AL WASEEL HILLS PHASE 1

J&P

ELECTRICAL MATERIAL SUBMITTAL PACKAGE


FOR
LOW CURRENT CABLES FOR MATV, FIRE ALARM & BMS SYSTEM

Supplier: Saudi Media Systems


LEVITON, Prysmian , Toner Cable Equipment, Inc. &
Manufacturer:
BELDEN

Prepared Reviewed Approved


Document Ref. REV. Date Document Description
by by by
MATERIAL SUBMITTAL FOR
LOW CURRENT CABLES FOR
MT-E-032A 02 18/03/2015 S. Narayanan D. Patsios
MATV, FIRE ALARM & BMS
SYSTEM
AL WASEEL HILLS PHASE 1

J&P

MATERIAL SUBMITTAL FOR LOW CURRENT CABLES FOR MATV, FIRE ALARM & BMS SYSTEM

Document Ref. No: MT-E-0032A-REV 02 Date: 18/03/2015

TABLE OF CONTENTS

Divider
# Subject
A Contractor's response to PMT comments on Submittal Rev.01

B Low Current Cables Sample Board


AL WASEEL HILLS PHASE 1

J&P

MATERIAL SUBMITTAL FOR LOW CURRENT CABLES FOR MATV, FIRE ALARM & BMS SYSTEM

Document Ref. No: MT-E-0032A-REV 02 Date: 18/03/2015

DIVIDER A

Contractor's Response to PMT Comments on Submittal


Rev.01
WSL/142.4 - AL WASEEL HILLS PROJECT - RIYADH

Material Submittal MTS-ELE-032A Rev 02 - Low Current Cables for MATV, Fire Alarm & BMS System

SPECIFICATION SECTIONS :

CONTRACTOR'S RESPONSE TO PMT COMMENTS ON MATERIAL SUBMITTAL MTS-ELE-032A Rev 01

SN PMT COMMENTS CONTRACTOR'S RESPONSE

Confirmation letter from the manufacturer to


Comply, please see attached. The fire rating is according to BS6387 category CWZ,
be submitted confirmong that the Fire Alarm
1 rated at 950 degree centegrade to resist fire for 3-hours and the sheath is made from
cable Prysmian FP200 Gold is 2 hours fire
rated. robust thermoplastic LSOH.

Comply,sample cable for MATV and Fire Alram are already have on board, plesase
Submit complete sample of cables in separate
2 find the sample board. Sample cable for BMS are partially provided and the rest of
sample board for each low current cables.
the cables will be submitted subsequently.
FIRE RESISTANT CABLES
PRVSMJAN

FP200 GOLD® 200


BS7629-1 :2 008 Certificate No 077f
Certificate No 077k
GOLD
> The original highly durable and dressable, easy to
FP200 GOLD® terminate and install fire resistant cable, using the unique
lnsudite'" damage resistant insulation system. Approved
for fire detection and fire alarm critical signal paths to
855839-1 :2002+A2:2008 and voice alarm systems to
855839-8:2008 in 'st andard' application areas, and emergency
lighting systems to 855266-1 :2005.

The changes to cable test methods and requirements first


introduced by 855839-1 :2002+A2:2008 ~Fire detection and fire
alarm systems for buildings - Part 1: Code of practice for system
design, installation, commissioning and maintenance· mean that
fire resistant cables must now be approved against new test
requirements.

APPROVALS > In addition to approvals to 857629-1 and 856387 Category


CWZ, FP200 Gold8 has received BASEC and LPC8 approval to
855839-1 :2002 for 'standard' applications. This includes
approval to 85 EN 50200 Class PH30 and the new integrated
fire, shock and water test 858434-1 for 30 minutes. FP200 Gold8
is also approved to 85 EN 50200 Class PH60 as required by
855266-1 :2005.

All Prysmian FP200Gold 9 cables are manufactured under an


150 9001 Quality System certified by BAS EC and LPC8.

DATA CAPABILITY > FP200 Gold 9 has excellent data/ signal transmission characteristics
making it ideal for voice alarm, addressable and networked
systems.

INSTALLATION > In accordance with 855839-1 and 855266-1 requirements,


cables must be supported by a fixing that can withstand the
same fire conditi ons as the cable. To meet this requirement the
use of Prysmian AP LSOH 9 coated metal P- cl ips or the new FP
Firefix'· rapid fixing system is recommended.

