REFERENCE
86 A1 47FF 03
ESCALA Power7
Hardware
October 2011
BULL CEDOC
357 AVENUE PATTON
B.P.20845
49008 ANGERS CEDEX 01
FRANCE
REFERENCE
86 A1 47FF 03
The following copyright notice protects this book under Copyright laws which prohibit such actions as, but not limited to, copying,
distributing, modifying, and making derivative works.
Printed in France
Suggestions and criticisms concerning the form, content, and presentation of this book are
invited. A form is provided at the end of this book for this purpose.
To order additional copies of this book or other Bull Technical Publications, you are invited
to use the Ordering Form also provided at the end of this book.
The information in this document is subject to change without notice. Bull will not be liable for errors contained herein, or
for incidental or consequential damages in connection with the use of this material.
Contents
Safety notices . . . . . . . . . . . vii (266E) Reference codes . . . . . . . 181
Contents v
(57B8) Reference codes . . . . . . . 907 (6333) Reference codes . . . . . . 1141
Several countries require the safety information contained in product publications to be presented in their
national languages. If this requirement applies to your country, a safety information booklet is included
in the publications package shipped with the product. The booklet contains the safety information in
your national language with references to the U.S. English source. Before using a U.S. English publication
to install, operate, or service this product, you must first become familiar with the related safety
information in the booklet. You should also refer to the booklet any time you do not clearly understand
any safety information in the U.S. English publications.
Das Produkt ist nicht für den Einsatz an Bildschirmarbeitsplätzen im Sinne § 2 der
Bildschirmarbeitsverordnung geeignet.
IBM® servers can use I/O cards or features that are fiber-optic based and that utilize lasers or LEDs.
Laser compliance
Electrical voltage and current from power, telephone, and communication cables are hazardous. To
avoid a shock hazard:
v Connect power to this unit only with the IBM provided power cord. Do not use the IBM
provided power cord for any other product.
v Do not open or service any power supply assembly.
v Do not connect or disconnect any cables or perform installation, maintenance, or reconfiguration
of this product during an electrical storm.
v The product might be equipped with multiple power cords. To remove all hazardous voltages,
disconnect all power cords.
v Connect all power cords to a properly wired and grounded electrical outlet. Ensure that the outlet
supplies proper voltage and phase rotation according to the system rating plate.
v Connect any equipment that will be attached to this product to properly wired outlets.
v When possible, use one hand only to connect or disconnect signal cables.
v Never turn on any equipment when there is evidence of fire, water, or structural damage.
v Disconnect the attached power cords, telecommunications systems, networks, and modems before
you open the device covers, unless instructed otherwise in the installation and configuration
procedures.
v Connect and disconnect cables as described in the following procedures when installing, moving,
or opening covers on this product or attached devices.
To Disconnect:
1. Turn off everything (unless instructed otherwise).
2. Remove the power cords from the outlets.
3. Remove the signal cables from the connectors.
4. Remove all cables from the devices
To Connect:
1. Turn off everything (unless instructed otherwise).
2. Attach all cables to the devices.
3. Attach the signal cables to the connectors.
4. Attach the power cords to the outlets.
5. Turn on the devices.
(D005)
DANGER
v Each rack cabinet might have more than one power cord. Be sure to disconnect all power cords in
the rack cabinet when directed to disconnect power during servicing.
v Connect all devices installed in a rack cabinet to power devices installed in the same rack
cabinet. Do not plug a power cord from a device installed in one rack cabinet into a power
device installed in a different rack cabinet.
v An electrical outlet that is not correctly wired could place hazardous voltage on the metal parts of
the system or the devices that attach to the system. It is the responsibility of the customer to
ensure that the outlet is correctly wired and grounded to prevent an electrical shock.
CAUTION
v Do not install a unit in a rack where the internal rack ambient temperatures will exceed the
manufacturer's recommended ambient temperature for all your rack-mounted devices.
v Do not install a unit in a rack where the air flow is compromised. Ensure that air flow is not
blocked or reduced on any side, front, or back of a unit used for air flow through the unit.
v Consideration should be given to the connection of the equipment to the supply circuit so that
overloading of the circuits does not compromise the supply wiring or overcurrent protection. To
provide the correct power connection to a rack, refer to the rating labels located on the
equipment in the rack to determine the total power requirement of the supply circuit.
v (For sliding drawers.) Do not pull out or install any drawer or feature if the rack stabilizer brackets
are not attached to the rack. Do not pull out more than one drawer at a time. The rack might
become unstable if you pull out more than one drawer at a time.
v (For fixed drawers.) This drawer is a fixed drawer and must not be moved for servicing unless
specified by the manufacturer. Attempting to move the drawer partially or completely out of the
rack might cause the rack to become unstable or cause the drawer to fall out of the rack.
(R001)
Safety notices ix
CAUTION:
Removing components from the upper positions in the rack cabinet improves rack stability during
relocation. Follow these general guidelines whenever you relocate a populated rack cabinet within a
room or building:
v Reduce the weight of the rack cabinet by removing equipment starting at the top of the rack
cabinet. When possible, restore the rack cabinet to the configuration of the rack cabinet as you
received it. If this configuration is not known, you must observe the following precautions:
– Remove all devices in the 32U position and above.
– Ensure that the heaviest devices are installed in the bottom of the rack cabinet.
– Ensure that there are no empty U-levels between devices installed in the rack cabinet below the
32U level.
v If the rack cabinet you are relocating is part of a suite of rack cabinets, detach the rack cabinet from
the suite.
v Inspect the route that you plan to take to eliminate potential hazards.
v Verify that the route that you choose can support the weight of the loaded rack cabinet. Refer to the
documentation that comes with your rack cabinet for the weight of a loaded rack cabinet.
v Verify that all door openings are at least 760 x 230 mm (30 x 80 in.).
v Ensure that all devices, shelves, drawers, doors, and cables are secure.
v Ensure that the four leveling pads are raised to their highest position.
v Ensure that there is no stabilizer bracket installed on the rack cabinet during movement.
v Do not use a ramp inclined at more than 10 degrees.
v When the rack cabinet is in the new location, complete the following steps:
– Lower the four leveling pads.
– Install stabilizer brackets on the rack cabinet.
– If you removed any devices from the rack cabinet, repopulate the rack cabinet from the lowest
position to the highest position.
v If a long-distance relocation is required, restore the rack cabinet to the configuration of the rack
cabinet as you received it. Pack the rack cabinet in the original packaging material, or equivalent.
Also lower the leveling pads to raise the casters off of the pallet and bolt the rack cabinet to the
pallet.
(R002)
(L001)
(L002)
or
All lasers are certified in the U.S. to conform to the requirements of DHHS 21 CFR Subchapter J for class
1 laser products. Outside the U.S., they are certified to be in compliance with IEC 60825 as a class 1 laser
product. Consult the label on each part for laser certification numbers and approval information.
CAUTION:
This product might contain one or more of the following devices: CD-ROM drive, DVD-ROM drive,
DVD-RAM drive, or laser module, which are Class 1 laser products. Note the following information:
v Do not remove the covers. Removing the covers of the laser product could result in exposure to
hazardous laser radiation. There are no serviceable parts inside the device.
v Use of the controls or adjustments or performance of procedures other than those specified herein
might result in hazardous radiation exposure.
(C026)
Safety notices xi
CAUTION:
Data processing environments can contain equipment transmitting on system links with laser modules
that operate at greater than Class 1 power levels. For this reason, never look into the end of an optical
fiber cable or open receptacle. (C027)
CAUTION:
This product contains a Class 1M laser. Do not view directly with optical instruments. (C028)
CAUTION:
Some laser products contain an embedded Class 3A or Class 3B laser diode. Note the following
information: laser radiation when open. Do not stare into the beam, do not view directly with optical
instruments, and avoid direct exposure to the beam. (C030)
CAUTION:
The battery contains lithium. To avoid possible explosion, do not burn or charge the battery.
Do Not:
v ___ Throw or immerse into water
v ___ Heat to more than 100°C (212°F)
v ___ Repair or disassemble
Exchange only with the IBM-approved part. Recycle or discard the battery as instructed by local
regulations. In the United States, IBM has a process for the collection of this battery. For information,
call 1-800-426-4333. Have the IBM part number for the battery unit available when you call. (C003)
The following comments apply to the IBM servers that have been designated as conforming to NEBS
(Network Equipment-Building System) GR-1089-CORE:
The intrabuilding ports of this equipment are suitable for connection to intrabuilding or unexposed
wiring or cabling only. The intrabuilding ports of this equipment must not be metallically connected to the
interfaces that connect to the OSP (outside plant) or its wiring. These interfaces are designed for use as
intrabuilding interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE) and require isolation
from the exposed OSP cabling. The addition of primary protectors is not sufficient protection to connect
these interfaces metallically to OSP wiring.
Note: All Ethernet cables must be shielded and grounded at both ends.
The ac-powered system does not require the use of an external surge protection device (SPD).
The dc-powered system employs an isolated DC return (DC-I) design. The DC battery return terminal
shall not be connected to the chassis or frame ground.
Reference codes are diagnostic aids that help you determine the source of a hardware or operating
system problem. Using a reference code enables you to find the solution to fix the problem. To use
reference codes effectively, you must use them in conjunction with other service and support procedures.
Note: System reference codes (SRCs) often indicate failing items. Some failing items are required to be
exchanged in groups until the problem is solved. Other failing items are flagged as mandatory exchange
and must be exchanged before the service action is complete, even if the problem appears to have been
repaired. For more information, see “Block replacement of FRUs.”
The priorities of performing the FRU replacements or procedures are shown in the following ways,
depending on how you view the SRC:
v Advanced System Management Interface (ASMI): The ASMI shows a priority with each callout in the
log.
v Control panel: The control panel shows one of the following priorities with each callout:
– H = High
– M = Medium
– MA = Medium group A
– MB = Medium group B
– MC = Medium group C
– L = Low
v Management console: The details of the serviceable event display the FRU replacement priority as
high, medium, and so on.
v Service action log: In the SAL, the Part Action for the FRU in the view of the event shows the
replacement priority.
100000AA 100000AA
10001503 10001503
Explanation: Download in process
Explanation: Power supply failure
Response: No action required. This reference code is
Response: Follow the instructions for the items listed
logged for information only.
in the FRU List.
Failing Item:
100000AC 100000AC
v PWRSPLY
Explanation: Detected AC loss
v TWRCARD
Response: If system powers on normally or stays
powered on after AC power failure, no replacement of
10001507 10001507
parts may be needed. If parts are replaced, follow the
instructions for the items listed in the FRU List. Explanation: Power supply plugging ID error
Failing Item: Response: Follow the instructions for the items listed
v ACMODUL in the FRU List.
Failing Item:
100000AD 100000AD v PWRSPLY
Explanation: A reset of the service processor caused v VPDPART
the system to power off.
10001511 10001511
10001500 10001500 Explanation: Power supply failure
Explanation: Detected AC loss Response: Follow the instructions for the items listed
Response: Before replacing any parts, verify that the in the FRU List.
AC input voltage is correct, follow the instructions for Failing Item:
the items listed in the FRU List.
v PWRSPLY
Failing Item: v TWRCARD
v PWRSPLY
v TWRCARD 10001512 10001512
Explanation: Power supply failure
10001501 10001501
Response: Follow the instructions for the items listed
Explanation: Power supply failure in the FRU List.
Response: Follow the instructions for the items listed Failing Item:
in the FRU List.
v PWRSPLY
Failing Item: v TWRCARD
v PWRSPLY v CBLALL
v TWRCARD
Response: The required power supplies are not Explanation: Power supply failure
installed. Follow the instructions for the items listed in Response: Follow the instructions for the items listed
the FRU List. in the FRU List.
Failing Item: Failing Item:
v PWRSPLY v PWRSPLY
v TWRCARD v TWRCARD
v PWR1900
10001B18 10001B18
v TWRCARD
Explanation: Load fault on the +1.5V bus
Response: Follow the instructions for the items listed 10002606 10002606
in the FRU List.
Explanation: Power-good fault
Failing Item:
Response: Follow the instructions for the items listed
v PWR1900
in the FRU List.
Failing Item:
10001DA0 10001DA0
v PWR1900
Explanation: I/O planar SPCN fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
10002607 10002607
Failing Item:
Explanation: Power-good fault
v PWR1900
Response: Follow the instructions for the items listed
in the FRU List.
10001F02 10001F02
Failing Item:
Explanation: SPCN trace information saved
v PWR1900
Response: No action required. This reference code is v TWRCARD
logged for information only.
10002608 10002608
10002600 10002600
Explanation: Power-good fault
Explanation: Power-good fault
Response: Follow the instructions for the items listed
Response: Follow the instructions for the items listed in the FRU List.
in the FRU List.
Failing Item:
Failing Item:
v PWR1900
v PGDPART
v TWRCARD
10002601 10002601
10002609 10002609
Explanation: Power-good fault
Explanation: Power-good fault
Response: Follow the instructions for the items listed
Response: Follow the instructions for the items listed
in the FRU List.
in the FRU List.
Failing Item:
Failing Item:
v PGDPART
v PWR1900
v TWRCARD
10002603 10002603
Explanation: Power-good fault 10002612 10002612
Response: Follow the instructions for the items listed Explanation: Optical Converter 5V Fault
in the FRU List.
Response: The SPCN detected a fault on the SPCN
Failing Item: card optical converter 5V. Follow the instructions for
v PGDPART the items listed in the FRU List.
Failing Item:
10002605 10002605 v CBLALL
Explanation: Power-good fault v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
Failing Item:
v I2CBUS
10003100 10003100
v TWRCARD
Explanation: I2C bus controller communication fault
Response: Follow the instructions for the items listed 10003106 10003106
in the FRU List.
Explanation: I2C bus 6 communication fault
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v TWRCARD
Failing Item:
v I2CBUS
10003101 10003101
v TWRCARD
Explanation: I2C bus 1 communication fault
Response: Follow the instructions for the items listed 1000310A 1000310A
in the FRU List.
Explanation: I2C bus SPCN VPD communication fault
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v TWRCARD
Failing Item:
v I2CBUS
10003102 10003102
v TWRCARD
Explanation: I2C bus 2 communication fault
Response: Follow the instructions for the items listed 1000310B 1000310B
in the FRU List.
Explanation: I2C bus SPCN VPD communication fault
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v TWRCARD
Failing Item:
v I2CBUS
10003103 10003103
v TWRCARD
Explanation: I2C bus 3 communication fault
Response: Follow the instructions for the items listed 10003110 10003110
in the FRU List.
Explanation: I2C bus DASD backplane 1
Failing Item: communication fault
v I2CBUS
Response: Follow the instructions for the items listed
v TWRCARD in the FRU List.
Failing Item:
10003104 10003104
v I2CBUS
Explanation: I2C bus 4 communication fault v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List. 10003111 10003111
Failing Item: Explanation: I2C bus DASD backplane 2
v I2CBUS communication fault
v TWRCARD Response: Follow the instructions for the items listed
in the FRU List.
10003105 10003105 Failing Item:
Explanation: I2C bus 5 communication fault v I2CBUS
Response: Follow the instructions for the items listed v TWRCARD
in the FRU List.
Failing Item:
v I2CBUS
10003145 10003145
v TWRCARD
Explanation: DCA0 I2C error
10003140 10003140 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: Midplane VPD I2C error
Failing Item:
Response: Follow the instructions for the items listed
v PWRSPLY
in the FRU List.
v I2CBUS
Failing Item:
v I2CBUS
10003146 10003146
v PWRSPLY
Explanation: DCA0 I2C fan 1 fault
10003141 10003141 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: Conduit I2C error
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v PWRSPLY
Failing Item:
v I2CBUS
10003147 10003147
v PWRSPLY
Explanation: DCA0 I2C fan 2 fault
10003142 10003142 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: DASD backplane VPD I2C error
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v PWRSPLY
Failing Item:
v I2CBUS
10003148 10003148
v PWRSPLY
Explanation: Port card 1 I2C error
10003143 10003143 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: Planar I2C error
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v PWRSPLY
Failing Item:
v I2CBUS
10003149 10003149
v PWRSPLY
Explanation: Port card 2 I2C error
10003144 10003144 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: DCA0 I2C multiplexer (MUX) error
Failing Item:
Response: Follow the instructions for the items listed
v I2CBUS
in the FRU List.
v PWRSPLY
Failing Item:
v PWRSPLY
1000314A 1000314A
Explanation: Port card 3 I2C error
Response: Follow the instructions for the items listed
in the FRU List.
Failing Item:
v I2CBUS
10004600 10004600
v PWRSPLY
Explanation: UPS Interface Failure
1000314B 1000314B Response: Follow the instructions for the items listed
in the FRU List.
Explanation: Port card 4 I2C error
Failing Item:
Response: Follow the instructions for the items listed
v UPSUNIT
in the FRU List.
v TWRCARD
Failing Item:
v I2CBUS
10004601 10004601
v PWRSPLY
Explanation: UPS Interface Failure
10003154 10003154 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: DCA1 I2C multiplexer (MUX) error
Failing Item:
Response: Follow the instructions for the items listed
v UPSUNIT
in the FRU List.
v TWRCARD
Failing Item:
v PWRSPLY
10006000 10006000
Explanation: Midplane VPD error
10003155 10003155
Response: Follow the instructions for the items listed
Explanation: DCA1 I2C error
in the FRU List.
Response: Follow the instructions for the items listed
Failing Item:
in the FRU List.
v VPDPART
Failing Item:
v PWRSPLY
10006001 10006001
v I2CBUS
Explanation: Conduit card VPD data error
10003156 10003156 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: DCA1 I2C fan 1 fault
Failing Item:
Response: Follow the instructions for the items listed
v VPDPART
in the FRU List.
Failing Item:
10006002 10006002
v I2CBUS
Explanation: DASD backplane VPD data error
v PWRSPLY
Response: Follow the instructions for the items listed
in the FRU List.
10003157 10003157
Failing Item:
Explanation: DCA1 I2C fan 2 fault
v VPDPART
Response: Follow the instructions for the items listed
in the FRU List.
10006003 10006003
Failing Item:
Explanation: I/O planar InfiniBand cable short
v I2CBUS
v PWRSPLY Response: Follow the instructions for the items listed
in the FRU List.
Failing Item:
v CBLALL
Response: Follow the instructions for the items listed Failing Item:
in the FRU List. v AIRMOVR
Failing Item: v TWRCARD
v AIRMOVR
10007621 10007621
10007602 10007602 Explanation: Fan missing error
Explanation: DCA1: fan 1 fault Response: A problem was detected with a Fan which
can be caused by a Fan not being installed. Install Fan
Response: Follow the instructions for the items listed if missing, replace if already installed. Follow the
in the FRU List. instructions for the items listed in the FRU List.
Failing Item: Failing Item:
v AIRMOVR v AIRMOVR
v TWRCARD
by product engineering to debug system power control the failure. Follow the instructions for the items listed
network (SPCN) failures. in the FRU List.
Failing Item:
10009021 10009021 v TWRCARD
Explanation: A command to an SPCN node was
rejected. 1000902D 1000902D
Response: No action required. This reference code is Explanation: Addressed frame is not in SPCN
logged for information only. configuration table.
Response: The addressed frame is not in the SPCN
10009022 10009022 configuration table. No action required. This reference
Explanation: Addressed Unit not in frame. code is logged for information only.
Explanation: SPCN Licensed Internal Code is not Response: A secondary node detected a BCC error on
valid. a transmission from the frame. The transmission is
attempted again. No action required. This reference
Response: The Licensed Internal Code in one of the code is logged for error analysis only.
frames is not valid. The code will be reloaded. No
action required. This reference code is logged for error
analysis only. 10009034 10009034
Explanation: Unsupported Packet Size
10009028 10009028 Response: The receiving node detected a packet
Explanation: SPCN Licensed Internal Code is not exceeding 70 bytes. The frame can also return this code
valid. if a secondary node returns more than 10 bytes to a
PAS command. No action required. This reference code
Response: The Licensed Internal Code in the primary is logged for error analysis only.
node is not valid. The code will be reloaded. No action
required. This reference code is logged for error
analysis only. 10009035 10009035
Explanation: Secondary SPCN node timeout.
10009029 10009029 Response: A secondary SPCN node did not respond
Explanation: SPCN VPD Damaged to a command. The command was attempted again and
failed. No action required. This reference code is logged
Response: The VPD record in the EEPROM has bad for error analysis only.
data. Exchange the failing items for the node reporting
Failing Item:
10009036 10009036
v TWRCARD
Explanation: Frame Timeout
Response: One or more frames did not respond to a 10009047 10009047
command. The command is attempted again. No action
required. This reference code is logged for error Explanation: QDS Block Sequence Error
analysis only. Response: The Block Sequence number is wrong. The
download was stopped. Follow the instructions for the
1000903B 1000903B items listed in the FRU List.
Failing Item:
10009080 10009080
v AJDG301
v TWRCARD Explanation: Undefined Status Code
Response: An SPCN node returned an unknown
10009042 10009042 status code. Exchange the failing SPCN node. Follow
the instructions for the items listed in the FRU List.
Explanation: EEPROM Failure
Failing Item:
Response: The EEPROM in an SPCN node cannot be v TWRCARD
written successfully. Exchange the SPCN node reported
in the failure. Follow the instructions for the items v SYSBKPL
listed in the FRU List.
Failing Item: 10009088 10009088
v PWR1907 v TWRCARD
v TWRCARD
v CBLALL 10009104 10009104
Explanation: Download Completion Timeout
100090F1 100090F1
Response: An SPCN node failed to leave the
Explanation: A frame was added to the SPCN download state. Exchange the failing SPCN node.
configuration. Follow the instructions for the items listed in the FRU
List.
Response: No action required. This reference code is
logged for information only. Failing Item:
v TWRCARD
100090F2 100090F2
Explanation: Slave disappeared 10009105 10009105
Response: A slave was dropped from the SPCN Explanation: Load Damaged Timeout
configuration. This is usually caused by a loss of ac Response: An SPCN node failed to enter the
power. If this SRC is logged during a concurrent operational state. Exchange the failing SPCN node.
maintenance operation, it is informational only and can Follow the instructions for the items listed in the FRU
be ignored. List.
