2A

(2) Fan Unit (RCON-FU)


No. Part Name Model Number Remarks 5. How to read the model code
1 Fan Unit RCON-FU - When ordered individually (1) 24V Driver Unit
(3) Simple Absolute Unit (RCON-ABU-P/A) RCON - PCF - 1
No. Part Name Model Number Remarks
-PC/PCF/AC/DC, -FU 1 Simple Absolute Unit
Refer to “How to read the model
plate”, “How to read the model code”
- P Driver Type/A Driver Type
<Series> < Number of Axes >
1: One-Axis Type
2: Two-Axis Type

-ABU-A/P, -EXT
<Type>
Accessories AC : A Driver Unit Note There should be only one-axis type for
2 Simple Absolute Battery AB-7 1 DC : D Driver Unit P Driver Unit (high-thrust type)
PC : P Driver Unit
24V Driver Unit, Fan Unit, 3 Motor/encoder Cable
4 First Step Guide
CB-ADPC-MPA005
ME0383
1
1 This Manual
PCF : P Driver Unit (High-Thrust Type)

Simple Absolute Unit, SCON Extension Unit 5 Safety Guide M0194 1


(2) Fan Unit (When ordered individually)

First Step Guide Second Edition (4) SCON Extension Unit (RCON-EXT)
No. Part Name Model Number Remarks
RCON - FU
Refer to “How to read the model <Series> <Type>
Thank you for purchasing our product. 1 SCON Extension Unit -
plate”, “How to read the model code” FU: Fan Unit
Make sure to read the Safety Guide and detailed Instruction Manual (DVD) included with the product Accessories
in addition to this First Step Guide to ensure correct use. Note Fan unit can be ordered with a model code for a gateway unit as an accessory of the gateway unit.
2 Terminal Connector RCON-EXT-TR 1 Terminal Resistance
This Instruction Manual is original. (3) Simple Absolute Unit
3 First Step Guide ME0383 1 This Manual
Warning: Operation of this equipment requires detailed installation and operation instructions 4 Safety Guide M0194 1 RCON - ABU - A
which are provided on the DVD Manual included in the box this device was packaged
2. Teaching Tool (Please purchase separately)
in. It should be retained with this device at all times. <Series> < Applicable Driver >
A teaching tool such as PC software is necessary when performing the setup for position setting, parameter
A copy of the DVD Manual can be requested by contacting your nearest IAI Sales <Type> A: For A Driver Unit
setting, etc. that can only be done on the teaching tool. Please prepare either of the following teaching tools. P: For P Driver Unit
Office listed at the back cover of the Instruction Manual or on the First Step Guide. ABU: Simple Absolute Unit
No. Part Name Model
• Using or copying all or part of this Instruction Manual without permission is prohibited. 1 PC Software (Includes USB Exchange Adapter + USB Cable + Peripheral Communication Cable) RCM-101-USB (4) SCON Extension Unit
• The company names, names of products and trademarks of each company shown in the sentences 2 Touch Panel Teaching Pendant TB-02 (Standard / Dead Man’s Switch Mounted) TB-02/TB-02D
3 Touch Panel Teaching Pendant TB-03 TB-03 RCON - EXT
are registered trademarks.
3. Instruction manuals related to this product, which are contained in the instruction manual (DVD). <Series> <Type>
R-unit is constructed with Gateway Unit (RCON-GW/GWG, RSEL-G), Terminal Unit (RCON-GW-TR), 24V No. Name Manual No. EXT : SCON Extension Unit
Driver Unit (RCON- PC/PCF/AC/DC), Simple Absolute Unit (RCON-ABU), 200V Power Supply Unit 1 RCON System Instruction Manual ME0384
(RCON-PS2-3), 200V Driver Unit (RCON-SC), Fan Unit (RCON-FU/FUH), PIO Unit (RCON-NP/PN),
2 SCON-CB/CGB/LC/LCG Controller Instruction Manual ME0340
PIO/SIO/SCON Extension Unit (RCON-EXT-NP/PN), SCON Extension Unit (RCON-EXT) and SCON
Controller (SCON-CB-*-RC) to connect to the SCON Extension Unit.
3 PC Software RCM-101-MW/RCM-101-USB Instruction Manual
4 Touch Panel Teaching Pendant TB-02 Applicable for Position Controller Instruction Manual
ME0155
ME0355
Basic Specifications
