Professional Documents
Culture Documents
Piping Class - BC21
Piping Class - BC21
ND (inch) 0.50 0.75 1.00 1.50 2.00 3.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00 20.00
OD (mm) 21.3 26.7 33.4 48.3 60.3 88.9 114.3 168.3 219.1 273.1 323.8 355.6 406.4 457.0 508.0
THK (mm) 4.78 5.56 6.35 5.08 5.54 5.49 6.02 7.11 8.18 9.27 10.31 11.13 12.70 14.27 15.09
SCH 160 160 160 80 80 40 40 40 40 40 40 40 40 40 40
WEIGHT XS XS STD STD STD STD STD XS
END
RANGE GEOMETRIC EDS/
ITEM TYPE CONN MATERIAL DESCR. MDS RATING SCHD. NOTES
FROM TO STANDARD VDS
#1 #2
PIPE 0.50 20.00 ASME B36.10M PE PE A106 B C01
PIPE 8.00 20.00 ASME B36.10M PE PE A672 C60 CL12 C01
PIPE NIPPLE 100MM LONG 0.50 1.00 ASME B36.10M TE PE A106 B C01 XXS
BENDING 0.50 20.00 MADE FROM PIPE NBE1
CAP 0.50 20.00 ASME B16.9 BE A234 WPB C01
CONCENTRIC REDUCER 0.75 20.00 ASME B16.9 BE BE A234 WPB C01
ECCENTRIC REDUCER 0.75 20.00 ASME B16.9 BE BE A234 WPB C01
ELBOW LONG RADIUS 45 DEG 0.50 20.00 ASME B16.9 BE BE A234 WPB C01
ELBOW LONG RADIUS 90 DEG 0.50 20.00 ASME B16.9 BE BE A234 WPB C01
STRAIGHT TEE 0.50 20.00 ASME B16.9 BE BE A234 WPB C01
REDUCING TEE 0.75 20.00 ASME B16.9 BE BE A234 WPB C01
WELDOLET 2.00 20.00 NORSOK EDS NOL1 BE BE A105 C01
REINFORCED NIPOFLANGE 2.00 20.00 NORSOK EDS NOL1 BE RF A105 C01
BLIND FLANGE 0.50 20.00 ASME B16.5 RF A105 C01
BLIND FLANGE 0.50 20.00 ASME B16.5 RF A516 Gr70 C11
WELDNECK FLANGE 0.50 20.00 ASME B16.5 NAF1 RF BE A105 C01
WELDNECK ORIFICE FLANGE 1.00 20.00 ASME B16.36 NAF1 RF BE A105 C01
SPECTACLE BLIND 0.50 12.00 NORSOK EDS NLB1 FF FF A516 Gr70 C11
SPADE 14.00 20.00 NORSOK EDS NLB1 FF FF A516 Gr70 C11
SPACER 14.00 20.00 NORSOK EDS NLB1 FF FF A516 Gr70 C11
GRAPHITE/METAL
GASKET FLAT 0.50 20.00 ASME B16.21 NGA1 RF RF
LAMIN
6000
HEX HEAD PLUG 0.50 1.00 ASME B16.11 MT A105
LBS
STUD BOLT C/W NUTS 0.50 20.00 ASME B16.5 NBO1 A193 B7/A194 2H
Notes :
001 REF. SECTION 6 FOR SERVICES REQUIRING NACE MR0175.
THE WALL THICKNESS TOLERANCE IS USED FOR DESIGN AND IS NOT PART OF THE PURCHASE SPECIFICATION WHEN DEVIATING FROM THE
002
INDIVIUAL PIPING ITEMS.
016 IF PIPE SIZES GREATER THAN 20" ARE IMPLEMENTED, IMPACT TESTING IS REQUIRED.
069 FOR GAS SERVICE IS SEAT SKIRT NOT NECESSARY.
071 IF ACTUATOR IS REQUIRED USE TRUNNION MOUNTED BALL VALVE.
072 IF BALL VALVE IS SELECTED IN RELIEF SYSTEM USE TRUNNION MOUNTED BALL VALVE.
075 MAX. 150 DEG C.