Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

Pleiger Elektronik

GmbH & Co. KG

PCM Pleiger Control Modules

Manual
CM3 EHS Control Module
IO 8/8/4 IO-Module
RK 16/8 Relay Module
BI Bus Interface
Author: H. Vögler
Issue: 05/2007
- subject to modification -

Pleiger Elektronik GmbH & Co. KG


D-58456 Witten - Im Hammertal 51
D-58423 Witten - Postfach 32 63
Telefon (0 23 24) *3 98- 0
Telefax (0 23 24) 3 98- 3 89
Internet www.pleiger-elektronik.de
E-Mail info@pleiger-elektronik.de
Pleiger Elektronik
GmbH & Co. KG

Contents

1 Overview .................................................................................................... 1
1.1 Assembly .................................................................................................................. 1

2 EHS control module CM3 ......................................................................... 2


2.1 Operation .................................................................................................................. 2
2.2 Control functions ..................................................................................................... 3
2.2.1 Types of actuators ...........................................................................................................3
2.2.2 Operation modes of the actuators ....................................................................................4
2.3 Adjusting the operating time................................................................................... 4
2.3.1 Calibration of the operating time ......................................................................................4
2.4 Extended operation modes ..................................................................................... 5
2.4.1 Extended operation mode set-up .....................................................................................5
2.4.2 Displaying extended operation modes .............................................................................5
2.6 Start reports and self test........................................................................................ 5
2.7 Alarm output............................................................................................................. 5
2.8 Lamp test .................................................................................................................. 6
2.9 Placing commands................................................................................................... 6
2.10 Terminal assignment ............................................................................................... 6
2.11 Technical data .......................................................................................................... 7

3 Input/output module IO 8/8/4 .................................................................... 8


3.1 Displays .................................................................................................................... 8
3.1.1 Start messages and self test............................................................................................8
3.1.2 Lamp test.........................................................................................................................8
3.2 Adjusting the address.............................................................................................. 9
3.3 Terminal assignment ............................................................................................... 9
3.4 Technical data ........................................................................................................ 10

4 Relay Module RK 16/8 ............................................................................. 11


4.1 Indication ................................................................................................................ 11
4.2 Operation ................................................................................................................ 11
4.3 Jumper B1............................................................................................................... 11
4.4 Counter function .................................................................................................... 11
4.5 Technical Data........................................................................................................ 12
4.6 Terminal assignment ............................................................................................. 12

5 Fieldbus interface BI ............................................................................... 13


5.1 Operation ................................................................................................................ 13
5.1.1 Parameterisation of the fieldbus.....................................................................................13
5.1.2 Setting the address of the EHS-CM3 modules ...............................................................13
5.1.3 Setting the address of the RK 16/8 ................................................................................14
5.1.4 Skipping addresses........................................................................................................14
5.1.5 Mimic control enable ......................................................................................................15
5.1.6 Set-up of Quick Close Functions....................................................................................15
5.1.7 Display functions............................................................................................................15
5.1.8 Start messages and self test..........................................................................................16

PCM – Manual Issue: 05/2007


Pleiger Elektronik
GmbH & Co. KG

5.1.9 Power management.......................................................................................................16


5.1.10 Alarm output ..................................................................................................................17
5.1.11 Lamp test.......................................................................................................................17
5.1.12 Bus Termination.............................................................................................................17
5.2 Terminal assignment ............................................................................................. 17
5.3 Technical data ........................................................................................................ 18

6 BI Modbus interface (slave).................................................................... 19


6.1 Modbus data model................................................................................................ 19
6.1.1 Fieldbus interface BI status, register 1, (read only) ........................................................19
6.1.2 CM3 status register (read only) ......................................................................................20
6.1.3 IO status register (read only)..........................................................................................20
6.1.4 Fieldbus interface BI remote control, register 142 (read/write) .......................................21
6.1.5 CM3 control register (read/write)....................................................................................21
6.1.6 IO control register (read/write)........................................................................................22
6.1.7 RK status register (read only) ........................................................................................22
6.1.8 RK control register (read / write) ....................................................................................22
6.2 Protocol Watchdog ................................................................................................ 23
6.3 Register summary.................................................................................................. 24

7 BI Profibus DP interface (slave) ............................................................. 25


7.1 Profibus data model............................................................................................... 25
7.1.1 Fieldbus interface to superimposed control system (status words).................................25
7.1.2 Superimposed control system to fieldbus interface (control words) ................................25
7.1.3 Data Valid Bit .................................................................................................................26

8 Assembly of the system ......................................................................... 27


8.1 24VDC current requirements................................................................................. 27
8.2 Controlling via circuit mimic diagram .................................................................. 27
8.3 Commissioning hints............................................................................................. 28
8.4 Safety Advice.......................................................................................................... 28
8.5 Accessories ............................................................................................................ 28
8.5.1 Adapting Cable ..............................................................................................................28
8.5.2 Extension Cable.............................................................................................................29
8.5.3 Adapting Cable for RK 16/8 ...........................................................................................29
8.5.4 Safety Advice Plate........................................................................................................29
8.5.5 End Holder.....................................................................................................................29
8.5.6 Noise Suppression Filter ................................................................................................29

PCM – Manual Issue: 05/2007


Pleiger Elektronik
GmbH & Co. KG

1 Overview
The system consists of three components:

EHS control module CM3 (control module, 3rd generation)


Input/output module IO 8/8/4 (IO module)
Relay module RK 16/8 (Relay module)
Fieldbus interface BI (bus interface)
The EHS control module is for the control and monitoring of electro hydraulic swivel drives. Operation
can be carried out manually with the assistance of the control module operation elements, via digital in-
puts and outputs of the control module and via a serial data connection to a supervisory control system.
The CM3 control function can be adapted to the different actuator types by means of a quadruple
switch.
The input/output module has 8 analogue inputs, 8 digital inputs and 4 digital outputs and is for monitor-
ing and output of control signals. Link-up to a supervisory control system is carried out via a serial data
connection.
The fieldbus interface forms the interface between the bus protocol of the local module bus and the
fieldbus according to the Modbus RTU or Profibus DP standard. Furthermore, the fieldbus interface
acts as a monitor for all modules at the local bus and enables simple parameterisation of these mod-
ules.

1.1 Assembly
The modules BI, CM3 and IO are installed in a narrow, compact top-hat rail housing (22.5x105x115,
WxHxD). They are interconnected via a connector system in the top-hat rail and can be removed from
the system independently or re-applied without interfering with the function of the overall system. The
RK 16/8 module is installed in a flat top-hat rail housing (102x126x30) connected to the local bus by
means of a prefabricated connetcion cable.

CM3 IO 8/8/4 BI RK 16/8

The local bus connects all modules to a 24V supply voltage, a serial databus and a mutual digital
control line. Up to 50 CM3 modules, 10 IO and 20 RK modules can be connected to a fieldbus
interface. In doing so the IO modules must be aligned to the left of the fieldbus interface and the CM3
and RK modules to the right of the fieldbus interface.

PCM – Manual Issue: 05/2007 Page 1


Pleiger Elektronik
GmbH & Co. KG

2 EHS control module CM3


The EHS CM3 control module monitors and controls electro-hydraulic flap or valve actuators manufac-
tured by Pleiger Maschinenbau. One control module is required for each actuator. The actuator can be
connected directly to the control module. The module has the necessary power relays and actuator
supply voltage fusing.

2.1 Operation
The EHS control module has several operating and display elements that enable manual on-site opera-
tion of the actuator.
switch „local - remote“ In position “local” the drive can be operated by means of the „close-0-
open“ switch. In position „remote” the can be operated using the digital
control inputs or the local serial bus.
button „close - 0 - open“ This button is used to operate the drive while the operating mode is
„local“. If the operation mode is “remote” pressing this button will indi-
cate the device and software version on the BI display.

