Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

International Journal of Modelling and Simulation

ISSN: 0228-6203 (Print) 1925-7082 (Online) Journal homepage: https://www.tandfonline.com/loi/tjms20

Invasive weed optimization-based automatic


generation control for multi-area power systems

Somanath Mishra, A. K. Barisal & B. Chitti Babu

To cite this article: Somanath Mishra, A. K. Barisal & B. Chitti Babu (2019) Invasive weed
optimization-based automatic generation control for multi-area power systems, International Journal
of Modelling and Simulation, 39:3, 190-202, DOI: 10.1080/02286203.2018.1554403

To link to this article: https://doi.org/10.1080/02286203.2018.1554403

Published online: 07 Dec 2018.

Submit your article to this journal

Article views: 19

View Crossmark data

Citing articles: 1 View citing articles

Full Terms & Conditions of access and use can be found at


https://www.tandfonline.com/action/journalInformation?journalCode=tjms20
INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION
2019, VOL. 39, NO. 3, 190–202
https://doi.org/10.1080/02286203.2018.1554403

ARTICLE

Invasive weed optimization-based automatic generation control for multi-area


power systems
Somanath Mishraa, A. K. Barisal b
and B. Chitti Babuc
a
Department of Electrical Engineering, VSSUT, Burla, India; bDepartment of Electrical Engineering, College of Engineering & Technology,
Bhubaneswar, India; cDepartment of Electronics Engineering, Indian Institute of Information Technology, Design & Manufacturing,
Kancheepuram, Chennai, India

ABSTRACT ARTICLE HISTORY


In this paper, Invasive weed optimization (IWO) algorithm is proposed for testing automatic Received 21 March 2018
generation control (AGC) of multi-area power systems. Initially, a two-area multi-source power Accepted 28 November 2018
system interconnected by a DC link is considered and IWO is employed to optimize the propor- KEYWORDS
tional integral derivative (PID) controller for AGC employing a modified objective function. The Automatic generation
superiority of the proposed approach is shown by comparing the results with recently published control (AGC); Multi-area
optimal algorithms for the similar system under study. The comparison is made using various multi-source power system;
performance criteria such as integral of time multiplied absolute error (ITAE), minimum damping HVDC link; Invasive Weed
ratio (MDR) of dominant eigenvalues, settling times and maximum overshoots. Furthermore, Optimization (IWO)
sensitivity analysis is performed to show the robustness of the proposed approach by varying the algorithm; sensitivity
system parameters, operating load conditions from their nominal values as well as size and analysis; Generation Rate
Constraints (GRC)
locations of disturbance. The proposed approach is also extended to three area system consider-
ing both thermal and hydro units with generation rate constraints (GRC) and the superiority of
the proposed approach is shown by comparing the results of Adaptive Neuro Fuzzy Inference
System (ANFIS), hybrid Bacteria Foraging Optimization Algorithm with Particle Swarm
Optimization (hBFOA–PSO) approaches for the identical interconnected power system.

1. Introduction pertaining to AGC problem have been discussed [4].


Lee et al. have proposed a gain scheduling control
The modern power systems are becoming complex day
method to AGC of interconnected power system to
by day and interconnected with each other through tie
improve the performance to wide range of operating
lines to exchange power between different control areas
conditions. The growth in size, complexity, and
for successful operation and reliable control. The purpose
changing load pattern of electric power system has
of automatic generation control (AGC) is to maintain
necessitated the use of intelligent control methods
scheduled system frequency and scheduled tie-line power
for satisfactory operation of power systems [5].
deviations during load disturbances. The AGC adjusts the
There has been remarkable turnaround in research
area control error (ACE) to zero so as to restore the
work attempting to propose and implement sophis-
frequency and tie line power to their nominal values [1,2].
ticated control strategies in AGC systems such as
Over the last decade, many researchers have
fuzzy logic-based gain scheduling [6], fuzzy logic
reported several control strategies for AGC of
controller [7], self tuning fuzzy type PID controller
power systems in order to stabilize system frequency
[8], reinforcement learning approach [9], artificial
and tie line power flow at their nominal values
neural network-based controller [10], adaptive
during normal operation as well as in small pertur-
neuro-fuzzy interference system [11], genetic algo-
bations. Cohn et al. [2] had initiated the AGC work
rithm-based fuzzy gain scheduling PI controller
by describing some aspects of tie line bias control of
[12], evolutionary fuzzy PI controller [13], com-
interconnected power systems. The design and con-
bined intelligent techniques [14], PSO-based con-
cept of modern optimal controller for intercon-
troller with fuzzy application [15], generalized
nected power system was initiated by Elgerd and
neural network approach [16], dynamic perfor-
Fosha [3]. The detail literature review on the AGC
mance analysis of AC/DC lines with multi-source
of power systems with different control techniques
of power generation in each area [17,18], optimal

