SAUDI ARAMCO INSPECTION CHECKLIST
Intrinsically Safe Circuit - Cable Installation, Termination,
SAIC-J-6905 24-Jul-18 INST
Identification and Pre-Commissioning
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The field termination cabinet will serve as a transition point from individual SAES-J-903
A5
pair/triad to a multi-pair/triad cable. Sec.9.2.3
Multi-core cables shall not combine intrinsically safe and non-intrinsically SAES-J-903
A6
safe signals. Sec.9.2.3
Cables shall be sealed against the passage of gas and vapors as required SAES-J-903
A8
by the National Electrical Code NFPA 70, SAES-B-008 and SAES-O-126. Sec.9.2.4