In this guide, describes about the 24V Driver Unit, Simple Absolute Unit, Fan Unit and SCON Extension Unit.
For instruction of other units, refer to the first step guide and instruction manual (DVD) of each unit. 5 Touch Panel Teaching Pendant TB-03 Wired Link Applicable for Position Controller Instruction Manual ME0376
1. Specifications of Power Supply
4. How to read the model plate Item Specification
Color P Driver P Driver (high thrust) A Driver D Driver
Label Green Green (Light) Blue Brown (1) 24V Driver Unit Power Input Voltage Range 24V DC ±10%
Supply Current Described in “Current Amperage”
Model Plate (small)
Model Plate (Large) Power Source Frequency Range -
Fan Unit Refer to “External Dimensions”
It is attached on the
Current Amperage Described in “Current Amperage”
bottom of the panel
for the attached position. front face. In-Rush Current Described in “Current Amperage”
Instantaneous Power Outage Endurance By 24V power supply
Model Protection Function against Electric Shock Class Ⅲ
Model
Serial Number Serial 2. Specifications of Control Part
Gateway Unit Number Item Specification
Terminal Unit Number of Controlled Axes RCON System 1 to 16 axes, RSEL System 1 to 8 axes
Position data and parameters are saved in the nonvolatile memory.
Data Memory System
(2) Fan Unit (There is no limitation in number of writing)
SCON SIO Interface (T. P. Connector) Communication System: RS485, Baud Rate: 9.6/19.2/38.4/57.6/115.2/230.4kbps
Model Serial Number SIO Interface (USB Connector) Communication System: USB, Baud Rate: 12Mbps
Extension
Unit PIO Interface None
Conformed Extension I/O Interface CC-Link, CC-Link IE Field, DeviceNet, EtherCAT, EtherNet /IP, PROFIBUS-DP and
(Field Network Interface) PROFINET IO
(3) Simple Absolute Unit Pulse Train Type Unavailable to Control
Model Plate (small) Brake Output Voltage 24V DC ±10%
Model Plate (Large) Connectable Brake Power Supply 11W Max.
Refer to “External Dimensions” It is attached on the
bottom of the panel Calendar Feature Maintained Duration: Approx. 10 days, Charge Time: Approx. 100 hours
for the attached position.
front face. Applied Safety Category B (Safety category applicable type is capable to achieve 4 with external circuit)
Driver Source Cutoff System Drive source cutoff with semiconductor (Power MOSFET)
Model Stop Input Break Contact Input
P Driver Unit Serial Number Serial Stop Action Turning servo OFF + Drive source cutoff
Model Code
Number Enable Input None
(Partially)
T. P. Enable Input Available
A Driver Unit
Enable Action Turning servo OFF
Protective functions Overcurrent, temperature error, encoder line breakage and overload
Simple Absolute Unit Simple Absolute Unit
D Driver Unit (4) SCON Extension Unit Preventive / Predictive Maintenance Feature Electrolytic capacitor capacity dropdown and Fan revolution dropdown
for P Driver Unit for A Driver Unit Model Plate (small) LED Display Described in “Troubleshooting”
Model Plate (Large) It is attached on the Brake Compulsory Release Feature Brake release switch equipped on driver unit
Product Check Refer to “External Dimensions” bottom of the panel
front face.
Jog Jog switch equipped on driver unit
for the attached position. Oversea Certifications CE Marking, UL Standard
This product is comprised of the following parts if it is of standard configuration. 3. Environmental Specifications
If you find any fault in the contained model or any missing parts, contact us or our distributor. Model
Item Specification
1. Parts Serial Number Serial Environment of Use Pollution Degree 2
Model Code
(1) 24V Driver Unit (RCON-PC/PCF/AC/DC) (Partially) Number Surrounding Air Temperature With Fan Unit: 0 to 55°C, With No Fan Unit: 0 to 40°C, Simple Absolute Unit: 0 to 40°C
No. Part Name Model Number Remarks Surrounding Humidity 85% RH or less (non-condensing)