FP200Gold should be installed in accordance with


BS7671 / IEE Wiring Regulat ions and/ or any other appropriate
national regulations or codes. It is suitable for indoor and
outdoor installation in suitably protected environments and
particularly appropriate for surface wiring, dir ect burial in
plaster, t ray or other installations requiring a dressable product.

CABLE CHARACTERISTICS

Ttmporotin BendlngRaclus Fint PorforlMllCt flexibilty Halogen Free Low Smoke Emissions Fire R~tstance
Rongo flndr-60 8S EN 60332- 1- 2 Rigid 85 EN 50267-2-1 85 EN 61034·2 856387 category cwz
- 20 to +70'C 8S EN 50266· 2· 4 85 EN 50200 PH30 & PH60'
85 EN 50200 Annex E

~ PRYSMIAN
~ caou a nnuu
FP200 LO

FIRE RESISTANT CABLES 300/SOOV


KEY APPLICATIONS CORE IDENTIFICATION
> Fire detection and fire alarm systems for buildings HARMONISED CORE IDENTIFICATION:
> Voice alarm systems o o brown-blue I o o o brown-black-grey
> Emergency lighting o o o o blue-brown-black-grey
> Other essential service circuits
NON HARMONISED CORE IDENTIFICATION:
o o red-black I o o red-yellow- blue
o o o black-red-yellow-blue
CABLE DESCRIPTION
Non harmonised colours to special order.
CONDUCTOR
Plain annealed copper solid (1.0 - 2.5 mm•) or stranded SCREEN/CPC
(4.0 mm•) circular conductor complying with BS EN 60228 Laminated aluminium tape screen bonded t o sheath and in
class 1 or class 2. contact with full size tinned annealed copper circuit protective
conductor which provides automatic screen earthing.

INSULATION SHEATH
High performance damage resistant lnsudite... Robust thermoplastic LSOH sheath; Colour - White
British Standard Type EIS. or Red. Other colours to special order. For external
exposure the use of a white sheath is recommended.

Nominal Conceptual Mean Approximate Maximum Current Current Volt drop Recommended accessories
cross Construction overall cable conductor rating DC or rating DC or DC or single Colour - White or Red
sectional diameter weight resistance single phase single phase phase • LSOH" •Nylon
area at2o·c AC AC AC fixing LSOH"
FP Firefix~
Enclosed Clipped direct fixing
mm' no.Imm mm kg/km ohms/km I Amps Amps mV/A/m
clips gland
clips

Two core
1.0' 1/ 1.13 8.0 78 18. 1 13 15 44 AP7 251/ GL2520 UFPNF02

251/GL2520 UFPNFOl'
1.5 111.38 8. 1 93 12.1 16.5 19.5 29 AP7
UFPNF02
2.5 1/1.78 9.5 140 7.4 23 27 18 AP9 251/GL2520

4.0 7/0.85 11.6 195 4.6 30 36 11 APl I 252/GL2520

Three core
1.0' 1/1.13 8.2 88 18. 1 13 15 44 AP7 251/GL2520 UFPNF02

1.5 1/1.38 8.4 116 12. I 16.5 19.5 29 AP8 251/GL2520 UFPNF04

2.5 1/1.78 10.4 180 7.4 23 27 18 AP10 252/GL2520

4.0 7/0.85 12.3 248 4.6 30 36 11 AP12 252

Four Core
1.0' 1/ 1.13 8.5 107 18. 1 13 15 44 AP8 251/GL2520 UFPNF04

1.5 1/ 1.38 10 143 12.1 16.5 19.5 29 AP9 25 1/ GL2520

2.5 1/1.78 11.9 225 7.4 23 27 18 APl 1 252/GL2520

4.0 7/0.85 13.5 310 4.6 30 36 11 AP13 254

Notes to table • Single clip


1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative.
3 855266-1:2005 clause 9.2.3 states a minimum cross- sectional area of conductor of 1.5mm 2

FP200 Gold" is also available in multi-core versions (7, 12 & 19 core}


Minimum recommended installation temperature o•c. Installation methods for current rating in accordance with BS76 71 / IEE Wiring Regulations.
The tabulated ratings are based upon a 30°( ambient temperature and 70°( operating temperature. For other ambient temperatures or where cables
are grouped together, appropriate rating factors should be applied.