Failing Item:
100090F3 100090F3
v TWRCARD
Explanation: Slave reappeared
Response: No action required. This reference code is 10009106 10009106
logged for information only.
Explanation: An SPCN LID was not found.
Response: No action required. This reference code is
10009101 10009101
logged for information only.
Explanation: VLIC-SPCN Timeout
Response: A Licensed Internal Code timeout occurred. 10009107 10009107
The SPCN failed to respond to a Licensed Internal
Explanation: An SPCN microcode download is
Code command. Follow the instructions for the items
required.
listed in the FRU List.
Response: No action required. This reference code is
Failing Item:
logged for error analysis only.
v TWRCARD
10009108 10009108
10009102 10009102
Explanation: A status change occurred in one of the
Explanation: Assign Permanent Address command SPCN nodes.
failure
Response: No action required. This reference code is
Response: A node failed to perform an Assign logged for information only.
Permanent Address command. Follow the instructions
for the items listed in the FRU List.
10009109 10009109
Failing Item:
Explanation: Licensed Internal Code part number is
v TWRCARD
not correct.
Response: The AROS part number field was not
10009103 10009103
updated to the correct level after the system attempted
Explanation: Download Initialize Timeout to load new Licensed Internal Code. Follow the
instructions for the items listed in the FRU List.
Response: An SPCN node failed to enter the
download state after an Initialize for Download Failing Item:
command. Exchange the failing SPCN node. Follow the v TWRCARD
instructions for the items listed in the FRU List.
Failing Item:
v TWRCARD
1000910A 1000910A
Explanation: RIO Download Required
10009115 10009115
Response: No action required. This reference code is
Explanation: SPCN Command rejected by the
logged for information only.
firmware.
Response: The service processor rejected an SPCN
1000910B 1000910B
command from the Licensed Internal Code. No action
Explanation: Maximum number of retries exceeded required. This reference code is logged for information
only.
Response: No action required. This reference code is
logged for information only.
10009116 10009116
10009111 10009111 Explanation: SPCN - Control Panel interface failure.
Explanation: SPCN is too large for hypervisor. Response: The SPCN to control panel interface is not
working.
Response: There are more nodes in the network than
the hypervisor can service. Go to System Configuration
in ASMI . Under Configure I/O Enclosures select Clear 10009117 10009117
Inactive Enclosures. If the error persists follow the
Explanation: SPCN - Control Panel interface is now
instructions for the items listed in the FRU List.
working.
Failing Item:
Response: The SPCN to control panel interface is now
v AJDG301 working. No action required. This reference code is
logged for information only.
10009112 10009112
Explanation: Primary SPCN node is reporting load 10009118 10009118
damaged. Explanation: Hypervisor out of memory
Response: The Licensed Internal Code for the primary Response: Follow the instructions for the items listed
SPCN node is damaged. The reload failed because the in the FRU List.
code could not be found. Follow the instructions for the
items listed in the FRU List. Failing Item:
v AJDG301
Failing Item:
v TWRCARD
10009119 10009119
Explanation: Secondary SPCN node is reporting load Response: Follow the instructions for the items listed
damaged. in the FRU List.
Response: Call your next level of support. Explanation: The manually started download was
interrupted
Failing Item:
10009139 10009139
v TWRCARD
Explanation: Open SPCN loop resolved
Response: No action required. This reference code is
logged for information only.
1000913A 1000913A
Explanation: RIO download sent retry
Response: No action required. This reference code is
logged for information only.
1000913B 1000913B
Explanation: Go to ASMi to start a download
manually
Response: Follow the instructions for the items listed
in the FRU List.
Failing Item:
v PWR1907
100091DD 100091DD
Explanation: All SPCN Downloads Complete
Response: No action required. This reference code is
logged for information only.
100091DE 100091DE
Explanation: RIO Download Complete
Response: No action required. This reference code is
logged for information only.
100091FB 100091FB
Explanation: Write VPD on next IPL
Response: No action required. This reference code is
logged for information only.
1000C62E 1000C62E
Explanation: Polling error
Response: An SPCN frame-to-frame communication
failure was detected. Follow the instructions for the
items listed in the FRU List.
Failing Item:
v TWRCARD
v CBLALL
1000CB15 1000CB15
Explanation: EEPROM Failure.
Response: Follow the instructions for the items listed
in the FRU List.
11001512 11001512
Failing Item:
11001611 11001611
v PWR1918
Explanation: Regulator 1 Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
11001623 11001623
Problem determination: No additional problem
Explanation: Regulator 2 Domain Fault
determination.
Response: Follow the instructions for the items listed
Failing Item:
in the FRU List.
v PWR1918
Problem determination: No additional problem
v TWRCARD
determination.
Failing Item:
11001612 11001612
v PWR1918
Explanation: Regulator 1 Communication Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
11001631 11001631
Problem determination: No additional problem
Explanation: Regulator 3 Fault
determination.
Response: Follow the instructions for the items listed
Failing Item:
in the FRU List.
v PWR1918
Problem determination: No additional problem
v TWRCARD
determination.
Failing Item:
11001613 11001613
v PWR1918
Explanation: Regulator 1 Domain Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
11001632 11001632
Problem determination: No additional problem
Explanation: Regulator 3 Communication Fault
determination.
Response: Follow the instructions for the items listed
Failing Item:
in the FRU List.
v PWR1918
Problem determination: No additional problem
v TWRCARD
determination.
Failing Item:
11001621 11001621
v PWR1918
Explanation: Regulator 2 Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
11001633 11001633
Problem determination: No additional problem
Explanation: Regulator 3 Domain Fault
determination.
Response: Follow the instructions for the items listed
Failing Item:
in the FRU List.
v PWR1918
Problem determination: No additional problem
v TWRCARD
determination.
Failing Item:
11001622 11001622
v PWR1918
Explanation: Regulator 2 Communication Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
Problem determination: No additional problem
determination.
Failing Item:
11002602 11002602
v SI_CARD
Explanation: Power Good Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
11001D63 11001D63
Problem determination: No additional problem
Explanation: RIO Adapter Card 2 Softswitch fault
determination.
Response: Follow the instructions for the items listed
Failing Item:
in the FRU List.
v PWR1918
Problem determination: No additional problem
v TWRCARD
determination.
Failing Item:
11002603 11002603
v SI_CARD
Explanation: Power Good Fault
v TWRCARD
Response: Follow the instructions for the items listed
in the FRU List.
11001F01 11001F01
Problem determination: No additional problem
Explanation: TMS limit reached - log only
determination.
Response: No action required. This reference code is
Failing Item:
logged for information only.
v PGDPART
Problem determination: No additional problem
determination.
11002610 11002610
Explanation: SPCN trace information saved Response: Follow the instructions for the items listed
in the FRU List.
Response: No action required. This reference code is
logged for information only. Problem determination: No additional problem
determination.
Problem determination: No additional problem
determination. Failing Item:
v SYSBKPL
11001F03 11001F03
11002611 11002611
Explanation: Invalid TMS or location code; log only.
Explanation: A power signal failure has been detected
Response: No action required. This reference code is
logged for information only. Response: Follow the instructions for the items listed
in the FRU List.
Problem determination: No additional problem
determination. Problem determination: No additional problem
determination.
11002600 11002600 Failing Item:
Explanation: Power Good Fault v SYSBKPL
Explanation: DASD 5V regulator P_GOOD fault. Response: Follow the instructions for the items listed
in the FRU List.
Response: Follow the instructions for the items listed
in the FRU List. Problem determination: No additional problem
determination.
Problem determination: No additional problem
determination. Failing Item:
v PWR1918
Failing Item:
v ANYPROC
v PWR1918
v SYSBKPL
1100262D 1100262D
11002633 11002633
Explanation: P_GOOD fault on the I/O backplane.
Explanation: Processor 1 1.2V VRM power-good fault
Response: Follow the instructions for the items listed
in the FRU List. Response: Follow the instructions for the items listed
in the FRU List.
Problem determination: No additional problem
determination. Problem determination: No additional problem
determination.
Failing Item:
Failing Item:
v SYSBKPL
v PWR1918
v SYSBKPL
1100262E 1100262E
Explanation: P_GOOD fault on the I/O backplane.
11002634 11002634
Response: Follow the instructions for the items listed
Explanation: Processor 1 1.8V VRM or processor 1
in the FRU List.
power-good fault
Problem determination: No additional problem
Response: Follow the instructions for the items listed
determination.
in the FRU List.
Failing Item:
Problem determination: No additional problem
v SYSBKPL determination.
Failing Item:
1100262F 1100262F
v ANYPROC
Explanation: P_GOOD fault on the I/O backplane. v SYSBKPL
Response: Follow the instructions for the items listed
in the FRU List. 11002635 11002635
Problem determination: No additional problem Explanation: VRM fault on the processor card.
determination.
Response: Follow the instructions for the items listed
Failing Item: in the FRU List.
v SYSBKPL
Problem determination: No additional problem
determination.
11002630 11002630
Failing Item:
Explanation: Processor 2 P7_VRM pgood fault v PWR1918
(pluggable)
Response: Follow the instructions for the items listed
in the FRU List.
v PWR1918
11002636 11002636
v ANYPROC
Explanation: VRM fault on the processor card.
v SYSBKPL
Response: Follow the instructions for the items listed
in the FRU List.
11002643 11002643
Problem determination: No additional problem
Explanation: Processor 2 1.8V VRM or processor 2
determination.
power-good fault
Failing Item:
Response: Follow the instructions for the items listed
v PWR1918 in the FRU List.
Problem determination: No additional problem
1100263A 1100263A determination.
Explanation: Memory card 1 pgood fault. Failing Item:
Response: Follow the instructions for the items listed v ANYPROC
in the FRU List. v SYSBKPL
Problem determination: No additional problem
determination. 11002645 11002645
Explanation: VRM fault on the processor card.
1100263B 1100263B
Response: Follow the instructions for the items listed
Explanation: Memory card 1 pgood fault. in the FRU List.
Response: Follow the instructions for the items listed Problem determination: No additional problem
in the FRU List. determination.
Problem determination: No additional problem Failing Item:
determination.
v PWR1918
1100263C 1100263C
1100264A 1100264A
Explanation: Memory card 1 pgood fault.
Explanation: Memory card 2 pgood fault.
Response: Follow the instructions for the items listed
Response: Follow the instructions for the items listed
in the FRU List.
in the FRU List.
Problem determination: No additional problem
Problem determination: No additional problem
determination.
determination.
11002640 11002640
1100264B 1100264B
Explanation: Processor 1 P7_VRM pgood fault
Explanation: Memory card 2 pgood fault.
(pluggable)
Response: Follow the instructions for the items listed
Response: Follow the instructions for the items listed
in the FRU List.
in the FRU List.
Problem determination: No additional problem
Problem determination: No additional problem
determination.
determination.
1100264C 1100264C
11002642 11002642
Explanation: Memory card 2 pgood fault.
Explanation: Processor 2 VRM2 array power-good
fault Response: Follow the instructions for the items listed
in the FRU List.
Response: Follow the instructions for the items listed
in the FRU List. Problem determination: No additional problem
determination.
Problem determination: No additional problem
determination.
Failing Item:
1100266A 1100266A Response: Follow the instructions for the items listed
in the FRU List.
Explanation: Memory card 4 pgood fault.
Problem determination: No additional problem
Response: Follow the instructions for the items listed determination.
in the FRU List.
Failing Item:
Problem determination: No additional problem
v PWR1918
determination.
11002702 11002702
1100266B 1100266B
Explanation: VRM fault on the DASD backplane.
Explanation: Memory card 4 pgood fault.
Response: Follow the instructions for the items listed
Response: Follow the instructions for the items listed
in the FRU List.
in the FRU List.
Problem determination: No additional problem
Problem determination: No additional problem
determination.
determination.
Failing Item:
1100266C 1100266C v PWR1918
Problem determination: No additional problem Response: Follow the instructions for the items listed
determination. in the FRU List.
Problem determination: No additional problem
11002690 11002690 determination.
Failing Item:
11007203 11007203
v AMBTMP2
Explanation: Ambient temperature exceeded limit
Response: The system will shut down in 15 minutes. 11007220 11007220
Follow the instructions for the items listed in the FRU
List. Explanation: The system is located at an altitude that
is outside the range of the system performance
Problem determination: No additional problem specification, and the thermal/power management
determination. firmware may reduce performance in heavy workload
Failing Item: situations.
v AMBTEMP Response: The system is located at an altitude that is
within the range of the system specification, but the
thermal/power management firmware may reduce
11007205 11007205
performance due to the altitude.
Explanation: Ambient temperature exceeded limit
Problem determination: No additional problem
Response: The system will shut down in 20 seconds. determination.
Follow the instructions for the items listed in the FRU
Failing Item:
list.
v ALTPERF
Problem determination: No additional problem
determination.
11007221 11007221
Failing Item:
Explanation: The ambient temperature is outside the
v AMBTEMP
range of the system performance specification, and the
thermal/power management firmware may reduce
11007207 11007207 performance in heavy workload situations.
Explanation: Ambient temperature has dropped below Response: The ambient temperature is outside the
the low temperature limit. range of the system performance specification, and the
thermal/power management firmware may reduce
Response: Follow the instructions for the items listed performance in heavy workload situations.
in the FRU List.
Problem determination: No additional problem
Problem determination: No additional problem determination.
determination.
Failing Item:
Failing Item:
v AMBPERF
v AMBTEMP
11007222 11007222
11007211 11007211
Explanation: The ambient temperature is back in
Explanation: Ambient temperature is out of range range.
Response: Ambient temperature is above nominal for Response: No action required. This reference code is
CPU performance. Follow the instructions for the items logged for information only.
listed in the FRU List.
Problem determination: No additional problem
Problem determination: No additional problem determination.
determination.
Failing Item: 11007610 11007610
v AMBTMP1
Explanation: Fan fault
v TWRCARD
11007631 11007631
Explanation: A problem was detected with a fan
11007611 11007611
which can be caused by a fan not being installed.
Explanation: Fan missing error Install the fan if it is missing; replace it if already
installed. Follow the instructions for the items listed in
Response: A problem was detected with a fan which the FRU list.
can be caused by a fan not being installed. Install fan if
missing, replace if already installed. Follow the Response: Follow the instructions for the items listed
instructions for the items listed in the FRU List. in the FRU List.
v TWRCARD v AIRMOVR
v TWRCARD
11007621 11007621
11007641 11007641
Explanation: Fan missing error
Explanation: A problem was detected with a fan
Response: A problem was detected with a fan which which can be caused by a fan not being installed.
can be caused by a fan not being installed. Install fan if Install the fan if it is missing; replace it if already
missing, replace if already installed. Follow the installed. Follow the instructions for the items listed in
instructions for the items listed in the FRU List. the FRU list.
Problem determination: No additional problem Response: Follow the instructions for the items listed
determination. in the FRU List.
Failing Item: Problem determination: No additional problem
v AIRMOVR determination.
v TWRCARD Failing Item:
v AIRMOVR
11007630 11007630 v TWRCARD
Explanation: A fan is operating at the wrong speed.
Follow the instructions for the items listed in the FRU 110076A0 110076A0
list.
Explanation: A problem was detected with a fan.
Response: Follow the instructions for the items listed Follow the instructions for the items listed in the FRU
in the FRU List. list.
Problem determination: No additional problem Response: Follow the instructions for the items listed
determination. in the FRU List.
Failing Item: Problem determination: No additional problem
v AIRMOVR determination.
v TWRCARD Failing Item:
v AIRMOVR
110076C1 110076C1
v TWRCARD
Explanation: Fan fault on a GX++ adapter card
110076A1 110076A1 Response: Follow the instructions for the items listed
in the FRU List.
Explanation: A problem was detected with a fan
which can be caused by a fan not being installed. Problem determination: No additional problem
Install the fan if it is missing; replace it if already determination.
installed. Follow the instructions for the items listed in
the FRU list. 11008400 11008400
Response: Follow the instructions for the items listed Explanation: No VPD was found due to invalid
in the FRU List. bypass
Problem determination: No additional problem Response: Follow the instructions for the items listed
determination. in the FRU List.
Failing Item: Problem determination: No additional problem
v AIRMOVR determination.
v TWRCARD Failing Item:
v AJDG301
110076B0 110076B0
Explanation: A problem was detected with a fan. 11008402 11008402
Follow the instructions for the items listed in the FRU
Explanation: Unable to collect VPD
list.
Response: Follow the instructions for the items listed
Response: Follow the instructions for the items listed
in the FRU List.
in the FRU List.
Problem determination: No additional problem
Problem determination: No additional problem
determination.
determination.
Failing Item:
Failing Item:
v VPDPART
v AIRMOVR
v TWRCARD
v TWRCARD
11008404 11008404
110076B1 110076B1
Explanation: Processor unit VPD mismatch
Explanation: A problem was detected with a fan
which can be caused by a fan not being installed. Response: Follow the instructions for the items listed
Install the fan if it is missing; replace it if already in the FRU List.
installed. Follow the instructions for the items listed in
the FRU list. Problem determination: No additional problem
determination.
Response: Follow the instructions for the items listed
in the FRU List. Failing Item:
v VPDPART
Problem determination: No additional problem
determination. v TWRCARD
Failing Item:
11008405 11008405
v AIRMOVR
v TWRCARD Explanation: Processor unit VPD mismatch
Response: Follow the instructions for the items listed
110076C0 110076C0 in the FRU List.
Explanation: Fan fault on a GX++ adapter card Problem determination: No additional problem
determination.
Response: Follow the instructions for the items listed
in the FRU List. Failing Item:
v VPDPART
Problem determination: No additional problem
determination. v TWRCARD
Failing Item:
11008406 11008406
v ANYPROC
Explanation: Processor unit VPD mismatch
Response: Follow the instructions for the items listed 11008416 11008416
in the FRU List.
Explanation: Invalid processor 4 VPD
Problem determination: No additional problem
determination. Response: Follow the instructions for the items listed
in the FRU List.
Failing Item:
Problem determination: No additional problem
v VPDPART
determination.
v TWRCARD
Failing Item:
v ANYPROC
11008409 11008409
Explanation: No processor installed
11008423 11008423
Response: Follow the instructions for the items listed
Explanation: No processor VPD
in the FRU List.
Response: Follow the instructions for the items listed
Problem determination: No additional problem
in the FRU List.
determination.
Problem determination: No additional problem
Failing Item:
determination.
v VPDPART
Failing Item:
v TWRCARD
v VPDPART
v TWRCARD
11008413 11008413
Explanation: Invalid processor VPD
11008424 11008424
Response: Follow the instructions for the items listed
Explanation: No processor VPD
in the FRU List.
Response: Follow the instructions for the items listed
Problem determination: No additional problem
in the FRU List.
determination.
Problem determination: No additional problem
Failing Item:
determination.
v VPDPART
Failing Item:
v TWRCARD
v VPDPART
v TWRCARD
11008414 11008414
Explanation: Invalid processor VPD
11008442 11008442
Response: Follow the instructions for the items listed
Explanation: An attempt was made to enable
in the FRU List.
TurboMode, but one or more processor cards in the
Problem determination: No additional problem system is not TurboMode-capable.
determination.
Response: Follow the instructions for the items listed
Failing Item: in the FRU List.
v VPDPART Problem determination: No additional problem
v TWRCARD determination.
Failing Item:
11008415 11008415 v VPDPART
Explanation: Invalid processor 3 VPD
Response: Follow the instructions for the items listed
in the FRU List.
Problem determination: No additional problem
determination.
Failing Item:
11008443 11008443
v PWRSPLY
Explanation: A drawer was added to a system that
v TWRCARD
has TurboMode enabled, but the newly-added drawer
is not TurboMode-capable.
11008453 11008453
Response: Follow the instructions for the items listed
in the FRU List. Explanation: There is an extra processor voltage
regulator in the system.
Problem determination: No additional problem
determination. Response: Follow the instructions for the items listed
in the FRU List.
Failing Item:
v VPDPART Problem determination: No additional problem
determination.
v TWRCARD
11008457 11008457
Explanation: The wrong processor VRMs are installed
110084A3 110084A3
in the system; high-power VRMs are required.
Explanation: Invalid service processor card VPD
Response: Follow the instructions for the items listed
in the FRU List. Response: Follow the instructions for the items listed
in the FRU List.
Problem determination: No additional problem
determination. Problem determination: No additional problem
determination.
Failing Item:
v PWR1918 Failing Item:
v TWRCARD v VPDPART
v TWRCARD
11008460 11008460
110084A4 110084A4
Explanation: All PWR nodes guarded
Explanation: Service processor card mismatch.
Response: No action required. This reference code is
logged for information only. Response: Follow the instructions for the items listed
in the FRU List.
Problem determination: No additional problem
determination. Problem determination: No additional problem
determination.
11008480 11008480 Failing Item:
Explanation: The DIMM or DIMM controller ID data v VPDPART
is missing or corrupt. v TWRCARD
Response: No action required. This reference code is
logged for information only. 11008700 11008700
Problem determination: No additional problem Explanation: BPC A lost input power
determination.
Response: Follow the instructions for the items listed
Failing Item: in the FRU list.
v FSPSP04 Problem determination: No additional problem
determination.
110084A1 110084A1 Failing Item:
Explanation: Invalid power distribution backplane v PWR2402
VPD
Response: Follow the instructions for the items listed 11008701 11008701
in the FRU List.
Explanation: BPC B lost input power
Problem determination: No additional problem
determination. Response: Follow the instructions for the items listed
in the FRU list.
Failing Item:
Problem determination: No additional problem
v VPDPART determination.
Failing Item:
110084A2 110084A2
v PWR2402
Explanation: Power distribution backplane mismatch
Response: Follow the instructions for the items listed 11008710 11008710
in the FRU List.
Explanation: DCA 1 UART communication fault
Problem determination: No additional problem
determination. Response: Follow the instructions for the items listed
in the FRU list.
Failing Item:
Problem determination: No additional problem
v VPDPART determination.
Note: Serviceable actions for the following SRCs require that you use the management console to access
more specific information, including isolation procedures, MAPs, and instruction on how to remove and
replace parts.
Explanation: The P2 node has indicated a critical VTM Explanation: The P8 node has indicated a critical VTM
failure and needs to be replaced. failure and needs to be replaced.