Furthermore, operation of the local-remote switch causes temporary display of the module address on
the fieldbus interface. In addition, these control elements are also used for the parameterisation of the
local bus (see also 5.1.2).

Three LED (red, yellow, green) signalise the operating status of the actuator and the control
module.
LED red LED green meaning
on off Drive in closed position
on blinking 1/s Drive in closed position, open command received
off blinking 1/s Drive is opening, closed position left
off on Drive in open position
blinking 1/s on Drive in open position, close command received
blinking 1/s off Drive is closing, open position left
blinking 2/s on / off Not closed within supervision time
on / off blinking 2/s Not opened within supervision time
blinking 2/s blinking 2/s No valid position on module start up
blinking 4/s blinking 4/s Illegal feed back
For drive type no. 10 only:
blinking 1/2s off Command close, opened manually, open position not reached
blinking 1/2s on Command close, opened manually completely
The yellow LED serves to display the operating status of the control module.
LED yellow meaning
on No 230VAC power supply or fuse blown
off Power supply OK, no (valid) data on local bus
blinking Power supply OK, valid data on local bus but module is not addressed
flickering, Power supply OK, data exchange OK
dim

PCM – Manual Issue: 05/2007 Page 2


Pleiger Elektronik
GmbH & Co. KG

2.2 Control functions


The control function that is required for the various types of actuators can be selected with the
assistance of a quadruple switch in the front of the control module housing. For this the
transparent module cover flap must be opened. To accept the new type the module has to be
reset. type

ATTENTION: It is absolutely necessary to adapt the control function to the type of actuator as
otherwise correct function of the actuator is not guaranteed and the actuator or the
control module can be damaged as the case may be.
Switch
Typ Type of actuator Operation mode Runtime
1 2 3 4
0 EHS double acting open / close 4s..260s 0 0 0 0
1 EHS double acting step open / close 4s..260s 1 0 0 0
2 EHS double acting open / step close 4s..260s 0 1 0 0
3 MOV open / close 4s..260s 1 1 0 0
4 EHS single acting, spring close open / close 4s..260s 0 0 1 0
5 EHS single acting, spring open open / close 4s..260s 1 0 1 0
6 EHS double acting % 4s..260s 0 1 1 0
7 EHS double acting %Pos 4s..260s 1 1 1 0
8 EHS single acting, spring close % 4s..260s 0 0 0 1
9 EHS single acting, spring open % 4s..260s 1 0 0 1
10 EHS single acting, spring close with handwheel open / close 4s..260s 0 1 0 1
11 EHS double acting with separated hydraulic unit open / close 4s..260s 1 1 0 1
12# EHS spring close, hydraulic override open / close 4s..260s 0 0 1 1
13.. not used
#
only for firmware version V2.0or higher Switch position 0= OFF, 1= ON

2.2.1 Types of actuators


Double-acting
This actuator actively opens and closes with activated drive motor. In the event of a power failure it
stops in the current position.
Single-acting, spring close
This actuator actively opens with activated drive motor. The closing procedure is carried out by spring
force. The actuator closes in the event of a power failure.
Single-acting, spring open
This actuator actively closes with activated drive motor. The opening procedure is carried out by spring
force. The actuator opens in the event of a power failure.
MOV, motor valve
This actuator behaves likes a double-acting actuator and contrary to this automatically turns the drive
motor off upon reaching the end position. The control module always leaves the current supply swit-
ched on during normal operation.
Spring close, mechanical override with handwheel
This actuator corresponds to a normal spring-close actuator, but can be opened manually with the as-
sistance of a handwheel. This operating status is permitted and the control module will not report this as
an error. In order to re-close the manually opened actuator this must initially be completely opened e-
lectrically. This function is carried out automatically by the control module.
spring close, hydraulic override with hand pump and separate hand valve
The actuator operates like a standard spring close type but can manually be opened by means of a
manual operated valve and a hand pump. This operation mode is signalised at the CM3 module but is

PCM – Manual Issue: 05/2007 Page 3


Pleiger Elektronik
GmbH & Co. KG

not indicated as a fault. The actuator may be closed by the CM3 by electrically opening the manual
valve again.

2.2.2 Operation modes of the actuators


Operation mode: open / close
After the drive command has been given, e.g. by pushing the command key in the direction of ”close“,
the actuator will operate until the final position is reached or the maximum permissible operating time is
exceeded. The alarm output is activated if the operating time is exceeded and alarm status signalised
via the light-emitting diodes on the module.
Operation mode: open / step closing
To a large extent this operation mode corresponds to the open/close operation mode. Upon closing,
however, the actuator is repeatedly stopped briefly in order to extend the closing time. In this connec-
tion the closing time is extended by the set operating time, i.e. the closing time is approximately dou-
bled. The turn-on times of the actuator amount to at least 1 second. Depending on the operating time
the actuator is halted up to 20 times.
Operation mode: step opening / step closing
To a large extent this operation mode corresponds to the open/close operation mode. Upon closing and
opening, however, the actuator is repeatedly stopped briefly in order to extend the closing or opening
time. In this connection the closing or opening time is extended by the set operating time. The turn-on
times of the actuator amount to at least 1 second. The actuator is halted up to 20 times.
Operation mode: %
In this operation mode the actuator is only operated for as long as the command key is depressed or
the command is pending. The actuator can thus be stopped in any position. Only exception: Insofar as
either of the actuator limit switches is operated, the actuator is moved to the appropriate end position
when the key is released. This ensures that the actuator has actually moved completely to the end posi-
tion if this is signalised by the end position switch. For example, this function is used for throttle valves.
Operation mode: %Pos
This operation mode is only used in connection with the issue of a command via a superimposed con-
trol system. In this case the superimposed control system prescribes the desired position of the valve
as a percentage and the control module automatically moves the valve into the target position. Devia-
tions from the target position not exceeding 2% are ignored by the module. This operation mode is al-
ways replaced by operation mode % during mimic diagram operation or local command input.

2.3 Adjusting the operating time


The operating time of the actuator can be adjusted by means of a potentiometer on the front side of the
module. The transparent module cover flap must be opened for this. In general a fairly rough adjust-
ment (-5% .. +25%) is sufficient whereby, if anything, the time should be assessed somewhat too gen-
erously.
The operating time should only be determined exactly for actuators with a successive opening or clos-
ing function and in particular for actuators with the %Pos operation mode. A help function is integrated
into the control software for this purpose, allowing this to be very simple and reliable.

2.3.1 Calibration of the operating time runtime


180
Set the operating time to maximum (r.h. limit stop). 120 260

60

Move the actuator from the closed position to the open position by selecting the “local” 40
20
4

operation mode and pushing the command key in the direction of “open”.

PCM – Manual Issue: 05/2007 Page 4


Pleiger Elektronik
GmbH & Co. KG

Once the actuator has opened completely, push the command key again in the direction of “open“
and hold depressed. Now slowly reduce the operating time until the red LED also turns on. If both
LED are turned on, the time has been adjusted correctly.

2.4 Extended operation modes


The function of the CM3 module can be changed by setting several extended operation modes. This
feature is implemented from Version V2.0 upwards. Up to four extended operation modes can be set:
1. mimic inputs are active even in local operation mode
2. reserved
3. reserved
4. reserved

2.4.1 Extended operation mode set-up


Depending on the requested extended operation mode one or more type selector switches 1..4 must be
changed while the module is running. Now turn operation mode to “remote”.
To set the extended operation push the command button to „close“ position until the yellow LED
starts flashing several times. The extended operation mode is set now.
To reset the extended operation push the command button to „open“ position until the yellow LED
starts flashing several times. The extended operation mode is reset now.
ATTENTION: Do not forget to turn the type selector switches back to the original position.