CONTACT B. Chitti Babu bcbabunitrkl@ieee.org Department of Electronics Engineering, Indian Institute of Information Technology, Design &
Manufacturing, Kancheepuram, Chennai 600127, India
© 2018 Informa UK Limited, trading as Taylor & Francis Group
INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION 191

output feedback controller for a multi-source system conditions as well as changes in size and loca-
[19,20], differential evolution (DE) algorithm tuned tions of load perturbations.
controller [21,22], and artificial bee colony (ABC) (v) To test the effectiveness of IWO in a three area
algorithm tuned controller [23] for AGC studies. power system with GRC and compare the results
Gozde et al. [23] have reported superior perfor- with ANFIS and hBFOA–PSO algorithms.
mance of PI and PID controller tuned by ABC
algorithm compared to PSO.
It is clear from literature survey that the perfor- 2. Materials and method
mance of the power system depends on the artificial
2.1. Two area multi-source power system with
intelligent techniques employed, the strategy of con-
HVDC links
troller structure and the objective function considered.
Hence, proposing and implementing new intelligent Initially, a two-area multisource power system has been
optimization algorithms to real-world AGC problems considered. It consists of generating units such as
are always welcome. Recently, a new biologically reheat thermal, hydro and gas units in each area with
inspired meta-heuristic algorithm, known as the inva- parallel AC–DC tie lines [19]. The transfer function
sive weed optimization (IWO), was developed by model of multi-area multi-source power system with
Mehrabian et al. [24]. It is based on the invasive habits HVDC link along with proposed PID controllers is
of growth of weeds and possessing a good balance shown in Figure 1. The different parameters of the
between exploration and exploitation ability. IOW has power system are provided in Appendix A.
been successfully employed to various engineering pro-
blems such as recommender system design [25],
antenna system design [26], state estimation of non- 2.2. Control scheme and objective function
linear systems [27], unit commitment problem solution
The proportional integral derivative (PID) controller is
[28] and large scale economic load dispatch of power
the most popular feedback controller. It is used in many
systems [29]. Similarly, other controllers like integral
process industries due to its simplicity, faster closed-loop
controller [30], hybrid BFOA_PSO controller [31] in
response and robustness. The design of objective function
AGC of multi-area power systems, ANFIS controller
to tune PID controller parameters is generally based on
[32] for speed control of induction motor, Performance
a performance index that considers the entire closed-loop
analysis using classical controllers tuned by moth flame
response. Typical performance indices considered in the
optimization algorithm for AGC system [33] have been
time domain are peak overshoot, rise time, settling time,
reported. The modified differential algorithm (MDE)
and steady-state error. However, the eigenvalues and
[34] provides better results than conventional DE in
modal analysis provides an extension of analytical meth-
identifying the Pendubot’ parameters. This work gives
ods to examine the low frequency oscillations that are
a message that modification of intelligent algorithm
present in a power system. Eigen value analysis investi-
still provides an improved result. The present work
gates the dynamic behavior of the power system under
focuses on the performance of the IWO as an optimiz-
different characteristic frequencies (modes). In a power
ing tool in tuning the PID controller parameters for
system, it is required that all modes to be stable. It is
AGC of multi-area power systems.
worth mentioning that all electromechanical oscillations
The main investigations of the present work:
are damped out as quickly as possible when the damping
ratios of dominant eigen values are maximized. To meet
(i) To develop a strategy based on IWO, for AGC
the above design specifications, three different objective
of multi-area power systems.
functions are employed in the present paper as given
(ii) To optimize the PID controller gains employ-
below:
ing IWO and analyze the dynamic performance
tsim  
of power system with IWO optimized control-
ler for AGC. J1 ¼ ISE ¼ ò jΔF1 j2 þ jΔF2 j2 þ jΔPTie j2 : dt (1)
0
(iii) To compare the dynamic performance of the
system without and with HVDC link with tsim  
IWO-based PID controller to that of optimal J2 ¼ ITSE ¼ ò jΔF1 j2 þ jΔF2 j2 þ jΔPTie j2 : t: dt (2)
0
controller.
(iv) To analyze the sensitivity for the proposed tsim
IWO-PID controller and test its robustness to J3 ¼ ITAE ¼ ò ðjΔF1 j þ jΔF2 j þ jΔPTie jÞ  t  dt (3)
0
wide changes in system parameters and loading
192 S. MISHRA ET AL.

Figure 1. Transfer function model of two area multisource power system interconnected by parallel AC–DC tie lines.

tsim tsim The error inputs to the controllers are the respective
J4 ¼ ò ω1 : ò ðjΔF1 j þ jΔF2 j þ jΔPTie jÞ  t  dt ACE represented in (2) and (3) for area-1 and area-2,
0 0
1 respectively,
þ ω2 :  nm  (4)
P ACE1 ¼ B1 ΔF1 þ ΔPTie (5)
min ð1  i Þ
i¼1
ACE2 ¼ B2 ΔF2  ΔPTie (6)
where ΔF1 and ΔF2 are the incremental change of
frequencies of area-1 and area-2, respectively. ΔPTie is The control inputs of the power system UT , UH and UG
the tie line power deviation, tsim is the range of simula- are the outputs of the controllers. These control inputs
tion time; i is the damping ratio, nm is the total are obtained as follows:
number of dominant eigen values, ω1 and ω2 are dACE1
weighting factors. Appropriate weighting factors are UT ¼ KP1 ACE1 þ KI1 ò ACE1 þ KD1 (7)
dt
being multiplied to the right hand side of individual
terms of Equation (4) which helps to make each term dACE1
UH ¼ KP2 ACE1 þ KI2 ò ACE1 þ KD2 (8)
in the objective function competitive enough during dt
the optimization process. A series of runs of optimized
algorithm reveals that the numerical value of ITAE lies dACE1
UG ¼ KP3 ACE1 þ KI3 ò ACE1 þ KD3 (9)
in the range of 0.16 to 0.4 and MDR lies in the range of dt
0.03 to 0.38 and settling times of ΔF1 , ΔF2 and ΔPTie lie The constraints of PID controller parameters should
in the range of 5–15 s. In the optimization process the satisfy its boundary values. Therefore, the objective
weights are chosen as ω1 = 1.0 and ω2 = 10, to make function can be formulated as the following optimiza-
each term competitive in the Equation (4). tion problem.
INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION 193