Explanation: The P3 node has indicated a critical VTM Explanation: The P9 node has indicated a critical VTM
failure and needs to be replaced. failure and needs to be replaced.
Explanation: The P4 node has indicated a critical VTM Explanation: The P10 node has indicated a critical
failure and needs to be replaced. VTM failure and needs to be replaced.
Explanation: The P5 node has indicated a critical VTM Explanation: The P11 node has indicated a critical
failure and needs to be replaced. VTM failure and needs to be replaced.
v MCM3
14020076 14020076
Explanation: The chilled input water to MWU1 is out
1402007D 1402007D
of specification (to Hot) or there is an issue with flow.
(Monitored by MWU1) If unable to correct contact IBM Explanation: A fault has been detected on MCM4 in
support. the PU book indicated in failure information. See
Power fault reason code for further information and
Failing Item:
contact next level of support.
v NOT_A_BPA_FRU
Failing Item:
v MCM4
14020077 14020077
Explanation: The chilled input water to MWU2 is out
1402007E 1402007E
of specification (to Hot) or there is an issue with flow.
((Monitored by MWU2) If unable to correct contact IBM Explanation: There is a problem with sensed and
support. passed configuration of the MCMs that are installed in
the system.
Failing Item:
v NOT_A_BPA_FRU
1402007F 1402007F
1402007A 1402007A
14020081 14020081
Explanation: A fault has been detected on MCM1 in
the PU book indicated in failure information. See Explanation: Input power to BPA A has been lost or
Power fault reason code for further information and partially lost.
contact next level of support. Failing Item:
Failing Item: v BPR-1A
v MCM1 v BPR-2A
v BPR-3A
1402007B 1402007B v CBL-PWRC-BPE-A1-PWR
Explanation: A fault has been detected on MCM2 in v BPC-A
the PU book indicated in failure information. See v BPE-BOARD-A
Power fault reason code for further information and
contact next level of support.
14020082 14020082
Failing Item:
Explanation: The input power to BPA B has been lost
v MCM2 or partially lost.
Failing Item:
1402007C 1402007C
v BPR-1B
Explanation: A fault has been detected on MCM3 in v BPR-2B
the PU book indicated in failure information. See
Power fault reason code for further information and v BPR-3B
contact next level of support. v CBL-PWRC-BPE-B1-PWR
Failing Item: v BPC-B
v BPE-BOARD-B
14020089 14020089
Explanation: The chilled input water to MWU4 is out
14020083 14020083
of specification (to Hot) or there is an issue with flow.
Explanation: Input power to BPA A has been lost or (Monitored by MWU4) If unable to correct contact IBM
partially lost. support.
Explanation: The voltage on voltage level 27 has Explanation: The voltage on voltage level 37 has
reached the warning undervoltage limit for the reached the warning undervoltage limit for the
specified cage or drawer. specified cage or drawer.
Explanation: The voltage on voltage level 28 has Explanation: The voltage on voltage level 38 has
reached the warning undervoltage limit for the reached the warning undervoltage limit for the
specified cage or drawer. specified cage or drawer.
Explanation: The voltage on voltage level 29 has Explanation: The voltage on voltage level 39 has
reached the warning undervoltage limit for the reached the warning undervoltage limit for the
specified cage or drawer. specified cage or drawer.
Explanation: The voltage on voltage level 30 has Explanation: The voltage on voltage level 40 has
reached the warning undervoltage limit for the reached the warning undervoltage limit for the
specified cage or drawer. specified cage or drawer.
Explanation: The voltage on voltage level 31 has Explanation: The voltage on voltage level 41 has
reached the warning undervoltage limit for the reached the warning undervoltage limit for the
specified cage or drawer. specified cage or drawer.
Explanation: The voltage on voltage level 32 has Explanation: The voltage on voltage level 42 has
reached the warning undervoltage limit for the reached the warning undervoltage limit for the
specified cage or drawer. specified cage or drawer.
v MSAA-1
14020143 14020143
v IO_DCA-01
Explanation: The voltage on voltage level 43 has
v IO_DCA-02
reached the warning undervoltage limit for the
specified cage or drawer. v MIDPLANE
Explanation: The voltage on voltage level 44 has Explanation: DCA 1's Air Moving Device number two
reached the warning undervoltage limit for the is defective.
specified cage or drawer. Failing Item:
v MSAA-2
14020145 14020145 v IO_DCA-01
Explanation: The voltage on voltage level 45 has v IO_DCA-02
reached the warning undervoltage limit for the v MIDPLANE
specified cage or drawer.
14020162 14020162
14020146 14020146
Explanation: DCA 1's Air Moving Device number
Explanation: The voltage on voltage level 46 has three is defective.
reached the warning undervoltage limit for the
specified cage or drawer. Failing Item:
v MSAA-3
14020147 14020147 v IO_DCA-01
Explanation: The voltage on voltage level 47 has v IO_DCA-02
reached the warning undervoltage limit for the v MIDPLANE
specified cage or drawer.
14020163 14020163
14020148 14020148
Explanation: DCA 2's Air Moving Device number one
Explanation: The voltage on voltage level 48 has is defective.
reached the warning undervoltage limit for the
Failing Item:
specified cage or drawer.
v MSAA-4
v IO_DCA-01
14020149 14020149
v IO_DCA-02
Explanation: The voltage on voltage level 49 has
v MIDPLANE
reached the warning undervoltage limit for the
specified cage or drawer.
14020164 14020164
14020150 14020150 Explanation: DCA 2's Air Moving Device number two
is defective.
Explanation: The voltage on voltage level 35 has
reached the warning undervoltage limit for the Failing Item:
specified cage or drawer. v MSAA-5
v IO_DCA-01
14020151 14020151 v IO_DCA-02
Explanation: The voltage on voltage level 36 has v MIDPLANE
reached the warning undervoltage limit for the
specified cage or drawer.
14020165 14020165
Explanation: DCA 2's Air Moving Device number
14020160 14020160
three is defective.
Explanation: DCA 1's Air Moving Device number one
Failing Item:
is defective.
v MSAA-6
Failing Item:
v IO_DCA-01
v IO_DCA-02
14020171 14020171
v MIDPLANE
Explanation: DCA 2's Air Moving Device number six
is defective.
14020166 14020166
Failing Item:
Explanation: DCA 1's Air Moving Device number four
v MSAA-12
is defective.
v IO_DCA-01
Failing Item:
v IO_DCA-02
v MSAA-7
v MIDPLANE
v IO_DCA-01
v IO_DCA-02
14020190 14020190
v MIDPLANE
Explanation: Input power has reached a high
threshold on BPA A line cord 1. Input should be
14020167 14020167 corrected or contact next level of service support for
Explanation: DCA 1's Air Moving Device number five assistance.
is defective.
Failing Item: 14020191 14020191
v IO_DCA-02
14020243 14020243
v IO_DCA-01
Explanation: The voltage on voltage level 43 has
v MIDPLANE
reached the warning over voltage limit for the specified
cage or drawer.
14020262 14020262
14020244 14020244 Explanation: DCA 1's Air Moving Device number
three is defective.
Explanation: The voltage on voltage level 44 has
reached the warning over voltage limit for the specified Failing Item:
cage or drawer. v MSAA-3
v IO_DCA-02
14020245 14020245 v IO_DCA-01
Explanation: The voltage on voltage level 45 has v MIDPLANE
reached the warning over voltage limit for the specified
cage or drawer.
14020263 14020263
14020246 14020246 Explanation: DCA 2's Air Moving Device number one
is defective.
Explanation: The voltage on voltage level 46 has
reached the warning over voltage limit for the specified Failing Item:
cage or drawer. v MSAA-4
v IO_DCA-02
14020247 14020247 v IO_DCA-01
Explanation: The voltage on voltage level 47 has v MIDPLANE
reached the warning over voltage limit for the specified
cage or drawer. 14020264 14020264
Explanation: DCA 2's Air Moving Device number two
14020248 14020248 is defective.
Explanation: The voltage on voltage level 48 has Failing Item:
reached the warning over voltage limit for the specified
v MSAA-5
cage or drawer.
v IO_DCA-02
v IO_DCA-01
14020249 14020249
v MIDPLANE
Explanation: The voltage on voltage level 49 has
reached the warning over voltage limit for the specified
cage or drawer. 14020265 14020265
Explanation: DCA 2's Air Moving Device number
14020260 14020260 three is defective.
Explanation: DCA 1's Air Moving Device number one Failing Item:
is defective. v MSAA-6
Failing Item: v IO_DCA-02
v MSAA-1 v IO_DCA-01
v IO_DCA-02 v MIDPLANE
v IO_DCA-01
v MIDPLANE 14020266 14020266
Explanation: DCA 2's Air Moving Device number four
14020261 14020261 is defective.
Explanation: DCA 1's Air Moving Device number two Failing Item:
is defective. v MSAA-7
Failing Item: v IO_DCA-02
v MSAA-2 v IO_DCA-01
v MIDPLANE
14020300 14020300
Explanation: An over current condition has been
14020267 14020267
detected on voltage level 0 for the specified cage or
Explanation: DCA 1's Air Moving Device number five drawer.
is defective.
Failing Item: 14020301 14020301
v MSAA-8 Explanation: An over current condition has been
v IO_DCA-02 detected on voltage level 1 for the specified cage or
v IO_DCA-01 drawer.
v MIDPLANE
14020302 14020302
14020268 14020268 Explanation: An over current condition has been
detected for voltage level 2 for the specified cage or
Explanation: DCA 1's Air Moving Device number six drawer.
is defective.
Failing Item: 14020303 14020303
v MSAA-9
Explanation: An over current condition has been
v IO_DCA-02 detected for voltage level 3 for the specified cage or
v IO_DCA-01 drawer.
v MIDPLANE
14020304 14020304
14020269 14020269 Explanation: An over current condition has been
Explanation: DCA 2's Air Moving Device number four detected for voltage level 4 level for the specified cage
is defective. or drawer.
Failing Item:
14020305 14020305
v MSAA-10
v IO_DCA-02 Explanation: An over current condition has been
detected for voltage level 5 for the specified cage or
v IO_DCA-01
drawer.
v MIDPLANE
14020306 14020306
14020270 14020270
Explanation: An over current condition has been
Explanation: DCA 2's Air Moving Device number five detected for voltage level 6 for the specified cage or
is defective. drawer.
Failing Item:
v MSAA-11 14020307 14020307
v IO_DCA-02 Explanation: An over current condition has been
v IO_DCA-01 detected for voltage level 7 for the specified cage or
v MIDPLANE drawer.
Explanation: DCA 2's Air Moving Device number six Explanation: An over current condition has been
is defective. detected for voltage level 8 for the specified cage or
drawer.
Failing Item:
v MSAA-12
14020309 14020309
v IO_DCA-02
Explanation: An over current condition has been
v IO_DCA-01
detected for voltage level 9 for the specified cage or
v MIDPLANE drawer.
v MSAA-6
14020349 14020349
v IO_DCA-02
Explanation: An over current condition has been
detected for voltage level 49 for the specified cage or
drawer. 14020400 14020400
14020360 14020360
14020401 14020401
Explanation: DCA 1's Air Moving Device number one
Explanation: An over voltage condition has been
is defective.
detected for voltage level 1 for the specified cage or
Failing Item: drawer.
v MSAA-1
v IO_DCA-01 14020402 14020402
Explanation: An over voltage condition has been
14020361 14020361 detected for voltage level 2 for the specified cage or
drawer.
Explanation: DCA 1's Air Moving Device number two
is defective.
14020403 14020403
Failing Item:
v MSAA-2 Explanation: An over voltage condition has been
detected for voltage level 3 for the specified cage or
v IO_DCA-01
drawer.
14020362 14020362
14020404 14020404
Explanation: DCA 1's Air Moving Device number
Explanation: An over voltage condition has been
three is defective.
detected for voltage level 4 for the specified cage or
Failing Item: drawer.
v MSAA-3
v IO_DCA-01 14020405 14020405
Explanation: An over voltage condition has been
14020363 14020363 detected for voltage level 5 for the specified cage or
drawer.
Explanation: DCA 2's Air Moving Device number one
is defective.
14020406 14020406
Failing Item:
v MSAA-4 Explanation: An over voltage condition has been
detected for voltage level 6 for the specified cage or
v IO_DCA-02 drawer.
14020440 14020440
14020501 14020501
Explanation: An over voltage condition has been
Explanation: Blower number one in the disk enclosure
detected for voltage level 40 specified cage or drawer.
is defective.
Failing Item:
14020441 14020441
v MSAA-1
Explanation: An over voltage condition has been
detected for voltage level 41 specified cage or drawer.
v MSAA-9
14020502 14020502
Explanation: Blower number two in the disk enclosure
14020510 14020510
is defective.
Explanation: Blower number ten in the disk enclosure
Failing Item:
is defective.
v MSAA-2
Failing Item:
v MSAA-10
14020503 14020503
Explanation: Blower number three in the disk
14020511 14020511
enclosure is defective.
Explanation: Blower number eleven in the disk
Failing Item:
enclosure is defective.
v MSAA-3
Failing Item:
v MSAA-11
14020504 14020504
Explanation: Blower number four in the disk
14020512 14020512
enclosure is defective.
Explanation: Blower number twelve in the disk
Failing Item:
enclosure is defective.
v MSAA-4
Failing Item:
v MSAA-12
14020505 14020505
Explanation: Blower number five in the disk enclosure
14020551 14020551
is defective.
Explanation: An error has been detected on port card
Failing Item:
one.
v MSAA-5
Failing Item:
v PORTCARD1
14020506 14020506
Explanation: Blower number six in the disk enclosure
14020552 14020552
is defective.
Explanation: An error has been detected on port card
Failing Item:
one.
v MSAA-6
Failing Item:
v PORTCARD1
14020507 14020507
v IO_DCA-01
Explanation: Blower number seven in the disk
v IO_DCA-02
enclosure is defective.
v MIDPLANE
Failing Item:
v MSAA-7
14020553 14020553
Explanation: An error has been detected on port card
14020508 14020508
one.
Explanation: Blower number eight in the disk
Failing Item:
enclosure is defective.
v PORTCARD1
Failing Item:
v IO_DCA-02
v MSAA-8
v IO_DCA-01
v MIDPLANE
14020509 14020509
Explanation: Blower number nine in the disk
enclosure is defective.
Failing Item:
v MIDPLANE
14020554 14020554
Explanation: An error has been detected on port card
1402055A 1402055A
two.
Explanation: An error has been detected on port card
Failing Item:
four.
v PORTCARD2
Failing Item:
v PORTCARD4
14020555 14020555
Explanation: An error has been detected on port card
1402055B 1402055B
two.
Explanation: An error has been detected on port card
Failing Item:
four.
v PORTCARD2
Failing Item:
v IO_DCA-01
v PORTCARD4
v IO_DCA-02
v IO_DCA-01
v MIDPLANE
v IO_DCA-02
v MIDPLANE
14020556 14020556
Explanation: An error has been detected on port card
1402055C 1402055C
two.
Explanation: An error has been detected on port card
Failing Item:
four.
v PORTCARD2
Failing Item:
v IO_DCA-02
v PORTCARD4
v IO_DCA-01
v IO_DCA-02
v MIDPLANE
v IO_DCA-01
v MIDPLANE
14020557 14020557
Explanation: An error has been detected on port card
1402055D 1402055D
three.
Explanation: An error has been detected on port card
Failing Item:
five.
v PORTCARD3
Failing Item:
v PORTCARD5
14020558 14020558
Explanation: An error has been detected on port card
1402055E 1402055E
three.
Explanation: An error has been detected on port card
Failing Item:
five.
v PORTCARD3
Failing Item:
v IO_DCA-01
v PORTCARD5
v IO_DCA-02
v IO_DCA-01
v MIDPLANE
v IO_DCA-02
v MIDPLANE
14020559 14020559
Explanation: An error has been detected on port card
1402055F 1402055F
three.
Explanation: An error has been detected on port card
Failing Item:
five.
v PORTCARD3
Failing Item:
v IO_DCA-02
v PORTCARD5
v IO_DCA-01
v IO_DCA-02
v IO_DCA-01 v IO_DCA-02
v MIDPLANE v IO_DCA-01
v MIDPLANE
14020560 14020560
Explanation: An error has been detected on port card 14020566 14020566
six. Explanation: An error has been detected on port card
Failing Item: eight.
v PORTCARD6 Failing Item:
v PORTCARD8
14020561 14020561
Explanation: An error has been detected on port card 14020567 14020567
six. Explanation: An error has been detected on port card
Failing Item: eight.
v PORTCARD6 Failing Item:
v IO_DCA-01 v PORTCARD8
v IO_DCA-02 v IO_DCA-01
v MIDPLANE v IO_DCA-02
v MIDPLANE
14020562 14020562
Explanation: An error has been detected on port card 14020568 14020568
six. Explanation: An error has been detected on port card
Failing Item: eight.
v PORTCARD6 Failing Item:
v IO_DCA-02 v PORTCARD8
v IO_DCA-01 v IO_DCA-02
v MIDPLANE v IO_DCA-01
v MIDPLANE
14020563 14020563
Explanation: An error has been detected on port card 14020569 14020569
seven. Explanation: An error has been detected on port card
Failing Item: nine.
v PORTCARD7 Failing Item:
v PORTCARD9
14020564 14020564
Explanation: An error has been detected on port card 1402056A 1402056A
seven. Explanation: An error has been detected on port card
Failing Item: nine.
v PORTCARD7 Failing Item:
v IO_DCA-01 v PORTCARD9
v IO_DCA-02 v IO_DCA-01
v MIDPLANE v IO_DCA-02
v MIDPLANE
14020565 14020565
Explanation: An error has been detected on port card 1402056B 1402056B
seven. Explanation: An error has been detected on port card
Failing Item: nine.
v PORTCARD7 Failing Item:
v PORTCARD9
14020571 14020571
v IO_DCA-02
Explanation: An error has been detected on port card
v IO_DCA-01
eleven.
v MIDPLANE
Failing Item:
v PORTCARD11
1402056C 1402056C
v IO_DCA-02
Explanation: An error has been detected on port card
v IO_DCA-01
ten.
v MIDPLANE
Failing Item:
v PORTCARD10
14020572 14020572
Explanation: An error has been detected on port card
1402056D 1402056D
twelve.
Explanation: An error has been detected on port card
Failing Item:
ten.
v PORTCARD12
Failing Item:
v PORTCARD10
14020573 14020573
v IO_DCA-01
Explanation: An error has been detected on port card
v IO_DCA-02
twelve.
v MIDPLANE
Failing Item:
v PORTCARD12
1402056E 1402056E
v IO_DCA-01
Explanation: An error has been detected on port card
v IO_DCA-02
ten.
v MIDPLANE
Failing Item:
v PORTCARD10
14020574 14020574
v IO_DCA-02
Explanation: An error has been detected on port card
v IO_DCA-01
twelve.
v MIDPLANE
Failing Item:
v PORTCARD12
1402056F 1402056F
v IO_DCA-02
Explanation: An error has been detected on port card
v IO_DCA-01
eleven.
v MIDPLANE
Failing Item:
v PORTCARD11
14020575 14020575
Explanation: An error has been detected on port card
14020570 14020570
thirteen.
Explanation: An error has been detected on port card
Failing Item:
eleven.
v PORTCARD13
Failing Item:
v PORTCARD11
14020576 14020576
v IO_DCA-01
Explanation: An error has been detected on port card
v IO_DCA-02
thirteen.
v MIDPLANE
Failing Item:
v PORTCARD13
v IO_DCA-01
v IO_DCA-02
v MIDPLANE v IO_DCA-02
v MIDPLANE
14020577 14020577
Explanation: An error has been detected on port card 1402057D 1402057D
thirteen. Explanation: An error has been detected on port card
Failing Item: fifteen.
v PORTCARD13 Failing Item:
v IO_DCA-02 v PORTCARD15
v IO_DCA-01 v IO_DCA-02
v MIDPLANE v IO_DCA-01
v MIDPLANE
14020578 14020578
Explanation: An error has been detected on port card 1402057E 1402057E
fourteen. Explanation: An error has been detected on port card
Failing Item: sixteen.
v PORTCARD14 Failing Item:
v PORTCARD16
14020579 14020579
Explanation: An error has been detected on port card 1402057F 1402057F
fourteen. Explanation: An error has been detected on port card
Failing Item: sixteen.
v PORTCARD14 Failing Item:
v IO_DCA-01 v PORTCARD16
v IO_DCA-02 v IO_DCA-01
v MIDPLANE v IO_DCA-02
v MIDPLANE
1402057A 1402057A
Explanation: An error has been detected on port card 14020580 14020580
fourteen. Explanation: An error has been detected on port card
Failing Item: sixteen.
v PORTCARD14 Failing Item:
v IO_DCA-02 v PORTCARD16
v IO_DCA-01 v IO_DCA-02
v MIDPLANE v IO_DCA-01
v MIDPLANE
1402057B 1402057B
Explanation: An error has been detected on port card 14020760 14020760
fifteen. Explanation: Disk enclosure Air Moving Device
Failing Item: number one is defective.
v PORTCARD15 Failing Item:
v MSAA-1
1402057C 1402057C v IO_DCA-01
Explanation: An error has been detected on port card v IO_DCA-02
fifteen. v MIDPLANE
Failing Item:
v PORTCARD15
v IO_DCA-01
v DASDBACKPLANE
1402130C 1402130C
Explanation: An error has been detected on the TRES
14021312 14021312
planar one.
Explanation: An error has been detected on the DASD
Failing Item:
backplane.
v PLANAR1
Failing Item:
v IO_DCA-02
v DASDBACKPLANE
v IO_DCA-01
v IO_DCA-01
v MIDPLANE
v IO_DCA-02
v MIDPLANE
1402130D 1402130D
v CONDUIT
Explanation: An error has been detected on the TRES
planar two.
14021313 14021313
Failing Item:
Explanation: An error has been detected on the DASD
v PLANAR2
backplane.
v IO_DCA-02
Failing Item:
v IO_DCA-01
v DASDBACKPLANE
v MIDPLANE
v IO_DCA-02
v IO_DCA-01
1402130E 1402130E
v MIDPLANE
Explanation: An error has been detected on the
v CONDUIT
conduit card.