2.4.2 Displaying extended operation modes


If at least one of the extended operation modes is set it will be displayed at the BI module if the „close“
button is pressed in operation mode „remote“. If no extended operation mode is selected the version
number of the CM3 is displayed as usual.
If extended operation mode1 is set and the mode switch is turned to local mode the yellow lamps starts
flashing several times to indicate that mimc commands can overrule local commands.

2.6 Start reports and self test


Directly after the programme has started up, the module displays the last “reset“ cause by illuminating
one or two LED briefly. The module subsequently carries out a short self test. In the event that the self
test is not carried out successfully, the yellow LED will start to flash.
Once the self test has been carried out successfully, the normal status display will start up.

2.7 Alarm output


Once the self test has been carried out successfully, the alarm output is closed initially. As soon as an
error occurs the output is opened. The output is not closed until the error is reset, e.g. by entering a
new drive command. Errors that will raise an alarm are:
power supply failure 24VDC or 230VAC
invalid or inadmissible position indications
timeout while closing or opening
local/remote switch in local position

PCM – Manual Issue: 05/2007 Page 5


Pleiger Elektronik
GmbH & Co. KG

2.8 Lamp test


Terminal no. 3 on the local bus is used as a lamp test input. As soon as 24V are applied, the 3 LED on
the module are illuminated and in addition to this both report outputs “LED open” and “LED closed” to
the mimic diagram are activated.

2.9 Placing commands


Commands can be placed in three different ways:
Using the open/close button while the operation mode is “local”
Using the control inputs “CMD-close / CMD-open” while the operation mode is “remote”
Using a command sent via the BI module
Note: As long as the command inputs are set they will overrule the commands sent via the BI module.

2.10 Terminal assignment


Lower terminals, to the control system:
X1 (grey) pluggable
1 LED-open o Drive open, to mimic diagram
2 LED-closed o Drive closed, to mimic diagram
3 CMD-open i Command open, from mimic diagram
4 CMD-close i Command close, from mimic diagram
X2 (red) pluggable
5 N i Drive supply voltage 230VAC max. 3,15A
6 L i Drive supply voltage 230VAC max. 3,15A
7 Alarm a o Contact opens in case of error
8 Alarm b o Contact opens in case of error

Upper terminals, to the EHS:


X3 (grey) pluggable
9 FB-closed i Feed back closed, 0V = closed, internal pull up
10 FB-open i Feed back open, 0V = open, internal pull up
11 0V o DC power supply for position sensors
12 24V o DC power supply for position sensors
X4 (black) pluggable
13 FB- analogue i Position signal (4..20mA) (optional)
14 N o Common power
15 L-close o Power output close
16 L-open o Power output open

Safety Advice: Always plug in red connector to connect AC supply voltage last and
always pull it off to disconnect AC supply voltage first! (see also 8.4)

Bus connector
1 Data A io Local data bus, rs485
2 Data B io Local data bus, rs485
3 lamp test i Lamp test input, 24V = lamps on
4 0VDC i Local power supply
5 +24VDC i Local power supply

PCM – Manual Issue: 05/2007 Page 6


Pleiger Elektronik
GmbH & Co. KG

ATTENTION: It is imperative to ensure that the supply voltage is not under any circumstances
applied to the local data bus. This may cause the destruction of all connected
modules.

2.11 Technical data


Supply voltage DC 24V
Current requirement DC max. 40mA, plus external load*
Fuse DC self resetting fuse, 500mA - 1100mA
Supply voltage AC 230V 20%
Fuse AC 2 x 3,15AT miniature fuse
Analogue input position 4..20mA = 0..100%, deviation 1%, resistance249Ohm
LED-open / -close semiconductor high side switches, max. load 150mA, short circuit
proof
size WxHxD 22,5mm x 105mm x 115mm
Terminal type max. 2,5mm²
Operating temperature 0°C – 50°C
protection IP20

*The current consumption of the feedback modules in the EHS, for example OC3 and the
currents emitted via the mimic diagram outputs X1, Pin1 and Pin2, must be added to the
current consumption of the module.
The miniature fuses for AC power supply are accessible at the lower side of the casing.
To exchange the fuses the casing has to be removed from the hat-rail. The fuse holder
can be opened by means of a screw driver.

PCM – Manual Issue: 05/2007 Page 7


Pleiger Elektronik
GmbH & Co. KG

3 Input/output module IO 8/8/4


The IO module is an assembly group for registering analogue and digital signals and for the output of
digital signals. All signal transmitters must be isolated, as this module does not provide internal poten-
tial separation. Generally speaking, this is the case for temperature and pressure sensors or limit
switches, floating switches and relay contacts. Insofar as this is not applicable, buffer amplifiers or cut-
off relays must be used.
This also applies correspondingly to the digital outputs that are designed as short-circuit proof semi-
conductor relays, dispensing 24V supply voltage.

3.1 Displays
The module has a total of 20 LED at its disposal to display the input or output status.
8 green LED indicate the status of the individual measured values.
green LED input signal meaning
on >=3.8mA and <=20.2 mA valid measurement
blinking fast > 20.2mA above range or short circuit
blinking slowly >0.2 mA and <3.8mA below range
off <=0.2mA not used or wire broken

8 yellow LED indicate the status of the digital inputs.


4 red LED indicate the status of the digital outputs.

Furthermore, the LED are used to display any error status. In this connection the 4 lower and 4 upper
green LED flash alternately whilst the yellow LED indicate the error number from 1..8.
LED Error status Comment
1. address changed the address of the module was changed
2-7. still free
8. module offline There is no data connection to the BI module

Alteration to the module address initially brings about the output of the “address altered“ error message.
This error message also brings about the display of the module address on the fieldbus interface. The
new module address is not accepted until the module has been re-started.

3.1.1 Start messages and self test


Directly after the start of the programme the module displays the last reset cause by illuminating one of
the yellow LED briefly. The module subsequently carries out a short self test. In the event that the self
test is not carried out successfully, the two lowest green LED will start to flash.
Normal status display commences once the self test has been carried out successfully (see above).

3.1.2 Lamp test


Terminal no. 3 on the local bus is used as a lamp test input. As soon as 24V are applied the 8 green
and 8 yellow LED are illuminated. The red LED are not activated during the lamp test.

PCM – Manual Issue: 05/2007 Page 8


Pleiger Elektronik
GmbH & Co. KG

3.2 Adjusting the address


module switch The module address is adjusted with the assis-

address
address S1 S2 S3 S4 tance of a quadruple switch. The switch is to be
51 0 0 0 0 found behind a transparent cover flap.
52 1 0 0 0 The address range of the IO modules starts at 51
53 0 1 0 0 and finishes at 60.
54 1 1 0 0 The range beginning with setting 0101 is also mapped to the
55 0 0 1 0 addresses 51 to 56. In this case the state of the digital input
56 1 0 1 0 is hold for at least 0,9s. By this means even very short
57 0 1 1 0 events can be detected securely (Version B.6 and higher).
58 1 1 1 0
59 0 0 0 1
60 1 0 0 1 0= OFF, 1= ON
51 0 1 0 1
52 1 1 0 1
53 0 0 1 1
54 1 0 1 1
55 0 1 1 1
56 1 1 1 1

3.3 Terminal assignment


Lower terminals (factory):
X1 (grey) pluggable
1 digital input 5 i 24V DC to 0V of supply voltage
2 digital input 6 i 24V DC to 0V of supply voltage
3 digital input 7 i 24V DC to 0V of supply voltage
4 digital input 8 i 24V DC to 0V of supply voltage
X2 (black) pluggable
5 digital output 1 o 24V DC to 0V of supply voltage
6 digital output 2 o 24V DC to 0V of supply voltage
7 digital output 3 o 24V DC to 0V of supply voltage
8 digital output 4 o 24V DC to 0V of supply voltage

Upper terminals (dockyard):


X3 (grey) pluggable
9 analogue input 4 i 0 .. 20mA, to 0V DC
10 analogue input 3 i 0 .. 20mA, to 0V DC
11 analogue input 2 i 0 .. 20mA, to 0V DC
12 analogue input 1 i 0 .. 20mA, to 0V DC
X4 (black) pluggable
13 analogue input 8 i 0 .. 20mA, to 0V DC
14 analogue input 7 i 0 .. 20mA, to 0V DC
15 analogue input 6 i 0 .. 20mA, to 0V DC
16 analogue input 5 i 0 .. 20mA, to 0V DC
X6 (grey) pluggable
17 digital input 4 i 24V DC to 0V of supply voltage
18 digital input 3 i 24V DC to 0V of supply voltage

PCM – Manual Issue: 05/2007 Page 9


Pleiger Elektronik
GmbH & Co. KG

19 digital input 2 i 24V DC to 0V of supply voltage


20 digital input 1 i 24V DC to 0V of supply voltage

Bus connector
1 Data A io Local data bus, rs485
2 Data B io Local data bus, rs485
3 Lamp test i Lamp test input, 24V = lamps on
4 0VDC i Local power supply
5 +24VDC i Local power supply

ATTENTION: It is imperative to ensure that the supply voltage is not under any circumstances
applied to the local data bus. This may cause the destruction of all connected
modules.