Minimize J deviations and σ f as final standard deviations and n is


subject to the nonlinear modulation index.
Kij min  Ki  Kij max (10) Step 6: The offspring and parents are participating
in evaluation process and ranking is done based on
where i ¼ P; I; D and j ¼ 1; 2; 3. their fitness value. Plants with lower ranking in the
The values of controller parameters are selected in colony are eliminated to satisfy the maximum number
between −2.0 and 2.0 in the present work. of plants in the colony (Popmax ).
Step 7: The best individual is selected among the
seed-parent combination in the colony during iterative
3. Overview of Invasive Weed Optimization process. When the predefined maximum number of
IWO is a meta-heuristic optimization algorithm iterations is reached, the iterative process is terminated
inspired by biological phenomenon. Early work on and the optimal gains of controller are displayed,
IWO was started by Mehrabian and Lucas [24]. This otherwise go to Step 3 for continuation.
optimization technique is based on the typical charac-
teristics of weed plants [25].
4. Results and discussions
The study has been realized and implemented in Matlab-
3.1. Computational procedure
7.10.0.499 (R2010a) environment on a Pentium-IV; with
The steps of the proposed approach are mentioned below: 3.06 GHz processor, 1GB RAM PC. The model of the
Step 1: The seeds are initialized based on selected system under study has been developed in MATLAB/
variables uniformly between their limits. SIMULINK and IWO program has been written (in .m
Step 2: A Seed matrix (S) of size (Popmax  d) is file). The developed model is simulated in a separate .m
created with more number of plants in the population file considering a 1% step load perturbation (SLP) in area-
Popmax having potential solutions. 1 at time zero second. The objective function is calculated
Step-3: The fitness value of each seed set (S) (each in .m file and used in optimization algorithm for tuning
row (plant) of S) is evaluated based on considered the gains of PID controller for power system. Series of
objective function. Then ranking is done in the colony experiments were conducted to properly select the con-
with best-fitted plant with rank no. 1. trol parameters of IWO. The values of algorithm are
Step 4: Every weed (plant) produces new seeds selected as Popmax = 10, σ 0 = 0.0015, σ f = 0.3, Nmin = 0,
depending on its rank in the whole population in Nmax = 3, itermax = 50, d = 3 and n = 3. The flow chart of
seed set. The best-fit plant produces maximum number proposed IWO technique to tune the controller para-
of seeds (Nmax ) and giving chance to all other plants to meters is shown in Figure 2. The optimization program
participate in reproduction process. with the model (Figure 2) were simulated 25 times for
Step5: The number of seeds to be created by each each objective functions and the best solution among the
weed varies linearly from Nmin to Nmax . 25 solutions is chosen as final controller parameters. To
Fi  Fworst investigate the effect of objective function on the dynamic
Number of seeds ¼ ðNmax  Nmin Þ performance of the system in terms of settling times (2%
Fbest  Fworst
þ Nmin (11) of final value) of frequency and tie-line power deviations
and MDRs for the system with AC/DC links are provided
where Fi is the current fitness of ith weed. The worst in Table 1. It can be seen from Table 1 that among the
and best fitness in weed population are denoted by three conventional objective functions (J1, J2, J3), less
Fworst and Fbest , respectively. The generated seeds are settling time with a comparatively high MDR is obtained
normally distributed over the field with zero mean and with ITAE objective function compared to the ISE and
varying standard deviation of σ iter described by ITSE objective functions. It is also clear from Table 1 that
  the proposed modified objective function J4 given by
itermax  iter n  
σ iter ¼ σ0  σf þ σf (12) Equation (4) gives the best system performance in terms
itermax
of high MDR values and less settling times values. The
where itermax and iter are the maximum number of final controller parameters employing the proposed
iteration cycles assigned by the user and current itera- objective function J4 are shown in Table 2 for two-area
tion number, respectively. σ 0 is initial standard multi-source power system without and with HVDC link.
194 S. MISHRA ET AL.

Table 1. Performance comparison with different objective


functions.
Objective function ISE: J1 ITSE: J2 ITAE: J3 Proposed: J4
Settling times ΔF1 1.88 2.58 2.2 1.98
(2% band) ΔF2 4.76 4.06 3.99 3.82
ΔPTie 0.0044 0.0052 0.0035 0.0027
MDR 0.0111 0.3395 0.3386 0.3577

