GW1-24 GW4 Type

Three Pole Outdoor Disconnector with Fuse-bases(Export) Outdoor High Voltage Disconnect Switch Series

RH-B High-voltage Disconnect Switch General Introduction


GW4-12(40.5) outdoor AC H.V. disconnect switch (disconnect switch for short) is
used to open and close circuit with voltage but no-load 50/60Hz,12(40.5)kV power
system.It accords with standards of IEC129-1984 AC Disconnect Switch and Earthing
Switch and GB1985 and other relative standards.

WOLUN
Model and Meaning
G W 4- □□□/□
Rated current
GW4
W: Anti pollution type (commom type not standard)
D: Single grounding
(DD: double ground, no mark if do not require grounding)
Rated voltage
Design code
Outdoor type
Disconnect switch

Outline and Mounting Dimensions


Technical Specification
1430 A-A Parameters
450±5 650
Item GW4- GW4- GW4- GW4- GW4-
40.5 72.5 126 126G 145

Rated voltage 40.5 72.5 126 126 145


900

630
630 630
1250 1250
Rated current 1250 1250 630
5
2000 2000
2000 2000 1250
2500 2500
2500 2500
4000
4750

4 20 20 20 20
Rated short-time 20
4420

31.5 31.5 31.5 31.5


withstand current (RMS) 31.5
3 40(46) 40(46) 40(46) 40(46)

50 50 50 50
Rated peak withstand 50
80 80 80 80
current (peak) 80
2 100(104) 100(104) 100(104) 100(104)
454.5

Rated short-time To the ground 80 140 185(230) 185 375


1
withstand voltage
(effective value) Fracture 110 160 210(265) 210 315

Rated lightning To the ground 185 325 450(550) 450 650


RH-B 11kV-33kV impulse withstand
voltage (peak) Fracture 215 375 520(630) 550 750
4S heat Power-frequency
Rated Rated Shock Impulse withstand
Type steady current withstand Wiring terminal rated the
voltage(kV) current(A) voltage(A) voltage(kV) 490(735) 735 735 735 960
(A) voltage(kV) horizontal tension
RH-B 11 400 12500 31500 95 42
Weight of single pole 80 200 240 300 300
RH-B 33 600 12500 31500 195 80

069 070
GW4 Type GW5 Type
Outdoor High Voltage Disconnect Switch Series Outdoor High Voltage Disconnect Switch Series

Working Conditions General Introduction


1. Ambient temperature: upper limit +40℃, lower limit -30℃ GW5-40.5/72.5/126/145 outdoor H.V. disconnect switch is used to make and break
2. Altitude: no more than 3000m; H.V. circuit of rated voltage 40.5kV, 72.5kV, 126/145kV,AC 50/60Hz system. It is able
3. Wind speed: no more than 35m/s; to open and close small capacitance and inductive H.V. Switches, GB1986 AC H.V
4. Earthquake intensity: do not exceed 8 degree;
Disconnect Switch andEarthing Switch and IEC60694&GB/T11022 Common technical
5. Pollution level: no more than III class
6. No severe vibration, no corrosive gas, no fire, no explosion danger place. requirements of H.V. switchgear and control equipment.

Outline and Mounting Dimensions

WOLUN
1200(40.5kV) 1200(40.5kV) Model and Meaning
1600(72.5kV) 1600(72.5kV)
2000(126kV) 2000(126kV) G W 5-□□□/□

GW4 GW5 Rated current


The main knife W: Anti pollution type (commom type not standard)
opening position
1120(72.5kV)
1650(126kV)
860(40.5kV)

D: Single grounding
(DD: double ground, no mark if do not require grounding)
Rated voltage
120(40.5/72.5kV) 620(40.5/72.5kV) Design code
135(126kV) 135(126kV)

B B
Outdoor type
Disconnect switch
D 11

Technical Specification
φ300 φ300
12
Parameters

Item Unit GW5- GW5- GW5- GW5-


620(40.5/72.5kV) 620(40.5/72.5kV)
40.5 72.5 126 145
1400(40.5)
635(126kV) 2200(72.5kV) 635(126kV)
3000(126kV) Voltage, current parameters
A direction basic installation size Rated voltage kV 40.5 72.5 126 145
Rated current A 630/1250/1600/2000
550(40.5) 40.5/72.5kV disconnector
650(72.5kV)
1300(126kV)
Rated frequency Hz 50
60