3.4 Technical data


supply voltage DC 24V
current requirement DC max. 70mA, plus external load*
fuse DC Self resetting fuse, 500mA - 1100mA
size WxHxD 22,5mm x 105mm x 115mm
terminal type max. 2,5mm²
operating temperature 0°C – 50°C
protection IP20
*Current via digital outputs

Analogue inputs
range 0 (4) .. 20mA
resolution 12 Bit, 0 = 0mA, 4000 = 20mA, 4096 = 20,48mA
precision 0,4% of full range, typ. 0,2%
filter Median / low pass app. 100ms
shunt resistance 100 Ohm
overload protection self resetting fuse 30 - 50mA per input (max. 30V)
Digital inputs
threshold app. 9,5V
input current app. 5mA
low pass filter app. 10ms
Digital outputs
output voltage 24VDC
output current, on max. 200mA per output, max. 400mA totally
output current, off <1mA

PCM – Manual Issue: 05/2007 Page 10


Pleiger Elektronik
GmbH & Co. KG

4 Relay Module RK 16/8


The relay module provides 16 opto-decoupled digital inputs and 8 relay outputs.
The inputs are arranged in two groups with common 0V. A jumper allows to
connect both groups to the same 0V. The relay outputs are designed as nor-
mally open contacts with one common terminal. The common terminal is fused
onboard. Standard fuse is 2AT, max. 10AT is allowed. The fuse is monitored. A
voltage drop of more than 100VAC will be indicated and signalled. The relay
contacts may switch up to 3A / 230V. A short cable with two plugs serves to
connect the RK 16/8.

4.1 Indication
The module is equipped with 24 LED for indication of the input and output state. An addi-
tional yellow LED is used for status display.
- 16 green LED indicate the state of the digital inputs
- 8 yellow LED indicate the state of the digital outputs
The status LED indicates the data traffic on the local bus, a fuse fail and also assists the user during
set-up of the module.
LED yellow meaning
on fuse fail, voltage drop on fuse > 100VAC
off no fuse fail, no data on the loval bus
blinking no fuse fail, valid data on local bus but module is not addressed
flickering no fuse fail, communication on local bus is running

4.2 Operation
A push button is used to show and to set-up the module address. This function is only available in con-
junction with a BI module with software version 2.1 or higher. To set up the address the BI must run in
set-up mode (see also 5.1.2).
If BI is running in normal operation mode the pus button is used to indicate the RK address. If the but-
ton is pressed for more than 3s the software version of the RK is indicated instead of the address.

4.3 Jumper B1
If the jumper B1 is plugged on (default) the common 0V of both input groups are connected. In this case
only pin 9 of terminal X1 or X2 must be connected to 0V. If both input groups are connected to inde-
pendent supply voltages the jumper must be removed.

4.4 Counter function


To collect rapidly changing input values the RK provides a counter function for the input 1. Both raising
and falling edges of the input signal are counted and stored in an 8 bit counter value. If the counter rea-
ches 255 it will be reset on the next edge of the input signal.
Each puls must last at least 15ms. The counter value must be read frequently to detect a counter over-
run reliably. With a puls duration of 15ms the counter must be read at least every 15ms*255 = 3825ms.

PCM – Manual Issue: 05/2007 Page 11


Pleiger Elektronik
GmbH & Co. KG

4.5 Technical Data


supply voltage DC 24V
current requirement DC max. 70mA, plus external load*
fuse DC Self resetting fuse, 500mA - 1100mA
size WxHxD 22,5mm x 105mm x 115mm
terminal type max. 2,5mm²
Input voltage 24VDC
Threshold 6-12V, typ 9V
Counter pulse length >= 15ms
Output voltage max. 230VAC
Output current max. 2A per output
Fuse outputs default 2AT, max. 10AT
operating temperature 0°C – 50°C
protection IP20

4.6 Terminal assignment


terminal X1:
1 digital input 1 i 24V DC
2 digital input 2 i 24V DC
… … i
8 digital input 8 i 24V DC
9 common 0V for 1-8 i common 0V

terminal X2:
1 digital input 9 i 24V DC
2 digital input 10 i 24V DC
... ... i
8 digital input 16 i 24V DC
9 common 0V for 9-16 i common 0V

terminal X3:
1 relay output 1 o normally open
2 relay output 2 o normally open
… … o
8 relay output 8 o normally open
9 common terminal o

terminal X5 and X6:


1 rs485 A i/o local data bus
2 rs485 B i/o local data bus
3 0VDC i/o power supply
4 24VDC i/o power supply
The RK 16/8 does not provide a lamp test input!

PCM – Manual Issue: 05/2007 Page 12


Pleiger Elektronik
GmbH & Co. KG

5 Fieldbus interface BI
The fieldbus interface serves to connect the control and IO modules to a superimposed
control system via a fieldbus. Furthermore, the module provides two control inputs and
a collective alarm output. The module and the local bus are supplied with 24VDC.
Two 7-segment displays and two push-buttons serve to parameterise the module and
display system status.

Two fieldbus protocol variations are available:


Modbus RTU, slave
Profibus DP V0, slave
The choice of the fieldbus protocol is carried out via the parameterisation functions on the module. The
fieldbus lines are connected via terminal screws. Bus termination in accordance with the Profibus stan-
dard can be activated via a miniature switch if required.

5.1 Operation
Parameterisation of the module is carried out with the assistance of the “set“ and “prgm“ push-buttons.
The push-buttons are only accessible if the transparent lid on the module is opened. Display of the cho-
sen parameters is by means of two 7-segment displays.

5.1.1 Parameterisation of the fieldbus


Parameterisation of the fieldbus settings is only possible if the “prgm“ push-button is depressed for at
least 3s when switching on the module. After this all parameters must be entered in succession. The
“set“ key is always used to set the value and the “prgm“ key to accept the value. All parameters are
saved in a non-volatile memory.
Parameter sequence
Step Meaning Range of values Display (example)
1 Address, least significant digit x 0h … x Fh, x = any
2 Address, most significant digit 0 xh … 6 xh, x = any …
3 Selection baud rate / protocol 4k8 / 9k6/ 19k2 / 38k4 / 56k / 57k6 /
76k8 / Profibus DP , , , , , ,

Modbus only
4 Selection of parity none / odd / even
, ,
If the Profibus is chosen during step 3, step 4 is not applicable.
Automatic baud rate setting is generally used for the Profibus protocol. When the last parameter is en-
tered the module changes to normal operation.

