Humidity
Time On Cooling Pump 01:0
Time Off Cooling Pump 10:0
14. Humidity off cooling pump 80%
15. Cool On Time 5.0
16. Cool Off Time 5.0
If the cooling pump is working by required Cool Temp (code 13) and Humidity Off Cooling Pump (Code 14) = 80%
and inside house the humidity is under 80%.
The cooling pump will on time is 5:00 min.(Code 15) and cool off time is 5:00min.(Code16)
If inside house the humidity is over than 80%.
The cooling pump will on time will be1.0 min. and cool off time will be 10.0 min (Code 44) and
If inside house the humidity is reduce 2% (Code 37) of 80% = 78%. Then
The cooling pump will on time will be5.0 min.(Code 15) and cool off time will be5.0 min.(Code16) again.
45. Differential Temperature for start cooling pump before Require Cool Temp
It is set point for differential temperature for start cooling pump before Require cool Temp (Code 13)
If set point is “ 0 ” that means. this function don’t working.
46.Cooling On / Off Time for start cooling pump before Require Cool Temp
This is the cooling pump ON time ( Red left display) and OFF time ( Green middle display) period,
set in minutes and seconds,
( 0.1 =10sec. / 0.2=20sec./ 0.3=30sec. / 0.4=40sec. / 0.5=50sec. ) which the cooling system will run.
If Cooling OFF time is 0.0 min. That means cooling pump will operate continuous until temperature cool down.
Example:

Code # Setting
13. Requested Cool Temperature 30 ° C
15.Cool ON Time (minutes. Seconds) 5.0
16.Cool OFF Time (minutes. Seconds) 5.0
45. Differential temperature for start cooling pump before Require cool Temp 3.0 ° C
46 Cooling ON Time /OFF Time for start cooling pump before Require cool Temp 2:00 / 8:00

E-mail : tmcc_cn@163.com Page18


Temp R-Tron 612 version 2.2 U Operation Manual
If the house temperature reaches to 27oC (Code13 = 30 oC – Code 45 = 3.0 oC ) the cooling pump system will start to operate.
The cooling pump will be run for 2:00 minutes and be off for 8:00 minutes. (Code 46)
If the house temperature increase from 27oC -30 oC
The cooling pump will change ON Time from 2:00 to 5:00 min. and Cooling OFF Time from 8:00 to 5:00 by Automatic
If the temperature is 27 oC then Cooling ON Time = 2:00 Cooling OFF Time = 8:00
If the temperature is 28 oC then Cooling ON Time = 3:00 Cooling OFF Time = 7:00
If the temperature is 29 oC then Cooling ON Time = 4:00 Cooling OFF Time = 6:00
If the temperature is 30 oC then Cooling ON Time = 5:00 Cooling OFF Time = 5:00
If Cooling OFF time (Code 46) is 0:0 min. This function don’t working ( no cooling On time / Off time)
47. Humidity Stage and Required Humidity Curve for Off Cooling Pump
It is possible to set a required Humidity off cooling pump table to reduce automatically the required Humidity off cooling
pump each day during the raising period. The day stage is use same as Fan stage
 : Required Humidity off cooling pump of stage1
 : Required Humidity off cooling pump of stage2
 : Required Humidity off cooling pump of stage3
 : Required Humidity off cooling pump of stage4
 : Required Humidity off cooling pump of stage5
 : Required Humidity off cooling pump of stage6
 : Required Humidity off cooling pump of stage7
 : Required Humidity off cooling pump of stage8
48.Select Time On-Off Cooling Pump by Outdoor Temperature mode or Stage mode
It is set point for select time On-Off cooling pump by Outdoor temperature mode or Stage mode
(0= Outdoor temperature mode ; 1 = Stage mode )
49. Min. % Inlet at Speed Fan Low
It is set point for minimum percentage of Inlet incase Fan speed Low.
50. Max. % Inlet at Speed Fan High
It is set point for maximum percentage of Inlet incase Fan speed High.

E-mail : tmcc_cn@163.com Page19


Temp R-Tron 612 version 2.2 U Operation Manual
51. Inlet percentage
It is set point of percentage to open Inlet step 1- 8.
 : Inlet will open as percentage of step 1 when Fan 1 On.
 : Inlet will open as percentage of step 2 when Fan 2 On.
 : Inlet will open as percentage of step 3 when Fan 3 On.
 : Inlet will open as percentage of step 4 when Fan 4 On.
 : Inlet will open as percentage of step 5 when Fan 5 On.
 : Inlet will open as percentage of step 6 when Fan 6 On.
 : Inlet will open as percentage of step 7 when Fan 7 On.
 : Inlet will open as percentage of step 8 when Fan 8 On.
52. Min. % Curtain at Speed Fan Low
It is set point for minimum percentage of curtain incase Fan speed Low.
53. Max. % Curtain at Speed Fan High
It is set point for maximum percentage of curtain incase Fan speed High.
54. Curtain percentage
It is set point of percentage to open curtain step 1- 8.
 : Curtain will open as percentage of step 1 when Fan 1 On.
 : Curtain will open as percentage of step 2 when Fan 2 On.
 : Curtain will open as percentage of step 3 when Fan 3 On.
 : Curtain will open as percentage of step 4 when Fan 4 On.
 : Curtain will open as percentage of step 5 when Fan 5 On.
 : Curtain will open as percentage of step 6 when Fan 6 On.
 : Curtain will open as percentage of step 7 when Fan 7 On.
 : Curtain will open as percentage of step 8 when Fan 8 On.
55. Select Relay Output mode and Analog Output to control Inlet / Curtain mode
It is set point of select relay output mode type 1 – 4and Analog output to control Inlet / Curtain mode

Note: In case electrical shut down and electrical come back. If user select output relay:
Output Type 2: Curtain will open to 100% first and adjust percentage as requirement.
Output Type 3and 4: Curtain and Inlet will close to 0% first and adjust percentage as requirement.