Failing Item:
14021314 14021314
v CONDUIT
Explanation: An error has been detected on port card
one.
1402130F 1402130F
Failing Item:
Explanation: An error has been detected on the
v PORTCARD1
conduit card.
Failing Item:
14021315 14021315
v CONDUIT
Explanation: An error has been detected on port card
v IO_DCA-01
one.
v IO_DCA-02
Failing Item:
v MIDPLANE
v PORTCARD1
v IO_DCA-01
14021310 14021310
v IO_DCA-02
Explanation: An error has been detected on the
v MIDPLANE
conduit card.
v CONDUIT
Failing Item:
v DASDBACKPLANE
v CONDUIT
v IO_DCA-02
14021316 14021316
v IO_DCA-01
Explanation: An error has been detected on port card
v MIDPLANE
one.
Failing Item:
14021311 14021311
v PORTCARD1
Explanation: An error has been detected on the DASD
v IO_DCA-02
backplane.
v IO_DCA-01
Failing Item:
v MIDPLANE
v CONDUIT
1402131C 1402131C
v DASDBACKPLANE
Explanation: An error has been detected on the port
card three.
14021317 14021317
Failing Item:
Explanation: An error has been detected on port card
v PORTCARD3
two.
v IO_DCA-02
Failing Item:
v IO_DCA-01
v PORTCARD2
v MIDPLANE
v CONDUIT
14021318 14021318
v DASDBACKPLANE
Explanation: An error has been detected on port card
two.
1402131D 1402131D
Failing Item:
Explanation: An error has been detected on port card
v PORTCARD2 four.
v IO_DCA-01
Failing Item:
v IO_DCA-02
v PORTCARD4
v MIDPLANE
v CONDUIT
1402131E 1402131E
v DASDBACKPLANE
Explanation: An error has been detected on port card
four.
14021319 14021319
Failing Item:
Explanation: An error has been detected on port card
v PORTCARD4
two.
v IO_DCA-01
Failing Item:
v IO_DCA-02
v PORTCARD2
v MIDPLANE
v IO_DCA-02
v CONDUIT
v IO_DCA-01
v DASDBACKPLANE
v MIDPLANE
v CONDUIT
1402131F 1402131F
v DASDBACKPLANE
Explanation: An error has been detected on port card
four.
1402131A 1402131A
Failing Item:
Explanation: An error has been detected on port card
v PORTCARD4
three.
v IO_DCA-02
Failing Item:
v IO_DCA-01
v PORTCARD3
v MIDPLANE
v CONDUIT
1402131B 1402131B
v DASDBACKPLANE
Explanation: An error has been detected on port card
three.
14022043 14022043
Failing Item:
Explanation: Bulk power fan one is defective in
v PORTCARD3 BPA-A.
v IO_DCA-01
Failing Item:
v IO_DCA-02
v BPF-A1
v MIDPLANE
v BPC-A
v CONDUIT
v DASDBACKPLANE
v BPF-B4
14022044 14022044
v BPC-B
Explanation: Bulk power fan two is defective in
BPA-A.
14022051 14022051
Failing Item:
Explanation: DCA number one is defective.
v BPF-A2
v BPC-A Failing Item:
v IO_DCA-01
14022045 14022045
14022052 14022052
Explanation: Bulk power fan Three is defective in
BPA-A. Explanation: DCA number two is defective.
Failing Item: Failing Item:
v BPF-A3 v IO_DCA-02
v BPC-A
14022054 14022054
14022046 14022046 Explanation: The bulk power fan is defective in
Explanation: Bulk power fan four is defective in BPA-A.
BPA-A. Failing Item:
Failing Item: v BPF-A
v BPF-A4 v BPC-A
v BPC-A
14022055 14022055
14022047 14022047 Explanation: The bulk power fan is defective in
Explanation: Bulk power fan one is defective in BPA-B.
BPA-B. Failing Item:
Failing Item: v BPF-B
v BPF-B1 v BPC-B
v BPC-B
14022056 14022056
14022048 14022048 Explanation: A local I2C failure has been detected on
Explanation: Bulk power fan two is defective in DCA1
BPA-B. Failing Item:
Failing Item: v IO_DCA-01
v BPF-B2 v IO_DCA-02
v BPC-B v MIDPLANE
v MIDPLANE
14022058 14022058
v IO_DCA-01
Explanation: A Plug ID error has been detected on
v IO_DCA-02
DCA1
Failing Item:
1402205F 1402205F
v IO_DCA-01
Explanation: A defective disk enclosure midplane has
v MIDPLANE
been detected.
Failing Item:
14022059 14022059
v MIDPLANE
Explanation: A Plug ID error has been detected on
v IO_DCA-02
DCA2
v IO_DCA-01
Failing Item:
v IO_DCA-02
14022069 14022069
v MIDPLANE
Explanation: All DCAs reported 'No airflow in cage' -
Make sure that there are no blocked or dirty air inlet or
1402205A 1402205A filters. Verify that all unused logic positions are filled
Explanation: A defective TRES midplane has been with filler books and that all 'circulation flaps' inside
detected. affected Air Moving Enclosure are not blocked.
Failing Item:
140220B9 140220B9
v MIDPLANE
Explanation: The EPO panel or the cable between
both BPCs and EPO panel is defective.
1402205B 1402205B
Failing Item:
Explanation: A defective TRES midplane has been
detected. v EPO-SWITCH
v CBL-BPCA-EPO
Failing Item:
v CBL-BPCB-EPO
v MIDPLANE
v BPC-A
v IO_DCA-01
v BPC-B
v IO_DCA-02
140220C1 140220C1
1402205C 1402205C
Explanation: The UEPO switch on the BPC A-side is
Explanation: A defective TRES midplane has been
defective or in the BYPASS posistion. Switch to the
detected.
NORMAL posistion.
Failing Item:
Failing Item:
v MIDPLANE
v BPC-A
v IO_DCA-01
v IO_DCA-02
140220C2 140220C2
Explanation: The BPC on the A-side has detected an
1402205D 1402205D
open UEPO loop.
Explanation: A defective disk enclosure midplane has
Failing Item:
been detected.
v EPO-SWITCH
Failing Item:
v BPC-A
v MIDPLANE
v BPR-1A
v BPR-2A
1402205E 1402205E
v BPR-3A
Explanation: A defective disk enclousure midplane v CBL-BPCA-EPO
has been detected.
v BPE-BOARD-A
Failing Item:
v BPC-B
140221AB 140221AB
v BPR-1B
Explanation: A communication fault between BPC A
v BPR-2B
and the load on port J10 (B) has been detected.
v BPR-3B
Failing Item:
v CBL-BPCB-EPO
v BPCA-PORT-10-B
v BPE-BOARD-B
140221AC 140221AC
1402221A 1402221A
Explanation: A communication fault between BPC A
Explanation: A communication fault between the BPD
and the load on port J10 (C) has been detected.
1A and the load on port J01 (A) has been detected.
Failing Item:
Failing Item:
v BPCA-PORT-10-C
v BPD1A-PORT-01-A
140221B9 140221B9
1402222A 1402222A
Explanation: The EPO panel or the cable between
Explanation: A communication fault between the BPD
both BPCHs and EPO panel is defective.
1A and the load on port J02 (A) has been detected.
Failing Item:
Failing Item:
v EPO-SWITCH
v BPD1A-PORT-02-A
v CBL-BPCHA-EPO
v CBL-BPCHB-EPO
1402223A 1402223A
v BPCH-A
Explanation: A communication fault between the BPD
v BPCH-B
1A and the load on port J03 (A) has been detected.
Failing Item:
140221BB 140221BB
v BPD1A-PORT-03-A
Explanation: A communication fault between BPC A
and the load on port J11 (B) has been detected.
1402224A 1402224A
Failing Item:
Explanation: A communication fault between the BPD
v BPCA-PORT-11-B
1A and the load on port J04 (A) has been detected.
Failing Item:
140221BC 140221BC
v BPD1A-PORT-04-A
Explanation: A communication fault between BPC A
and the load on port J11 (C) has been detected.
14022251 14022251
Failing Item:
Explanation: DCA number one is defective.
v BPCA-PORT-11-C
Failing Item:
140221C1 140221C1 v P2_CEC_DCA-01
v BPD1A-PORT-09-A
1402226A 1402226A
Explanation: A communication fault between the BPD
1402229B 1402229B
1A and the load on port J06 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1A and the load on port J09 (B) has been detected.
v BPD1A-PORT-06-A
Failing Item:
v BPD1A-PORT-09-B
1402227A 1402227A
Explanation: A communication fault between the BPD
1402229C 1402229C
1A and the load on port J07 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1A and the load on port J09 (C) has been detected.
v BPD1A-PORT-07-A
Failing Item:
v BPD1A-PORT-09-C
1402227B 1402227B
Explanation: A communication fault between the BPD
140222AA 140222AA
1A and the load on port J07 (B) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1A and the load on port J10 (A) has been detected.
v BPD1A-PORT-07-B
Failing Item:
v BPD1A-PORT-10-A
1402227C 1402227C
Explanation: A communication fault between the BPD
140222AB 140222AB
1A and the load on port J07 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1A and the load on port J10 (B) has been detected.
v BPD1A-PORT-07-C
Failing Item:
v BPD1A-PORT-10-B
1402228A 1402228A
Explanation: A communication fault between the BPD
140222AC 140222AC
1A and the load on port J08 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1A and the load on port J10 (C) has been detected.
v BPD1A-PORT-08-A
Failing Item:
v BPD1A-PORT-10-C
1402228B 1402228B
Explanation: A communication fault between the BPD
140222C1 140222C1
1A and the load on port J08 (B) has been detected.
Explanation: The UEPO switch on the BPCH A-side is
Failing Item:
defective or in the BYPASS posistion. Switch to the
v BPD1A-PORT-08-B NORMAL posistion.
Failing Item:
1402228C 1402228C
v BPCH-A
Explanation: A communication fault between the BPD
1A and the load on port J08 (C) has been detected.
140222C2 140222C2
Failing Item:
Explanation: The BPCH on the A-side has detected an
v BPD1A-PORT-08-C open UEPO loop.
Failing Item:
1402229A 1402229A
v EPO-SWITCH
Explanation: A communication fault between the BPD v BPCH-A
1A and the load on port J09 (A) has been detected.
v BPR-1A
Failing Item: v BPR-2A
v BPR-3A
14022309 14022309
v CBL-BPCHA-EPO
Explanation: A Problem has been detectected on the
v BPE-BOARD-A
fill and drain tool.
Failing Item:
14022301 14022301
v MDA-FD-A
Explanation: Water cooling system one has failed to
v FDT-A
adequately cool.
Failing Item:
1402230A 1402230A
v MDAW-1
Explanation: A Problem has been detectected on the
v MWU-1
fill and drain tool.
Failing Item:
14022302 14022302
v MDA-FD-B
Explanation: Water cooling system two has failed to
v FDT-B
adequately cool.
Failing Item:
1402230B 1402230B
v MDAW-2
Explanation: A Problem has been detectected on the
v MWU-2
fill and drain tool.
Failing Item:
14022303 14022303
v FDT-A
Explanation: A problem with water supply has been
be detected on water cooling system one.
1402230C 1402230C
Failing Item:
Explanation: A Problem has been detectected on the
v MDAW-1
fill and drain tool.
v MWU-1
Failing Item:
v FDT-B
14022304 14022304
Explanation: A problem with water supply has been
1402230D 1402230D
be detected on water cooling system two.
Explanation: A Problem has been detectected on the
Failing Item:
fill and drain tool.
v MDAW-2
Failing Item:
v MWU-2
v MDA-FD-A
14022305 14022305
1402230E 1402230E
Explanation: A leak has been detectected on water
cooling system one. Explanation: A Problem has been detectected on the
fill and drain tool.
Failing Item:
Failing Item:
v MWU-1
v MDA-FD-B
v MDAW-1
1402230F 1402230F
14022306 14022306
Explanation: Water cooling system three has failed to
Explanation: A leak has been detectected on water
adequately cool.
cooling system two.
Failing Item:
Failing Item:
v MDAW-3
v MWU-2
v MWU-3
v MDAW-2
14022314 14022314
1402236A 1402236A
Explanation: A leak has been detectected on water
cooling system four. Explanation: A communication fault between the BPD
2A and the load on port J06 (A) has been detected.
Failing Item:
Failing Item:
v MWU-4
v BPD2A-PORT-06-A
v MDAW-4
1402237A 1402237A
1402231A 1402231A
Explanation: A communication fault between the BPD
Explanation: A communication fault between the BPD
2A and the load on port J07 (A) has been detected.
2A and the load on port J01 (A) has been detected.
Failing Item:
Failing Item:
v BPD2A-PORT-07-A
v BPD2A-PORT-01-A
1402237B 1402237B
1402232A 1402232A
Explanation: A communication fault between the BPD
Explanation: A communication fault between the BPD
2A and the load on port J07 (B) has been detected.
2A and the load on port J02 (A) has been detected.
Failing Item:
Failing Item:
v BPD2A-PORT-07-B
v BPD2A-PORT-02-A
v BPD2A-PORT-10-A
1402237C 1402237C
Explanation: A communication fault between the BPD
140223AB 140223AB
2A and the load on port J07 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2A and the load on port J10 (B) has been detected.
v BPD2A-PORT-07-C
Failing Item:
v BPD2A-PORT-10-B
1402238A 1402238A
Explanation: A communication fault between the BPD
140223AC 140223AC
2A and the load on port J08 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2A and the load on port J10 (C) has been detected.
v BPD2A-PORT-08-A
Failing Item:
v BPD2A-PORT-10-C
1402238B 1402238B
Explanation: A communication fault between the BPD
140223C1 140223C1
2A and the load on port J08 (B) has been detected.
Explanation: The UEPO switch on the BPCH B-side is
Failing Item:
defective or in the BYPASS posistion. Switch to the
v BPD2A-PORT-08-B NORMAL posistion.
Failing Item:
1402238C 1402238C
v BPCH-B
Explanation: A communication fault between the BPD
2A and the load on port J08 (C) has been detected.
140223C2 140223C2
Failing Item:
Explanation: The BPCH on the B-side has detected an
v BPD2A-PORT-08-C open UEPO loop.
Failing Item:
1402239A 1402239A
v EPO-SWITCH
Explanation: A communication fault between the BPD v BPCH-B
2A and the load on port J09 (A) has been detected.
v BPR-1B
Failing Item: v BPR-2B
v BPD2A-PORT-09-A v BPR-3B
v CBL-BPCHB-EPO
1402239B 1402239B v BPE-BOARD-B
Explanation: A communication fault between the BPD
2A and the load on port J09 (B) has been detected. 1402241A 1402241A
Failing Item: Explanation: A communication fault between the BPD
v BPD2A-PORT-09-B 3A and the load on port J01 (A) has been detected.
Failing Item:
1402239C 1402239C v BPD3A-PORT-01-A
Explanation: A communication fault between the BPD
2A and the load on port J09 (C) has been detected. 1402242A 1402242A
Failing Item: Explanation: A communication fault between the BPD
v BPD2A-PORT-09-C 3A and the load on port J02 (A) has been detected.
Failing Item:
140223AA 140223AA v BPD3A-PORT-02-A
Explanation: A communication fault between the BPD
2A and the load on port J10 (A) has been detected.
Failing Item:
v BPE-BOARD-A
14022A03 14022A03
Explanation: A communication fault between the BPC
14022A09 14022A09
(BPA-A) and BPD 2A has been detected.
Explanation: Communication error btween BPC A and
Failing Item:
BPR 5A.
v BPD-2A
Failing Item:
v BPC-A
v BPR-5A
v BPE-BOARD-A
v BPC-A
v BPE-BOARD-A
14022A04 14022A04
Explanation: A communication fault between the BPC
14022A0A 14022A0A
(BPA-A) and BPD 3A has been detected.
Explanation: Communication error btween BPC A and
Failing Item:
BPR 6A.
v BPD-3A
Failing Item:
v BPC-A
v BPR-6A
v BPE-BOARD-A
v BPC-A
v BPE-BOARD-A
14022A05 14022A05
Explanation: Communication error btween BPC A and
14022A0B 14022A0B
BPR 1A.
Explanation: Communication error btween BPC A and
Failing Item:
BPH A.
v BPR-1A
Failing Item:
v BPC-A
v BPCA-PORT-02
v BPE-BOARD-A
14022A0C 14022A0C
14022A06 14022A06
Explanation: Communication error btween BPC A and
Explanation: Communication error btween BPC A and
BPH B.
BPR 2A.
Failing Item:
Failing Item:
v BPCA-PORT-03
v BPR-2A
v BPC-A
14022A10 14022A10
v BPE-BOARD-A
Explanation: BPA-A has reported an over-current on
the 350VDC bulk.
14022A07 14022A07
Failing Item:
Explanation: Communication error btween BPC A and
BPR 3A. v BPR-1A
v BPD-1A
Failing Item:
v BPC-A
v BPR-3A
v BPD-2A
v BPC-A
v BPR-2A
v BPE-BOARD-A
v BPR-3A
v BPE-BOARD-A
14022A08 14022A08
Explanation: Communication error btween BPC A and
14022A11 14022A11
BPR 4A.
Explanation: BPR-1A has reported an over-current on
Failing Item:
the 350VDC bulk.
v BPR-4A
Failing Item:
v BPC-A
v BPR-1A
v BPD-1A v BPR-5A
v BPC-A v BPD-1A
v BPD-2A v BPC-A
v BPR-2A v BPD-2A
v BPR-3A v BPR-4A
v BPE-BOARD-A v BPR-6A
v BPE-BOARD-A
14022A12 14022A12
Explanation: BPR-2A has reported an over-current on 14022A16 14022A16
the 350VDC bulk. Explanation: BPR-6A has reported an over-current on
Failing Item: the 350VDC bulk.
v BPR-2A Failing Item:
v BPD-1A v BPR-6A
v BPC-A v BPD-1A
v BPD-2A v BPC-A
v BPR-1A v BPD-2A
v BPR-3A v BPR-4A
v BPE-BOARD-A v BPR-5A
v BPE-BOARD-A
14022A13 14022A13
Explanation: BPR-3A has reported an over-current on 14022A20 14022A20
the 350VDC bulk. Explanation: A BPA has reported 'No airflow in cage' -
Failing Item: Make sure that there are no blocked or dirty air inlet or
filters. Verify that all unused logic positions are filled
v BPR-3A
with filler books and that the BPF on the A-side has a
v BPD-1A cover over it / BPF on B-side does not.
v BPC-A
Failing Item:
v BPD-2A
v NOT_A_BPA_FRU
v BPR-1A
v BPR-2A
14022A21 14022A21
v BPE-BOARD-A
Explanation: BPR-1A located in BPA-A has reported
an 'Over Temperature' Make sure that the Air inlets are
14022A14 14022A14 not blocked / filler books installed in empty locations
Explanation: BPR-4A has reported an over-current on and no heat source is located near the BPR ASM.
the 350VDC bulk. Failing Item:
Failing Item: v BPR-1A
v BPR-4A
v BPD-1A 14022A22 14022A22
v BPC-A Explanation: BPR-2A located in BPA-A has reported
v BPD-2A an 'Over Temperature' Make sure that the Air inlets are
v BPR-5A not blocked / filler books installed in empty locations
and no heat source is located near the BPR ASM.
v BPR-6A
v BPE-BOARD-A Failing Item:
v BPR-2A
14022A15 14022A15
Explanation: BPR-5A has reported an over-current on
the 350VDC bulk.
Failing Item:
v IBF-2A
14022A23 14022A23
v BPR-2A
Explanation: BPR-3A located in BPA-A has reported
v BPC-A
an 'Over Temperature' Make sure that the Air inlets are
not blocked / filler books installed in empty locations v BPE-BOARD-A
and no heat source is located near the BPR ASM.
Failing Item: 14022A41 14022A41
v BPR-3A Explanation: BPA-A side detects that IBF-1A has been
charged to normal capcity. The IBF is available to again
to provide power. (IBF is connected to BPA-A BPR-1A)
14022A24 14022A24
Failing Item:
Explanation: BPR-4A located in BPA-A has reported
an 'Over Temperature' Make sure that the Air inlets are v IBF-1A
not blocked / filler books installed in empty locations
and no heat source is located near the BPR ASM. 14022A42 14022A42
Failing Item: Explanation: BPA-A side detects that IBF-2A has been
v BPR-4A charged to normal capcity. The IBF is available to again
to provide power. (IBF is connected to BPA-A BPR-2A)
14022A25 14022A25 Failing Item:
Explanation: BPR-5A located in BPA-A has reported v IBF-2A
an 'Over Temperature' Make sure that the Air inlets are
not blocked / filler books installed in empty locations 14022A51 14022A51
and no heat source is located near the BPR ASM.
Explanation: BPC-A side detects that IBF-1A is
Failing Item: disconnected. (IBF is connected to BPA-A BPR-1A)
v BPR-5A
Failing Item:
v BPR-1A
14022A26 14022A26
v IBF-1A
Explanation: BPR-6A located in BPA-A has reported v CBL-IBF1A
an 'Over Temperature' Make sure that the Air inlets are
not blocked / filler books installed in empty locations v BPC-A
and no heat source is located near the BPR ASM. v BPE-BOARD-A
Failing Item:
v BPR-6A 14022A52 14022A52
Explanation: BPC-A side detects that IBF-2A is
14022A31 14022A31 disconnected. (IBF is connected to BPA-A BPR-2A)
v BPD1B-PORT-01-A
1402327C 1402327C
Explanation: A communication fault between the BPD
1402322A 1402322A
1B and the load on port J07 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J02 has been detected (A).
v BPD1B-PORT-07-C
Failing Item:
v BPD1B-PORT-02-A
1402328A 1402328A
Explanation: A communication fault between the BPD
1402323A 1402323A
1B and the load on port J08 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J03 has been detected (A).
v BPD1B-PORT-08-A
Failing Item:
v BPD1B-PORT-03-A
1402328B 1402328B
Explanation: A communication fault between the BPD
1402324A 1402324A
1B and the load on port J08 (B) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J04 has been detected (A).
v BPD1B-PORT-08-B
Failing Item:
v BPD1B-PORT-04-A
1402328C 1402328C
Explanation: A communication fault between the BPD
1402325A 1402325A
1B and the load on port J08 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J05 (A) has been detected.
v BPD1B-PORT-08-C
Failing Item:
v BPD1B-PORT-05-A
1402329A 1402329A
Explanation: A communication fault between the BPD
1402326A 1402326A
1B and the load on port J09 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J06 (A) has been detected.
v BPD1B-PORT-09-A
Failing Item:
v BPD1B-PORT-06-A
1402329B 1402329B
Explanation: A communication fault between the BPD
1402327A 1402327A
1B and the load on port J09 (B) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J07 (A) has been detected.
v BPD1B-PORT-09-B
Failing Item:
v BPD1B-PORT-07-A
1402329C 1402329C
Explanation: A communication fault between the BPD
1402327B 1402327B
1B and the load on port J09 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J07 (B) has been detected.
v BPD1B-PORT-09-C
Failing Item:
v BPD1B-PORT-07-B
140232AA 140232AA
Explanation: A communication fault between the BPD
1B and the load on port J10 (A) has been detected.