5.1.2 Setting the address of the EHS-CM3 modules


The address of the CM3 control modules is adjusted with the assistance of the CM3 control elements.
The module does not have a separate address switch. Operation mode changeover on the CM3 mod-
ule brings about the indication of the current module address on the fieldbus interface for the duration of
approx. 2 seconds.
As the address setting needs to be protected against unintentional alteration, it is necessary to put
the system in addressing mode. In this connection the “prgm” and “set” keys on the fieldbus inter-

PCM – Manual Issue: 05/2007 Page 13


Pleiger Elektronik
GmbH & Co. KG

face are pressed simultaneously. This operation mode is shown as SU on the display. To leave this
mode just press both push buttons once more.
The CM3 module to be programmed is now switched to “remote“ operation mode. The lowest
available address on the local bus is now displayed by operating the command key in any direction.
An available address is an address to which a CM3 module does not respond. The two program-
ming functions “delete“ and “accept“ are now available.
New modules are programmed in turn from left to right. Once programming has been completed the
fieldbus interface must be set to normal operation mode. For this both keys are again pressed simulta-
neously.
PLEASE NOTE: The module address determines which register / data word is used by this actuator in
the data model of the fieldbus connection. If the address is not allocated as arranged,
the wrong valve will be activated. If possible, addressing should be carried out in such
a way that the address complies with the slot, i.e. that the 7th module, for example, is
given address no. 7.
5.1.2.1 Deleting the module address
If the command key is pushed in the direction of “open“ and the operation mode then switched to local
while the command key is depressed, the module address is set to (FFh) 255. The module is then no
longer visible for the fieldbus interface.

5.1.2.2 Accepting the lowest available address


If the command key is pushed in the direction of “close“ and the operation mode then switched to local
while the command key is depressed, the module address is set to the lowest available address. This
new address can be displayed again by changing the operation mode.

5.1.3 Setting the address of the RK 16/8


The address of the CM3 control modules is adjusted with the assistance of the push buttom S1 of the
relay module. If the button is pressed the module’s address is displayed at the BI.
As the address setting needs to be protected against unintentional alteration, it is necessary to put
the system in addressing mode. In this connection the “prgm” and “set” keys on the fieldbus inter-
face are pressed simultaneously. This operation mode is shown as SU on the display. To leave this
mode just press both push buttons once more.
Now the push button of the appropriate RK must be pressed for some seconds. The status LED
first lights brightly and the turns off. The BI module now shows the lowest unused address for an
RK module in the range 61..80. As soon as the LED turns on again the button may be released.
The RK is now programmed.
If the button is kept pressed after the LED turns on again for at least 2,5s the LED starts blinking. This
indicates a certain operation mode. In this case the state of each digital input is hold for at least 0,9s.
By this means even very short events can be detected securely. The version changes from D.x to E.x if
this operation mode is turned on (Version D.3 and higher).

5.1.3.1 Deleting the module address


To erase the module address the button must be pressed again. As soon as the LED turns off the but-
ton mist be released. The module address is now set to 255 and the module becomes invisible for the
BI.

5.1.4 Skipping addresses


If necessary an address gap may be inserted at an arbitrary position. If the BI module is in the “set-up
mode” and the CM3 is set to “remote” operation, the lowest unused address is show when the close

PCM – Manual Issue: 05/2007 Page 14


Pleiger Elektronik
GmbH & Co. KG

button of the CM3 is pressed. Now the address may be increased by pressing the BI´s “Set” button or
decreased again by pressing the “Prgm” button. Only unused addresses are selected by the BI. This
set-up, that means the number of address gaps, is also used for further addressing of the CM3 modules
until the BI´s “set-up mode” is left. (Remark: This function is only available for BI firmware version V1.6
or higher).

5.1.5 Mimic control enable


The mimic control inputs of each CM3 can be enabled by sending the mimic enable command to each
CM3. This can be done by the computer control system individually for each CM3 or alternatively by
setting the control input E1 of the BI module to enable the mimic control inputs of all CM3. If the control
input is set the computer control system can not send commands to the CM3 any longer. As soon as
the control input is reset the original CM3 commands are restored.

5.1.6 Set-up of Quick Close Functions none, no quick close function


The control input E2 of the BI module is used to activate differ- close, if the operation mode is
ent quick close functions. As soon as the input is set a close or „remote“
open command is sent to all CM3 modules that are appropri- open, if the operation mode is
ately parameterised. This parameterisation is done in the set-up „remote“
mode of the BI module. At first the appropriate CM3 is selected emergency close in any case
by changing its operation mode. Afterwards the “Prgm” push-
button is pressed. The present mode is now displayed. emergency open in any case
By pressing the „Set“ push-button the required mode is se-
lected and confirmed by pressing the “Prgm” push-button once more. The mode that is valid at present
is displayed with the decimal points turned on otherwise the decimal points are turned off.
This function must be repeated for all required CM3. Press both push-buttons simultaneously to leave
the set-up mode.

5.1.7 Display functions


Various system data can be displayed for diagnosis purposes in connection with the “Set” and “Prgm”
keys of the fieldbus interface or the operation mode switches of the CM.
Display of the address of a CM3 module
Upon changing the operation mode (local – remote) of a CM3 its address is displayed for 2 sec-
onds via the 7 digit display of the BI (“1.2“ = address 12).
Display of the lowest available address
The lowest available local address is displayed by pressing the set key of the fieldbus interface
(”17.” = address 17). The address of the module in position 17 should be programmed as the next
CM3 module.
Display of modules that have failed
If a module does not respond to queries from the fieldbus interface for a certain period of time, it
moves to “offline“ status. The address of this module is then displayed for 3 seconds (“1.3.“ =
address 13). The display of the address of the module to have last moved to offline status can be re-
peated at any time by pressing the “prgm” key. Display of “0.0.” indicates that none of the modules have
gone offline.
PLEASE NOTE: Only the change to offline status is registered. If a module never answers, it will not be
displayed.
Position indication of actuators with analog position feedback
If an actuator with analog position feedback is operated in „local“ mode the current position is displayed

PCM – Manual Issue: 05/2007 Page 15


Pleiger Elektronik
GmbH & Co. KG

at the 7-segments display of the BI module. This indication is turned off a few seconds after the actua-
tor comes to a standstill. (Remark: This function is only available for BI firmware version V1.6 or
higher).
Display of control inputs 1 and 2
If control input 1 or 2 is set, “E1“ or “E2“ output will appear on the display.

Normal operation
If status display is not necessary, the display will switch to PE.
(program execution).
Display LEDs
LED Modbus RTU Profibus DP
TxD red Transmit Data Error
RxD green Receive Data Data exchange
24V yellow supply voltage DC

5.1.8 Start messages and self test


Directly after the programme has started up, the module displays the last “reset“ cause in the form of
two digits. The module subsequently carries out a short self test. In the event that the self test is not
carried out successfully, the red LED will start to flash. If Profibus DP is selected as fieldbus the red
LED always indicates an error while the error code is shown in the display.
Once the self test has been carried out successfully the version number of the software (x.y) is dis-
played briefly. The normal status display begins subsequently (see above).

5.1.9 Power management


The BI module provides a power management function to limit the 230VAC supply current. To avoid
that the high starting current of the drives blows the fuses the actuators are started successively always
0ne drive each 100ms. Additionally the number of running drives that are connected to the same fuse is
limited to 8. The current required to keep the magnetic valve of a single acting drive closed is ne-
glected. A motor valve is treated like an EHS even though the current is much less.
If more than 8 actuators of a group connected to the same fuse get a command, the execution of this
command is delayed in such a way that not more than 8 actuators run simultaneously. Up to 4 of those
groups can be configured for each BI. The first group begins with the drive using the address 1 and
ends with address A1, the second groups begins with A1+1 and ends with A2 and so on.
The default set up uses 2 groups:
group 1: drive 1..25
group 2: drive 26..50
number of drives: 8

5.1.9.1 Configuring the power management


To configure the power management the „Set“ button must be pressed for at least 3s while the BI starts
up. The display will now show “G.1”. By pressing the “Set” button the group number can be increased.
Pressing the “Prgm” button will select this group and the last address of this group is shown in the dis-
play. The “Set” button may now be used to increment the last address. The highest value is 50, the
lowest value is the last address of the preceding group plus one. Pressing the “Prgm” button once more
will store the address and return to the group number display. If the last group (no 3) is programmed or
any group is programmed to address 50 the set-up is finished an the set-up mode is left.