1
Rated peak
2 kA 50/80/100
3 4×φ14 320 withstand current
Rated short-time
Disconnector kA 20/31.5/40
4 126kV disconnector withstand current
A 1300
5 Rated short s 4
circuit duration
100

8×φ18 Rated peak


240 240 kA 25
withstand current
6
1. Wiring terminal I type Rated short-time
7 kA 10
2. Contact earth knife withstand current
8 3. Contact finger
Rated short s
4. Support insulator 4
circuit duration
5. Switch base
6. The main knife operating crank arm Rated peak
9 kA 100
7. The main knife vertical rod (galvanized steel pipe of φ45×45) withstand current
8. Anchor ear II type Rated short-time
kA 40
9. The main knife operating mechanism (CJ6 or CS17) earth knife withstand current
10. Grounding contact finger
Rated short s
11. The earth knife vertical rod (galvanized steel pipe of φ45×5) 2
circuit duration
12. The earth knife operating mechanism (CJ78CS17)

071 072
GW5 Type JN15-12/31.5
Outdoor High-Voltage Disconnect Switch Series High Voltage Earthing Switch (ES1-10/31.5)

Working Conditions Model and Meaning


J N 15 - 12 / 31.5 - □
1. The ambient temperature: upper limit +40℃,lower limit -40 ℃;
2. Altitude: no more than 3000m; Central distance between poles
3. Wind speed: not more than 35m/s; Rated short-time withstand current(KA)
4. Earthquake intensity: do not exceed 8 degree;
Rated voltage(KV)
5. Pollution level: no more than III;
Design No.
6. No severe vibration, no corrosive gas, no fire, no explosion danger place.
Indoor
Earthing switch

Outline and Mounting Dimensions

WOLUN
1075(40.5kV)
General Introduction
≥1200(40.5kV) ≥1200(40.5kV) 1285(72.5kV)
≥1600(72.5kV) ≥1600(72.5kV) 1660(126kV)
JN15-12/31.5 series indoor earthing switch is a new design and improved product of
1 our company according to the ES1 type, suitable with electric power system with 3-
1070(40.5kV)
1295(72.5kV)

Main knife
2 12KV, Three-phase, AC 50(60)Hz, support with various kinds of HV switchgear and as
1695(126kV)

opening position 3
4 earthing protection. It is manufactured comply with GB1985-2004 and IEC129

5
standard.
6

B B 7
8

9
Working Conditions
1. Ambient temperature:-10~+40℃
≥1100

2. Altitude: ≤1000m (sensor height:140mm)


1. Connecting terminal
2. Main contact 3. Relative humidity: Day average relative humidity ≤95%
500 1400(40.5kV) 3. Main contact finger
2200(72.5kV) 4. Porcelain insulator Month average relative humidity ≤90%
3000(126kV) 5. Switch base
6. Cross-pin type joint
4. Earthquake intensity: ≤8degree
240 10
7. The main knife vertical rod
5. Dirtiness degree: II
(1 galvanized steel user owned)
4-φ20
300

8. Friction plate
Mounting hole
9. The main operating mechanism
(CJ6 electric operation or CS17 manual operation)
10. The main knife three-phase linkage rod

240
Technical Specification
-
4 φ20
Mounting hole
Item Units Data
B direction
7 8
Fixed position Rated voltage kV 12
of user welding
Rated short time withstand current kA 31.5
300

Rated short circuit withstand time s 4


Rated short circuit making current kA 80
Rated peak withstand current kA 80
Fixed position
of user welding
1min power frequency
withstand voltage kV 42
420 Rated
300
180 120
120 120 insulation
level Lightning Impulse
withstand voltage kV 75
150
150

150

Mechanism life time 2000


90° 90° 90° 90° 90° 90°

GS17 I type GS17 II type GS17 III type


manual operating mechanism manual operating mechanism manual operating mechanism

The main knife handle at the closing position


The main knife handle is in the off position
Earthing switch operation handle is in the closing position
Earthing switch operation handle is in the off position