E-mail : tmcc_cn@163.com Page20


Temp R-Tron 612 version 2.2 U Operation Manual

Relay Output Type Output Type Output Type Output Type Output Type Output Type Output Type
number 1 2 3 4 5 6 7
No use all Use Curtain Use Inlet Use All Analog Curtain Analog Inlet Analog All

Code 55 = 1 Code 55 = 2 Code 55 = 3 Code 55 = 4 Code 55 = 5 Code 55 = 6 Code 55 = 7


1 Fan group 1 Fan group 1 Fan group 1 Fan group 1 Fan group 1 Fan group 1 Fan group 1
2 Fan group 2 Fan group 2 Fan group 2 Fan group 2 Fan group 2 Fan group 2 Fan group 2
3 Fan group 3 Fan group 3 Fan group 3 Fan group 3 Fan group 3 Fan group 3 Fan group 3
4 Fan group 4 Fan group 4 Fan group 4 Fan group 4 Fan group 4 Fan group 4 Fan group 4
5 Fan group 5 Fan group 5 Fan group 5 Curtain open Fan group 5 Fan group 5 Fan group 5
6 Fan group 6 Fan group 6 Fan group 6 Curtain close Fan group 6 Fan group 6 Fan group 6
7 Fan group 7 Curtain open Inlet open Inlet open Fan group 7 Fan group 7 Fan group 7
8 Fan group 8 Curtain close Inlet close Inlet close Fan group 8 Fan group 8 Fan group 8
9 Cooling Cooling Cooling Cooling Cooling Cooling Cooling
10 Heating Heating Heating Heating Heating Heating Heating
11 Lighting Lighting Lighting Lighting Lighting Lighting Lighting
12 Alarm Alarm Alarm Alarm Alarm Alarm Alarm

56. Spray Time On


Spray On time is set in seconds (0.1=10sec. / 0.2=20sec./ 0.3=30sec./0.4=40sec./0.5=50sec.)
57. Spray Time On
Spray Off time is set in seconds (0.1=10sec. / 0.2=20sec./ 0.3=30sec./0.4=40sec./0.5=50sec.)
58. Light dimming control
It is set point of select Light dimming control mode. ( 0 = By time ; 1 = By Turn On )
By time : Incase electrical shut down between Light On. Then electrical is come back. Light is On without dimming.
By Turn On : Incase electrical shut down between Light On. Then electrical is come back. Light is On with dimming.
59. Minimum Number of Fan
It is set point of minimum number of fan
60. Maximum Number of Fan
It is set point of maximum number of fan
61. Select Fan Ventilation
It is set point of which fan want to use minimum ventilation. It is have 3 type of function.
1. Key with one digit.  to  This means, User can select which fan for minimum ventilation but only one fan.

E-mail : tmcc_cn@163.com Page21


Temp R-Tron 612 version 2.2 U Operation Manual
Example: Setting
Code 00: Requested Fan Temperature 30 ° C
Code 05: Fan 5 5.0° C
Code 09: Fan on time (min. : sec.) 2.3
Code 10: Fan off time (min. : sec.) 5.0
Code 34: Differential temperature for Off Fan 1.0
Code 61: Select Fan Ventilation 005
If the house temperature reduce below 34 oC (Code 00 + Code 05 – Code34 = 30+5-1=34 oC)
Fan 5 will be in minimum ventilation cycle. Fan 5 will be run 2 minute 30 seconds and will be off 5 minutes
2. Key with two digit  This means, User select Fan 2 and Fan 4 for minimum ventilation. OR
 This means, User select Fan 3 and Fan 8 for minimum ventilation.
Example:
Setting
Code 00: Requested Fan Temperature 25 ° C
Code 03: Fan 3 3.0° C
Code 08: Fan 8 8.0° C
Code 09: Fan on time (min. : sec.) 2.3
Code 10: Fan off time (min. : sec.) 5.0
Code 34: Differential temperature for Off Fan 1.0
Code 61: Select Fan Ventilation 038
If the house temperature reduce below 32 oC (Code 00 + Code 08 – Code 34 = 25+8-1 = 32 oC)
Fan 8 will be in minimum ventilation cycle. Fan 8 will be run 2 minute 30 seconds and will be off 5 minutes.
Fan 3 will be run continuous.
If the house temperature reduce below 27 oC (Code 00 + Code 03 – Code34 = 25+3-1 = 27 oC)
Fan 8 will be in minimum ventilation cycle. Fan 8 will be run 2 minute 30 seconds and will be off 5 minutes.
Fan 3 will be in minimum ventilation cycle. Fan 3 will be run 2 minute 30 seconds and will be off 5 minutes.
3. Key with Three digit  This means, Rotating manner 2 Fan min. ventilation between Fan 1 and Fan 2.
By Fan 1 running first after finished cycle then Fan 2 will running.
 This means, Rotating manner 3 Fan min. ventilation Fan 1 , Fan 2 and Fan 3.
By Fan 1 running first after finished cycle then Fan 2 will running if Fan 2 have finished.
Then Fan 3 will run. After Fan 3 have finished then will go back to Fan 1.
 This means, Rotating manner 4 Fan min. ventilation Fan 1 , Fan 2 , Fan 3 and Fan 4
Example: Setting
Code 00: Requested Fan Temperature 25 ° C
Code 01: Fan 1 1.0° C
Code 09: Fan on time (min. : sec.) 2.3
Code 10: Fan off time (min. : sec.) 5.0
Code 34: Differential temperature for Off Fan 1.0
Code 61: Select Fan Ventilation 400