PCM – Manual Issue: 05/2007 Page 16


Pleiger Elektronik
GmbH & Co. KG

From BI V2.2 the number of drives running at the same time can also be adjusted. Instead of leaving
the set-up mode the number of drives is displayed in the lower digit while the upper digit shows a “n.”.
The number can be changed using the “Set” button. Pressing the “Prgm” button will store the selected
number and leave the set-up mode.
PLEASE NOTE: The BI firmware secures that the last address of a succeeding group is always
higher than the last address of the preceding one. If this condition is not fulfilled the
firmware will adjust the addresses automatically.

5.1.10 Alarm output


To begin with the alarm output is closed after the self test has been carried out successfully. Cyclical
testing is carried out subsequently as to whether the modules connected to the local bus are working
accurately. If a module is not available (offline) or if a CM3 module reports a fault (e.g. timeout), the
alarm output will be opened and not closed until the fault has been removed and the alarm acknowl-
edged on the CM3 module.

5.1.11 Lamp test


Terminal no. 3 on the local bus is used as a lamp test input. As soon as 24V are applied, the 3 LED
and all segments of the 7-segment display of the module are illuminated.

5.1.12 Bus Termination


If the BI module is placed at a physical end of the bus the bus cable has to be terminated. This can be
done by means of a miniature switch at the front of the module. If both sliders are set to ON position the
termination is turned on, if they are set to the opposite position the termination is turned off. All other
settings are not allowed.
The bus termination is an active one and meets the Profibus standard.

5.2 Terminal assignment


Lower terminals
X2 (black) pluggable
1 PE Protective earth of the hat-rail
2 0V 0V of field bus interface
3 Field bus A io rs485 data
4 Field bus B io rs485 data

Upper terminals
X3 (grey) pluggable
5 E2 0V i Control input 2
6 E2 24V i Control input 2, opto
7 E1 0V i Control input 1
8 E1 24V i Control input 1, opto
X4 (black) pluggable
9 0V i DC power supply, max. 6A
10 24VDC i DC power supply, max. 6A
11 Alarm o Alarm output, opens in case of error
12 Alarm o Alarm output, opens in case of error

PCM – Manual Issue: 05/2007 Page 17


Pleiger Elektronik
GmbH & Co. KG

Bus connector
1 Data A io Local data bus, rs485
2 Data B io Local data bus, rs485
3 Lamp test i Lamp test input, 24V = lamps on
4 0VDC i Local power supply
5 +24VDC i Local power supply

ATTENTION: It is imperative to ensure that the supply voltage is not under any circumstances
applied to the local data bus. This leads to the destruction of all connected
modules.

5.3 Technical data


supply voltage DC 24V
current requirement DC max. 50mA, plus external load*
control inputs 24V DC
alarm output Relay, 24V, 0,5A
size WxHxD 22,5mm x 105mm x 115mm
terminal type max. 2,5mm²
operating temperature 0°C – 50°C
Protection IP20

PCM – Manual Issue: 05/2007 Page 18


Pleiger Elektronik
GmbH & Co. KG

6 BI Modbus interface (slave)


The Modbus interface of the fieldbus interface serves to exchange data with a superimposed control
and visualisation system, hereinafter referred to as Modbus master. A register in both report direction
and control direction is used for every valve. Transmission is carried out via an RS485 connection. The
baud rate (4800-76800 baud), the parity (none, even, odd) and the Modbus address (1h..6Fh) can be
parameterised. The number off data bit is fixed to 8. One stop bit is used.
The fieldbus interface has a Modbus RTU interface (slave) and serves the following functions:
03 Read holding registers
06 Preset single register
16 Set multiple registers
This chapter describes the applied data model, i.e. the use and meaning of the individual registers of
the Modbus. This information is required for the preparation of the data model of the superimposed con-
trol system and for the commissioning of the Modbus interface as the case may be. More detailed in-
formation about the Modbus protocol may be obtained from www.modbus.org.

6.1 Modbus data model


The data model described here complies with the program version 1.5 or higher.
The first register is always used to monitor the fieldbus interface itself. The following registers are used
for the CM3 and the IO modules.
In detail, the binary digits of the registers have the following meaning:

6.1.1 Fieldbus interface BI status, register 1, (read only)


Bit Meaning
Bit0 CM3 fault collective message
Bit1 IO fault collective message
Bit2 Fault on the local data bus
Bit3 control input E1 set
Bit4 control input E2 set
Bit5 control input „lamp test“ set
Bit6..14 not used
Bit15 live bit, changes state every 2s *
*implemented in BI version V1.6 or higher
CM3 fault collective message
This binary digit is set if at least one EHS-CM3 reports a fault.
IO fault collective message
This binary digit is set if at least one IO module reports a fault.
Fault on the local data bus
This binary digit is set if at least one module on the local bus replies to broadcast address 0 or if further
faults arise that cannot be allocated to a specific bus participant.
Control input E1 / E2 set
This binary digit is set if control input E1 / E2 has been set (24V).
Control input lamp test set
This binary digit is set if lamp test input has been set.

PCM – Manual Issue: 05/2007 Page 19


Pleiger Elektronik
GmbH & Co. KG

6.1.2 CM3 status register (read only)


The CM3 status register includes the valve position and the valve error messages. The register number
depends on the module address (1-50).
Register number = module address + 1
(50 registers, from no 2 to no 51)
The lower-order byte of the register contains the position information:
Value Meaning
0..100 actual position of valves with analogue position feedback
(128..228) most significant bit is set while drive is running (add128)
101 drive closed and in a standstill
102 drive neither open nor closed
103 drive open and in a standstill
105 drive in open position, close command received
106 drive in closed position, open command received
107 drive neither open nor closed while closing
108 drive neither open nor closed while opening
109 drive indicating closed position but is still running
110 drive indicating open position but is still running
111 unknown position

The higher-order byte of the register indicates the error messages:


Bit Meaning
Bit 0: error message 0 = no error
Bit 1: (Bit 0-2 binary) 1 = timeout while opening
Bit 2: 2 = timeout while closing
3 = invalid feedback
4 = invalid command
5 = self test error
6..7 = not used
Bit 3: command close received via mimic input*
Bit 4: command open received via mimic input*
Bit 5: local / remote switch in local position
Bit 6: no AC supply (230VAC)
Bit 7: offline, no response on local bus
The error flags 1..4 stay set until the cause of the error is removed or a new command is sent. Runtime
errors generally require resending a command (see also 6.1.5).
*These status bit are implemented in CM3 firmware V1.6 or higher. They indicate the commands sent
via mimic inputs as long as they are valid that means they were not overwritten by a BI command.
ATTENTION: This function was slightly changed from CM3 V1.9 upwards. The bit is set as soon as the
corresponding input is set and reset when the input is released. In any case the bit is set for at least 5s.
This way also the resetting of the inputs is indicated.

6.1.3 IO status register (read only)


The IO status registers contain the status of the analogue and digital inputs of an IO module. An IO
module occupies a total of 9 registers. The register number depends on the module address.
The module addresses are in the range of 51 – 60.

PCM – Manual Issue: 05/2007 Page 20


Pleiger Elektronik
GmbH & Co. KG

Register number of the first register = 9*(module addresses -51) + 52


(90 registers, from no 52 to no 141)
The first register contains the status of the 8 digital inputs in the lower-order byte and error messages in
the higher-order byte.
Bit Meaning
Bit 0..7: digital input 1..8 set
Bit 8: address was changed after last start up
Bit 9: error analog input 1..8
Bit 10: used internally
Bit 15: offline, no response on local bus
The following 8 registers contain one each of the 8 measured values as 12 binary digit value (0..20mA
= 0..4000 Incr.). A valid value must be even.
Attention: An odd value indicates that the last measurement has not been updated because of an in-
valid measurement.