Environment
Refer to “How to read the model Two-Axis Type/One-Axis Type Peripheral Ambience of Use [Refer to section in Installation Environment]
1 RCON P Driver Unit -
plate”, “How to read the model code” /High-Thrust Type Surrounding Storage Temperature -20 to 70°C
Refer to “How to read the model Frequency 10 to 57Hz/Swing width: 0.075mm
2 RCON A Driver Unit - Two-Axis Type / One-Axis
plate”, “How to read the model code” Mark Explanation of Mark Vibration Endurance Frequency 57 to 150Hz/Acceleration: 9.8m/s2
Refer to “How to read the model XYZ Each direction Sweep time: 10min. Number of sweep: 10times
3 RCON D Driver Unit - Two-Axis Type / One-Axis
plate”, “How to read the model code” Protection Class IP20
Use IAI specified cables only.
Accessories Altitude 1000m
Drive Source Cutoff DFMC1.5/2-STF-3.5 Recommended Cable Size Cooling Method Natural air-cooling and Forced air cooling with fan unit
4 1 Dielectric Withstanding Voltage Between power supply terminal and FG 500V DC 10MΩ or more
Connector (Manufactured by PHOENIX CONTACT) 0.5 to 1.25mm2 (AWG20 to 16) Do not touch product when power is ON. Risk of burn.
5 First Step Guide ME0383 1 This Manual
6 Safety Guide M0194 1
2. Fan Unit
Current Amperage Restrictions in Unit Connection Item Specification
External Dimensions 34.2W × 49H × 12.5D [mm]
The current amperage should be divided into the control power capacity and motor power capacity. (1) Number of 24V Driver Units to Connect Mass Approx. 15g
Each power supply should be input from the control power supply connector and the motor power supply The maximum number of control axes to be connected should be 16 axes in the RCON system and 8
connector on the gateway unit. However, it is necessary that the 0V of the control power supply and the axes in the RSEL system.
motor power supply are in common. From the structural perspective of the unit, it can accept connection without any upper limit, but make it
accept the number of axes described above of driver units at the maximum.
The necessary capacity of the current amperage should be figured out by [Total of control power capacity of
Have two gateway units or more in the construction when it is necessary to control number of axes
used units] + [Total of motor power capacity of used actuators].
described above or more of actuators.
It is necessary that the rated current of 24V power supply satisfies the rated current of the motor power
capacity and the peak current satisfies the maximum current of the motor power capacity. However, when
several axes get connected, unless all the actuators operates at the same time, the rated current and (2) Current Restrictions
Shown below is the restricting values of current for selecting calculation. 3. Simple Absolute Unit
maximum current would not flow at the same time, thus the calculation should not be simply the total of all Item Specification
the axes.
Item Restricting Value of Current for Selecting Calculation External Dimensions 22.6W × 115H × 95D [mm]
The specifications related to the power capacities should be as shown below. Mass Approx. 270g (included battery weight: 183g)
[Control Power Supply] Control Power Supply (CP) 9.0A or less
Item Specification Motor Power Supply (MP) 37.5A or less
Power Supply Voltage 24V DC ±10%
0.8A (Ethernet option: Not equipped)
Gateway unit RCON Gateway Unit Check that the calculation result of the control power supply and motor power supply of each unit based
1.0A (Ethernet option: Equipped)
(terminal unit included)
SEL Unit 1.2A
on the construction of RCON/RSEL system does not exceed the restricting values of current for selecting
calculation.
Brake: Not equipped 0.2A Also, the gateway units should not be included for the calculation. Model Code
24V Driver unit Brake: Equipped (one-axis type) 0.4A Plate (Large)
Adhered
Brake: Equipped (two-axis type) 0.6A Shown below is some examples for calculation. Position

