Fire Suppression System

System Component Datasheet

DT-STV-P1LE Rev 1.1


Actuator cabinet 1L Effective: July 2019
P/N STV-P1L

FEATURES
 Completed set with pilot cylinder, solenoid,  For using with SFS FM-200 system and
discharge pressure switch. SNS IG-100 system.
 Completed assembly in factory

DESCRIPTION The released actuation gas is then used to activate the


corresponding FM-200 needle cylinder valve, or selector
The actuation cabinet STV-P1L is used to trigger the fire
valves.
suppression system. The actuation cabinet STV-P1L can
be used to actuate the FM-200 needle cylinder valve, or The actuation cylinder is factory-fitted with a discharge
selector valves. It is also used to trigger the agent valve that is opened via the activation of solenoid cutter.
discharge alarm though the discharge pressure switch. As part of the cylinder safety feature, the actuation cylinder
The actuation box assembly consists of a solenoid cutter, valve is fitted with rupture disc-fitted safety plug to prevent
an CO2 pilot cylinder 1L 0.65kg, and a discharge pressure unsafe pressure built-up and damage of the device.
switch. DISCHARGE PRESSURE SWITCH
The actuation box assembly is enclosed in a steel box and The discharge pressure switch is used to activate the
factory pre-assembled. discharge alarm system (supplied separately).
SOLENOID CUTTER It is connected to the selection valve or discharge pipe via
The solenoid cutter is used to actuate the actuation pressure switch actuation tube.
cylinder. As the discharged extinguishing agent has reached the
It is an integral component of the actuation box and is selection valve or pipe, pressure from the discharged
activated via electric signal that is sent by the control panel extinguishing agent is used to activate the pressure switch.
(supplied separately) upon fire detection. The pressure switch is then used to allow the flow of
The solenoid cutter is fitted with PUSH button that is and electricity via electrical wires to activate the discharge
should only be used for emergency manual activation alarm (system).
should the electronics fail

TECHNICAL INFORMATION
Box
ACTUATION CYLINDER Box material :Cold-reduced steel sheet
The actuation cylinder is an integral part of the actuation Steel Thickness :1.2mm
box that is filled with 0.65kg of CO2. Painting : Powder coating
Dimensions : 355 (H) x 340(W) x 140 (D)

Solenoid Cutter
Voltage : 24Vdc
Current : 1.5A

Pilot cylinder
Cylinder capacity : 1L
Filled : 0.65 kg CO2
Painting : Powder coating
S-TECVINA Ltd.,
Dong Van IV IZ, Ha Nam, Vietnam
Phone: (+84) 0226 2460 114
© 2019 S-TECVINA Ltd.,    www.stecvina.com 
DT-STV-P1LE Rev 1.1

Discharge pressure switch


Pressure Connection : Ø6.3mm Copper tube
Minimum Operating : 5 bar
Max. Working Pressure : 100bar
DC Switch Rating : 250V - 3A
:16A (1/2HP 125/ 250 VAC)
: 0.6A – 125 VDC
: 0.3A – 250 VDC
Installation Environment : Indoor

ORDERING INFORMATION
The part number for ordering the Actuator cabinet 1L with
acessories as below table:

Part number Description  


Actuator cabinet 1L (included pilot
STV-P1L cylinder, solenoid valve, discharge
pressure switch)
Cabinet

Pilot cylinder, 1L, 0.65kg CO2 -


Included
Solenoid cutter

Discharge pressure switch

This literature is provided for informational purposes only. S-TECVINA Ltd.,. FM-200 is a registered trademark of The Chemours
assumes no responsibility for the product’s suitability for a particular Company FC, LLC. 1007 Market Street Wilmington,
application. The product must be properly applied to work correctly. If you need DE19899 United States of America (USA)
more information on this product, or if you have a particular problem or
S-TECVINA Ltd.,
question, contact S-TECVINA Ltd.,.
Dong Van IV IZ, Ha Nam, Vietnam
Phone: (+84) 0226 2460 114
© 2019 S-TECVINA Ltd.,    www.stecvina.com 

You might also like