E-mail : tmcc_cn@163.com Page22


Temp R-Tron 612 version 2.2 U Operation Manual
If the house temperature reduce below 25oC (Code 00 + Code 01 – Code 34 = 25+1-1=25 oC)
Fan 1 will be in minimum ventilation cycle. Fan 1 will be run 2 minute 30 seconds and will be off 5 minutes.
Then Fan 2 will be in minimum ventilation cycle. Fan 2 will be run 2 minute 30 seconds and will be off 5 minutes.
Then Fan 3 will be in minimum ventilation cycle. Fan 3 will be run 2 minute 30 seconds and will be off 5 minutes.
Then Fan 4 will be in minimum ventilation cycle. Fan 4 will be run 2 minute 30 seconds and will be off 5 minutes.
Then rotate to Fan 1 again.
62. Diff Speed Fan 1 and Diff Speed Fan 2 ( 2 Channel)
It is set point differential temperature of speed fan 1 and fan 2 low.
63. Diff Band Width Speed Fan 1 and Diff Band Width Speed Fan 2 ( 2 Channel)
It is set point differential band temperature of speed fan1 and fan 2.
64. Speed Fan 1 Low and Speed Fan 2 Low
It is set point of low percentage of speed fan1 and fan 2.
65. Speed Fan 1 High and Speed Fan 2 High
It is set point of high percentage of speed fan1 and fan 2
Example: .
Code # Setting
00 Required Fan Temperature 20 C
62 Diff Speed Fan 1 1.0
63 Diff Band Width Speed Fan 1 9.0
64 Speed Fan 1 Low 10%
65 Speed Fan 1 High 100%
If Code 00 = 20 C and Code 62 Diff Speed Fan 1 = 1.0Then Low temperature of low speed is 21C
Code 63 Diff Band Width Speed Fan 1 = 9.0 Then High temperature of high speed is 30 C
If in house temperature is increase to 21C the speed fan is 10% and if temperature is increase to 30 C
the speed fan 1 is 100%
% FAN SPEED

Speed Fan
High 100
CODE 65=100%
90

80

70

60

50

40

30

20
Speed Fan
Low
10 Temperature C
CODE 64=10%

20 21 22 23 24 25 26 27 28 29 30
Required Diff
Fan Temp Speed Diff Band Width Speed Fan
Fan
CODE 00 CODE 62 CODE 63=9.0C
= =
20.0C 1.0C

E-mail : tmcc_cn@163.com Page23


Temp R-Tron 612 version 2.2 U Operation Manual
66. Feed Mode
It is set point of feed mode. The controller can measure feed consumption in 2 ways
Select 0 = feed measure by time. The controller will receive a dry contact (Feed digital input) and converting time
into amount.
Select 1 = feed measure by pulse. The controller will receive a dry contact pulse (Feed digital input) from a weighing
machine. Each pulse represents a preset amount of feed.
67. Feed Multiply
It is set point of feed multiply. Multiply number (1 X 10 It is mean 1 min. 10 Kg or 1 pulse 10 Kg)
68. Alarm On Time( seconds )
It is set point of alarm ON time.
69. Alarm Off Time( seconds )
It is set point of alarm Off time.
Example: if code 68 = 10 sec. and code 69 = 3 sec. then alarm is working 10 sec. and off (wait) 3sec.
70. Diff Indoor Temperature Alarm
It is set point of alarm for differential temperature between Temp. sensor 1 and 2
71. Temperature Sensor 1 Control
It is set point of select Temperature sensor 1( 0 = not use / 1= use)
72. Temperature Sensor 2 Control
It is set point of select Temperature sensor 2 ( 0 = not use / 1= use)
73. Temperature Sensor 3 Control
It is set point of select Temperature sensor 3 ( 0 = not use / 1= use)
74. Temperature Sensor 4 Control
It is set point of select Temperature sensor 4 ( 0 = not use / 1= use)
75. Humidity Sensor Control
It is set point of select Humidity sensor ( 0 = not use / 1= use)
76. Temperature Display (Average)
It is set point of select which Temperature sensor to display
(1 = Temp. sensor 1, 2 = Temp. sensor 1+2 , 3= Temp. sensor 1+2+4 , 4 = All Temp)
77. Select Temperature sensor for control Heater
It is set point for select which temperature sensor for control heater.
(0=use indoor temperature (code76); 1 = Temp. sensor 1, 2 = Temp. sensor 2 , 3 = Temp. sensor 3 , 4 = Temp. sensor 4
78. Select Analog output 1 for Light Dimming mode or Speed Fan 2 mode
It is set point to select Analog output 1 for Light Dimmer or Speed Fan 2 mode.
(0 = Light Dimmer mode ; 1 = Speed Fan 2 mode)
79. Select Fan 4 mode or Spray mode
It is set point for select Fan4 mode or Spray mode. ( 0 = Fan 4 mode ; 1 = Spray mode )