Control Power Capacity 200V Driver unit Brake: Not equipped 0.2A
(for one unit) (200V power supply [Control Power Supply] * The gateway units should not be included for the calculation.
unit included) Brake: Equipped 0.5A
Actuator × 16 axes, All axes equipped with brake (2 axes/unit)
SCON Extension Unit 0.1A Example 1
Driver unit (with brake) 0.6A × 8 = 4.8A ⇒ OK
Extension unit PIO/SIO/SCON Extension Unit 0.3A
PIO Unit 0.2A Actuator × 16 axes, All axes equipped with brake (1 axis/unit)
Example 2
Simple absolute unit (in common for all types) 0.2A Driver unit (with brake) 0.4A × 16 = 6.4A ⇒ OK
EC Connection Unit 0.1A Actuator × 16 axes, All axes equipped with brake (2 axes/unit), All axes simple absolute type
[24V Motor Power Supply] Example 3
Driver unit (with brake) 0.6A × 8 + Simple absolute 0.2A × 16 = 8.0A ⇒ OK
Actuator / Driver unit Max. current
Rated Actuator × 16 axes, All axes equipped with brake (1 axis/unit), All axes simple absolute type
Item When Example 4 4. SCON Extension Unit
Series Motor type Current energy-saving Driver unit (with brake) 0.4A × 16 + Simple absolute 0.2A × 16 = 9.6A ⇒ NG
is set Item Specification
20P/20SP/28P 0.8A - - External Dimensions 22.6W × 115H × 95D [mm]
RCP2
(Note 1) Without PowerCON
[Motor Power Supply] Mass Approx. 99g
RCP3 28P 1.9A - -
Stepper motor /35P/42P/56P RCON-PC (with PowerCON) × 16 axes
/ RCON-PC RCP4
Example 5
28P/35P/42P Without PowerCON 1.9A - - RCON-PC (with PowerCON) rated current 2.3A × 16 axes = 36.8A ⇒ OK
RCP5
/42SP/56P With PowerCON 2.3A - 3.9A
RCP6 When RCON-PCF × 16 axes or 6 axes
RCP2 Example 6
Stepper motor RCP4 RCON-PCF rated current 5.7A × 16 axes = 91.2A ⇒ NG
56SP/60P/86P Without PowerCON 5.7A - - RCON-PCF rated current 5.7A × 6 axes = 34.2A ⇒ OK
/ RCON-PCF RCP5
RCP6 RCON-PC (with no PowerCON), RCON-AC, RCON-DC Model Code
Plate (Large)
5W
Standard
1.0A - 3.3A Example 7 Adhered
Motor power capacity / Hi-accel./decel. Rated current for all the units is low and it would not exceed current limit with 16 axes ⇒ OK Position
(1 axis per actuator) 10W 1.3A 2.5A 4.4A
RCA RCON-PCF × 3 axes, RCON-PC (with PowerCON) × 7 axes, RCON-AC × 3 axes
RCA2 20W Standard 1.3A 2.5A 4.4A Example 8
/ Hi-accel./decel. 5.7 × 3 + 2.3 × 7 + 1.3 × 3 = 37.1A ⇒ OK
AC servo motor 20W (20S) / Energy-saving 1.7A 3.4A 5.1A
/ RCON-AC
30W 1.3A 2.2A 4.0A Note When the operation pattern is to have all the axes operate acceleration and deceleration only and
2W 0.8A - 4.6A the operation duty is 100%, it is necessary that the calculation is done with the maximum current
RCL 5W
Standard
1.0A - 6.4A for the motor power supply.
/ Hi-accel./decel.
10W 1.3A - 6.4A
DC brush-less
motor RCD 3W Standard 0.7A - 1.5A External Dimensions
/ RCON-DC
8.3A 1. 24V Driver Unit (in common for P Driver Unit / A Driver Unit / D Driver Unit)
Pulse motor / RCON-PC
(with in-rush current limiting circuit) Item Specification
Pulse motor / RCON-PCF
10.0A External Dimensions 22.6W × 115H × 95D [mm] 5. When Units Linked
In-Rush Current (with in-rush current limiting circuit) Item Specification
Mass Approx. 180g
(Approx. 5ms) 10.0A
Servo AC motor / RCON-AC External Dimensions (42.6 + 22.6 × N) W × 115H × 95D [mm] N: Total number of driver units and extension units
(with in-rush current limiting circuit)
Mass Approx. (206 + 180 × N1 + 99 × N2) g N1: Number of driver units, N2: Number of extensions units
10.0A
Brushless DC motor / RCON-DC
(with in-rush current limiting circuit)
PowerCON
5.0W
: Not equipped
RCON-PC
PowerCON
8.0W
: Not equipped
Model Code
PowerCON Plate (Large)
Heat Generation RCON-PCF 19.2W
: Equipped Adhered
Standard Position
RCON-AC / High-acceleration 4.5W
/deceleration
RCON-DC Standard 3.0W
Note 1 Applicable Models: RCP2-RA3, RCP2-RGD3 120
If there is no fan unit equipped, operation can be performed
without derating in the temperature range between 0 and 100
Operation Duty [%]