Table 2. IWO tuned controller parameters of two area multi-


source power system without and with DC link.
Controller Parameter Thermal Hydro Gas
System with AC lines KP = 1.8347 KP = 0.8420 KP = 1.5027
KI = 0.0744 KI = 0.0911 KI = 0.1208
KD = 1.1720 KD = 1.8504 KD = 1.4443
System with AC–DC KP = 1.2362 KP = 1.7908 KP = 1.7099
parallel lines
KI = 1.8644 KI = 1.165 KI = 0.0697
KD = 1.6702 KD = 1.1655 KD = 1.7708

of the proposed approach is shown by comparing the


results with recently published optimal controller [19]
for the same power systems.
Case A: Step load change in area-1
A 1% SLP in area 1 is considered at t = 0 s. The
system modes, MDR, ITAE value, settling times of
frequency and tie-line power deviations (2% tolerance
band) and maximum over shoot (MOS) with proposed
IWO-PID controller for the system with AC lines only
as well as with both AC/DC lines are provided in Table
3. For comparison, the corresponding values with opti-
mal control [19] are also given in Table 3. It is clear
from Table 3 that, the eigen values lie in the left half of
s plane for both cases thus maintaining the stability. It
is also evident from the Table 2 that minimum damp-
ing ratio (MDR = 0.3577) with IWO optimized PID
controller is superior to that of optimal controller
(MDR = 0.2896) in AC/DC lines which is very impor-
tant for stability point of view. It is also evident from
Table 3 that for similar power system, settling times
and MOS in fof Δf1 , Δf2 and ΔPTie are significantly
reduced with proposed approach compared to recently
published optimal control approach [19] for the iden-
tical power system. Hence, it can be concluded that the
proposed approach gives an improved dynamic perfor-
Figure 2. Flow chart of IWO algorithm to tune the controller mance compared to the optimal control method. For
parameters. better illustration of improved results with proposed
approach, these improvements are given in Table 4. It
can be seen from Table 4 that, the values of ITAE, ISE,
4.1. Investigation of tuning performance ITSE, IAE, settling time of Δf1 , Δf2 and ΔPTie are
improved by 94.49%, 99.78%, 99.86%, 95.05%,
4.1.1. Multi-area multi-source power system without
85.63%, 69.97%, and 99.98%, respectively, with IWO
and with DC link
tuned PID controller compared to that of optimal
To study the dynamic performance of designed con-
controller [19] for system with AC/DC parallel lines.
trollers, time domain simulations are performed for
The dynamic responses of the system for the above
step load change at different locations. The superiority
disturbance are shown in Figures 3 and 4. It is evident
INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION 195

Table 3. System modes, minimum damping ratio, settling times, maximum overshoot and ITAE values for two area multi-source
power system without and with DC link.
IWO controller with Optimal controller IWO controller Optimal controller
Methods AC/DC Links AC/DC Links [19] with AC tie only with AC tie only [19]
System −23.8477
Modes −12.7552 −21.9656 −12.9350 −23.9591
−12.7381 −15.9350 −12.9010 −21.3382
−1.9007 ± 4.9626i −10.4836 0.0747 ± 2.3775i −15.8966
−2.1160 ± 4.7464i −2.2658 ± 7.4892i −4.8657 ± 0.5316i −6.5196 ± 5.4667i
−4.0603 −5.7721 ± 2.8965i −4.8409 ± 0.4653i −6.4950
−3.8651 ± 0.1011i −6.2593 −2.8966 −6.2617
−3.6712 −4.6014 ± 0.2316i −2.7307 −4.4414
−2.2749 −3.6601 −0.2848 ± 1.2647i −3.8534 ± 0.0428i
−2.2148 −2.3957 −1.6240 −0.3465 ± 1.9436i
−0.9610 −2.0112 −1.1412 ± 0.6372i −2.3489
−0.8247 −1.2278 −1.0639 −1.8534
−0.3112 ± 0.4421i −1.0783 −0.2055 −1.2576
−0.2572 ± 0.0948i −0.4370 ± 0.4344i −0.0784 ± 0.0295i −1.0725
−0.2584 −0.0813 ± 0.1552i −0.0830 −0.4414 ± 0.4327i
−0.0398 −0.2318 −0.0484 −0.1269 ± 0.1044i
−0.0422 ± 0.0034i −0.2041 −0.0354 −0.2048
−0.0485 −0.0415 −0.0355 −0.0417
−5.0000 −0.0417 −5.0000 −0.0416
−5.0000 −5.0000 −5.0000 −5.0000
−5.0000 −5.0000 −5.0000
−5.0000
MDR 0.3577 0.2896 0.3139 0.1755
ITAE 0.1968 3.5764 0.312 5.1482
Settling times (2% band) ΔF1 1.98 13.78 4.06 13.3
ΔF2 3.82 12.72 3.76 12.4
ΔPTie 0.0027 13.46 3.41 9.69
MOS ΔF1 × 10−4 5.15 91 31 105
ΔF2 × 10−4 4.6 87 20 84
ΔPTie × 10−4 4.99 6.8 11 14

Table 4. Performance criteria for two area multi-source power from Figures 3 to 4 that the superb damping perfor-
system with parallel AC/DC links. mances in term of settling time, overshoot and under
Optimal shoot in Δf1 , Δf2 and ΔPTie are significantly better than
Objective function & Control Proposed IWO % Improvement by
Parameters [19] PID Controller Proposed approach those of optimal controller [19] in both the cases.
ITAE 3.5764 0.1968 94.49
ISE 0.0454 9.9090 × 10−5 99.78
ITSE 0.1076 1.5194 × 10−4 99.86 4.1.2. Case-B: step load change in area-2
IAE 0.7989 0.1968 95.05
Settling times Δf1 13.78 85.63 85.63 To test the effectiveness of the proposed controller with
(0.002% Δf2 12.72 69.97 69.97 the change in location of SLP, a 1% SLP in area-2 is
band) ΔPTie 13.46 99.98 99.98
considered. The dynamic responses of area 1 of the system

Figure 3. Frequency deviation of area-1 for 1% SLP in area-1.