Failing Item:
v BPD1B-PORT-10-A
1402336A 1402336A
Explanation: A communication fault between the BPD
140232AB 140232AB
2B and the load on port J06 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J10 (B) has been detected.
v BPD2B-PORT-06-A
Failing Item:
v BPD1B-PORT-10-B
1402337A 1402337A
Explanation: A communication fault between the BPD
140232AC 140232AC
2B and the load on port J07 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
1B and the load on port J10 (C) has been detected.
v BPD2B-PORT-07-A
Failing Item:
v BPD1B-PORT-10-C
1402337B 1402337B
Explanation: A communication fault between the BPD
1402331A 1402331A
2B and the load on port J07 (B) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J01 (A) has been detected.
v BPD2B-PORT-07-B
Failing Item:
v BPD2B-PORT-01-A
1402337C 1402337C
Explanation: A communication fault between the BPD
1402332A 1402332A
2B and the load on port J07 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J02 (A) has been detected.
v BPD2B-PORT-07-C
Failing Item:
v BPD2B-PORT-02-A
1402338A 1402338A
Explanation: A communication fault between the BPD
1402333A 1402333A
2B and the load on port J08 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J03 (A) has been detected.
v BPD2B-PORT-08-A
Failing Item:
v BPD2B-PORT-03-A
1402338B 1402338B
Explanation: A communication fault between the BPD
1402334A 1402334A
2B and the load on port J08 (B) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J04 (A) has been detected.
v BPD2B-PORT-08-B
Failing Item:
v BPD2B-PORT-04-A
1402338C 1402338C
Explanation: A communication fault between the BPD
1402335A 1402335A
2B and the load on port J08 (C) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J05 (A) has been detected.
v BPD2B-PORT-08-C
Failing Item:
v BPD2B-PORT-05-A
1402339B 1402339B
Explanation: A communication fault between the BPD
2B and the load on port J09 (B) has been detected.
Failing Item:
v BPD2B-PORT-09-B
1402344A 1402344A
Explanation: A communication fault between the BPD
1402339C 1402339C
3B and the load on port J04 (A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J09 (C) has been detected.
v BPD3B-PORT-04-A
Failing Item:
v BPD2B-PORT-09-C
14023A01 14023A01
Explanation: Communication fault between BPCH-A
140233AA 140233AA
and BPCH-B.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J10 (A) has been detected.
v BPCHA-PORT-01
Failing Item:
v BPD2B-PORT-10-A
14023A02 14023A02
Explanation: A communication fault between the
140233AB 140233AB
BPCH and BPD (BPA-A) has been detected.
Explanation: A communication fault between the BPD
Failing Item:
2B and the load on port J10 (B) has been detected.
v BPD-1A
Failing Item:
v BPCH-A
v BPD2B-PORT-10-B
v BPE-BOARD-A
140233AC 140233AC
14023A05 14023A05
Explanation: A communication fault between the BPD
Explanation: Communication error btween BPCH A
2B and the load on port J10 (C) has been detected.
and BPR 1A.
Failing Item:
Failing Item:
v BPD2B-PORT-10-C
v BPR-1A
v BPCH-A
1402341A 1402341A
v BPE-BOARD-A
Explanation: A communication fault between the BPD
3B and the load on port J01 (A) has been detected.
14023A06 14023A06
Failing Item:
Explanation: Communication error btween BPCH A
v BPD3B-PORT-01-A and BPR 2A.
Failing Item:
1402342A 1402342A
v BPR-2A
Explanation: A communication fault between the BPD v BPCH-A
3B and the load on port J02 (A) has been detected.
v BPE-BOARD-A
Failing Item:
v BPD3B-PORT-02-A 14023A07 14023A07
Explanation: Communication error btween BPCH A
1402343A 1402343A and BPR 3A.
Explanation: A communication fault between the BPD Failing Item:
3B and the load on port J03 (A) has been detected.
v BPR-3A
Failing Item: v BPCH-A
v BPD3B-PORT-03-A v BPE-BOARD-A
v BPE-BOARD-B
14024007 14024007
Explanation: A Power redundancy command was run
14023B85 14023B85
and produced this log. This is not an error and contains
Explanation: The B-side BPCH has detected that the informationthat development would use to investigate
cross feed from the A-side has failed. system FRU redundancy problems.
Failing Item:
1402521A 1402521A
v NOT_A_BPA_FRU
Explanation: An over current has been detected on
350V between BPD 1A and the load on its port J01 (A).
14024005 14024005
Failing Item:
Explanation: A DHCP address was not assigned on
Network A. Contact next level of support for v BPD1A-PORT-01-A
assistance.
Failing Item: 1402522A 1402522A
v NOT_A_BPA_FRU Explanation: An over current has been detected on
350V between BPD 1A and the load on its port J02 (A).
14024006 14024006 Failing Item:
Explanation: The Flash that is loaded on BPC A and B v BPD1A-PORT-02-A
do not match. Contact next level of support for
assistance.
Failing Item:
v NOT_A_BPA_FRU
v BPD1A-PORT-08-A
1402523A 1402523A
Explanation: An over current has been detected on
1402528B 1402528B
350V between BPD 1A and the load on its port J03 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J08 (B).
v BPD1A-PORT-03-A
Failing Item:
v BPD1A-PORT-08-B
1402524A 1402524A
Explanation: An over current has been detected on
1402528C 1402528C
350V between BPD 1A and the load on its port J04 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J08 (C).
v BPD1A-PORT-04-A
Failing Item:
v BPD1A-PORT-08-C
1402525A 1402525A
Explanation: An over current has been detected on
1402529A 1402529A
350V between BPD 1A and the load on its port J05 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J09 (A).
v BPD1A-PORT-05-A
Failing Item:
v BPD1A-PORT-09-A
1402526A 1402526A
Explanation: An over current has been detected on
1402529B 1402529B
350V between BPD 1A and the load on its port J06 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J09 (B).
v BPD1A-PORT-06-A
Failing Item:
v BPD1A-PORT-09-B
1402527A 1402527A
Explanation: An over current has been detected on
1402529C 1402529C
350V between BPD 1A and the load on its port J07 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J09 (C).
v BPD1A-PORT-07-A
Failing Item:
v BPD1A-PORT-09-C
1402527B 1402527B
Explanation: An over current has been detected on
140252AA 140252AA
350V between BPD 1A and the load on its port J07 (B).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J10 (A).
v BPD1A-PORT-07-B
Failing Item:
v BPD1A-PORT-10-A
1402527C 1402527C
Explanation: An over current has been detected on
140252AB 140252AB
350V between BPD 1A and the load on its port J07 (C).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 1A and the load on its port J10 (B).
v BPD1A-PORT-07-C
Failing Item:
v BPD1A-PORT-10-B
1402528A 1402528A
Explanation: An over current has been detected on
350V between BPD 1A and the load on its port J08 (A).
Failing Item:
v BPD2A-PORT-07-A
140252AC 140252AC
Explanation: An over current has been detected on
1402537B 1402537B
350V between BPD 1A and the load on its port J10 (C).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J07 (B).
v BPD1A-PORT-10-C
Failing Item:
v BPD2A-PORT-07-B
1402531A 1402531A
Explanation: An over current has been detected on
1402537C 1402537C
350V between BPD 2A and the load on its port J01 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J07 (C).
v BPD2A-PORT-01-A
Failing Item:
v BPD2A-PORT-07-C
1402532A 1402532A
Explanation: An over current has been detected on
1402538A 1402538A
350V between BPD 2A and the load on its port J02 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J08 (A).
v BPD2A-PORT-02-A
Failing Item:
v BPD2A-PORT-08-A
1402533A 1402533A
Explanation: An over current has been detected on
1402538B 1402538B
350V between BPD 2A and the load on its port J03 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J08 (B).
v BPD2A-PORT-03-A
Failing Item:
v BPD2A-PORT-08-B
1402534A 1402534A
Explanation: An over current has been detected on
1402538C 1402538C
350V between BPD 2A and the load on its port J04 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J08 (C).
v BPD2A-PORT-04-A
Failing Item:
v BPD2A-PORT-08-C
1402535A 1402535A
Explanation: An over current has been detected on
1402539A 1402539A
350V between BPD 2A and the load on its port J05 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J09 (A).
v BPD2A-PORT-05-A
Failing Item:
v BPD2A-PORT-09-A
1402536A 1402536A
Explanation: An over current has been detected on
1402539B 1402539B
350V between BPD 2A and the load on its port J06 (A).
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2A and the load on its port J09 (B).
v BPD2A-PORT-06-A
Failing Item:
v BPD2A-PORT-09-B
1402537A 1402537A
Explanation: An over current has been detected on
350V between BPD 2A and the load on its port J07 (A).
Failing Item:
v BPD3A-PORT-04-A
1402539C 1402539C
Explanation: An over current has been detected on
14026150 14026150
350V between BPD 2A and the load on its port J09 (C).
Explanation: The voltage on voltage level 50 has
Failing Item:
reached the warning undervoltage limit for the
v BPD2A-PORT-09-C specified cage or drawer.
1402622A 1402622A
14026256 14026256
Explanation: An over current has been detected on
350V between BPD 1B and the load on its port J02 (A). Explanation: The voltage on voltage level 56 has
reached the warning over voltage limit for the specified
Failing Item: cage or drawer.
v BPD1B-PORT-02-A
1402629A 1402629A
1402626A 1402626A
Explanation: An over current has been detected on
Explanation: An over current has been detected on 350V between BPD 1B and the load on its port J09 (A).
350V between BPD 1B and the load on its port J06 (A).
Failing Item:
Failing Item:
v BPD1B-PORT-09-A
v BPD1B-PORT-06-A
1402629B 1402629B
1402627A 1402627A
Explanation: An over current has been detected on
Explanation: An over current has been detected on 350V between BPD 1B and the load on its port J09 (B).
350V between BPD 1B and the load on its port J07 (A).
Failing Item:
Failing Item:
v BPD1B-PORT-09-B
v BPD1B-PORT-07-A
1402629C 1402629C
1402627B 1402627B
Explanation: An over current has been detected on
Explanation: An over current has been detected on 350V between BPD 1B and the load on its port J09 (C).
350V between BPD 1B and the load on its port J07 (B).
Failing Item:
Failing Item:
v BPD1B-PORT-09-C
v BPD1B-PORT-07-B
140262AA 140262AA
Explanation: An over current has been detected on
350V between BPD 1B and the load on its port J10 (A).
Failing Item:
v BPD1B-PORT-10-A
14026351 14026351
Explanation: An over current condition has been
140262AB 140262AB
detected for voltage level 50 for the specified cage or
Explanation: An over current has been detected on drawer.
350V between BPD 1B and the load on its port J10 (B).
Failing Item:
Failing Item: v FRULEVEL51
v BPD1B-PORT-10-B
14026352 14026352
140262AC 140262AC
Explanation: An over current condition has been
Explanation: An over current has been detected on detected for voltage level 52 for the specified cage or
350V between BPD 1B and the load on its port J10 (C). drawer.
Explanation: An over current has been detected on Explanation: An over current condition has been
350V between BPD 2B and the load on its port J01 (A). detected for voltage level 53 for the specified cage or
drawer.
Failing Item:
v BPD2B-PORT-01-A Failing Item:
v FRULEVEL53
1402632A 1402632A
14026354 14026354
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J02 (A). Explanation: An over current condition has been
detected for voltage level 54 for the specified cage or
Failing Item: drawer.
v BPD2B-PORT-02-A
Failing Item:
v FRULEVEL54
1402633A 1402633A
Explanation: An over current has been detected on 14026355 14026355
350V between BPD 2B and the load on its port J03 (A).
Explanation: An over current condition has been
Failing Item: detected for voltage level 55 for the specified cage or
v BPD2B-PORT-03-A drawer.
Failing Item:
1402634A 1402634A v FRULEVEL55
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J04 (A). 14026356 14026356
Failing Item: Explanation: An over current condition has been
v BPD2B-PORT-04-A detected for voltage level 56 for the specified cage or
drawer.
14026350 14026350 Failing Item:
Explanation: An over current condition has been v FRULEVEL56
detected for voltage level 50 for the specified cage or
drawer. 14026357 14026357
Failing Item: Explanation: An over current condition has been
v FRULEVEL50 detected for voltage level 57 for the specified cage or
drawer.
Failing Item:
v FRULEVEL57
Failing Item:
1402639A 1402639A
v FRULEVEL60
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J09 (A).
1402636A 1402636A
Failing Item:
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J06 (A). v BPD2B-PORT-09-A
Failing Item:
1402639B 1402639B
v BPD2B-PORT-06-A
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J09 (B).
1402637A 1402637A
Failing Item:
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J07 (A). v BPD2B-PORT-09-B
Failing Item:
1402639C 1402639C
v BPD2B-PORT-07-A
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J07 (C).
1402637B 1402637B
Failing Item:
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J07 (B). v BPD2B-PORT-09-C
Failing Item:
140263AA 140263AA
v BPD2B-PORT-07-B
Explanation: An over current has been detected on
350V between BPD 2B and the load on its port J10 (A).
Failing Item:
v BPD2B-PORT-10-A
14026451 14026451
Explanation: An over voltage condition has been
140263AB 140263AB
detected for voltage level 51 specified cage or drawer.
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2B and the load on its port J07 (B).
v FRULEVEL51
Failing Item:
v BPD2B-PORT-10-B
14026452 14026452
Explanation: An over voltage condition has been
140263AC 140263AC
detected for voltage level 52 specified cage or drawer.
Explanation: An over current has been detected on
Failing Item:
350V between BPD 2B and the load on its port J10 (C).
v FRULEVEL52
Failing Item:
v BPD2B-PORT-10-C
14026453 14026453
Explanation: An over voltage condition has been
1402641A 1402641A
detected for voltage level 53 specified cage or drawer.
Explanation: An over current has been detected on
Failing Item:
350V between BPD 3B and the load on its port J01 (A).
v FRULEVEL53
Failing Item:
v BPD3B-PORT-01-A
14026454 14026454
Explanation: An over voltage condition has been
1402642A 1402642A
detected for voltage level 54 specified cage or drawer.
Explanation: An over current has been detected on
Failing Item:
350V between BPD 3B and the load on its port J02 (A).
v FRULEVEL54
Failing Item:
v BPD3B-PORT-02-A
14026455 14026455
Explanation: An over voltage condition has been
1402643A 1402643A
detected for voltage level 55 specified cage or drawer.
Explanation: An over current has been detected on
Failing Item:
350V between BPD 3B and the load on its port J03 (A).
v FRULEVEL55
Failing Item:
v BPD3B-PORT-03-A
14026456 14026456
Explanation: An over voltage condition has been
1402644A 1402644A
detected for voltage level 56 specified cage or drawer.
Explanation: An over current has been detected on
Failing Item:
350V between BPD 3B and the load on its port J04 (A).
v FRULEVEL56
Failing Item:
v BPD3B-PORT-04-A
14026457 14026457
Explanation: An over voltage condition has been
14026450 14026450
detected for voltage level 57 specified cage or drawer.
Explanation: An over voltage condition has been
Failing Item:
detected for voltage level 50 specified cage or drawer.
v FRULEVEL57
Failing Item:
v FRULEVEL50
14026458 14026458
Explanation: An over voltage condition has been
detected for voltage level 58 specified cage or drawer.
Failing Item:
v FRULEVEL58
14027095 14027095
Explanation: BPA-A BPR-1 is defective.
14026459 14026459
Failing Item:
Explanation: An over voltage condition has been
detected for voltage level 59 specified cage or drawer. v BPR-1A
v BPC-A
Failing Item:
v BPD-1A
v FRULEVEL59
v BPD-2A
v IBF-1A
14026460 14026460
v BPE-BOARD-A
Explanation: An over voltage condition has been
detected for voltage level 60 specified cage or drawer.
14027096 14027096
Failing Item:
Explanation: BPA-A BPR-2 is defective.
v FRULEVEL60
Failing Item:
14027090 14027090 v BPR-2A
v BPC-A
Explanation: The BPCH in BPA-A is defective.
v BPD-1A
Failing Item:
v BPD-2A
v BPCH-A
v IBF-2A
v BPE-BOARD-A
14027091 14027091
Explanation: The BPC in BPA-A is defective. 14027097 14027097
Failing Item: Explanation: BPA-A BPR-3 is defective.
v BPC-A
Failing Item:
v BPR-3A
14027092 14027092
v BPC-A
Explanation: BPD-1 is defective in BPA-A. v BPD-1A
Failing Item: v BPD-2A
v BPD-1A v BPE-BOARD-A
v BPC-A
14027098 14027098
14027093 14027093 Explanation: BPA-A BPR-4 is defective.
Explanation: BPD-2 is defective in BPA-A. Failing Item:
Failing Item: v BPR-4A
v BPD-2A v BPC-A
v BPC-A v BPD-1A
v BPD-2A
14027094 14027094 v BPE-BOARD-A
Explanation: BPD-3 is defective in BPA-A.
14027099 14027099
Failing Item:
v BPD-3A Explanation: BPA-A BPR-5 is defective.
v BPE-BOARD-B
140271A2 140271A2
Explanation: BPC-B side detects that IBF-2B is
14027198 14027198
defective. (IBF is connected to BPA-B BPR-2B)
Explanation: BPA-B BPR-4 is defective.
Failing Item:
Failing Item: v IBF-2B
v BPR-4B v BPR-2B
v BPC-B v CBL-IBF2B
v BPD-1B v BPC-B
v BPD-2B v BPE-BOARD-B
v BPE-BOARD-B
14028072 14028072
14027199 14027199
Explanation: BPA-A has reported a temperature
Explanation: BPA-B BPR-5 is defective. warning in cage - Make sure that there are no
blocked/dirty air inlet or filters. Verify that all unused
Failing Item: logic positions are filled with filler books and that the
v BPR-5B BPF on the A-side has a cover over it / BPF on B-side
v BPC-B does not.
v BPD-1B
v BPD-2B 14028073 14028073
v BPE-BOARD-B Explanation: BPA-B has reported a temperature
warning in cage - Make sure that there are no
blocked/dirty air inlet or filters. Verify that all unused
1402719A 1402719A
logic positions are filled with filler books and that the
Explanation: BPA-B BPR-6 is defective. BPF on the A-side has a cover over it / BPF on B-side
does not.
Failing Item:
v BPR-6B
14028074 14028074
v BPC-B
v BPD-1B Explanation: The Room Ambient Humdity has been
reported as being out of specification. If unable to
v BPD-2B
correct condition contact next level of support. The
v BPE-BOARD-B Sensor(s) are located in the UEPO assembly.
14028084 14028084
14028132 14028132
Explanation: Input power to BPA B has been
recovered after loss or partial loss. IBM support should Explanation: A send secure vpd command was
be notified of potential problem if this occurs without received - Informational SRC.
cause being identified. Failing Item:
v NOT_A_BPA_FRU
14028090 14028090
Explanation: Input power to BPA A line cord 1 has 14028133 14028133
returned to normal levels. IBM support should be
notified of potential problem if this occurs without Explanation: A TMS (60) was received - Informational
cause being identified. SRC.
Failing Item:
14028091 14028091 v NOT_A_BPA_FRU
Explanation: Input power to BPA A line cord 2 has
returned to normal levels. IBM support should be 14028134 14028134
notified of potential problem if this occurs without
Explanation: This contains an ACDL log -
cause being identified.
Informational SRC.
Failing Item:
14028092 14028092
v NOT_A_BPA_FRU
Explanation: Input power to BPA B line cord 1 has
returned to normal levels. IBM support should be
notified of potential problem if this occurs without 14028135 14028135
cause being identified. Explanation: There has been an internal bulk power
software error. This is an informational reference code.
14028093 14028093 Failing Item:
Explanation: Input power to BPA B line cord 2 has v NOT_A_BPA_FRU
returned to normal levels. IBM support should be
notified of potential problem if this occurs without
14028136 14028136
cause being identified.
Explanation: A PU book has entered throttling mode.
This is an informational reference code.
140280C3 140280C3
Explanation: A-side BPC detects that the room UEPO
14028172 14028172
is in bypass. Verify the room UEPO loop is enabled.