40°C, but it is necessary to reduce the operation duty by 20%


80
in every 5°C in the temperature range between 40 and 55°C.
In case of fan unit equipped, operation can be performed 60
with no derating up to 55°C. With Fan
40
With No Fan

20
N: Total number of driver units and extension units
0
0 10 20 30 40 50 60
Temperature Environment of Use [°C]
Linking Units Installation and Noise Elimination 24V Driver Unit Connection Cable List
Actuator Connection cable (Note 2)
Conversion Wiring
RCON/RSEL Systems are capable to construct a system with the gateway allocated at the left end as the For installation and noise elimination, refer to the first step guide for RCON Gateway Unit or RSEL Gateway No. (-RB: Robot cable )
Series Target type unit diagram
Unit. [Each actuator connection cable]
interface for the field network connection and freely combine multiple driver units and extension units. There
is an order of allocation for each unit. RCP6
Item Document Control (1) RCP6CR Other than high thrust type (Note 1) CB-ADPC-MPA□□□(-RB) - A
RCON Gateway Unit First Step Guide ME0382 RCP6W
Gateway Unit (Left End) - Extension Unit (Right Side of Gateway Unit) - Driver Unit (No Order among P/A/D) - Terminal Unit (Right End) RCP5
RSEL Gateway Unit First Step Guide ME0393 CB-ADPC-MPA□□□(-RB)
(2) RCP5CR High thrust type (Note 1) - B
CB-CAN-AJ002 (conversion cable)
RCP5W
Wiring Layout for Motor/Encoder Cables (3) Gripper (GR*), ST4525E, SA3/RA3 CB-ADPC-MPA□□□(-RB) - A
RCP4 CB-ADPC-MPA□□□(-RB)
(4) RCP4CR High thrust type (Note 1) - B
P P A D CB-CAN-AJ002 (conversion cable)
RCP4W
(High Thrust) Driver Driver Driver CB-ADPC-MPA□□□(-RB)
Driver Unit Unit Unit Unit (5) Other than (3), (4) - B
CB-CAN-AJ002 (conversion cable)
(6) RCP3 CB-RCAPC-MPA□□□(-RB) - C
RCP2 (standard type)
CB-ADPC-MPA□□□(-RB)
(7) Rotary compact type Required D
[CB-RPSEP-MPA□□□]
RCP2-RTBS/RTBSL/RTCS/RTCSL
RCP2CR (clean room type),
RCP2W (dust-proof/splash-proof type)
(8) CB-ADPC-MPA□□□(-RB) - A
Rotary (RT*) of above types
GRS/GRM/GR3SS/GR3SM of above types
Unit should be linked in the process shown below. (Make sure it gets linked before connected to the DIN rails.) RCP2
All (standard / clean room /
1) Twist the operation parts of the link upper parts and the link bottom parts towards the panel side and RCP2CR
dust-proof/splash-proof) types of
place them at the panel side end. RCP2W
(9) GRSS/GRLS/GRST/GRHM/GRHB CB-RCAPC-MPA□□□(-RB) - C
2) Adjust the position of two units so the link upper parts come to Point [A], link bottom parts to [B] and the Short type (RCP2 only)
four positioning bosses to [C] and all the six points fit to each other. RCP2-SRA4R/SRGS4R/SRGD4R
3) Once positioning is done, firmly insert the connectors at two points.
CB-ADPC-MPA□□□(-RB)
4) Twist the operation parts of the link upper parts and the link bottom parts towards the rear side till they (10) High thrust type (Note 1) Required D
[CB-CFA-MPA□□□(-RB)]
make click feeling.
Panel Side Link Upper Parts CB-ADPC-MPA□□□(-RB)
[A] (11) Other than (7) to (10) Required D
(Unlink) Operation Part [CB-PSEP-MPA□□□]
Rear Side (Link) (12) RCA2/RCA2CR/RCA2W, RCL CB-RCAPC-MPA□□□(-RB) - C