196 S. MISHRA ET AL.

Figure 4. Tie-line power deviation for 1% SLP in area-1.

with AC tie only and with AC/DC link are shown in 4.2. Sensitivity analysis
Figures 5 and 6. It is clear from Figures 5 to 6 that the
Sensitivity analysis is performed to study the robustness the
designed controllers are equally effective when the loca-
system to changes in the operating conditions and system
tion of disturbances change. In this case also improved
parameters in the range of  25% without changing the
dynamic responses are obtained with proposed approach
optimum values of IWO tuned PID controller gains. The
compared to the optimal control method [19].
various performance indexes (ITAE, ISE, ITSE, settling
time, maximum overshoots and MDRs) under normal
4.1.3. Case C: step load change in both areas and parameter variation cases for the system with AC/DC
The performance of proposed controllers is also ver- link for a 1% SLP in area-1 are reported in Table 5. It can be
ified under simultaneous disturbances in both areas. seen from Table 5 that settling times, maximum over-
The he dynamic response of area 2 and tie line power shoots, MDRs, ITAE, ISE, and ITSE values vary within
for SLP of 2 % in area-1 and 1 % in area-2 both acceptable ranges and are nearby equal to the respective
occurring at t = 0 s are shown in Figures 7 and 8. It values obtained with nominal system parameter. Hence, it
is evident from Figures 7 to 8 that in this case also can be concluded that the proposed controllers are consis-
considerable improvements in dynamic performances tent and perform satisfactory operation when system para-
are obtained with proposed approach compared to meters changes in the range ±25%. As an example, the
optimal control approach [19]. frequency deviation of area-1 under varied loading

Figure 5. Frequency deviation of area-1 for 1% SLP in area-2.


INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION 197

Figure 6. Tie-line power deviation for 1% SLP in area-2.

Figure 7. Frequency deviation of area-2 for 1% SLP in area-1 and 2% SLP in area-2.

Figure 8. Tie-line power deviation for 1% SLP in area-1 and 2% SLP in area-2.

condition is shown in Figure 9. It can be observed from For completeness, SLP in area-1 is increased from
Figure 9 that the effect of the variation of operating loading 1% to 4% in a step of 1% and the dynamic response of
conditions on the system responses is unchanged. area 1 for the system with AC/DC line is shown in
198 S. MISHRA ET AL.

Table 5. Sensitivity analysis of power system with parallel AC/DC links.


Performance index Settling time Ts (s) MOS
−5 −4 −4
Parameter variation % change ITAE ISE (×10 ) ITSE (×10 ) IAE Δf1 Δf2 ΔPTie Δf1 (×10 ) Δf2 (×10−4) MDR
Loading Condition. +25 0.1901 9.88 1.519 0.0395 1.98 3.8 .0002 5.15 4.60 0.3586
+50 0.1902 9.86 1.52 0.0395 1.99 3.8 0.002 5.14 4.60 0.3596
−25 0.1899 9.93 1.519 0.0395 1.98 3.8 0.002 5.16 4.60 0.3567
−50 0.1898 9.95 1.519 0.0395 1.98 3.8 0.002 5.17 4.60 0.3457
Tsg +25 0.1903 10.0 1.52 0.0396 1.97 3.81 .0002 5.20 4.63 0.3563
+50 0.1906 10.1 1.53 0.0397 1.94 3.81 0.002 5.24 4.66 0.3563
−25 0.1897 9.79 1.51 0.0394 1.99 3.8 0.002 5.11 4.57 0.0294
−50 0.1895 9.69 1.50 0.0393 1.92 3.79 0.002 5.07 4.54 0.365
Tr +25 0.2204 10.14 1.60 0.0413 2.04 3.91 .0002 4.48 4.34 0.3577
+50 01326 10.30 1.67 0.0426 2.07 3.97 0.002 3.92 4.07 0.3577
−25 0.1607 9.56 1.39 0.0372 1.91 3.64 0.002 5.94 4.77 0.3576
−50 0.1326 8.97 1.21 0.0341 1.81 3.38 0.002 6.71 4.63 0.3574
Tt +25 0.1913 10.23 1.55 0.0398 1.95 3.82 .0002 5.31 4.71 0.3664
+50 0.1929 10.60 1.58 0.0402 1.91 3.84 0.002 5.51 4.85 0.0217
−25 0.1888 9.56 1.49 0.0398 2.01 3.78 0.002 4.98 4.48 0.1438
−50 0.1878 9.21 1.47 0.0388 2.01 3.76 0.002 4.82 4.37 0.3512
Trh +25 0.1952 9.94 1.56 0.04 2.02 3.86 .0002 5.11 4.60 0.0556
+50 0.1978 9.97 1.58 0.0403 2.05 3.9 0.002 5.06 4.59 0.3598
−25 0.18 9.88 1.46 0.0386 1.9 3.71 0.002 5.19 4.56 0.3547
−50 0.1643 9.98 1.34 0.0368 1.72 3.5 0.002 5.1 4.36 0.0495
Tgh +25 0.1902 9.902 1.52 0.0395 1.99 3.8 .0002 5.18 4.62 0.3668
+50 0.1903 9.89 1.53 0.0396 1.99 3.82 0.002 5.2 4.63 0.3715
−25 0.1899 9.92 1.51 0.0394 1.99 3.8 0.002 5.14 4.60 0.3432
−50 0.1897 9.91 1.51 0.0394 2.03 3.8 0.002 5.12 4.59 0.3254
Trs +25 0.1849 9.88 1.4 7 0.0388 1.93 3.74 .0002 5.02 4.47 0.3550
+50 0.1801 9.88 1.42 0.0382 1.86 3.69 0.002 4.90 4.34 0.3518
−25 01954 9.95 1.57 0.0402 2.03 3.87 0.002 5.30 4.8 0.3599
−50 0.2009 10.02 1.63 0.0408 2.06 3.92 0.002 5.44 4.88 0.3615
Tw +25 0.1908 10.09 1.54 0.0397 1.97 3.82 .0002 5.27 4.67 0.3643
+50 0.1918 10.27 1.56 0.0400 1.97 3.83 0.002 5.41 4.74 0.3686
−25 0.1894 9.69 1.50 0.0393 2.01 3.79 0.002 5.06 4.55 0.3469
−50 0.1890 9.44 1.49 0.0391 2.04 3.78 0.002 5.00 4.49 0.3306
Tcd +25 0.1901 9.96 1.53 0.0396 1.99 3.82 .0002 5.29 4.66 0.2276
+50 0.1902 10.03 1.55 0.0398 2.0 3.84 0.002 5.44 4.71 0.3550
−25 0.1900 9.85 1.51 0.0394 1.97 3.78 0.002 5.04 4.56 0.3575
−50 0.1901 9.79 1.50 0.0392 1.96 3.76 0.002 5.00 4.51 0.2171
T12 +25 0.1808 9.63 1.41 0.0383 1.86 3.64 .0002 3.26 4.35 0.3457
+50 0.1747 9.42 1.34 0.0375 1.78 3.5 0.002 2.00 4.12 0.3221
−25 0.2052 10.30 1.70 0.0411 2.16 3.84 0.002 7.58 4.77 0.3698
−50 0.2326 10.86 1.97 0.0433 2.4 3.89 0.002 0.001 4.57 0.3822