6.1.4 Fieldbus interface BI remote control, register 142 (read/write)


This register can be used by the Modbus master to control various functions of the fieldbus interface.
Bit Meaning
Bit0 reserved for function “enable all mimic diagram inputs”
Bit1 reserved for function “operation mode is passive”
Bit2..14 not used
Bit15 *Profibus data are valid (see also 7.3.1)
*implemented in BI version V1.6 or higher

6.1.5 CM3 control register (read/write)


A CM3 control register is used to send a command to a valve. The register number depends on the
module address (1-50).
Register number = module address + 142
(50 registers, from no 143 to no 192)
Only the lower-order byte of the valve control register is used.
Command Meaning
0..100 position set point for %Pos drives
101 close drive
102 stop drive
103 open drive
104 acknowledge error, erase last command
111 commands by mimic diagram inputs only
If command 111 is sent the BI completely passes control to the CM3 modules. The CM3 acts as if there
is no BI. CM3 versions V1.6 and older require this command to enable the mimic inputs permanently
and not only as long as the inputs are set. V1.7 and newer always react properly on mimic inputs in re-
mote mode and do not absolutely require this command.
Any command change will reset the errors 1..4. There are two ways to force a command change.
1. Sending a 104 and a 101/103 afterwards with a sufficient delay ( 1s). This will erase the old com-
mand first and then send a new one.

PCM – Manual Issue: 05/2007 Page 21


Pleiger Elektronik
GmbH & Co. KG

2. Setting the most significant bit of the command byte to indicate a new command. The CM3 will react
on this command immediately. The bit should be kept high for at least 1s and should be reset after-
wards. This procedure is recommended because of the faster reaction.
Beside resetting error conditions restarting a command may be useful in certain applications like actua-
tors that may be operated manually by handwheel (override). If such a drive is closed by command and
opened manually afterwards a repeated close command will close it again.
example:
send close command 128+101=229, actuator starts running, wait 1s, send close command 101
actuator is closed
actuator is opened manually
send close command 128+101=229 once more , actuator starts running, wait 1s, send close
command 101
actuator is closed again

6.1.6 IO control register (read/write)


The IO control register is used to set the 4 digital outputs of the IO 8/8/4 module. The register number
depends on the module address. The module addresses are in the range of 51 – 60.
Register number = (module address – 51) + 193
(10 registers, from no 193 to no 202)
Bit Meaning
Bit 0..3: digital output 1..4 set, outputs are reset if IO 8/8/4 goes offline
Bit 4..7: digital output 1..4 set, outputs stay on if IO 8/8/4 goes offline

6.1.7 RK status register (read only)


The RK status registers contain the status of the digital inputs and error flags of an RK module. An RK
module occupies a total of 2 registers. The register number depends on the module address.
The module addresses are in the range of 61 – 80.
Register number = 2*(module address – 61) + 203
(40 registers, from no 203 to no 241)
The first register shows the error flags in the lower byte and a 8 bit counter value in the upper byte.
Value Meaning
Bit 0: fuse is damaged
Bit 1: address button pressed
Bit 2: used internally
Bit 7: offline, no response at the local bus
Bit 8-15 8 Bit counter, all changes of input 1 are counted.
The second register shows the status of the 16 digital inputs.
Value Meaning
Bit 0: digital input 1 (24V = Bit set)

Bit 15: digital input 16 (24V = Bit set)

6.1.8 RK control register (read / write)


The RK control register are used to control the relay outputs. Each module uses one register.

PCM – Manual Issue: 05/2007 Page 22


Pleiger Elektronik
GmbH & Co. KG

The register number depends on the module address.


The module addresses are in the range of 61 – 80.
Register number = (module address – 61) + 243
(20 registers, from no 243 to no 262)
Value Meaning
Bit 0..7: set relay output 1..8;
all outputs are reset if the data connection between PLC and PCM system fails
Bit 8..15: set relay output 1..8;
all outputs keep the current state if the data connection between PLC and PCM system fails

6.2 Protocol Watchdog


The BI Module permanently supervises the proper function of the Modbus (Profibus). The BI must re-
ceive at least one valid Modbus request every 5s otherwise the following functions will be carried out:
A command 111 „enable mimic diagram inputs“ is sent to all CM3 modules.
All control bits 0..3 of all IO8/8/4 are set to 0, that means that all outputs are reset
All control bits 0..7 of all RK16/8 are set to 0, that means that all outputs are reset
We recommend to start a request at least every second. This function is implemented for the Profibus
protocol is the same way.

PCM – Manual Issue: 05/2007 Page 23


Pleiger Elektronik
GmbH & Co. KG

6.3 Register summary


Reg. Status-Register higher -order byte lower-order byte
No Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1 BI status Inputs Faults
2 CM3 status, module 1 messages Errors Position information
up to
51 CM3 status, module 50 messages Errors Position information
52 IO status, module 51 Error messages 8 <---digital inputs---> 1
53 analogue input 1
54 analogue input 2
55-
up to
59
60 analogue input 8
up to
133 IO status, module 60 Error messages 8 <---digital inputs---> 1
134 analogue input 1
135 analogue input 2
136-
up to
140
141 analogue input 8
Reg. Control-Register higher -order byte lower-order byte
No Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
142 BI control Mi
143 CM3 control, module 1 control commands
up to
192 CM3 control, module 50 control commands
193 IO control, module 51 4<dig.outp.>1 4<dig.outp.>1
up to
202 IO control, module 60 4<dig.outp.>1 4<dig.outp.>1
Reg. Status-Register higher -order byte lower-order byte
Nr. Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
203 relay module 61 counter Error messages
204 16 <---digital inputs---> 9 8 <---digital inputs---> 1
up to
241 relay module 80 counter Error messages
242 16 <---digital inputs---> 9 8 <---digital inputs---> 1
Reg. Control-Register higher -order byte lower-order byte
Nr. Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
243 relay module 61 8 <-- digital outputs --> 1 8 <-- digital outputs --> 1
up to
262 relay module 80 8 <-- digital outputs --> 1 8 <-- digital outputs --> 1
not used =

PCM – Manual Issue: 05/2007 Page 24


Pleiger Elektronik
GmbH & Co. KG

7 BI Profibus DP interface (slave)


The Profibus DPV0 interface is available as an alternative to the Modbus and can be chosen via the
set-up menu of the fieldbus interface (BI). Automatic baud rate identification is used. Baud rates be-
tween 9600 baud and 1.5 Mbaud are permissible. If required a bus terminator (in accordance with the
Profibus standard) can be connected via a miniature two-pole switch in the front of the housing.
The advanced V1 and V2 services are not available. Differing from the Profibus standard an inexpen-
sive screw-type terminal is used for the electrical connection instead of a sub-D connector. More de-
tailed information about the Profibus protocol may be obtained from the standard EN 50170 or from the
„Profibus Nutzer Organisation“ (PNO, www.profibus.com).

7.1 Profibus data model


For compatibility reasons the same data model is used as for the Modbus. 16 binary digit-wide data
words are used instead of the Modbus registers. On account of the maximum telegram length of 244
bytes a maximum of 7 IO modules can be used for the Profibus protocol. The data model is described
in the “PE_PCM_2.gsd“ GSD file. The meaning of the individual data words corresponds to those in
the registers for the Modbus protocol.
To avoid unnecessary data transfer the BI module is set-up as a modular station. The following mod-
ules are available.
Module 1 BI, status & control, 1 word read, 1 word write
Module 2 5x CM3, status & control, 5 words read, 5 words write
Module 3 10x CM3, status & control, 10 words read, 10 words write
Module 4 1x IO8/8/4, status & control, 9 words read, 1 word write
Module 5 1x RK16/8, status & control, 2 words read, 1 word write
Module 6 5x RK16/8, status & control, 10 words read, 5 words write
The module type 1 must always be inserted in first place. Next up to 50 CM3, 7 IO8/8/4 and 20 RK16/8
may be added. Please keep in mind that the number of data bytes both read and write must not exceed
244.