(13) RCA2/RCA2CR/RCA2W (CNS option) CB-ADPC-MPA□□□(-RB) - A


Short type (RCA only)
(14) RCA CB-RCAPC-MPA□□□(-RB) - C
RCA-SRA4R/SRGS4R/SRGD4R
RCACR
CB-ADPC-MPA□□□(-RB)
(15) RCAW Other than (14) Required D
[CB-ASEP2-MPA□□□]
[C]
(16) RCD RCD-RA1DA, RCD-GRSNA CB-ADPC-MPA□□□(-RB) - A

Conversion Note 1 Actuators using high-thrust pulse motor (56SP, 60P and 86P)
RCP□ High Thrust Actuator Cable RCD Actuator
Conversion Note 2 Up to 20 m from each driver unit to the actuator, with or without the conversion unit.
Unit However, the maximum length from the D driver unit to the RCD actuator will be 10 m.

Wiring 24V
Driver Unit Actuator

RCP□ Actuator
RCA□ Actuator
A Motor/Encoder
Connector
CB-ADPC-MPA□□□(-RB)

Panel Side
Rear Side Wiring 24V
Actuator
[B] (Unlink) Driver Unit Conversion Cable
(Link) CB-ADPC-MPA□□□(-RB)
B Motor/Encoder CB-CAN-AJ002
Connector Connector
Order Separately
Link Bottom Parts Operation Part Note This wiring diagram shows an example for connection.
Required equipments, such as conversion cable and conversion unit, should differ
Wiring 24V
Installation Environment depending on the type of actuator. Driver Unit Actuator