Figure 9. Frequency deviation of area-1 with varied loading condition.

Figure 10. It is clear from Figure 10 that satisfactory reveals an intelligent control strategy under wide varia-
performance is obtained for different value of SLP. tion in the system loading conditions, system para-
Hence, it is evident that, the proposed control scheme meters and size and location of disturbance.
INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION 199

Figure 10. Frequency deviation of area-1 with different SLP in area-1.

4.3. Extension to three-area hydro thermal power unit are considered. Once again the same procedure is
system with generation rate constraints adopted for tuning the controller parameters for the
above system. The final controller parameters obtained
To demonstrate the capability of the proposed algorithm,
for each area using proposed IWO algorithm employing
the work is further applied to the three area system with
objective function given in Equation (1) are as follows:
nonlinearity and multiple tie-lines [11,30,31] as shown in
Figure 11. The system considers two thermal and one Area-1: KP1 = 0.1149, KI1 = 0.0648, KD1 = 0.0648
hydro unit with identical controller for each area. The Area-2: KP2 = −0.0030, KI2 = 0.1674, KD2 = −0.0545
rated system parameters are provided in Appendix B. The Area-3: KP3 = 0.0002, KI3 = 0.0584, KD3 = 0.0921
GRC of 3%/min for thermal units and 270%/min for Exactly, at t = 0 sec, an SLP of 1% is applied simulta-
rising and 360%/min for lowering generation for hydro neously in all the areas and the frequency and tie line

Figure 11. Transfer function model of three-area hydro-thermal system with generation rate constraint.
200 S. MISHRA ET AL.

power response of area 2 are depicted in Figures 12 and with appropriate weights is proposed to improve the
13, respectively. In order to show the superiority of system performance in terms of settling time and peak
proposed method, the simulation results are being overshoots. Simulation findings show that the pro-
compared with ANFIS-based controller [11], hBFOA- posed IWO optimized PID controller provides signif-
PSO [18] based controller and conventional integral icantly improved system performance compared to
controller [30] as shown in Figures 12 and 13. The recently published optimal output feedback controller
overall performance of the considered system is signif- for similar power system. Further, sensitivity analysis
icantly improved with the proposed approach com- is performed by changing the operating loading con-
pared to some recently published research work. ditions and system parameters in the range of  25%
and it is found that the designed controllers are robust
and also perform satisfactorily under wide changes in
5. Conclusions the system loading condition, system parameters and
This paper reports the design and performance ana- size and location of disturbance. Finally, the proposed
lysis of IWO-based PID controller applied to AGC of approach is extended to a three area hydro thermal
interconnected power systems. Initially, a two area system with GRC. It is observed that the proposed
multi-source power system without and with HVDC approach reveals superior performance compared to
link has been considered to demonstrate the proposed some recently proposed controllers such as ANFIS-
approach. The objective function is modified with an based controller, hBFOA-PSO tuned controller and
integral time absolute error (ITAE) criterion and conventional integral controller for the identical
damping ratio of evaluated dominant eigenvalues power system.

-0.05
Δ F2 (Hz)

-0.1

Integral controller [31]


-0.15
ANFIS controller[12]
hBFOA-PSO optimized controller[32]
-0.2 Proposed IWO optimized controller

0 10 20 30 40 50 60 70 80
Time (sec)

Figure 12. Frequency deviation in area 2 for 1% SLPs in all areas.