E-mail : tmcc_cn@163.com Page24


Temp R-Tron 612 version 2.2 U Operation Manual
80. Delay Fan Turn On
It is set point of delay time for control fan ON ( not too fast)
81. Delay Fan Turn Off
It is set point of delay time for control fan Off( not too fast)
82. Delay System
It is set point of delay system. Normally delay system is 3 seconds. User can key different second for each house.
83. Password
It is set point of password. User can key password 3 digit. After controller have password. It will ask password before
change parameter. Even user forgot password. User can use master key password “381”.
84. House Number
It is set point of house number ID. User can set in each house from 1 to 30.
85. Test Relay
It is function for test relay. User can check every output relay.
86. Test Speed Fan
It is function for test speed fan (Analog Output 0-10 VDC).
User can check by connect with inverter speed fan and Start from 0 -100%
87. Test Dimmer
It is function for test dimmer (Analog Output 0-10 VDC).
User can check by connect with electronic Ballast or electronic DimmerStart from 0 -100%
88. Test Display
It is function for test display. User can check all LED display and all number display.
89. Test Digital Input
It is function for test digital Input. User can check digital input by connect with water counter or feed counter.
91. Day
It is set point of Day of week. User can set 1=Monday,2=Tuesday,3=Wednesday,….7=Sunday.
92. Date
It is set point of Date. User can set 1 to 31.
93. Month
It is set point of Month. User can set 1 to 12.
94. Year
It is set point of Year. User can set 01 to 99.
95. Hour
It is set point of Hour. User can set 00 to 23.
96. Minute
It is set point of Minute. User can set 00 to 59.

E-mail : tmcc_cn@163.com Page25


Temp R-Tron 612 version 2.2 U Operation Manual
99. Reset
It is function of Reset. User can set :
1 = User Reset 2 = Clear Adjust Sensor 3 = Clear Data logger
4 = Clear Max, Min Value 5 = Factory Reset 8 = Save User Parameter

E-mail : tmcc_cn@163.com Page26


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


00 Required Fan Temp C Required fan temperature for the house
01 Fan 1 C Differential temperature of fan 1 above the required fan temperature
02 Fan 2 C Differential temperature of fan 2 above the required fan temperature
03 Fan 3 C Differential temperature of fan 3 above the required fan temperature
04 Fan 4 (see code 79) C Differential temperature of fan 4 above the required fan temperature
Spray (see code 79) %RH Differential humidity of Spray below the required humidity curve
05 Fan 5 C Differential temperature of fan 5 above the required fan temperature
06 Fan 6 C Differential temperature of fan 6 above the required fan temperature
07 Fan 7 C Differential temperature of fan 7 above the required fan temperature
08 Fan 8 C Differential temperature of fan 8 above the required fan temperature
09 Fan On Time (    ) min:sec The length of ON time for the minimum ventilation
10 Fan Off Time (    ) min:sec The length of Off time for the minimum ventilation
11 Fan Humidity Set % Increase ventilation if humidity reaches to set point
12 Required Heat Temp C Required heat temperature for the house
13 Required Cool Temp C Required cool temperature for the house
14 Humidity Off Cooling Pump % Stop cooling pump if high humidity
15 Cool On Time min:sec The length of ON time for the cooling pump
16 Cool Off Time min:sec The length of Off time for the cooling pump
17 High Temp Alarm / Diff. High Temp Alarm C High temperature alarm / Diff. High Temp Alarm
18 Low Temp Alarm / Diff. LowTemp Alarm C Low temperature alarm / Diff. Low Temp Alarm
19 High Humidity Alarm/ Diff. High Hum. Alarm % High humidity alarm / Diff. High Humidity Alarm
20 Growth Day Day The current grow day
21  C Maximum Inside House Temperature Today
TIME Time at Maximum Inside House Temperature Today
 C Minimum Inside House Temperature Today
TIME Time at Minimum Inside House Temperature Today

E-mail : tmcc_cn@163.com Page27


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


 C Maximum Outside House Temperature Today
TIME Time at Maximum Outside House Temperature Today
 C Minimum Outside House Temperature Today
TIME Time at Minimum Outside House Temperature Today
 % Maximum Inside House Humidity Today
TIME Time at Maximum Inside House Humidity Today
 % Minimum Inside House Humidity Today
TIME Time at Minimum Inside House Humidity Today
22  C Maximum Inside House Temperature Yesterday
TIME Time at Maximum Inside House Temperature Yesterday
 C Minimum Inside House Temperature Yesterday
TIME Time at Minimum Inside House Temperature Yesterday
 C Maximum Outside House Temperature Yesterday
TIME Time at Maximum Outside House Temperature Yesterday
 C Minimum Outside House Temperature Yesterday
TIME Time at Minimum Outside House Temperature Yesterday
 % Maximum Inside House Humidity Yesterday
TIME Time at Maximum Inside House Humidity Yesterday
 % Minimum Inside House Humidity Yesterday
TIME Time at Minimum Inside House Humidity Yesterday
23  C Maximum Inside House Temperature 2 Day ago
TIME Time at Maximum Inside House Temperature 2 Day ago
 C Minimum Inside House Temperature 2 Day ago
TIME Time at Minimum Inside House Temperature 2 Day ago
 C Maximum Outside House Temperature 2 Day ago
TIME Time at Maximum Outside House Temperature 2 Day ago