C
CB-RCAPC-MPA□□□(-RB)
Refer to “24V Driver Unit Connection Cable List” shown in the following page for Motor/Encoder
Connector
This product is capable for use in the environment of pollution degree 2 *1 or equivalent. details.
*1 Pollution Degree 2: Environment that may cause non-conductive pollution or transient conductive
pollution by frost (IEC60664-1) RCM-CV Each Actuator
Wiring 24V
Driver Unit -APCS Connection Cable Actuator
1. Installation Environment [Conversion Unit] CB-ADPC-MPA□□□(-RB)
Do not use this product in the following environment.
For those actuators which cannot be connected using 24V Driver Unit connection cables
D Motor/Encoder
Connector
Conversion
Unit
• Location where the ambient temperature is out of the range between 0 and 55°C (with fan) or Order Separately
0 and 40°C (with no fan) CB-ADPC-MPA□□□(-RB) and CB-RCAPC-MPA□□□(-RB) or a conversion cable CB-CAN-AJ002, it is Order Separately
• Location where condensation occurs due to abrupt temperature changes necessary to use this conversion unit and connection cable for each actuator in order to establish
• Location where relative humidity exceeds 85%RH connection.
• Location exposed to corrosive gases or combustible gases
• Location exposed to significant amount of dust, salt or iron powder
• Location subject to direct vibration or impact
• Location exposed to direct sunlight RCON
• Location where the product may come in contact with water, oil or chemical droplets Actuator Side
Controller Side
• Environment that blocks the air vent [Refer to section in Installation and Noise Elimination]
When using the product in any of the locations specified below, provide a sufficient shield.
• Location subject to electrostatic noise
• Location where high electrical or magnetic field is present
• Location with the mains or power lines passing nearby
2. Storage and Preservation Environment
The storage and preservation environment should comply with the same standards as those for the
installation environment.
In particular, when the machine is to be stored for a long time, pay close attention to environmental
conditions so that no condensation forms. Unless specially specified, moisture absorbency protection is
not included in the package when the machine is delivered. In the case that the machine is to be stored
and preserved in an environment where condensation is anticipated, take the condensation preventive
measures from outside of the entire package, or directly after opening the package.
Power Supply and Stop Circuit (Example) Wiring Layout for SCON Connection Cables Wiring Layout for Simple Absolute Unit
In the diagram below shows a circuit related to a drive source cutoff. For RCON/RSEL System, 24V motor When the SCON-CB/CGB RCON connected type controller is to be connected using an SCON Extension When it is required to use a simple absolute unit (in common for P Driver and A Driver), conduct wiring as
power is supplied from the gateway unit, but the circuit related to the drive-source cutoff is on the driver unit Unit, conduct wiring as shown in the figure below. (SCON Controllers with model code SCON-CB/CGB-*-RC shown in the figure below.
side. are only those available to connect.) One unit of the simple absolute unit is necessary for one unit of an actuator.
• Each driver unit possesses a drive source cutoff circuit by semiconductor. The motor power should be RCON connection communication connector in SCON Controller has IN on lower end and OUT on upper
cut off by STOP Signal. The drive source cutoff circuit by semiconductor possesses features to detect RCON System Simple Absolute Unit
end. Pay attention not to connect other way around. It is necessary to connect the terminal connector
the overcurrent and to limit the in-rush current. (RCON-EXT-TR) at the terminal. RSEL System

Gateway unit Driver unit Driver unit RCON System SCON-CB/CGB Controller
RCON System Teaching pendant
RSEL System
Stop switch SIO connector
24V RCON Connection
Note 1 Communication
Connector Actuator
Stop Connector (MPG)
reset Stop Upper End: OUT
switch switch System I/O Lower End: IN

Motor power Ⅰ

Motor power Ⅱ

Motor power Ⅰ

Motor power Ⅱ
connector

Driver Unit
24V

High-side protection circuit

High-side protection circuit

High-side protection circuit

High-side protection circuit


dedicated CB-ADPC-MPA005
for stop
circuit SCON Extension Unit (Supplied with
Simple Absolute Unit)
Motor Connection Cable: CB-RE-CTL□□□
power
connector (Supplied with SCON-CB/CGB-*-RC)
Driver Connector (CONT)
Total Cable Length: 10m Max. Length of Cables between Devices: 3m Max. Terminal Connector:
RCON-EXT-TR
(Supplied with
SCON Extension
Control
power
Unit)
connector
Control Cable for each actuator
power Refer to SCON-CB Actuator
Instruction Manual
For the wiring of this part, refer to the
24V Driver Unit connection cable list
Drive-source Drive-source in “Wiring Layout for Motor/Encoder
cutoff cutoff
connector connector Cables”.
Actuator

Servo-pressing type (SCON-CB/CGB-F) and


Note 1 RCON-GW : If nothing is connected to the SIO connector, S1 and S2 will be short-circuited in the controller. PLC feature equipped type (SCON-LC/LCG) are not available to connect.
RCON-GWG : If nothing is connected to the SIO connector, S1 and S2 will not be short-circuited in the controller.
To short-circuit, connect the supplied dummy plug DP-5 to the SIO connector.