Temperature ratings factor


Ambient Temperature°C 25 30 35 40 45 50

Rating factor 1.03 1.00 0.94 0.87 0.79 0.71

Rating Factors for Groupings


Number of circuits 2 3 4 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54

w:
~ PRYSMIAN
CAIU S • nnuu
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
Uncontrolled when printed
AL WASEEL HILLS PHASE 1

J&P

MATERIAL SUBMITTAL FOR LOW CURRENT CABLES FOR MATV, FIRE ALARM & BMS SYSTEM

Document Ref. No: MT-E-0032A-REV 02 Date: 18/03/2015

DIVIDER B

Low Current Cables Sample Board


AL WASEEL HILLS PHASE 1

J&P

MATERIAL SUBMITTAL FOR LOW CURRENT CABLES FOR MATV, FIRE ALARM & BMS SYSTEM

Document Ref. No: MT-E-0032A-REV 02 Date: 18/03/2015

LIST OF PROPOSED MAJOR PRODUCTS

Model / Datasheet Country of


S/N Product description Mnfr.
Part No. Page No. Origin

LOW CURRENT CABLES

SAMPLE BOARD # 1
A MATV SYSTEM (MT-E 042)
1 6-core FOC I/O Central Loose Tube Armor Leviton SMLAZ-062 35-37 USA

Toner Cable
2 RG-11, 60%, Riser Rated, Black Coax Cable, 1000' Reel RG11-60RRB-M 42-43 USA
Equipment. Inc
RG6-60R Series RG-6 Coaxial Cable 60% Braid R Rated,UL Listed, Toner Cable
3 RG6-60RBB-M 44-45 USA
3 GHz Equipment. Inc
B FIRE ALARM SYSTEM (MT-E 047)

1 Prysmian FP200 Gold Solid 2 Core 1.5mm² ( 16 AWG ) Prysmian FP200-2x1.5mm² 38-41 USA

SAMPLE BOARD # 2
C BMS SYSTEM (MT-E 066)

BMS Partial Sample Cables on Board


Security & Commercial Audio Cable, Riser-CMR, 2-18 AWG
1 stranded bare copper conductors with BELDEN 5300UE 5-7 USA
polyolefin insulation, PVC jacket with ripcord
Security & Commercial Audio Cable, Riser-CMR, 3-22 AWG
2 stranded bare copper conductors with polyolefin insulation, BELDEN 5501FE 24-26 USA
Beldfoil® shield and PVC jacket with ripcord
Security & Alarm Cable, Riser-CMR, 6-22 AWG stranded bare
3 copper conductors with polyolefin insulation, Beldfoil® shield and BELDEN 5504FE 28-31 USA
PVC jacket with ripcord
Security & Alarm Cable, Riser-CMR, 2-22 AWG stranded bare copper
4 conductors with polyolefin insulation, Beldfoil® shield and PVC jacket with BELDEN 5500FE 20-22 USA
ripcord

Security & Alarm Cable, Riser-CMR, 2-22 AWG stranded bare copper pairs
5 with polyolefin insulation,Beldfoil® shield and PVC jacket with ripcord BELDEN 5541FE 32-34 USA

BMS Sample Cables to Follow


20 AWG pairs stranded (7x28) bare copper conductors, twisted
1 pairs, PVC insulation, overall Beldfoil shield (100% coverage), PVC BELDEN 1056A 1-3 USA
jacket.
Security & Alarm Cable, Riser-CMR, 2-18 AWG stranded bare
2 BELDEN 5341UE 8-10 USA
copper pairs with polyolefin insulation, PVC jacket with ripcord

Security & Alarm Cable, Riser-CMR, 3-18 AWG stranded bare


3 BELDEN 5342UE 11-13 USA
copper pairs with polyolefin insulation, PVC jacket with ripcord

Security & Alarm Cable, Riser-CMR, 4-18 AWG stranded bare


4 BELDEN 5343UE 14-16 USA
copper pairs with polyolefin insulation, PVC jacket with ripcord

Security & Alarm Cable, Riser-CMR, 6-18 AWG stranded bare


5 BELDEN 5345UE 17-19 USA
copper pairs with polypropylene insulation,PVC jacket with ripcord

COMMENTS:
All remaining BMS cable will be submitted subsequently.