E-mail : tmcc_cn@163.com Page28


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


 C Minimum Outside House Temperature 2 Day ago
TIME Time at Minimum Outside House Temperature 2 Day ago
 % Maximum Inside House Humidity 2 Day ago
TIME Time at Maximum Inside House Humidity 2 Day ago
 % Minimum Inside House Humidity 2 Day ago
TIME Time at Minimum Inside House Humidity 2 Day ago
28 Over Outside Temperature for compensation C Over outside temperature for compensation 100% of minimum ventilation
29 Lower Outside Temperature for compensation C Lower outside temperature for compensation min. % of minimum ventilation
30 Minimum percentage for compensation % Minimum percentage for compensation time on-off
31  Day Day and Required fan temperature for Stage 1
 Day Day and Required fan temperature for Stage 2
 Day Day and Required fan temperature for Stage 3
 Day Day and Required fan temperature for Stage 4
 Day Day and Required fan temperature for Stage 5
 Day Day and Required fan temperature for Stage 6
 Day Day and Required fan temperature for Stage 7
 Day Day and Required fan temperature for Stage 8
32  C Required heat temperature for Stage 1
 C Required heat temperature for Stage 2
 C Required heat temperature for Stage 3
 C Required heat temperature for Stage 4
 C Required heat temperature for Stage 5
 C Required heat temperature for Stage 6
 C Required heat temperature for Stage 7
 C Required heat temperature for Stage 8

E-mail : tmcc_cn@163.com Page29


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


33  C Required cool temperature for Stage 1
 C Required cool temperature for Stage 2
 C Required cool temperature for Stage 3
 C Required cool temperature for Stage 4
 C Required cool temperature for Stage 5
 C Required cool temperature for Stage 6
 C Required cool temperature for Stage 7
 C Required cool temperature for Stage 8
34 Diff Fan C Differential temperature for Off Fan
35 Diff Heater C Differential temperature for ON heat
36 Diff Cooling Pump C Differential temperature for Off cooling pump
37 Diff Humidity % Differential humidity for ON cooling pump
38  hh.min Light Period 1 ON/OFF
 hh.min Light Period 2 ON/OFF
 hh.min Light Period 3 ON/OFF
 hh.min Light Period 4 ON/OFF
 hh.min Light Period 5 ON/OFF
 hh.min Light Period 6 ON/OFF
 hh.min Light Period 7 ON/OFF
 hh.min Light Period 8 ON/OFF
39 Light Intensity % Min. and Max. Light Intensity
40 Light Delay Min. Light Delay
41  hh.min Start time Cooling Pump Stage 1
hh.min End Time Cooling Pump Stage 1
 hh.min Start time Cooling Pump Stage 2
hh.min End Time Cooling Pump Stage 2

E-mail : tmcc_cn@163.com Page30


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


 hh.min Start time Cooling Pump Stage 3
hh.min End Time Cooling Pump Stage 3
 hh.min Start time Cooling Pump Stage 4
hh.min End Time Cooling Pump Stage 4
 hh.min Start time Cooling Pump Stage 5
hh.min End Time Cooling Pump Stage 5
 hh.min Start time Cooling Pump Stage 6
hh.min End Time Cooling Pump Stage 6
 hh.min Start time Cooling Pump Stage 7
hh.min End Time Cooling Pump Stage 7
 hh.min Start time Cooling Pump Stage 8
hh.min End Time Cooling Pump Stage 8
42  C Outdoor Temperature Control Cooling Pump Period 1
 C Outdoor Temperature Control Cooling Pump Period 2

 C Outdoor Temperature Control Cooling Pump Period 3


 C Outdoor Temperature Control Cooling Pump Period 4
 C Outdoor Temperature Control Cooling Pump Period 5
43  min:sec Time On Cooling Pump Stage 1
min:sec Time Off Cooling Pump Stage 1
 min:sec Time On Cooling Pump Stage 2
min:sec Time Off Cooling Pump Stage 2
 min:sec Time On Cooling Pump Stage 3
min:sec Time Off Cooling Pump Stage 3
 min:sec Time On Cooling Pump Stage 4
min:sec Time Off Cooling Pump Stage 4

E-mail : tmcc_cn@163.com Page31


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


 min:sec Time On Cooling Pump Stage 5
min:sec Time Off Cooling Pump Stage 5
 min:sec Time On Cooling Pump Stage 6
min:sec Time Off Cooling Pump Stage 6
 min:sec Time On Cooling Pump Stage 7
min:sec Time Off Cooling Pump Stage 7
 min:sec Time On Cooling Pump Stage 8
min:sec Time Off Cooling Pump Stage 8
44 Cooling On /Off Time by High Humidity min:sec Cooling On / Off Time by High Humidity
45 Diff Temperature for Start Cooling C Differential temperature for start cooling pump before
Before Require Cool Pump Require cool Temp
46 Cooling On / Off Time for Start Cooling min:sec Cooling On / Off Time for Start Cooling before Require Cool Pump
Before Require Cool Pump
47  % RH Required Humidity for Off cooling pump Stage 1
 % RH Required Humidity for Off cooling pump Stage 2
 % RH Required Humidity for Off cooling pump Stage 3
 % RH Required Humidity for Off cooling pump Stage 4
 % RH Required Humidity for Off cooling pump Stage 5
 % RH Required Humidity for Off cooling pump Stage 6
 % RH Required Humidity for Off cooling pump Stage 7
 % RH Required Humidity for Off cooling pump Stage 8
48 Select time On-Off cooling pump 0-1 0 = Outdoor temperature mode : 1 = Stage mode
49 Min. Percentage of Inlet at Speed Fan Low % Set Min. percentage of Inlet Incase Speed Fan Low
50 Max. Percentage of Inlet at Speed Fan High % Set Max. percentage of Inlet Incase Speed Fan High
51  Percentage Inlet step 1 % Open percent of Inlet step 1 when Fan 1 On
 Percentage Inlet step 2 % Open percent of Inlet step 2 when Fan 2 On

