Ac - DC Converter Manual
Ac - DC Converter Manual
CONTROLLER
7AVR0100
AC/DC CONVERTER 57V 9KW
- USER’S GUIDE -
- INTRODUCTION -
The system consists of a permanent magnets generator and a DC/DC converter to be
applied to a generating set (with a gasoline engine)
As the application is in the telecom field, the stability and the quality of the generated
voltage must grant the correct working and safety of electronics devices connected .
Optimizing the engine performances adapting the speed in function of the output load,
the fuel consumption and noise are reduced.
The system is designed in accordance with the most important EC standards.
- FEATURES -
INPUT VOLTAGE FROM PMG 48-145Veff THREE PHASES
OUTPUT VOLTAGE 44-57 Vdc +/-1%
MAX CURRENT 190 Adc
MAX HEATSINK TEMPERATURE 100 °C
OPERATING TEMPERATURE -15°C / 50°C
ENGINE SPEED REGULATION DC MOTOR ACTUATOR
ENGINE SPEED RANGE 1350-2900RPM
AUX VOLTAGE 10Vrms / 30Vrms
PARAMETERS PROGRAMMABLE
BATTERY CHARGE FUNCTION
PROTECTION IP40
SERIAL COMMUNICATION - RS232 PORT (modbus protocol)
- RS485 PORT (modbus protocol)
- FIX IT IN THE VERTICAL POSITION WITH THE FAN IN THE LEFT SIDE NEAR
THE FRESH AIR ENTRY TO OBTAIN THE BEST POWER DISSIPATION
MODE Key:
Confirms a selection and the change of value.
DOWN Key:
Rolls down parameters and decreases values.
At power-on, handheld programmer displays the “Tester Mode” page. In this pages , you’ll find running
information of the device.
To start the programming function push the button “MODE” .
Will appear the first parameter; pushing the “UP” button the number of the parameter will be increased and
with the “DOWN” button the number will be decreased. When a parameter is selected , push the button
“MODE” to enter in the change menu, change the value with the buttons “UP” and “DOWN”, then confirm
the parameter with the button “MODE”. To return to the TESTER menu push together the buttons
“MODE “and “UP”, or wait few seconds.
TESTER MODE
NOTE3: regulation of output voltage, output current and battery current reading:
• With NO load and NO batteries connected to the converter, set the correct OUTPUT VOLTAGE
reading. First of all, connect a multimeter at output of converter, then set parameters
“COEFF.VOUT” and “COEFF. OUT1” until the voltage red on programmer reaches the voltage
measured by multimeter. Then set “COEFF.PWM1” parameter until it reaches the value set in
“OUTPUT VOLTAGE” parameter.
• With a fixed load (20A for example) and NO batteries, set the correct OUTPUT CURRENT and
BATTERY CURRENT reading. Connect a current probe and LEM on output load, then set
parameters “COEFF.IOUT” and “COEFF. LEM” until the current red on programmer reaches the
current measured by the probe.
TIME-OUT : each time the next step position speed isn’t reached within 60 seconds the
actuator is powered-off to avoid overload and alarm A8 is visualized.
On the logic PCB there are two relays: alarm relay and start-stop relay.
1. ALARM RELAY:
Each time an alarm acts (after the delay indicated on “Alarms” paragraph) this relay
switches.
2. START-STOP RELAY:
INTRODUCTION Page 1
FEATURES Page 1
INSTALLATION Page 2
PARAMETERS Page 7
ALARMS Page 9