RSEL System
Teaching Pendant Troubleshooting (LED Display)
Teaching In this section, describes for LED on each unit.
Connector 24V Driver Unit Utilize them to check normal operation status and recovery after error occurrence.
(1) 24V Driver Unit
System I/O
Connector Panel Display Color Status Explanation
Inside bus communication in normal
T RUN LED Illuminating
Enable Switch, conditions Head Office: 577-1 Obane Shimizu-KU Shizuoka City Shizuoka 424-0103, Japan
GN
Door Switch, etc. T RUN Waiting for initializing communication TEL +81-54-364-5105 FAX +81-54-364-2589
Motor Power SupplyⅠ

Motor Power SupplyⅡ

Flashing
/Communication error at initialization website: www.iai-robot.co.jp/
OR Illuminating Inside bus communication in error
ENB Detection SYSⅠ LED
Illuminating Turning servo ON
GN Technical Support available in USA, Europe and China
Stop Reset SYSⅡ LED SYS OFF Turning servo OFF
Switch
Alarm being generated, During STOP
RD Illuminating
High-Side Protection Circuit

High-Side Protection Circuit

input
(2) Simple Absolute Unit Head Office: 2690 W. 237th Street, Torrance, CA 90505
TEL (310) 891-6015 FAX (310) 891-0815
Panel Display Color Status Explanation Chicago Office: 110 East State Parkway, Schaumburg, IL 60173
Motor Power Supply
TEL(847) 908-1400 FAX (847) 908-1399
Connector GN Illuminating Operation in normal conditions
SYS LED SYS Atlanta Office: 1220 Kennestone Circle, Suite 108, Marietta, GA 30066
RD Illuminating Alarm being generated TEL (678) 354-9470 FAX (678) 354-9471
website: www.intelligentactuator.com
Control STATUS1 LED GN Illuminating Home-return operation complete
Power STATUS1
Connector RD Illuminating Home-return operation incomplete
Control
Power STATUS0 LED GN Illuminating Battery fully charged
STATUS0 RD Illuminating Battery not connected
Ober der Röth 4, D-65824 Schwalbach am Taunus, Germany
OR
Illuminating Battery charging TEL 06196-88950 FAX 06196-889524
(GN/RD) website:www.iai-gmbh.de
SEL Unit (3) SCON Controller (Field Network LED)
Refer to the instruction manual for SCON controller (ME0340) for the status display LED lamps (PWR,
SV, ALM and EMG).
SHANGHAI JIAHUA BUSINESS CENTER A8-303, 808, Hongqiao Rd. Shanghai 200030, China
Panel Display Color Status Explanation TEL 021-6448-4753 FAX 021-6448-3992
website: www.iai-robot.com
Illuminating Communication in normal conditions
NS GN Startup ~
NS Flashing
Initialization Communication Completed
Note ● When externally shutting off the motor drive source to comply with the safety category or the like, connect a contact OR Illuminating Communication Error Occurred
MS
such as a relay to the wiring between the MPI* and MPO* terminals. 825 PhairojKijja Tower 7th Floor, Debaratana RD., Bangna-Nuea, Bangna, Bangkok 10260, Thailand
GN Illuminating In Normal Condition
● The rating of the STOP-signal to be turned ON/OFF with the contact CR1 is 24 VDC / 10 mA or less. MS TEL +66-2-361-4458 FAX +66-2-361-4456
● The CR1 coil current must be 0.1 A or less. OR Illuminating Error Occurred website:www.iai-robot.co.th
● When supplying power by turning ON/OFF 24 VDC, leave 0 V connected and supply/cut off +24 V.
Manual No.: ME0383-2A