E-mail : tmcc_cn@163.com Page32


Temp R-Tron 612 version 2.2 U Operation Manual
Code Parameter Unit Function
 Percentage Inlet step 3 % Open percent of Inlet step 3 when Fan 3 On
 Percentage Inlet step 4 % Open percent of Inlet step 4 when Fan 4 On
 Percentage Inlet step 5 % Open percent of Inlet step 5 when Fan 5 On
 Percentage Inlet step 6 % Open percent of Inlet step 6 when Fan 6 On
 Percentage Inlet step 7 % Open percent of Inlet step 7 when Fan 7 On
 Percentage Inlet step 8 % Open percent of Inlet step 8 when Fan 8 On
52 Min. Percentage of Curtain at Speed Fan Low % Set Min. percentage of Curtain Incase Speed Fan Low
53 Max. Percentage of Curtain at Speed Fan High % Set Max. percentage of Curtain Incase Speed Fan High
54  Percentage Curtain step 1 % Open percent of Curtain step 1 when Fan 1 On
 Percentage Curtain step 2 % Open percent of Curtain step 2 when Fan 2 On
 Percentage Curtain step 3 % Open percent of Curtain step 3 when Fan 3 On
 Percentage Curtain step 4 % Open percent of Curtain step 4 when Fan 4 On
 Percentage Curtain step 5 % Open percent of Curtain step 5 when Fan 5 On
 Percentage Curtain step 6 % Open percent of Curtain step 6 when Fan 6 On
 Percentage Curtain step 7 % Open percent of Curtain step 7 when Fan 7 On
 Percentage Curtain step 8 % Open percent of Curtain step 8 when Fan 8 On
1= not use Inlet and Curtain: 2 = use Curtain only: 3= use Inlet only:
Select Relay Output mode and Analog
55 1-7 4 = use Inlet and Curtain: 5 =Analog Output for Curtain:
Output to control Inlet/Curtain
6 =Analog Output for Inlet: 7 =Analog Output for Curtain and Inlet
56 Spray Time On Sec. Set Spray Time On
57 Spray Time Off Sec. Set Spray Time Off
58 Light control 0-1 0 = By time ; 1 = By Turn On
59 Min Number of Fan 1-8 Minimum Number of fans
60 Max Number of fan 1-8 Maximum Number of Fans
61 Select Fan Ventilation XXX Select Fan Ventilation
62 Diff Speed Fan 1/ Fan 2 C Different Temp. Speed Fan 1 / Fan 2
63 Diff Band Width Speed Fan 1 / Fan 2 C Different Band Width Speed Fan 1 / Fan 2
64 Speed Fan 1 / Fan 2 Low % Speed Fan / Fan 2 Low
65 Speed Fan / Fan 2 High % Speed Fan / Fan 2 High

E-mail : tmcc_cn@163.com Page33


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


66 Feed Mode 0-1 0=By time, 1=By pulse
67 Feed Multiply No. Multiply number (1 X 10 It is mean 1 min. 10 Kg or 1 pulse 10 Kg)
68 Alarm On Time sec. Alarm On Time
69 Alarm Off Time sec. Alarm Off Time
70 Diff Indoor Temperature Alarm C Alarm for differential temperature between Temp. sensor 1 and 2
71 Temperature1 Sensor Control 0-1 Use Temperature sensor 1( 0 = not use / 1= use)
72 Temperature2 Sensor Control 0-1 Use Temperature sensor 2( 0 = not use / 1= use)
73 Temperature3 Sensor Control 0-1 Use Temperature sensor 3( 0 = not use / 1= use)
74 Temperature4 Sensor Control 0-1 Use Temperature sensor 4( 0 = not use / 1= use)
75 Humidity Sensor Control 0-1 Use Humidity sensor ( 0 = not use / 1= use)
1=Temp.sensor1, 2=Temp. sensor 1+2 , 3=Temp. sensor 1+2+4,
76 Temperature Display (Average) 1-4
4=All Temp
77 Select Temp. sensor for control Heater 0-4 0 = use indoor Temperature (Code76); 1 = Temp. sensor 1 ,
2 = Temp. sensor 2 , 3 = Temp. sensor 3 , 4 = Temp. sensor 4
Select Analog Output 1 for Light Dimmer
78 0-1
mode OR Speed Fan 2 mode 0 = Light Dimmer mode ; 1 = Speed Fan 2 mode
79 Select Fan 4 mode OR Spray mode 0-1 0 = Fan 4 mode ; 1 = Spray mode
80 Delay Fan Turn On sec. Delay time for control fan ON ( not too fast)
81 Delay Fan Turn Off sec. Delay time for control fan Off ( not too fast)
82 Delay System sec. Delay time for ON controller
83 Password XXX Password
84 House Number 1-30 House Number
85 Test Relay Test all relay output
86 Test Speed Fan % Test speed fan (Analog Output 0-10 VDC)
87 Test Dimmer % Test Dimmer Light intensity (Analog Output 0-10 VDC)
88 Test Display Test Display
89 Test Digital Input Test Digital Input

E-mail : tmcc_cn@163.com Page34


Temp R-Tron 612 version 2.2 U Operation Manual

Code Parameter Unit Function


91 Day 1-7 Set Day (1=Monday,2=Tuesday,3=Wednesday,….7=Sunday)
92 Date 1-31 Set Date
93 Month 1-12 Set Month
94 Year 1-99 Set Year
95 Hour 0-23 Set Hour
96 Minute 0-59 Set Minute
99 Reset 1 = User Reset
2 = Clear Adjust Sensor
3 = Clear Data logger
4 = Clear Max, Min Value
5 = Factory Reset
8 = Save User Parameter