7.1.1 Fieldbus interface to superimposed control system (status words)


Data word Meaning
1 Status field bus interface
1 each Status CM3, address 1..50
9 each Status IO 8/8/4, address 51..57
2 each Status RK 16/8, address 61..80

7.1.2 Superimposed control system to fieldbus interface (control words)


Data word Meaning
1 Command field bus interface
1 each Command CM3, address 1..50
1 each Command IO 8/8/4, address 51..57
1 each Command RK 16/8, address 61..80

PCM – Manual Issue: 05/2007 Page 25


Pleiger Elektronik
GmbH & Co. KG

7.1.3 Data Valid Bit


Some Profibus DP masters keep on sending data even if the supervisory controller is stopped. In this
case all commands are set to 0. This is not suitable for PCM system. Therefore the highest Bit15 of the
control word of the BI is used as a „Data Valid Bit“. If this bit is not set the Profibus connection is treated
as invalid.
This Bit is used only if the Bit0 of the first Parameter Byte is set to 1, otherwise the data is always
treated as valid data. This function is only implemented in BI firmware version V1.6 or higher.

PCM – Manual Issue: 05/2007 Page 26


Pleiger Elektronik
GmbH & Co. KG

8 Assembly of the system


Certain boundary conditions must be adhered to during the assembly of the complete control systems
in order to ensure reliable and trouble free operation.
Only a maximum of 50 CM3 and 10 (7 for the Profibus DP) IO modules are to be connected to a
fieldbus interface.
The IO modules must be aligned to the left and the CM3 modules to the right of the fieldbus inter-
face.
All 230VAC supplies must be fused with 16A B characteristic.
The 24VDC supply may be connected several times to separate the supply for different systems
(etc. bilge, ballast). Each 24V supply is separately fused up to 4AT. All 0V supplies must be con-
nected directly to the same terminal. 0V supply is fused with a common 6AT fuse. For the
connection of the DC supply the BI (9, 10) or the plugs of the prefabricated cable sets must be
used.
The local data bus and the lamp test control may be extended by means of prefabricated cable
sets. Up to 4 adapting cable and one extension cable may be used per BI module. The screen of
these cable must be connected to a PE terminal right beside the plug connector. The PE terminal is
also used to fix the modules on the rail mount.
All control signals from and to the CM3 and IO 8/8/4 modules are supplied via the 24VDC of the
CM3 respectively the IO 8/8/4 modules.
All cables leaving the control cabinet and being connected to the modules must be screened. The
screen must be connected extensively to the mounting plate. So-called “pigtails“, i.e. cables be-
tween the screen and a PE terminal, are not permissible.

8.1 24VDC current requirements


To calculate the 24VDC supply current of a PCM system the following values may be used.
Module Operation mode max. average
BI 50mA 40mA
CM3 incl. OC3 feed back module 60mA 40mA
incl. conti feedback module 80mA 60mA
additionally, if mimic interface is used 70mA 35mA
IO 8/8/4 200mA 150mA

8.2 Controlling via circuit mimic diagram


The CM3 modules can be used without a fieldbus interface for applications in which the actuators are
controlled exclusively by a circuit mimic diagram. The feeding-in of the 24VDC supply voltage is then
via the local bus connector pins 4 and 5. The voltage must have external fuse protection amounting to a
maximum of 6A. Insofar as necessary, a 24VDC lamp test signal is also connected via the local bus
connector. The current consumption of this control input amounts to approx. 1mA per CM3 module.

PCM – Manual Issue: 05/2007 Page 27


Pleiger Elektronik
GmbH & Co. KG

8.3 Commissioning hints


Incorrectly connected drives of defective cables may cause damage of the CM3 modules or
the OC3 feedback modules. To avoid this some tests must be performed before 24VDC or
230VAC supply is turned on.
1. 24VDC and 230VAC are completely separated from each other and from PE e.g. the rail-hat.
Therefore a high insulation resistance must be measured between those circuits. The insulation re-
sistance measurement should be performed with an
insulation resistance meter with 50 to 500VDC test 1. 0VDC to PE 1 MOhm
voltage. The following minimum resistance values 2. 0VDC to L, N 1 MOhm
must be achieved: 3. 24VDC to PE 1 MOhm
If a suitable insulation meter is not available a stan- 4. 24VDC to L, N 1 MOhm
dard multimeter may be used instead. This measuring 5. N to PE 1 MOhm
must be performed during commissioning and should
6. L to PE 1 MOhm
be repeated after any repair works on the cabling of
the actuators.
2. Please also check that pin 13 of the CM3 module, this is the position feedback input 4..20mA, is
connected only for those actuators that really use an analog position feedback signal.
3. Turn on 230VAC for a few devices only and check proper operation carefully before connecting the
next devices top 230VAC.

8.4 Safety Advice


The blade beside shows an important safety advice and
CM3 Safety Advice
must be fixed at the top-hat rail right beside the installed
Always plug in CM3 modules.
red connector last
and pull it off first! If CM3 modules are mounted on different top-hat rails one
(AC supply voltage) blade has to be fixed at each rail.

Pay attention to this safety advice during any kind of work on the pluggable screw
terminals!

8.5 Accessories
For the proper installation of PCM systems the following accessories are required.

8.5.1 Adapting Cable


This cable is used if the 24VDC supply shall be feed several times. The length of the cable is app.
20cm must not be extended or replaced by a different cable. The modules are fixed on both sides of the
cable by means of an end holder that is fastened on the hat-rail. The right plug (4+5) must be con-
nected to 24VDC power weiß weiß
1 we
iß 1
supply. Connect pin 4 to 2
braun

b ra
grün
un
braun
2
grün
3 elb 3
the common 0V directly, 4 grü
n+g
4
5 5
connect pin 5 to 24V fused
up to 4A.
Article-No: 9319710190

PCM – Manual Issue: 05/2007 Page 28


Pleiger Elektronik
GmbH & Co. KG

8.5.2 Extension Cable


This cable is used to connect additional modules on a second hat-rail to the same BI module. Only one
cable can be used per BI module. The shield of the extension cable must be connected to the hat-rail
via PE terminals. These terminals
are also used to fix the modules
mechanically. The cable is app. 150 5
cm long and must not be extended! 4
+g
e lb
we 3 gr
ün

If such a cable is used the 24VDC 1


2

b ra
un
2 bra
we
un

1 iß

power supply must be connected to 3


4
grü
n+g
elb

the modules separately. 5

Article-No: 9319710180

8.5.3 Adapting Cable for RK 16/8


This cable is required to connect one or
more relay modules to the local bus of BI,
CM3 or IO 8/8/4.
Artikel-Nr.: 9319710330

8.5.4 Safety Advice Plate


This safety advice must be fixed at the hat-rail close by the installed
CM3 modules (at each hat-rail with CM3).
Article-No: 9319932210

8.5.5 End Holder


The end holder are fixed to the hat-rail on the right side of the modules.
If the adapter cable is used one holder is also fixed on the left side of
the modules.
Article-No: 4639020830

8.5.6 Noise Suppression Filter


If a BI module is used on the bridge one filter must be inserted in the common 24VDC supply of all
modules (according GL-Rule EMC1: Using on the bridge or on the open deck).
The current must not exceed 16A.
The filter is screwed on the mounting plate directly.
A sufficient electrical and thermal contact to the mounting
plate must be ensured.
Article-No: 4470200050

PCM – Manual Issue: 05/2007 Page 29

You might also like