-3
x 10

0
Δ P T ie2 (pu)

-5

Integral controller [31]


-10 ANFIS controller [12]
hBFOA-PSO optimized controller [32 ]
Proposed IWO optimized controller
-15
0 10 20 30 40 50 60 70 80 90 100
Time (sec)

Figure 13. Tie-line power deviation in area 2 for 1% SLPs in all areas.
INTERNATIONAL JOURNAL OF MODELLING AND SIMULATION 201

Disclosure statement [2] Cohn N. Some aspects of tie-line bias control on


interconnected power systems. Am Inst Electr Eng
No potential conflict of interest was reported by the authors. Trans. 1957;75:1415–1436.
[3] Elgerd OI, Fosha CE. Optimum megawatt-frequency
control of multi-area electric energy systems. IEEE
Notes on contributors Trans Power Apparatus Syst. 1970;89(4):556–563.
[4] Ibraheem KP, Kothari DP. Recent philosophies of
Somanath Mishra received B.Tech degree in electrical engineer- automatic generation control strategies in power
ing from Seemanta Engineering College, Mayurbhanj, Odisha, systems. IEEE Trans Power Syst. 2005;20(1):346–357.
India and M.Tech degree in power system engineering from C. [5] Rubaai A, Udo V. Self-tuning LFC: multilevel adaptive
V. Raman College of Engineering, Bhubaneswar, India. He is approach. Proc Inst Electr Eng Gen Trans Distrib.
currently pursuing his Ph.D degree in VSSUT Burla, Odisha, 1994;141(4):285–290.
India. His current research interests include power generation, [6] Chang CS, Fu W. Area load frequency control using
load frequency control of multi area power systems with non- fuzzy gain scheduling of PI controllers. Electr Power
conventional energy sources using intelligent techniques. Syst Res. 1997;42:145–152.
[7] Cam E, Kocaarslan I. Load frequency control in two
A. K. Barisal received his B.E in Electrical Engineering from
area power system using fuzzy logic controller. Energy
UCE Burla (now VSSUT Burla), his ME (Eng.) in Power
Convers Manage. 2005;46(2):233–243.
systems from BESU, Howrah (Now IIEST) and his PhD
[8] Yesil E, Guzelkaya M, Eksin I. Sef-tuning fuzzy PID
(Eng.) from Jadavpur University, Kolkata. He has published
type load and frequency controller. Energy Convers
over 100 articles in different journals and conferences. His
Manage. 2004;45:377–390.
research interests include economic load dispatch,
[9] Ahamed TPI, Rao PSN, Sastry PS. A reinforcement
Hydrothermal Scheduling and soft computing applications to
learning approach to automatic generation control.
power system operation and control. He is currently working
Electr Power Syst Res. 2002;63:9–26.
as a Professor in the Department of Electrical Engineering,
[10] Demiroren A, Sengor NS, Zeynelgil HL. Automatic
College of Engineering & Technology, Bhubaneswar, India.
generation control by using ANN technique. Electr
B. Chitti Babu received Ph.D. degree in Electrical Power Compon Syst. 2001;29(10):883–896.
Engineering from the National Institute of Technology [11] Khuntia SR, Panda S. Simulation study for automatic
Rourkela (NITR), Rourkela, India, in 2012. He was an generation control of a multi-area power system by
Assistant Professor in the Department of Electrical ANFIS approach. Appl Soft Comput. 2012;12:333–341.
Engineering, NITR, from 2007 to 2013. He had Post- [12] Chang CS, Fu W, Wen F. Load frequency control using
Doctoral research appointments with the Wroclaw genetic-algorithm based fuzzy gain scheduling of PI
University of Science and Technology, Wroclaw, Poland, controllers. Electr Power Syst Res. 1998;26(1):39–52.
from December 2013 to June 2014, and with the VSB- [13] Juang C-F, Lu C-F Power system load frequency control
Technical University of Ostrava, Ostrava, Czech Republic, by evolutionary fuzzy PI controller. In: Proceedings of
from September 2014 to September 2015. Both of these IEEE international conference on fuzzy systems.
appointments were sponsored by the European Budapest, Hungary; 2004: p. 715–719.
Commission, UK. He was an Assistant Professor in faculty [14] Karnavas YL, Papadopulos DP. AGC for autonomous
of engineering, University of Nottingham (U.K) Malaysia power system using combined intelligent techniques.
Campus, Malaysia from Sep 2016- June 2018. Since June Electr Power Syst Res. 2002;62(3):225–239.
2018, he serves as an Assistant Professor in Indian Institute [15] Ghosal SP. Optimization of PID gains by particle
of Information Technology, Design and Manufacturing, swarm optimization in fuzzy based automatic genera-
Kancheepuram, Chennai, India He serves as an editorial tion control. Electr Power Syst Res. 2004;72:203–212.
board member of many peer reviewed journals, [16] Chaturvedi DK, Satsangi PS, Kalra PK. Load frequency
particularly IET Renewable Power Generation, Intr. Trans. control: a generalized neural network approach. Electr
On Electrical Energy Systems, IEEE Access. Energy Sources Power Energy Syst. 1999;21:405–415.
(Part-A), Energy & Environment, AUTOMATIKA, Inter. [17] Ibraheem KP. Current status of the Indian power
Journal of Modelling & Simulation. His current research system and dynamic performance enhancement of
interests include power electronics applications in smart dis- hydro-power systems with asynchronous tie-lines.
tribution grids containing renewable energy sources. Electr Power Compon Syst. 2003;31(7):605–626.
[18] Ibraheem KP, Khatoon S. Effect of parameter uncer-
tainties on dynamic performance of an interconnected
power system incorporating AC/DC links. Int J Power
ORCID Energy Syst. 2005;25(3):198–210.
A. K. Barisal http://orcid.org/0000-0002-7991-8214 [19] Ibraheem N, Bhatti TS. AGC of two area power system
interconnected by AC/DC links with diverse sources in
each area. Int J Electr Power Energy Syst. 2014;55:
297–304.
References [20] Parmar KPS, Majhi S, Kothari DP. Load frequency
control of a realistic power system with multi-source
[1] Kundur P. Power system stability and control. power generation. Int J Electr Power Energy Syst.
New York (NY): TMH; 1994. 2012;42:426–433.
202 S. MISHRA ET AL.