E-mail : tmcc_cn@163.com Page35


TEMP 3-4 ANALOG OUT D-IN 3-4
T3 0V T4 0V X3 X4 CM2

INV
DIM
TEMP 1-2 HUMIDITY D-IN 1-2

T1 0V T2 +V 0V X1 X2 CM1

HUM
O U T P U T

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
HEAT
COOL
LIGHT
ALARM

E-mail : tmcc_cn@163.com
NC

NO
COM
COMMON OUTPUT 220V/240V

G N L

CMC

COM1
COM2
COM3
COM4
COM5
COM6
COM7
COM8
COML
COMH
SIREN
220 VAC
L
220VAC

N
Ground 0 VAC
N
0VAC L

Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual

Seleter Seleter Seleter Seleter Seleter Seleter Seleter Seleter Seleter Seleter Seleter
Switch FAN 1 Switch FAN 2 Switch FAN 3 Switch FAN 4 Switch FAN 5 Switch FAN 6 Switch FAN 7 Switch FAN 8 Switch COOL Switch HEAT Switch LIGHT
Temp R-Tron 612 version 2.2 U Operation Manual

Overload Overload Overload Overload Overload Overload Overload Overload Overload Overload Overload

Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11
coil coil coil coil coil coil coil coil coil coil coil

FAN 1 FAN 2 FAN 3 FAN 4 FAN 5 FAN 6 FAN 7 FAN 8 COOL HEAT LIGHT

N 0VAC
Wiring Diagram Temp R-Tron 612 Type 1 : 8Fan/1Cool/1Heat/1Light/1Alarm

Page36
TEMP 3-4 ANALOG OUT D-IN 3-4
T3 0V T4 0V X3 X4 CM2

INV
DIM
TEMP 1-2 HUMIDITY D-IN 1-2

T1 0V T2 +V 0V X1 X2 CM1

HUM
O U T P U T

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
HEAT
COOL
LIGHT
ALARM

E-mail : tmcc_cn@163.com
NC

NO
COM
COMMON OUTPUT 220V/240V

G N L

CMC

COM1
COM2
COM3
COM4
COM5
COM6
COM7
COM8
COML
COMH
SIREN
220 VAC
L
220VAC

N
Ground 0 VAC
N
0VAC L

Manual Manual

Push Push
Button Curtain Button Curtain
Switch Open Switch Close

Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual

Seleter Seleter Seleter Seleter Seleter Seleter Seleter Curtain Seleter Curtain Seleter Seleter Seleter
Switch FAN 1 Switch FAN 2 Switch FAN 3 Switch FAN 4 Switch FAN 5 Switch FAN 6 Switch Open Switch Close Switch COOL Switch HEAT Switch LIGHT

NC NC
Overload
Temp R-Tron 612 version 2.2 U Operation Manual

Overload Overload Overload Overload Overload Overload K8 K7 Overload Overload

Overload Overload

Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic


K1 K2 K3 K4 K5 K6 K9 K10 K11
coil coil coil coil coil coil coil coil coil
K7 Magnetic K8 Magnetic
coil coil

FAN 1 FAN 2 FAN 3 FAN 4 FAN 5 FAN 6 Curtain Open Curtain Close COOL HEAT LIGHT
Limit Switch Limit Switch

N 0VAC Wiring Diagram Temp R-Tron 612 Type 2 : 6Fan/1Curtain open/1Curtain Close/1Cool/1Heat/1Light/1Alarm

Page37
TEMP 3-4 ANALOG OUT D-IN 3-4
T3 0V T4 0V X3 X4 CM2

INV
DIM
TEMP 1-2 HUMIDITY D-IN 1-2

T1 0V T2 +V 0V X1 X2 CM1

HUM
O U T P U T

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
HEAT
COOL
LIGHT
ALARM

E-mail : tmcc_cn@163.com
NC

NO
COM
COMMON OUTPUT 220V/240V

G N L

CMC

COM1
COM2
COM3
COM4
COM5
COM6
COM7
COM8
COML
COMH
SIREN
220 VAC
L
220VAC

N
Ground 0 VAC
N
0VAC L

Manual Manual

Push Push
Button Inlet Button Inlet
Switch Open Switch Close

Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual

Seleter Seleter Seleter Seleter Seleter Seleter Seleter Inlet Seleter Inlet Seleter Seleter Seleter
Switch FAN 1 Switch FAN 2 Switch FAN 3 Switch FAN 4 Switch FAN 5 Switch FAN 6 Switch Open Switch Close Switch COOL Switch HEAT Switch LIGHT
Temp R-Tron 612 version 2.2 U Operation Manual

NC NC
Overload Overload Overload Overload Overload Overload K8 K7 Overload Overload Overload

Overload Overload

Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic


K1 K2 K3 K4 K5 K6 K9 K10 K11
coil coil coil coil coil coil coil coil coil
K7 Magnetic K8 Magnetic
coil coil

FAN 1 FAN 2 FAN 3 FAN 4 FAN 5 FAN 6 Inlet Open Inlet Close
Limit Switch COOL HEAT LIGHT
Limit Switch

N 0VAC
Wiring Diagram Temp R-Tron 612 Type 3 : 6Fan/1Inlet open/1Inlet Close/1Cool/1Heat/1Light/1Alarm