Explanation: BPA-A has reported a temperature
Failing Item:
warning in cage - Make sure that there are no
v EPO-SWITCH blocked/dirty air inlet or filters. Verify that all unused
v BPC-A logic positions are filled with filler books.
v CBL-BPCA-EPO
14028173 14028173
14028130 14028130 Explanation: BPA-B has reported a temperature
Explanation: CAGE P/T Fru recovery. Cage in power warning in cage - Make sure that there are no
recovery mode for information only. blocked/dirty air inlet or filters. Verify that all unused
logic positions are filled with filler books.
v BPCHA-PORT-14
1402A022 1402A022
Explanation: A fault between (BPA-A) BPCH and the
1402A015 1402A015
load on port T22 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T15 has been detected.
v BPCHA-PORT-22
Failing Item:
v BPCHA-PORT-15
1402A023 1402A023
Explanation: A fault between (BPA-A) BPCH and the
1402A016 1402A016
load on port T23 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T16 has been detected.
v BPCHA-PORT-23
Failing Item:
v BPCHA-PORT-16
1402A024 1402A024
Explanation: A fault between (BPA-A) BPCH and the
1402A017 1402A017
load on port T24 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T17 has been detected.
v BPCHA-PORT-24
Failing Item:
v BPCHA-PORT-17
1402A025 1402A025
Explanation: A fault between (BPA-A) BPCH and the
1402A018 1402A018
load on port T25 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T18 has been detected.
v BPCHA-PORT-25
Failing Item:
v BPCHA-PORT-18
1402A026 1402A026
Explanation: A fault between (BPA-A) BPCH and the
1402A019 1402A019
load on port T26 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T19 has been detected.
v BPCHA-PORT-26
Failing Item:
v BPCHA-PORT-19
1402A027 1402A027
Explanation: A fault between (BPA-A) BPCH and the
1402A020 1402A020
load on port T27 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T20 has been detected.
v BPCHA-PORT-27
Failing Item:
v BPCHA-PORT-20
1402A028 1402A028
Explanation: A fault between (BPA-A) BPCH and the
1402A021 1402A021
load on port T28 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T21 has been detected.
v BPCHA-PORT-28
Failing Item:
v BPCHA-PORT-21
1402A029 1402A029
Explanation: A fault between (BPA-A) BPCH and the
load on port T29 has been detected.
Failing Item:
v BPCHA-PORT-29
1402A037 1402A037
Explanation: A fault between (BPA-A) BPCH and the
1402A030 1402A030
load on port T37 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T30 has been detected.
v BPCHA-PORT-37
Failing Item:
v BPCHA-PORT-30
1402A038 1402A038
Explanation: A fault between (BPA-A) BPCH and the
1402A031 1402A031
load on port T38 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T31 has been detected.
v BPCHA-PORT-38
Failing Item:
v BPCHA-PORT-31
1402A039 1402A039
Explanation: A fault between (BPA-A) BPCH and the
1402A032 1402A032
load on port T39 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T32 has been detected.
v BPCHA-PORT-39
Failing Item:
v BPCHA-PORT-32
1402A040 1402A040
Explanation: A fault between (BPA-A) BPCH and the
1402A033 1402A033
load on port T40 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T33 has been detected.
v BPCHA-PORT-40
Failing Item:
v BPCHA-PORT-33
1402A041 1402A041
Explanation: A fault between (BPA-A) BPCH and the
1402A034 1402A034
load on port T41 has been detected.
Explanation: A between (BPA-A) BPCH and the load
Failing Item:
on port T34 has been detected.
v BPCHA-PORT-41
Failing Item:
v BPCHA-PORT-34
1402A042 1402A042
Explanation: A fault between (BPA-A) BPCH and the
1402A035 1402A035
load on port T42 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T35 has been detected.
v BPCHA-PORT-42
Failing Item:
v BPCHA-PORT-35
1402A101 1402A101
Explanation: A fault between (BPA-A) BPD and the
1402A036 1402A036
load on port T1 has been detected.
Explanation: A fault between (BPA-A) BPCH and the
Failing Item:
load on port T36 has been detected.
v BPDA-PORT-01
Failing Item:
v BPCHA-PORT-36
1402A102 1402A102
Explanation: A fault between (BPA-A) BPD and the
load on port T2 has been detected.
Failing Item:
v BPDA-PORT-02
1402A110 1402A110
Explanation: A fault between (BPA-A) BPD and the
1402A103 1402A103
load on port T10 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T3 has been detected.
v BPDA-PORT-10
Failing Item:
v BPDA-PORT-03
1402A111 1402A111
Explanation: A fault between (BPA-A) BPD and the
1402A104 1402A104
load on port T11 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T4 has been detected.
v BPDA-PORT-11
Failing Item:
v BPDA-PORT-04
1402A112 1402A112
Explanation: A fault between (BPA-A) BPD and the
1402A105 1402A105
load on port T12 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T5 has been detected.
v BPDA-PORT-12
Failing Item:
v BPDA-PORT-05
1402A113 1402A113
Explanation: A fault between (BPA-A) BPD and the
1402A106 1402A106
load on port T13 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T6 has been detected.
v BPDA-PORT-13
Failing Item:
v BPDA-PORT-06
1402A114 1402A114
Explanation: A fault between (BPA-A) BPD and the
1402A107 1402A107
load on port T14 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T7 has been detected.
v BPDA-PORT-14
Failing Item:
v BPDA-PORT-07
1402A115 1402A115
Explanation: A fault between (BPA-A) BPD and the
1402A108 1402A108
load on port T15 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T8 has been detected.
v BPDA-PORT-15
Failing Item:
v BPDA-PORT-08
1402A116 1402A116
Explanation: A fault between (BPA-A) BPD and the
1402A109 1402A109
load on port T16 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T9 has been detected.
v BPDA-PORT-16
Failing Item:
v BPDA-PORT-09
1402A117 1402A117
Explanation: A fault between (BPA-A) BPD and the
load on port T17 has been detected.
Failing Item:
v BPDA-PORT-17
1402A125 1402A125
Explanation: A fault between (BPA-A) BPD and the
1402A118 1402A118
load on port T25 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T18 has been detected.
v BPDA-PORT-25
Failing Item:
v BPDA-PORT-18
1402A126 1402A126
Explanation: A fault between (BPA-A) BPD and the
1402A119 1402A119
load on port T26 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T19 has been detected.
v BPDA-PORT-26
Failing Item:
v BPDA-PORT-19
1402B006 1402B006
Explanation: A fault between (BPA-B) BPCH and the
1402A120 1402A120
load on port T6 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T20 has been detected.
v BPCHB-PORT-06
Failing Item:
v BPDA-PORT-20
1402B007 1402B007
Explanation: A fault between (BPA-B) BPCH and the
1402A121 1402A121
load on port T7 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T21 has been detected.
v BPCHB-PORT-07
Failing Item:
v BPDA-PORT-21
1402B008 1402B008
Explanation: A fault between (BPA-B) BPCH and the
1402A122 1402A122
load on port T8 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T22 has been detected.
v BPCHB-PORT-08
Failing Item:
v BPDA-PORT-22
1402B009 1402B009
Explanation: A fault between (BPA-B) BPCH and the
1402A123 1402A123
load on port T9 has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T23 has been detected.
v BPCHB-PORT-09
Failing Item:
v BPDA-PORT-23
1402B010 1402B010
Explanation: A fault between (BPA-B) BPCH and FDT
1402A124 1402A124
(T10) has been detected.
Explanation: A fault between (BPA-A) BPD and the
Failing Item:
load on port T24 has been detected.
v BPCHB-PORT-10
Failing Item:
v BPDA-PORT-24
1402B011 1402B011
Explanation: A fault between (BPA-B) BPCH and the
load on port T11 has been detected.
Failing Item:
v BPCHB-PORT-11
1402B019 1402B019
Explanation: A fault between (BPA-B) BPCH and the
1402B012 1402B012
load on port T19 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T12 has been detected.
v BPCHB-PORT-19
Failing Item:
v BPCHB-PORT-12
1402B020 1402B020
Explanation: A fault between (BPA-B) BPCH and the
1402B013 1402B013
load on port T20 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T13 has been detected.
v BPCHB-PORT-20
Failing Item:
v BPCHB-PORT-13
1402B021 1402B021
Explanation: A fault between (BPA-B) BPCH and the
1402B014 1402B014
load on port T21 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T14 has been detected.
v BPCHB-PORT-21
Failing Item:
v BPCHB-PORT-14
1402B022 1402B022
Explanation: A fault between (BPA-B) BPCH and the
1402B015 1402B015
load on port T22 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T15 has been detected.
v BPCHB-PORT-22
Failing Item:
v BPCHB-PORT-15
1402B023 1402B023
Explanation: A fault between (BPA-B) BPCH and the
1402B016 1402B016
load on port T23 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T16 has been detected.
v BPCHB-PORT-23
Failing Item:
v BPCHB-PORT-16
1402B024 1402B024
Explanation: A fault between (BPA-B) BPCH and the
1402B017 1402B017
load on port T24 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T17 has been detected.
v BPCHB-PORT-24
Failing Item:
v BPCHB-PORT-17
1402B025 1402B025
Explanation: A fault between (BPA-B) BPCH and the
1402B018 1402B018
load on port T25 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T18 has been detected.
v BPCHB-PORT-25
Failing Item:
v BPCHB-PORT-18
1402B026 1402B026
Explanation: A fault between (BPA-B) BPCH and the
load on port T26 has been detected.
Failing Item:
v BPCHB-PORT-26
1402B034 1402B034
Explanation: A fault between (BPA-B) BPCH and the
1402B027 1402B027
load on port T34 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T27 has been detected.
v BPCHB-PORT-34
Failing Item:
v BPCHB-PORT-27
1402B035 1402B035
Explanation: A fault between (BPA-B) BPCH and the
1402B028 1402B028
load on port T35 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T28 has been detected.
v BPCHB-PORT-35
Failing Item:
v BPCHB-PORT-28
1402B036 1402B036
Explanation: A fault between (BPA-B) BPCH and the
1402B029 1402B029
load on port T36 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T29 has been detected.
v BPCHB-PORT-36
Failing Item:
v BPCHB-PORT-29
1402B037 1402B037
Explanation: A fault between (BPA-B) BPCH and the
1402B030 1402B030
load on port T37 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T30 has been detected.
v BPCHB-PORT-37
Failing Item:
v BPCHB-PORT-30
1402B038 1402B038
Explanation: A fault between (BPA-B) BPCH and the
1402B031 1402B031
load on port T38 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T31 has been detected.
v BPCHB-PORT-38
Failing Item:
v BPCHB-PORT-31
1402B039 1402B039
Explanation: A fault between (BPA-B) BPCH and the
1402B032 1402B032
load on port T39 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T32 has been detected.
v BPCHB-PORT-39
Failing Item:
v BPCHB-PORT-32
1402B040 1402B040
Explanation: A fault between (BPA-B) BPCH and the
1402B033 1402B033
load on port T40 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T33 has been detected.
v BPCHB-PORT-40
Failing Item:
v BPCHB-PORT-33
1402B041 1402B041
Explanation: A fault between (BPA-B) BPCH and the
load on port T41 has been detected.
Failing Item:
v BPCHB-PORT-41
1402B107 1402B107
Explanation: A fault between (BPA-B) BPD and the
1402B042 1402B042
load on port T7 has been detected.
Explanation: A fault between (BPA-B) BPCH and the
Failing Item:
load on port T42 has been detected.
v BPDB-PORT-07
Failing Item:
v BPCHB-PORT-42
1402B108 1402B108
Explanation: A fault between (BPA-B) BPD and the
1402B101 1402B101
load on port T8 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T1 has been detected.
v BPDB-PORT-08
Failing Item:
v BPDB-PORT-01
1402B109 1402B109
Explanation: A fault between (BPA-B) BPD and the
1402B102 1402B102
load on port T9 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T2 has been detected.
v BPDB-PORT-09
Failing Item:
v BPDB-PORT-02
1402B110 1402B110
Explanation: A fault between (BPA-B) BPD and the
1402B103 1402B103
load on port T10 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T3 has been detected.
v BPDB-PORT-10
Failing Item:
v BPDB-PORT-03
1402B111 1402B111
Explanation: A fault between (BPA-B) BPD and the
1402B104 1402B104
load on port T11 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T4 has been detected.
v BPDB-PORT-11
Failing Item:
v BPDB-PORT-04
1402B112 1402B112
Explanation: A fault between (BPA-B) BPD and the
1402B105 1402B105
load on port T12 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T5 has been detected.
v BPDB-PORT-12
Failing Item:
v BPDB-PORT-05
1402B113 1402B113
Explanation: A fault between (BPA-B) BPD and the
1402B106 1402B106
load on port T13 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T6 has been detected.
v BPDB-PORT-13
Failing Item:
v BPDB-PORT-06
1402B114 1402B114
Explanation: A fault between (BPA-B) BPD and the
load on port T14 has been detected.
Failing Item:
v BPDB-PORT-14
1402B122 1402B122
Explanation: A fault between (BPA-B) BPD and the
1402B115 1402B115
load on port T22 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T15 has been detected.
v BPDB-PORT-22
Failing Item:
v BPDB-PORT-15
1402B123 1402B123
Explanation: A fault between (BPA-B) BPD and the
1402B116 1402B116
load on port T23 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T16 has been detected.
v BPDB-PORT-23
Failing Item:
v BPDB-PORT-16
1402B124 1402B124
Explanation: A fault between (BPA-B) BPD and the
1402B117 1402B117
load on port T24 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T17 has been detected.
v BPDB-PORT-24
Failing Item:
v BPDB-PORT-17
1402B125 1402B125
Explanation: A fault between (BPA-B) BPD and the
1402B118 1402B118
load on port T25 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T18 has been detected.
v BPDB-PORT-25
Failing Item:
v BPDB-PORT-18
1402B126 1402B126
Explanation: A fault between (BPA-B) BPD and the
1402B119 1402B119
load on port T26 has been detected.
Explanation: A fault between (BPA-B) BPD and the
Failing Item:
load on port T19 has been detected.
v BPDB-PORT-26
Failing Item:
v BPDB-PORT-19
1402B120 1402B120
Explanation: A fault between (BPA-B) BPD and the
load on port T20 has been detected.
Failing Item:
v BPDB-PORT-20
1402B121 1402B121
Explanation: A fault between (BPA-B) BPD and the
load on port T21 has been detected.
Failing Item:
v BPDB-PORT-21
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
169C3100 169C3100 level of support.
169CFFF4 169CFFF4
169C4060 169C4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
169CFFF5 169CFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
169C4061 169C4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
169C4100 169C4100
169CFFF6 169CFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
169CFFFB 169CFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
169CFFFC 169CFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
169CFFFD 169CFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
1750FFF6 1750FFF6
Explanation: Disk device detected recoverable error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCDEV
1750FFFA 1750FFFA
Explanation: Disk device wrong response was
recovered by the IOP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCDEV
v FCIOA
v OPT_CLN
1750FFFE 1750FFFE
Explanation: Temporary Fibre Channel interface error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCINTF
v FCDEV
v FCIOA
v OPT_CLN
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
198B3100 198B3100 level of support.
198BFFF4 198BFFF4
198B4060 198B4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
198BFFF5 198BFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
198B4061 198B4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
198B4100 198B4100
198BFFF6 198BFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
198BFFFB 198BFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
198BFFFC 198BFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
198BFFFD 198BFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
198C3100 198C3100 level of support.
198CFFF4 198CFFF4
198C4060 198C4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
198CFFF5 198CFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
198C4061 198C4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
198C4100 198C4100
198CFFF6 198CFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
198CFFFB 198CFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
198CFFFC 198CFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
198CFFFD 198CFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
198D3100 198D3100 level of support.
198DFFF4 198DFFF4
198D4060 198D4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
198DFFF5 198DFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
198D4061 198D4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
198D4100 198D4100
198DFFF6 198DFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
198DFFFB 198DFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
198DFFFC 198DFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
198DFFFD 198DFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
198E3100 198E3100 level of support.
198EFFF4 198EFFF4
198E4060 198E4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
198EFFF5 198EFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
198E4061 198E4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
198E4100 198E4100
198EFFF6 198EFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
198EFFFB 198EFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
198EFFFC 198EFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
198EFFFD 198EFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19A13100 19A13100 level of support.
19A1FFF4 19A1FFF4
19A14060 19A14060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19A1FFF5 19A1FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19A14061 19A14061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19A14100 19A14100
19A1FFF6 19A1FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19A1FFFB 19A1FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19A1FFFC 19A1FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19A1FFFD 19A1FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19A33100 19A33100 level of support.
19A3FFF4 19A3FFF4
19A34060 19A34060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19A3FFF5 19A3FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19A34061 19A34061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19A34100 19A34100
19A3FFF6 19A3FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19A3FFFB 19A3FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19A3FFFC 19A3FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19A3FFFD 19A3FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19A43100 19A43100 level of support.
19A4FFF4 19A4FFF4
19A44060 19A44060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19A4FFF5 19A4FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19A44061 19A44061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19A44100 19A44100
19A4FFF6 19A4FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19A4FFFB 19A4FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19A4FFFC 19A4FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19A4FFFD 19A4FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19B03100 19B03100 level of support.
19B0FFF4 19B0FFF4
19B04060 19B04060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19B0FFF5 19B0FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19B04061 19B04061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19B04100 19B04100
19B0FFF6 19B0FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19B0FFFB 19B0FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19B0FFFC 19B0FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19B0FFFD 19B0FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19B13100 19B13100 level of support.
19B1FFF4 19B1FFF4
19B14060 19B14060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19B1FFF5 19B1FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19B14061 19B14061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19B14100 19B14100
19B1FFF6 19B1FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19B1FFFB 19B1FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19B1FFFC 19B1FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19B1FFFD 19B1FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19B33100 19B33100 level of support.
19B3FFF4 19B3FFF4
19B34060 19B34060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19B3FFF5 19B3FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19B34061 19B34061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19B34100 19B34100
19B3FFF6 19B3FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19B3FFFB 19B3FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19B3FFFC 19B3FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19B3FFFD 19B3FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19B43100 19B43100 level of support.
19B4FFF4 19B4FFF4
19B44060 19B44060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19B4FFF5 19B4FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19B44061 19B44061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19B44100 19B44100
19B4FFF6 19B4FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19B4FFFB 19B4FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19B4FFFC 19B4FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19B4FFFD 19B4FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19B53100 19B53100 level of support.
19B5FFF4 19B5FFF4
19B54060 19B54060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19B5FFF5 19B5FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19B54061 19B54061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19B54100 19B54100
19B5FFF6 19B5FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19B5FFFB 19B5FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19B5FFFC 19B5FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19B5FFFD 19B5FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
19B73100 19B73100 level of support.
19B7FFF4 19B7FFF4
19B74060 19B74060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
19B7FFF5 19B7FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
19B74061 19B74061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
19B74100 19B74100
19B7FFF6 19B7FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
19B7FFFB 19B7FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
19B7FFFC 19B7FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
19B7FFFD 19B7FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
2105FFF6 2105FFF6
Explanation: Disk device detected recoverable error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCDEV
2105FFFA 2105FFFA
Explanation: Disk device wrong response was
recovered by the IOP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCDEV
v FCIOA
v OPT_CLN
2105FFFE 2105FFFE
Explanation: Temporary Fibre Channel interface error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCINTF
v FCDEV
v FCIOA
v OPT_CLN
2107FFF6 2107FFF6
Explanation: Disk device detected recoverable error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCDEV
2107FFFA 2107FFFA
Explanation: Disk device wrong response was
recovered by the IOP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCDEV
v FCIOA
v OPT_CLN
2107FFFE 2107FFFE
Explanation: Temporary Fibre Channel interface error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v FCINTF
v FCDEV
v FCIOA
v OPT_CLN
266DB9B0 266DB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
266EB9B0 266EB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
266FB904 266FB904
Explanation: I/O Adapter Licensed Internal Code
failed
Failing Item:
v AJDGP01
v FI00719
266FB934 266FB934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
266FB940 266FB940
Explanation: I/O adapter hardware error detected.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
266FB941 266FB941
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
266FB942 266FB942
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
Explanation: Adapter card storage error Explanation: I/O adapter Licensed Internal Code
failed.
Failing Item:
Failing Item:
v AJDGP01
v AJDGP01
v AJDG301
v IOA
26893081 26893081
Failing Item:
26896228 26896228
v NETSERV
v IOA Explanation: Windows initiated a warm boot
v AJDGP01 Failing Item:
v AJDGP01
v IOA
26896534 26896534
Explanation: A Virtual SCSI error was detected.
26896501 26896501
Failing Item:
Explanation: A Windows fatal error occurred
v AS4NTDD
Failing Item:
v AJDGP01
v IOA
v NTOPSYS
v AJDGP01
26896535 26896535
26896502 26896502
Explanation: A Virtual SCSI error was detected.
Explanation: A Windows fatal error occurred
Failing Item:
Failing Item:
v NTUSER
v AJDGP01
v NTDEVDR
v IOA
v AJDGP01
26896530 26896530
26896538 26896538
Explanation: A Virtual SCSI error was detected.
Explanation: A Virtual SCSI error was detected.
Failing Item:
Failing Item:
v NTVSCSI
v NTVSCSI
v NTOPSYS
v NTOPSYS
26896531 26896531
26896539 26896539
Explanation: A Virtual SCSI error was detected.
Explanation: A Virtual SCSI error was detected.
Failing Item:
Failing Item:
v NTVSCSI
v NTVSCSI
v AS4NTDD
v AS4NTDD
v NTOPSYS
v NTOPSYS
v AJDGP01
v AJDGP01
26896532 26896532
2689653A 2689653A
Explanation: A Virtual SCSI error was detected.
Explanation: A Virtual SCSI error was detected.
Failing Item:
Failing Item:
v NTOPSYS
v NTOPSYS
v AJDGP01
v AJDGP01
v AS4NTDD
v AS4NTDD
26896533 26896533
2689653B 2689653B
Explanation: A Virtual SCSI error was detected.
Explanation: A Virtual SCSI error was detected.
Failing Item:
Failing Item:
v NTUSER
v NTUSER
v NTOPSYS
v NTOPSYS
v AS4NTDD
v AS4NTDD
v NTVSCSI
2689653C 2689653C
Explanation: A Virtual SCSI error was detected.
26896544 26896544
Failing Item:
Explanation: A Virtual SCSI error was detected.
v AS4NTDD
Failing Item:
v AJDGP01
v NTVSCSI
v NTOPSYS
v NTOPSYS
2689653D 2689653D
26896580 26896580
Explanation: A Virtual SCSI error was detected.
Explanation: A Windows fatal error occurred
Failing Item:
Failing Item:
v NTUSER
v DISKIMG
v NTDEVDR
v IOA
v AJDGP01
v AJDGP01
2689653F 2689653F
26896590 26896590
Explanation: A Virtual SCSI error was detected.
Explanation: A Netfinity Server error was detected
Failing Item:
v NTDEVDR
268965B0 268965B0
v NTOPSYS
Explanation: A HostLAN error was detected
v AJDG301
Failing Item:
26896540 26896540 v NTLANDD
v NTOPSYS
Explanation: A Virtual SCSI error was detected.
