Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Data sheet

Project: UBS_ASR 1040 CW_Germany


Editor: Th
Date : 26.11.2019

Unit
Unit type: ASR 1040 CW
Cooling capacity (total): 70.0 kW Airflow: 18,400 m³/h
Cooling capacity (sensible): 65.8 kW Air velocity: 1.9 m/s
Net total cooling capacity: 68.2 kW Return air temperature: 23 °C
Net sensible cooling capacity: 64.0 kW Return air humidity: 50 rel.%
EER: 38.89 kW/kW Supply air temperature: 12 °C
AER: 0.10 W/(m³/h) Altitude above sea level: 0 m
Sound power level: 71.3 dB(A) Height: 2,495 mm
LpA (2m freefield): 50.8 dB(A) Width: 1,750 mm
Total power consumption: 1.8 kW Depth: 890 mm
Weight: 575 kg
Power supply: 400V/50Hz/3Ph/N/PE

Fan (Data per unit)


Fan type: R3G630 Power consumption: 1.8 kW
Number: 2 ESP external static pressure: 50 Pa
Max. revolutions: 1,423 U/min Total pressure drop: 236 Pa
Nominal power: 7.4 kW Control voltage: 5.8 V
Revolutions: 870 rpm Motor-efficiency: 89 %

Hydraulics (Data per unit)


Pressure drop CW Coil: 15 kPa Medium inlet temperature: 8.5 °C
Pressure drop 2-way PIC-valve: 12 kPa Medium outlet temperature: 14.0 °C
Pressure drop pipework: 6 kPa Medium volume flow: 10.9 m³/h
Total pressure drop: 33 kPa Percentage of glycol: 0 %
Type of Medium: Water
Nominal valve size: DN50
Medium volume flow (from - to): 5.2 - 17.3 m³/h
Information with ''Standard coil (A)''!

The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all data refer to a product in basic version. Page 1 of 1
StulzSelect Vers. 3.2.1 - Proj.: UBS_ASR 1040 CW_Germany 1 x ASR 1040 CW