Page38
TEMP 3-4 ANALOG OUT D-IN 3-4
T3 0V T4 0V X3 X4 CM2

INV
DIM
TEMP 1-2 HUMIDITY D-IN 1-2

T1 0V T2 +V 0V X1 X2 CM1

HUM
O U T P U T

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
HEAT
COOL
LIGHT
ALARM

NC

NO

E-mail : tmcc_cn@163.com
COM
COMMON OUTPUT 220V/240V

G N L

CMC

COM1
COM2
COM3
COM4
COM5
COM6
COM7
COM8
COML
COMH
SIREN
220 VAC
L
220VAC

N
Ground 0 VAC
N
0VAC L

Manual Manual Manual Manual

Push Push Push Push


Button Curtain Button Curtain Button Inlet Button Inlet
Switch Open Switch Close Switch Open Switch Close

Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual Auto Manual

Seleter Seleter Seleter Seleter Seleter Curtain Seleter Curtain Seleter Inlet Seleter Inlet Seleter Seleter Seleter
Switch FAN 1 Switch FAN 2 Switch FAN 3 Switch FAN 4 Switch Open Switch Close Switch Open Switch Close Switch COOL Switch HEAT Switch LIGHT

NC NC NC NC
Temp R-Tron 612 version 2.2 U Operation Manual

Overload Overload Overload Overload K6 K5 K8 K7 Overload Overload Overload

Overload Overload Overload Overload

Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic Magnetic


K1 K2 K3 K4 K9 K10 K11
coil coil coil coil coil coil coil
K5 Magnetic K6 Magnetic K7 Magnetic K8 Magnetic
coil coil coil coil

FAN 1 FAN 2 FAN 3 FAN 4 Curtain Open Curtain Close Inlet Open Inlet Close COOL HEAT LIGHT
Limit Switch Limit Switch Limit Switch Limit Switch

N 0VAC
Wiring Diagram Temp R-Tron 612 Type 4 : 4Fan/1Curtain open/1Curtain Close/1Inlet open/1Inlet Close/1Cool/1Heat/1Light/1Alarm

Page39
TEMP 3-4 ANALOG OUT D-IN 3-4
T3 0V T4 0V X3 X4 CM2

INV
DIM
TEMP 1-2 HUMIDITY D-IN 1-2

T1 0V T2 +V 0V X1 X2 CM1

HUM
O U T P U T

OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
HEAT
COOL
LIGHT
ALARM

NC

NO

E-mail : tmcc_cn@163.com
COM
COMMON OUTPUT 220V/240V

G N L

CMC

COM1
COM2
COM3
COM4
COM5
COM6
COM7
COM8
COML
COMH

Feed back
Inlet

Curtain Feed back


L
220VAC

N
Ground 0 VAC
L1 L2 L3
X3
L
Manual Manual Manual Manual

Contact Push Push Push Push


Curtain Contact Button Button L1 L2 L3
NO NO Curtain Button Curtain Inlet Button Inlet
Open Close L1 L3 L2 Switch Open Switch Close Switch Open Switch Close X4

K5 K6
Auto Manual Auto Manual Auto Manual Auto Manual

Seleter Curtain Seleter Curtain Seleter Inlet Seleter Inlet


Switch Open Switch Close Switch Open Switch Close Contact Inlet Contact
Inlet NO NO
CM2 Open Close L1 L3 L2
NC NC NC NC
K7 K8
K6 K5 K8 K7
Temp R-Tron 612 version 2.2 U Operation Manual

CurtainGear Motor
M Overload Overload Overload Overload

CM2
K5 Magnetic K6 Magnetic K7 Magnetic K8 Magnetic
coil coil coil coil

Inlet Gear Motor


M
Curtain Open Curtain Close Inlet Open Inlet Close
N 0VAC Limit Switch Limit Switch Limit Switch Limit Switch

Wiring Diagram Temp R-Tron 612 Type 4 : Connect to Curtain motor and Inlet motor

Page40
Temperature sensor and Feed counter wiring diagram
Humidity sensor and Water counter wiring diagram
T3 Temperature Sensor Outside
BROWN
WHITE/BLACK
TEMP 3-4

T3 0V T4

TEMP 1-2

INV
T1 Temperature Sensor Inside
BROWN Humidity Sensor Inside
T1 0V T2 +V
0V

WHITE/BLACK BROWN HUM


DIM
ANALOG OUT

HUMIDITY

WHITE

TEMP 3-4

E-mail : tmcc_cn@163.com
T3 0V T4

TEMP 1-2
INV GREEN
D-IN 3-4

T1 0V T2 +V
D-IN 1-2

T2 Temperature Sensor Inside

0V
WHITE/BLACK
X3 X4 CM2

HUM
0V X1 X2 CM1

DIM

ANALOG OUT

HUMIDITY
BROWN

D-IN 3-4

D-IN 1-2
T4 Temperature Sensor Inside

X3 X4 CM2
WHITE/BLACK Water counter

0V X1 X2 CM1
BROWN

Feed counter

R S T L N

INVERTER DIMMER CONTROL

TEMP 3-4
TEMP 3-4

TEMP 1-2
TEMP 1-2

SPEED FAN

T3 0V T4
T3 0V T4

INV INV

T1 0V T2 +V
T1 0V T2 +V
Temp R-Tron 612 version 2.2 U Operation Manual

0V
HUM
0V

HUM
Input Signal

HUMIDITY
DIM
HUMIDITY

ANALOG OUT

DIM
ANALOG OUT

0 – 10VDC 0V

0V Input Signal
0 – 10VDC
D-IN 3-4

D-IN 1-2
D-IN 3-4

D-IN 1-2

U V W
X3 X4 CM2
X3 X4 CM2

0V X1 X2 CM1
0V X1 X2 CM1

L1 N

Motor

Inverter Speed Fan Wiring Diagram Dimmer Control Wiring Diagram

Page41