Failing Item:
268965B1 268965B1
v NTVSCSI
Explanation: A HostLAN error was detected
v AJDGP01
v AJDG301 Failing Item:
v NTLANDD
26896541 26896541 v NTOPSYS
v AJDG301
Explanation: A permanent I/O processor failure
occurred
268965B2 268965B2
Failing Item:
v IOA Explanation: A HostLAN error was detected
v AJDGP01 Failing Item:
v NTDEVDR
26896542 26896542 v NTOPSYS
Explanation: Licensed Internal Code error detected. v AJDG301
Failing Item:
26898301 26898301
v AJDG301
v AJDGP01 Explanation: An I/O adapter failure occurred.
Failing Item:
26896543 26896543 v AJDGP01
Explanation: A Windows fatal error occurred v IOA
Failing Item:
v NTOPSYS
Failing Item:
2689B4B1 2689B4B1
v IOA
Explanation: A Netfinity Server error was detected
2689B3B5 2689B3B5 Failing Item:
Explanation: A permanent I/O processor failure v NETSERV
occurred v AJDGP01
Failing Item:
v IOA 2689B4B9 2689B4B9
Explanation: An I/O adapter failure occurred.
2689B3B6 2689B3B6 Failing Item:
Explanation: A permanent I/O processor failure v IOA
occurred
Failing Item: 2689B4BC 2689B4BC
v IOA Explanation: A Netfinity Server error was detected
Failing Item:
2689B3B7 2689B3B7
v NETSERV
Explanation: A permanent I/O processor failure
occurred
2689B4BF 2689B4BF
Failing Item:
Explanation: A Netfinity Server error was detected
v IOA
Failing Item:
2689B3B8 2689B3B8 v NSCABLE
2689B904 2689B904
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v IOA
2689B935 2689B935
Explanation: Incompatible hardware detected.
Failing Item:
v AJDGP01
v IOA
2689B960 2689B960
Explanation: I/O processor Licensed Internal Code
error
Failing Item:
v AJDGP01
v IOA
2689BE00 2689BE00
Explanation: An I/O adapter failure occurred.
Failing Item:
v AJDGP01
v IOA
2742B940 2742B940
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDGP01
v MA_BRDG
2742B941 2742B941
Explanation: One of the ports on the IOA has failed.
Failing Item:
v FI00719
v AJDGP01
2743B951 2743B951
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2744B920 2744B920
Explanation: I/O adapter Licensed Internal Code
failed
Failing Item:
v AJDGP01
v FI00718
v FI00719
2744B921 2744B921
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2744B934 2744B934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
2745B934 2745B934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
2745B940 2745B940
Explanation: I/O adapter hardware error detected.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2745B941 2745B941
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2745B942 2745B942
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2746B934 2746B934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
2746B940 2746B940
Explanation: I/O adapter hardware error detected.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2746B941 2746B941
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2746B942 2746B942
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 27492202 27492202
Explanation: Removable media error during IPL
27491307 27491307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 27493000 27493000
Explanation: A permanent I/O processor failure
27491310 27491310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
27493001 27493001
Explanation: Not valid condition in I/O Processor 27493022 27493022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
27493002 27493002 v STORIOA
Explanation: Addressed device failed to respond to
selection 27493023 27493023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
27493006 27493006
Explanation: System bus error 27493080 27493080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
27493102 27493102
27493120 27493120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 27493121 27493121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 27493150 27493150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27493205 27493205
Explanation: Disk sector read error
27493142 27493142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
27493250 27493250
27496070 27496070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
27496071 27496071
27496075 27496075
27493401 27493401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
27496076 27496076
27493501 27493501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
27499041 27499041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
27499081 27499081
27499050 27499050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
2749BE00 2749BE00
Explanation: I/O processor detected a fault condition
2749B3E0 2749B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
2749B3E1 2749B3E1
2749FF3D 2749FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
2749B410 2749B410
2749FF6D 2749FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
2749B411 2749B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
2749B412 2749B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
2749B935 2749B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
Explanation: I/O processor detected a SCSI bus Response: Error occurred on SCSI bus 0.
configuration error Failing Item:
Response: Error occurred on SCSI bus 0. v IOPIP13
Failing Item: v FI01107
v IOPIP17 v STORIOA
v USER v FI01140
v FI01107 v DEVBPLN
v STORIOA
27573101 27573101
27573021 27573021 Explanation: I/O processor card detected interface
error
Explanation: I/O processor detected a SCSI bus
configuration error Response: Error occurred on SCSI bus 1.
Response: Error occurred on SCSI bus 1. Failing Item:
Failing Item: v IOPIP13
v IOPIP17 v FI01107
v USER v STORIOA
v FI01107 v FI01140
v STORIOA v DEVBPLN
Explanation: I/O processor detected a SCSI bus Explanation: I/O processor card detected interface
configuration error error
Response: Error occurred on SCSI bus 2. Response: Error occurred on SCSI bus 2.
v FI01140 v SVCDOCS
v DEVBPLN
27573140 27573140
27573103 27573103 Explanation: I/O Processor detected that the bus is
Explanation: I/O processor card detected interface now operational
error Response: This reference code and the 3120 reference
Response: Error occurred on SCSI bus 3. code that occurred before it require no service action,
since SCSI bus 0 is now operational.
Failing Item:
v IOPIP13
27573141 27573141
v FI01107
Explanation: I/O Processor detected that the bus is
v STORIOA
now operational
v FI01140
Response: This reference code and the 3121 reference
v DEVBPLN
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27573120 27573120
Explanation: I/O Processor detected that the bus is 27573142 27573142
not operational
Explanation: I/O Processor detected that the bus is
Response: A device was added to SCSI bus 0 of the now operational
I/O Adapter and caused the bus to become not
Response: This reference code and the 3122 reference
operational. Remove the device.
code that occurred before it require no service action,
Failing Item: since SCSI bus 2 is now operational.
v SVCDOCS
27573143 27573143
27573121 27573121 Explanation: I/O Processor detected that the bus is
Explanation: I/O Processor detected that the bus is now operational
not operational Response: This reference code and the 3123 reference
Response: A device was added to SCSI bus 1 of the code that occurred before it require no service action,
I/O Adapter and caused the bus to become not since SCSI bus 3 is now operational.
operational. Remove the device.
Failing Item: 27573150 27573150
v ANYBRDG
2757FF6D 2757FF6D
Explanation: I/O processor detected a recoverable
system bus error
Failing Item:
v IOP
v ANYBUS
2760B951 2760B951
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
Explanation: I/O processor detected a SCSI bus Response: Error occurred on SCSI bus 0.
configuration error Failing Item:
Response: Error occurred on SCSI bus 0. v IOPIP13
Failing Item: v FI01107
v IOPIP17 v STORIOA
v USER v FI01140
v FI01107 v DEVBPLN
v STORIOA
27633101 27633101
27633021 27633021 Explanation: I/O processor card detected interface
error
Explanation: I/O processor detected a SCSI bus
configuration error Response: Error occurred on SCSI bus 1.
Response: Error occurred on SCSI bus 1. Failing Item:
Failing Item: v IOPIP13
v IOPIP17 v FI01107
v USER v STORIOA
v FI01107 v FI01140
v STORIOA v DEVBPLN
Explanation: I/O processor detected a SCSI bus Explanation: I/O processor card detected interface
configuration error error
Response: Error occurred on SCSI bus 2. Response: Error occurred on SCSI bus 2.
v FI01140 v SVCDOCS
v DEVBPLN
27633140 27633140
27633103 27633103 Explanation: I/O Processor detected that the bus is
Explanation: I/O processor card detected interface now operational
error Response: This reference code and the 3120 reference
Response: Error occurred on SCSI bus 3. code that occurred before it require no service action,
since SCSI bus 0 is now operational.
Failing Item:
v IOPIP13
27633141 27633141
v FI01107
Explanation: I/O Processor detected that the bus is
v STORIOA
now operational
v FI01140
Response: This reference code and the 3121 reference
v DEVBPLN
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27633120 27633120
Explanation: I/O Processor detected that the bus is 27633142 27633142
not operational
Explanation: I/O Processor detected that the bus is
Response: A device was added to SCSI bus 0 of the now operational
I/O Adapter and caused the bus to become not
Response: This reference code and the 3122 reference
operational. Remove the device.
code that occurred before it require no service action,
Failing Item: since SCSI bus 2 is now operational.
v SVCDOCS
27633143 27633143
27633121 27633121 Explanation: I/O Processor detected that the bus is
Explanation: I/O Processor detected that the bus is now operational
not operational Response: This reference code and the 3123 reference
Response: A device was added to SCSI bus 1 of the code that occurred before it require no service action,
I/O Adapter and caused the bus to become not since SCSI bus 3 is now operational.
operational. Remove the device.
Failing Item: 27633150 27633150
v ANYBRDG
2763FF6D 2763FF6D
Explanation: I/O processor detected a recoverable
system bus error
Failing Item:
v IOP
v ANYBUS
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 27672202 27672202
Explanation: Removable media error during IPL
27671307 27671307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 27673000 27673000
Explanation: A permanent I/O processor failure
27671310 27671310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
27673001 27673001
Explanation: Not valid condition in I/O Processor 27673022 27673022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
27673002 27673002 v STORIOA
Explanation: Addressed device failed to respond to
selection 27673023 27673023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
27673006 27673006
Explanation: System bus error 27673080 27673080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
27673102 27673102
27673120 27673120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 27673121 27673121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 27673150 27673150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27673205 27673205
Explanation: Disk sector read error
27673142 27673142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
27673250 27673250
27676070 27676070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
27676071 27676071
27676075 27676075
27673401 27673401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
27676076 27676076
27673501 27673501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
27679041 27679041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
27679081 27679081
27679050 27679050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
2767BE00 2767BE00
Explanation: I/O processor detected a fault condition
2767B3E0 2767B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
2767B3E1 2767B3E1
2767FF3D 2767FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
2767B410 2767B410
2767FF6D 2767FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
2767B411 2767B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
2767B412 2767B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
2767B935 2767B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 27682202 27682202
Explanation: Removable media error during IPL
27681307 27681307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 27683000 27683000
Explanation: A permanent I/O processor failure
27681310 27681310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
27683001 27683001
Explanation: Not valid condition in I/O Processor 27683022 27683022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
27683002 27683002 v STORIOA
Explanation: Addressed device failed to respond to
selection 27683023 27683023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
27683006 27683006
Explanation: System bus error 27683080 27683080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
27683102 27683102
27683120 27683120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 27683121 27683121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 27683150 27683150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27683205 27683205
Explanation: Disk sector read error
27683142 27683142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
27683250 27683250
27686070 27686070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
27686071 27686071
27686075 27686075
27683401 27683401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
27686076 27686076
27683501 27683501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
27689041 27689041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
27689081 27689081
27689050 27689050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
2768BE00 2768BE00
Explanation: I/O processor detected a fault condition
2768B3E0 2768B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
2768B3E1 2768B3E1
2768FF3D 2768FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
2768B410 2768B410
2768FF6D 2768FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
2768B411 2768B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
2768B412 2768B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
2768B935 2768B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
2771B934 2771B934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
2771B940 2771B940
Explanation: I/O adapter hardware error detected.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2771B941 2771B941
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2771B942 2771B942
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2772B934 2772B934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
2772B940 2772B940
Explanation: I/O adapter hardware error detected.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2772B941 2772B941
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2772B942 2772B942
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
Explanation: I/O processor detected a SCSI bus Response: Error occurred on SCSI bus 0.
configuration error Failing Item:
Response: Error occurred on SCSI bus 0. v IOPIP13
Failing Item: v FI01107
v IOPIP17 v STORIOA
v USER v FI01140
v FI01107 v DEVBPLN
v STORIOA
27803101 27803101
27803021 27803021 Explanation: I/O processor card detected interface
error
Explanation: I/O processor detected a SCSI bus
configuration error Response: Error occurred on SCSI bus 1.
Response: Error occurred on SCSI bus 1. Failing Item:
Failing Item: v IOPIP13
v IOPIP17 v FI01107
v USER v STORIOA
v FI01107 v FI01140
v STORIOA v DEVBPLN
Explanation: I/O processor detected a SCSI bus Explanation: I/O processor card detected interface
configuration error error
Response: Error occurred on SCSI bus 2. Response: Error occurred on SCSI bus 2.
v FI01140 v SVCDOCS
v DEVBPLN
27803140 27803140
27803103 27803103 Explanation: I/O Processor detected that the bus is
Explanation: I/O processor card detected interface now operational
error Response: This reference code and the 3120 reference
Response: Error occurred on SCSI bus 3. code that occurred before it require no service action,
since SCSI bus 0 is now operational.
Failing Item:
v IOPIP13
27803141 27803141
v FI01107
Explanation: I/O Processor detected that the bus is
v STORIOA
now operational
v FI01140
Response: This reference code and the 3121 reference
v DEVBPLN
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27803120 27803120
Explanation: I/O Processor detected that the bus is 27803142 27803142
not operational
Explanation: I/O Processor detected that the bus is
Response: A device was added to SCSI bus 0 of the now operational
I/O Adapter and caused the bus to become not
Response: This reference code and the 3122 reference
operational. Remove the device.
code that occurred before it require no service action,
Failing Item: since SCSI bus 2 is now operational.
v SVCDOCS
27803143 27803143
27803121 27803121 Explanation: I/O Processor detected that the bus is
Explanation: I/O Processor detected that the bus is now operational
not operational Response: This reference code and the 3123 reference
Response: A device was added to SCSI bus 1 of the code that occurred before it require no service action,
I/O Adapter and caused the bus to become not since SCSI bus 3 is now operational.
operational. Remove the device.
Failing Item: 27803150 27803150
v ANYBRDG
2780FF6D 2780FF6D
Explanation: I/O processor detected a recoverable
system bus error
Failing Item:
v IOP
v ANYBUS
Explanation: I/O processor detected a SCSI bus Response: Error occurred on SCSI bus 0.
configuration error Failing Item:
Response: Error occurred on SCSI bus 0. v IOPIP13
Failing Item: v FI01107
v IOPIP17 v STORIOA
v USER v FI01140
v FI01107 v DEVBPLN
v STORIOA
27823101 27823101
27823021 27823021 Explanation: I/O processor card detected interface
error
Explanation: I/O processor detected a SCSI bus
configuration error Response: Error occurred on SCSI bus 1.
Response: Error occurred on SCSI bus 1. Failing Item:
Failing Item: v IOPIP13
v IOPIP17 v FI01107
v USER v STORIOA
v FI01107 v FI01140
v STORIOA v DEVBPLN
Explanation: I/O processor detected a SCSI bus Explanation: I/O processor card detected interface
configuration error error
Response: Error occurred on SCSI bus 2. Response: Error occurred on SCSI bus 2.
v FI01140 v SVCDOCS
v DEVBPLN
27823140 27823140
27823103 27823103 Explanation: I/O Processor detected that the bus is
Explanation: I/O processor card detected interface now operational
error Response: This reference code and the 3120 reference
Response: Error occurred on SCSI bus 3. code that occurred before it require no service action,
since SCSI bus 0 is now operational.
Failing Item:
v IOPIP13
27823141 27823141
v FI01107
Explanation: I/O Processor detected that the bus is
v STORIOA
now operational
v FI01140
Response: This reference code and the 3121 reference
v DEVBPLN
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
27823120 27823120
Explanation: I/O Processor detected that the bus is 27823142 27823142
not operational
Explanation: I/O Processor detected that the bus is
Response: A device was added to SCSI bus 0 of the now operational
I/O Adapter and caused the bus to become not
Response: This reference code and the 3122 reference
operational. Remove the device.
code that occurred before it require no service action,
Failing Item: since SCSI bus 2 is now operational.
v SVCDOCS
27823143 27823143
27823121 27823121 Explanation: I/O Processor detected that the bus is
Explanation: I/O Processor detected that the bus is now operational
not operational Response: This reference code and the 3123 reference
Response: A device was added to SCSI bus 1 of the code that occurred before it require no service action,
I/O Adapter and caused the bus to become not since SCSI bus 3 is now operational.
operational. Remove the device.
Failing Item: 27823150 27823150
v ANYBRDG
2782FF6D 2782FF6D
Explanation: I/O processor detected a recoverable
system bus error
Failing Item:
v IOP
v ANYBUS
Explanation: A permanent I/O processor failure IPL the I/O processor, see Debug the resource. If an
occurred I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v FCIOA Failing Item:
v ANYBRDG v SVCDOCS
v OPT_CLN
2787FF3D 2787FF3D
27878151 27878151 Explanation: Recovered IOA error
Explanation: I/O processor Licensed Internal Code Failing Item:
error v FCIOA
Failing Item: v ANYBRDG
v AJDGP01 v OPT_CLN
v FCIOA
v IOP
v OPT_CLN
27878155 27878155
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
27878156 27878156
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
27879091 27879091
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
IPL the I/O processor, see Debug the resource. If an
I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v SVCDOCS
27879092 27879092
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
2793B940 2793B940
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDGP01
v MA_BRDG
2793B941 2793B941
Explanation: One of the ports on the IOA has failed.
Failing Item:
v FI00719
v AJDGP01
2805B940 2805B940
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDGP01
v MA_BRDG
2805B941 2805B941
Explanation: One of the ports on the IOA has failed.
Failing Item:
v FI00719
v AJDGP01
Explanation: A permanent I/O processor failure IPL the I/O processor, see Debug the resource. If an
occurred I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v FCIOA Failing Item:
v ANYBRDG v SVCDOCS
v OPT_CLN
280DFF3D 280DFF3D
280D8151 280D8151 Explanation: Recovered IOA error
Explanation: I/O processor Licensed Internal Code Failing Item:
error v FCIOA
Failing Item: v ANYBRDG
v AJDGP01 v OPT_CLN
v FCIOA
v IOP
v OPT_CLN
280D8155 280D8155
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
280D8156 280D8156
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
280D9091 280D9091
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
IPL the I/O processor, see Debug the resource. If an
I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v SVCDOCS
280D9092 280D9092
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
Explanation: A permanent I/O processor failure IPL the I/O processor, see Debug the resource. If an
occurred I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v FCIOA Failing Item:
v ANYBRDG v SVCDOCS
v OPT_CLN
280EFF3D 280EFF3D
280E8151 280E8151 Explanation: Recovered IOA error
Explanation: I/O processor Licensed Internal Code Failing Item:
error v FCIOA
Failing Item: v ANYBRDG
v AJDGP01 v OPT_CLN
v FCIOA
v IOP
v OPT_CLN
280E8155 280E8155
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
280E8156 280E8156
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
280E9091 280E9091
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
IPL the I/O processor, see Debug the resource. If an
I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v SVCDOCS
280E9092 280E9092
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
2838B930 2838B930
Explanation: I/O adapter Licensed Internal Code
failed
Failing Item:
v AJDGP01
v FI00718
v FI00719
2838B931 2838B931
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2838B933 2838B933
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v AJDGP01
283C8401 283C8401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
283C8404 283C8404
Explanation: System log entry only, no service action
required
283CFFF4 283CFFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
283D8401 283D8401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
283D8404 283D8404
Explanation: System log entry only, no service action
required
283DFFF4 283DFFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 28422202 28422202
Explanation: Removable media error during IPL
28421307 28421307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 28423000 28423000
Explanation: A permanent I/O processor failure
28421310 28421310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
28423001 28423001
Explanation: Not valid condition in I/O Processor 28423022 28423022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
28423002 28423002 v STORIOA
Explanation: Addressed device failed to respond to
selection 28423023 28423023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
28423006 28423006
Explanation: System bus error 28423080 28423080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
28423102 28423102
28423120 28423120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 28423121 28423121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 28423150 28423150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
28423205 28423205
Explanation: Disk sector read error
28423142 28423142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
28423250 28423250
28426070 28426070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
28426071 28426071
28426075 28426075
28423401 28423401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
28426076 28426076
28423501 28423501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
28429041 28429041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
28429081 28429081
28429050 28429050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
2842BE00 2842BE00
Explanation: I/O processor detected a fault condition
2842B3E0 2842B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
2842B3E1 2842B3E1
2842FF3D 2842FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
2842B410 2842B410
2842FF6D 2842FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
2842B411 2842B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
2842B412 2842B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
2842B935 2842B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 28432202 28432202
Explanation: Removable media error during IPL
28431307 28431307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 28433000 28433000
Explanation: A permanent I/O processor failure
28431310 28431310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
28433001 28433001
Explanation: Not valid condition in I/O Processor 28433022 28433022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
28433002 28433002 v STORIOA
Explanation: Addressed device failed to respond to
selection 28433023 28433023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
28433006 28433006
Explanation: System bus error 28433080 28433080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
28433102 28433102
28433120 28433120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 28433121 28433121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 28433150 28433150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
28433205 28433205
Explanation: Disk sector read error
28433142 28433142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
28433250 28433250
28436070 28436070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
28436071 28436071
28436075 28436075
28433401 28433401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
28436076 28436076
28433501 28433501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
28439041 28439041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
28439081 28439081
28439050 28439050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
2843BE00 2843BE00
Explanation: I/O processor detected a fault condition
2843B3E0 2843B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
2843B3E1 2843B3E1
2843FF3D 2843FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
2843B410 2843B410
2843FF6D 2843FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
2843B411 2843B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
2843B412 2843B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
2843B935 2843B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 28442202 28442202
Explanation: Removable media error during IPL
28441307 28441307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 28443000 28443000
Explanation: A permanent I/O processor failure
28441310 28441310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
28443001 28443001
Explanation: Not valid condition in I/O Processor 28443022 28443022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
28443002 28443002 v STORIOA
Explanation: Addressed device failed to respond to
selection 28443023 28443023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
28443006 28443006
Explanation: System bus error 28443080 28443080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
28443102 28443102
28443120 28443120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 28443121 28443121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 28443150 28443150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
28443205 28443205
Explanation: Disk sector read error
28443142 28443142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
28443250 28443250
28446070 28446070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
28446071 28446071
28446075 28446075
28443401 28443401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
28446076 28446076
28443501 28443501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
28449041 28449041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
28449081 28449081
28449050 28449050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
2844BE00 2844BE00
Explanation: I/O processor detected a fault condition
2844B3E0 2844B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
2844B3E1 2844B3E1
2844FF3D 2844FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
2844B410 2844B410
2844FF6D 2844FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
2844B411 2844B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
2844B412 2844B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
2844B935 2844B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
v OPT_CLN
28473501 28473501
Explanation: I/O processor Licensed Internal Code
28473087 28473087
error
Explanation: I/O processor resource not available
Failing Item:
Response: The Licensed Internal Code could not v AJDGP01
allocate resources on the I/O processor card.
v IOP
Failing Item:
v AJDGP01 28476070 28476070
v AJDG301
Explanation: A permanent I/O processor failure
v FCIOA occurred
v OPT_CLN
Failing Item:
v IOP
28473100 28473100
Explanation: I/O processor card detected interface 28476071 28476071
error
Explanation: I/O processor Licensed Internal Code
Failing Item: error
v FCINTF
Failing Item:
v ANYFC
v AJDGP01
v FCIOA
v OPT_CLN
28476072 28476072
Explanation: I/O processor Licensed Internal Code
28473109 28473109
error
Explanation: I/O processor timed out a device
Failing Item:
command
v AJDGP01
Failing Item:
v IOP
v FCDEV
v FCINTF
28476075 28476075
v FCIOA
Explanation: I/O processor resource not available
v OPT_CLN
Failing Item:
28473120 28473120 v AJDGP01
v ANYBRDG
28476082 28476082
v OPT_CLN
Explanation: I/O processor Licensed Internal Code
error
28478155 28478155
Failing Item:
Explanation: A permanent I/O processor failure
v AJDGP01
occurred
v IOP
Failing Item:
v AJDGP01
28476083 28476083
v FCIOA
Explanation: I/O processor Licensed Internal Code
v OPT_CLN
error
Failing Item:
28478156 28478156
v AJDGP01
Explanation: A permanent I/O processor failure
v IOP
occurred
Failing Item:
28476085 28476085
v AJDGP01
Explanation: I/O processor Licensed Internal Code
v FCIOA
error
v OPT_CLN
Failing Item:
v AJDGP01
28478200 28478200
v IOP
Explanation: I/O processor Licensed Internal Code
v MA_BRDG
error
Failing Item:
28476200 28476200
v AJDGP01
Explanation: A permanent IOA hardware error
v IOP
occurred
Failing Item:
28478300 28478300
v FCIOA
Explanation: I/O processor card or Licensed Internal
v OPT_CLN
Code error
Response: A microprocessor exception occurred on the
28476201 28476201
I/O processor.
