Professional Documents
Culture Documents
Legends: General Notes and Specification:: Electrical Lighting Layout Electrical Power Layout
Legends: General Notes and Specification:: Electrical Lighting Layout Electrical Power Layout
Legends: General Notes and Specification:: Electrical Lighting Layout Electrical Power Layout
REF
REF
REF
REF
REF
ALL ELECTRICAL WORKS SHALL CONFORM WITH THE RULES AND
REF
3.
REF
CEILING LIGHT OUTLET
REF
B
PANEL BOARD
REGULATIONS OF AUTHORITIES HAVING JURISDICTION.
REF
4. ALL MATERIAL AND EQUIPMENT SHALL BE NEW AND APPROVED FOR
CIRCUIT BREAKER THE PARTICULAR PURPOSE.
CIRCUIT RUN
S1 B
5. ALL CONDUIT SYSTEM SHALL BE DONE USING RIGID STEEL CONDUIT FOR
SERVICE ENTRANCE AND PVC CONDUIT FOR BRANCH CIRCUITS.
S
B
CIRCUIT HOMERUN 1 GANG PLATE 6. CONDUIT SYSTEMS AND INSTALLATIONS SHALL BE COMPLETE IN EVERY
1 1
NO. INDICATE CIRCUIT DETAIL, PLASTERED, AND FASTENED IN PLACE FROM BOXES TO BOXES
2
RETURN SWITCH
S 2 2 GANG PLATE
7.
PRIOR TO INSTALLATION OF CONDUITS.
WHENEVER REQUIRED, PULL BOXES AND JUNCTION BOXES SHALL BE
INSTALLED AT CONVENIENT LOCATIONS ALTHOUGH SUCH BOXES ARE
REFRIGERATOR NOT INDICATED IN PLANS.
REF 8. SPARE CONDUITS FOR SPARE CIRCUITS SHALL BE INSTALLED FROM
SERVICE EQUIPMENT TO CEILING OR OUTSIDE THE BUILDING FOR FUTURE
COOKING UNIT
CU
PURPOSES THEY WILL SERVE.
A A
9. IN BRANCH CIRCUIT HOMERUN WIRING, WHERE THE RUN FROM
SERVICE EQUIPMENT TO FIRST OUTLET OF THE CIRCUIT, EXCESS 15m, THE
SIZE OF BRANCH CIRCUIT HOMERUN SHALL BE MADE ONE SIZE HIGHER.
10. MOUNTING HEIGHTS IN EQUIPMENT AND WIRING DEVICES SHALL BE AS
3
ACU FOLLOWS:
KWHM - 1830 mm FROM FINISHED GRADE LINE TO THE CENTER OF THE
S1 A
DEVICE.
SERVICE EQUIPMENT - 1830 mm FROM THE FINISH FLOOR LINE TO THE TOP OF
THE EQUIPMENT.
SWITCHES - 137 mm FROM FINISH FLOOR LINE TO THE CENTER OF THE BOX.
RECEPTACLES - 30 mm FROM FINISH FLOOR LINE TO THE CENTER OF THE BOX;
15mm FROM FINISHED COUNTER SURFACE TO THE COUNTER BOX.
ELECTRICAL LIGHTING LAYOUT ELECTRICAL POWER LAYOUT 11. GFCI OUTLET SHALL BE INSTALLED FOR PARTICULAR APPLICATIONS
SCALE 1:100 MTS SCALE 1:100 MTS REQUIRED BY THE CODE.
12. THE TYPE POWER SERVICE TO BE SUPPLIED SHALL BE 220V, 1PH, 21V, 60
SINGLE LINE DIAGRAM: Hz LINE-TO-GROUND.
SCHEDULE OF LOADS:
N
Use: 2-8 sq.mm THHN copper wire in 25mm
TYPE OF SERVICE: 230V, 2 WIRE, 60 HZ
LINE TO GROUND SYSTEM
PANELBOARD diameter RSC PIPE
SIZE OF HOMERUN
QTY DESCRIPTION LOAD QTY VA VOLTS AMPS CB RATING
WIRE mm2THHN CONDUIT mmø W E
1 LIGHTING OUTLET 7 700 230 3.04 15 2-2.0 mm2 THHN WIRE in 20 mm dia. pipe LOCATION MAP:
2 CONVINIENCE OUTLET 9 1,620 230 7.04 20 2-3.5 mm2 THHN WIRE in 20 mm dia. pipe KILOWATT-HOUR M
3 AIRCONDITION 2-3.5 mm2 THHN WIRE in 20 mm dia. pipe
METER
1 2,760 230 12 20
5 KITCHEN OUTLET 1 2,300 230 10 20 2-3.5 mm2 THHN WIRE in 20 mm dia. pipe Use: 2-14 sq.mm THHN copper wire in 32mm
diameter PVC PIPE SITE
TOTAL 19 9,220 230 40.08 60 2-14 mm2 THHN WIRE in 32 mm dia. pipe
PB
D1
230 VOLTS 1 2
COPPER (G)
D1
= 40.08 AMPERES 20AT 20AT
ACU 3 4 REF D1
WITH 80% DEMAND FACTOR 20AT
KITCHEN OUTLET 5
ISSUED NO. IMPORTANT PROFESSIONAL ELECTRICAL ENGINEER REMARKS PROJECT TITLE CONFORME SHEET NO.:
DATE ISSUED: PRC REG NO.:
DRAWN BY: VALID UNTIL:
SINGLE FAMILY DWELLING UNIT KENWIN NEIL G. AGCAOILI
DESIGNED BY:
CHECKED BY: ENGR. RIGOR GABUR
SIGNATURE OVER PRINTED NAME
ISSUED ON:
ISSUED AT: LAOAG CITY, ILOCOS NORTE OWNER
1
TIN NO. :