[21] Rout UK, Sahu RK, Panda S. Design and analysis of and nonlinear interconnected power systems. Appl
differential evolution algorithm based automatic gen- Soft Comput. 2013;13(12):4718–4730.
eration control for interconnected power system. Ain [32] Menghal PM, Jaya Laxmi A. Modelling, simulation
Shams Eng J. 2013;4(3):409–421. & analysis of induction motor using artificial intel-
[22] Mohanty B, Panda S, Hota PK. Controller parameters ligent controller. Int J Model Simulat. 2016;36(4):
tuning of differential evolution algorithm and its appli- 120–135.
cation to load frequency control of multi-source power [33] Mohanty B. Performance analysis of moth flame opti-
System. Int J Electr Power Energy Syst. 2014;54:77–85. mization algorithm for AGC system. Int J Model
[23] Gozde H, Taplamacioglu MC, Kocaarslan I. Comparative Simulat. 2018. DOI:10.1080/02286203.1476799
performance analysis of Artificial Bee Colony algorithm in [34] Nguyen NS, Nguyen DK. Parameter estimation of
automatic generation control for interconnected reheat Pendubot model using modified differential evolution
thermal power system. Int J Electr Power Energy Syst. algorithm. Int J Model Simulat. 2018. DOI:10.1080/
2012;42:167–178. 02286203.2018.1525938
[24] Mehrabian AR, Lucas C. A novel numerical optimiza-
tion algorithm inspired from weed colonization,
Elsevier. Ecol Inf. 2006;1(4):355–366.
Appendix A. Nominal parameter of the two
[25] Sepehri HR, Lucas C A recommender system based on
invasive weed optimization algorithm. In: IEEE congress area multi source power system [19]
on evolutionary computation. Singapore, CEC; 2007.
f = 60 Hz; B1 = B2 = 0.425 pu MW/Hz;PR = 2000
[26] Karimkashi S, Kishk Ahmed A. Invasive weed optimi-
MW (rating),PL ¼ 1840 MW (nominal loading);
zation and its features in electromagnetics. IEEE Trans
R1 ¼ R2 ¼ R3 ¼ 2.4 Hz/pu MW; Tsg ¼ 0.08 s; Tr ¼ 10 s;
Antennas Propag. 2010;58(4):1269–1278.
Kr ¼ 0.3; Tt ¼ 0.3 s; KT ¼ 0.6; KH = 0.25;
[27] Ahmadi M, Mojallali H, Izadi-Zamanabadi R. State
KG = 0.15;Tgh ¼ 0.2 s; Trh ¼ 28.75 s; Trs ¼ 5 s; TW ¼ 1 s;
estimation of nonlinear stochastic systems using
a novel meta-heuristic particle filter. Swarm Evol b ¼ 0.05; c ¼ 1 s;X ¼ 0.6 s; Y ¼ 1 s; Tcr ¼ 0.3 s; Tfc ¼ 0.23s;
Comput. 2012;4(6):44–53. Tcd ¼ 0.2 s; Tps ¼ 20 s; Kps ¼ 120 Hz/pu MW;Tdc ¼ 0.2 s;
[28] Saravanan B, Vasudevan ER, Kothari DP. Unit commit- Kdc ¼ 1; T12 ¼ 0.0433 pu; a12 ¼ -1.
ment problem solution using invasive weed optimization
algorithm. Int J Electr Power Energy Syst. 2014;55:21–28.
[29] Barisal AK, Prusty RC. Large scale economic dispatch Appendix B. Nominal parameter of the three
of power systems using oppositional invasive weed area hydro thermal power system [11,30,31]
optimization. Appl Soft Comput. 2015;29:122–137.
[30] Nanda J, Parida M, Kalam A Automatic generation control f = 60 Hz; B1 = B2 = B3 = 0.425 pu MW/Hz; R1 = R2 = R3 = 2.4
of a multi-area power system with conventional integral Hz/pu MW; TG1 = TG2 = 0.08 s; Tr1 = Tr2 = 10.0 s;
controllers. Proc. AUPEC 2006, TS13 (2)—Load and TT1 = TT2 = 0.3 s; TW = 1.0 s; TR = 5 s; Nominal power
Frequency Control. Melbourne, Australia; 2006. system parameters: KPS1 = KPS2 = KPS3 = 120 Hz/p.u. MW;
[31] Panda S, Mohanty B, Hota PK. Hybrid BFOA-PSO TPS1 = TPS2 = TPS3 = 20 s; T12 = T23 = T31 = 0.086 pu;
algorithm for automatic generation control of linear a12 = a23 = a31 = −1.

You might also like