Explanation: IOA LID is not valid
Failing Item:
Failing Item: v FCIOA
v AJDGP01 v IOP
v AJDGP01
28478100 28478100 v OPT_CLN
Explanation: I/O processor Licensed Internal Code
error 28478301 28478301
Failing Item: Explanation: Not valid condition in I/O Processor
v AJDGP01 Licensed Internal Code
v IOP Response: The Licensed Internal Code found a
condition that should not have occurred.
28478150 28478150 Failing Item:
Explanation: A permanent I/O processor failure v FCIOA
occurred v AJDGP01
Failing Item: v IOP
v FCIOA v OPT_CLN
v IOP
2847B3B1 2847B3B1
Explanation: A permanent I/O processor failure
2847B3E0 2847B3E0
occurred
Explanation: I/O processor detected a fault condition
Failing Item:
v IOP Failing Item:
v IOP
2847B3B2 2847B3B2 v MA_BRDG
2847B3B7 2847B3B7
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v IOP
2847B3B8 2847B3B8
Explanation: Multi-adapter Bridge error detected
Failing Item:
v MA_BRDG
2849B930 2849B930
Explanation: I/O adapter Licensed Internal Code
failed
Failing Item:
v AJDGP01
v FI00718
v FI00719
2849B931 2849B931
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2849B933 2849B933
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v AJDGP01
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 284B2202 284B2202
Explanation: Removable media error during IPL
284B1307 284B1307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 284B3000 284B3000
Explanation: A permanent I/O processor failure
284B1310 284B1310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
284B3001 284B3001
Explanation: Not valid condition in I/O Processor 284B3022 284B3022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
284B3002 284B3002 v STORIOA
Explanation: Addressed device failed to respond to
selection 284B3023 284B3023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
284B3006 284B3006
Explanation: System bus error 284B3080 284B3080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
284B3102 284B3102
284B3120 284B3120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 284B3121 284B3121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 284B3150 284B3150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
284B3205 284B3205
Explanation: Disk sector read error
284B3142 284B3142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
284B3250 284B3250
284B6070 284B6070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
284B6071 284B6071
284B6075 284B6075
284B3401 284B3401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
284B6076 284B6076
284B3501 284B3501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
284B9041 284B9041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
284B9081 284B9081
284B9050 284B9050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
284BBE00 284BBE00
Explanation: I/O processor detected a fault condition
284BB3E0 284BB3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
284BB3E1 284BB3E1
284BFF3D 284BFF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
284BB410 284BB410
284BFF6D 284BFF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
284BB411 284BB411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
284BB412 284BB412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
284BB935 284BB935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
28758404 28758404
Explanation: System log entry only, no service action
required
2875FFF4 2875FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
28768404 28768404
Explanation: System log entry only, no service action
required
2876FFF4 2876FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
Explanation: I/O adapter resource not available. Explanation: A permanent I/O processor failure
occurred
Failing Item:
Failing Item:
v AJDGP01
v AJDGP01
v IOP
28906083 28906083
Explanation: I/O adapter Licensed Internal Code
28906223 28906223
failed.
Explanation: A permanent I/O processor failure
Failing Item:
occurred
v AJDGP01
Failing Item:
v IOP
v IOP
v AJDGP01
28906085 28906085
Explanation: I/O adapter Licensed Internal Code
28906224 28906224
failed.
Explanation: A permanent I/O processor failure
Failing Item:
occurred
v AJDGP01
Failing Item:
v IOP
v DISKIMG
v MA_BRDG
v AJDGP01
v IOP
28906201 28906201
v MEMORY
Explanation: A permanent I/O processor failure
occurred
28906225 28906225
Failing Item:
Explanation: A permanent I/O processor failure
v IOP
occurred
v AJDGP01
Failing Item:
v AJDGP01
28906202 28906202
v AJDG301
Explanation: I/O processor Licensed Internal Code
v IOP
error
Failing Item:
28906226 28906226
v AJDGP01
Explanation: I/O processor card detected device error
v IOP
Failing Item:
v AJDG301
v AS4NTDD v AJDGP01
v AS4NTDD
28906227 28906227
Explanation: A HostLAN error was detected 28906533 28906533
Failing Item:
28906538 28906538
v AJDGP01
v IOP Explanation: A Virtual SCSI error was detected.
Failing Item:
28906530 28906530 v NTVSCSI
Explanation: A Virtual SCSI error was detected. v NTOPSYS
Failing Item:
28906539 28906539
v NTVSCSI
v NTOPSYS Explanation: A Virtual SCSI error was detected.
Failing Item:
28906531 28906531 v NTVSCSI
Explanation: A Virtual SCSI error was detected. v AS4NTDD
v NTOPSYS
Failing Item:
v AJDGP01
v NTVSCSI
v AS4NTDD
2890653A 2890653A
v NTOPSYS
v AJDGP01 Explanation: A Virtual SCSI error was detected.
Failing Item:
28906532 28906532 v NTOPSYS
Explanation: A Virtual SCSI error was detected. v AJDGP01
v AS4NTDD
Failing Item:
v NTOPSYS
v IOP
2890B3B1 2890B3B1
Explanation: A permanent I/O processor failure
2890B3B9 2890B3B9
occurred
Explanation: A permanent I/O processor failure
Failing Item:
occurred
v IOP
Failing Item:
v IOP
2890B3B2 2890B3B2
Explanation: A permanent I/O processor failure
2890B3E0 2890B3E0
occurred
Explanation: I/O processor detected a fault condition
Failing Item:
v IOP Failing Item:
v IOP
2890B3B3 2890B3B3 v MA_BRDG
Explanation: Multi-adapter bridge error detected. Explanation: I/O adapter hardware error detected
v IOA v MA_BRDG
v MEMORY
2890B960 2890B960
2890B4B5 2890B4B5 Explanation: I/O processor Licensed Internal Code
Explanation: An I/O adapter failure occurred. error
2890B4BE 2890B4BE
Explanation: Adapter card storage error
Failing Item:
v MEMORY
v IOP
2890B904 2890B904
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v IOP
2890B935 2890B935
Explanation: Incompatible hardware detected.
Failing Item:
v IOA
v AJDGP01
v IOP
Explanation: Adapter card storage error Explanation: I/O adapter Licensed Internal Code
failed.
Failing Item:
Failing Item:
v AJDGP01
v IOP
v AJDG301
v AJDGP01
v IOP
v MA_BRDG
28923006 28923006
v AJDGP01
28926201 28926201
v AJDG301
Explanation: A permanent I/O processor failure
v NTUSER
occurred
v IOA
Failing Item:
v IOP
28926070 28926070
v AJDGP01
Explanation: An I/O adapter failure occurred.
Failing Item: 28926202 28926202
v IOP
Explanation: I/O processor Licensed Internal Code
error
28926071 28926071
Failing Item:
Explanation: I/O adapter Licensed Internal Code v AJDGP01
failed.
v IOP
Failing Item:
v AJDGP01 28926204 28926204
Explanation: I/O adapter failure due to a thermal
28926072 28926072 condition
Explanation: I/O adapter Licensed Internal Code Failing Item:
failed.
v IOP
Failing Item:
v AJDGP01 28926210 28926210
v IOP
Explanation: I/O processor Licensed Internal Code
error
28926075 28926075
Failing Item:
Explanation: I/O adapter resource not available. v AJDGP01
Failing Item:
v AJDGP01 28926221 28926221
Explanation: I/O processor resource not available
28926083 28926083
Failing Item:
Explanation: I/O adapter Licensed Internal Code v AJDG301
failed.
Failing Item: 28926222 28926222
v AJDGP01
Explanation: A permanent I/O processor failure
v IOP occurred
Failing Item:
28926085 28926085
v AJDGP01
Explanation: I/O adapter Licensed Internal Code v IOP
failed.
Failing Item: 28926223 28926223
v AJDGP01
Explanation: A permanent I/O processor failure
v IOP occurred
v MA_BRDG
Failing Item:
v IOP
v AJDGP01
28926535 28926535
Explanation: A Virtual SCSI error was detected.
Failing Item:
v NTUSER
v NTDEVDR
2892653F 2892653F
v AJDGP01
Explanation: A Virtual SCSI error was detected.
Failing Item:
2892B3B9 2892B3B9
v IOP
Explanation: A permanent I/O processor failure
occurred
2892B3B2 2892B3B2
Failing Item:
Explanation: A permanent I/O processor failure
occurred v IOP
Failing Item:
2892B3E0 2892B3E0
v IOP
Explanation: I/O processor detected a fault condition
2892B3B3 2892B3B3 Failing Item:
Explanation: A permanent I/O processor failure v IOP
occurred v MA_BRDG
Failing Item:
v IOP 2892B3E1 2892B3E1
Explanation: An I/O adapter failure occurred.
2892B3B4 2892B3B4 Failing Item:
Explanation: A permanent I/O processor failure v IOP
occurred v MA_BRDG
Failing Item:
v IOP
2892BE00 2892BE00
Explanation: An I/O adapter failure occurred.
Failing Item:
v AJDGP01
v IOP
v IOA
v MA_BRDG
28B98401 28B98401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
28B98404 28B98404
Explanation: System log entry only, no service action
required
28B9FFF4 28B9FFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
28CB8401 28CB8401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
28CB8404 28CB8404
Explanation: System log entry only, no service action
required
28CBFFF4 28CBFFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
28CC8401 28CC8401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
28CC8404 28CC8404
Explanation: System log entry only, no service action
required
28CCFFF4 28CCFFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
293C8404 293C8404
Explanation: System log entry only, no service action
required
293CFFF4 293CFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
293D8404 293D8404
Explanation: System log entry only, no service action
required
293DFFF4 293DFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
297D8404 297D8404
Explanation: System log entry only, no service action
required
297DFFF4 297DFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
2A398404 2A398404
Explanation: System log entry only, no service action
required
2A39FFF4 2A39FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
Problem determination: IPL the IOP to retry the Explanation: Incomplete multipath connection
device identification process. If the error persists then
Response: Incomplete multipath connection between
contact your service provider.
device backplane and device.
Failing Item:
Failing Item:
v PTFSRCH
v SIP3146
2B4C34FF 2B4C34FF
2B4C4050 2B4C4050
Explanation: Format in progress
Explanation: Enclosure does not support required
Response: No action required. This reference code is multipath function
logged for information only.
Failing Item:
v SIP3148
2B4C3601 2B4C3601
Explanation: System log entry only. No service action 2B4C4060 2B4C4060
required.
Explanation: Multipath redundancy level reduced
Response: A redundant disk unit connection has
failed.
Failing Item:
v SIP4153
2B4C4150 2B4C4150
v SASCABL
Explanation: I/O adapter detected PCI bus error
v SASEXP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
2B4C4061 2B4C4061
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been If you are working with one of the card types below,
restored. No service action is required. the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
2B4C4070 2B4C4070
Card type 2BE1 (feature RAID enablement card for
Explanation: System log entry only. No service action embedded IOA) read the following: When working the
required. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
2B4C4100 2B4C4100 three physical parts:
v The embedded storage adapter on the I/O
Explanation: Device bus fabric error
backplane.
Response: For card type 2BE1 (feature RAID v The RAID enablement card.
enablement card for embedded IOA) read the
v The Battery charger and carrier card.
following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has three See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
1. The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
2. The RAID enablement card. card for embedded IOA) read the following: When
3. The Battery charger and carrier card. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
See symbolic FRU FEATCRD for the location codes of (STORIOA) has two physical parts:
the FRUs if they are not listed in the serviceable event v The embedded storage adapter on the I/O
or if you are working the failing item list here. backplane.
Failing Item: v The Battery charger and carrier card.
v SIP4152
See symbolic FRU FEATCRD for the location codes of
v SASCABL the FRUs if they are not listed in the serviceable event
v SASEXP or if you are working the failing item list here.
v DEVBPLN
v STORIOA Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v FI01105 embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
2B4C4101 2B4C4101 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Temporary device bus fabric error
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SIP4152 v The dual battery charger and carrier card. To
determine which battery is connected to which
embedded IOA use the bus number of the IOA with
2B4C4110 2B4C4110
symbolic FRU CACHBAT.
Explanation: Unsupported enclosure function detected
See symbolic FRU FEATCRD for the location code of
Failing Item:
the dual battery charger and carrier card if it is not
v SIP3145 listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card) read the following: When working the FRUs from
or if you are working the failing item list here. the serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has two
Card type 57CF (embedded IOAs on DASD backplane physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card) read
symbolic FRU CACHBAT. the following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
Failing Item: symbolic FRU CACHBAT.
v CACHBAT
See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 2B4C8141 2B4C8141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter
Response: No action is required. This reference code
(STORIOA) has two physical parts:
is logged for information only.
v The embedded storage adapter on the I/O
backplane.
2B4C8146 2B4C8146
v The Battery charger and carrier card.
Explanation: Disk device detected recoverable error
See symbolic FRU FEATCRD for the location codes of
Failing Item:
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v FI01105
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v PTFSRCH v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2B4C8157 2B4C8157
See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error
the dual battery charger and carrier card if it is not
Response: The FRU list in the Service Action Log will listed in the serviceable event or if you are working the
vary based on the conditions this event was logged for. failing item list here.
Display the Service Action Log entry for this SRC. If Failing Item:
the Failing Item indicates an I/O adapter, then replace v SVCDOCS
the I/O adapter. If the Failing Item indicates
v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated 2B4C8300 2B4C8300
with this I/O adapter. Other resources attached to the
Explanation: IOA hardware error or PCI bus error
virtual I/O processor may then need to be Varied On.
Response: If you are working with one of the card
If you are replacing the I/O adapter and you are
types below, the adapter has mulitple physical parts.
working with one of the card types below, the adapter
Choose the card type to identify the physical parts of
has mulitple physical parts. Choose the card type to
the storage adapter.
identify the physical parts of the storage adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has
three physical parts:
three physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The RAID enablement card.
v The RAID enablement card.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v STORIOA Failing Item:
v ANYBRDG v PTFSRCH
v PTFSRCH v STORIOA
Explanation: Not valid condition in Licensed Internal Explanation: Missing Licensed Internal Code
Code Response: Ensure that the code necessary to support
Response: If you are working with one of the card this I/O adapter is loaded.
types below, the adapter has mulitple physical parts. If you are working with one of the card types below,
Choose the card type to identify the physical parts of the adapter has mulitple physical parts. Choose the
the storage adapter. card type to identify the physical parts of the storage
Card type 2BE1 (feature RAID enablement card for adapter.
embedded IOA) read the following: When working the Card type 2BE1 (feature RAID enablement card for
FRUs from the serviceable event or the failing item list embedded IOA) read the following: When working the
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2B4C8400 2B4C8400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
2B4C8404 2B4C8404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
2B4C9001 2B4C9001
2B4C9000 2B4C9000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
2B4C9002 2B4C9002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 2B4C9008 2B4C9008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 2B4C9010 2B4C9010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
2B4C9026 2B4C9026
Explanation: Disk unit not found at required physical
2B4C9011 2B4C9011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
2B4C9020 2B4C9020
2B4C9027 2B4C9027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
2B4C9021 2B4C9021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
2B4C9028 2B4C9028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
2B4C9022 2B4C9022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
2B4C9032 2B4C9032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
2B4C9054 2B4C9054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
2B4C9070 2B4C9070
2B4C9040 2B4C9040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
2B4C9071 2B4C9071
Explanation: Link from IOA to auxiliary or remote
2B4C9041 2B4C9041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
2B4C9072 2B4C9072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
2B4C9042 2B4C9042
2B4C9073 2B4C9073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP4140
Failing Item:
v NEXTLVL
2B4C9074 2B4C9074
2B4C9051 2B4C9051
2B4C9075 2B4C9075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP4149
2B4C9052 2B4C9052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
2B4C9076 2B4C9076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP4147 2B4C9082 2B4C9082
Explanation: Device error
2B4C9081 2B4C9081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
2B4C9500 2B4C9500
v STORIOA
Explanation: Internal program error in driver code.
2B56B9B0 2B56B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
2B57B9B0 2B57B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
2B6CB934 2B6CB934
Explanation: Incompatible hardware detected.
Failing Item:
v FI00719
v FI00718
2B6CB940 2B6CB940
Explanation: I/O adapter hardware error detected.
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
2B6CB941 2B6CB941
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
2B6CB942 2B6CB942
Explanation: One half of I/O adapter failed.
Failing Item:
v FI00719
v FI00718
v AJDGP01
Explanation: A port failure was detected on port 0 v Check the Product Activity Log for other entries that
indicate interface problems and work those
Failing Item: problems.
v FCPORT v Check the device firmware level and apply the latest
v FCIOA PTFs.
v FCDEV v Check for LIC logs with major code 2E00. Contact
your next level of support with the information you
v OPT_CLN
have gathered.
Problem determination: IPL the IOP to retry the
2B933121 2B933121
device identification process. If the error persists then
Explanation: A port failure was detected on port 1 contact your service provider.
Failing Item: Failing Item:
v PTFSRCH
2B938300 2B938300
Explanation: IOA hardware error or PCI bus error
2B9334FF 2B9334FF
Failing Item:
Explanation: Format in progress
v FCIOA
Response: The device indicated that a format is in
v ANYBRDG
progress. When the format is complete, the device
should be usable. No action is required. This reference v PTFSRCH
code is logged for information only. v OPT_CLN
2B938131 2B938131
2B939903 2B939903
Explanation: Recovered Fibre Channel interface error
on port 1 Explanation: Tape device information was logged.
Informational event, no service required.
Response: No action required. This reference code is
logged for information only.
2B93A001 2B93A001
2B93B402 2B93B402
Explanation: Licensed Internal Code error
Failing Item:
v PTFSRCH
2B93B9B0 2B93B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
2B93C000 2B93C000
Explanation: System log entry only, no service action
required
Response: No action is required. This reference code
is logged for information only.
2B93C402 2B93C402
Explanation: Licensed Internal Code error
Failing Item:
v PTFSRCH
2BBE8404 2BBE8404
Explanation: System log entry only, no service action
required
2BBEFFF4 2BBEFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
2BD68404 2BD68404
Explanation: System log entry only, no service action
required
2BD6FFF4 2BD6FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
2BD88404 2BD88404
Explanation: System log entry only, no service action
required
2BD8FFF4 2BD8FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
Problem determination: IPL the IOP to retry the Explanation: Incomplete multipath connection
device identification process. If the error persists then
Response: Incomplete multipath connection between
contact your service provider.
device backplane and device.
Failing Item:
Failing Item:
v PTFSRCH
v SIP3146
2BD934FF 2BD934FF
2BD94050 2BD94050
Explanation: Format in progress
Explanation: Enclosure does not support required
Response: No action required. This reference code is multipath function
logged for information only.
Failing Item:
v SIP3148
2BD93601 2BD93601
Explanation: System log entry only. No service action 2BD94060 2BD94060
required.
Explanation: Multipath redundancy level reduced
Response: A redundant disk unit connection has
failed.
Failing Item:
v SIP4153
2BD94150 2BD94150
v SASCABL
Explanation: I/O adapter detected PCI bus error
v SASEXP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
2BD94061 2BD94061
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been If you are working with one of the card types below,
restored. No service action is required. the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
2BD94070 2BD94070
Card type 2BE1 (feature RAID enablement card for
Explanation: System log entry only. No service action embedded IOA) read the following: When working the
required. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
2BD94100 2BD94100 three physical parts:
v The embedded storage adapter on the I/O
Explanation: Device bus fabric error
backplane.
Response: For card type 2BE1 (feature RAID v The RAID enablement card.
enablement card for embedded IOA) read the
v The Battery charger and carrier card.
following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has three See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
1. The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
2. The RAID enablement card. card for embedded IOA) read the following: When
3. The Battery charger and carrier card. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
See symbolic FRU FEATCRD for the location codes of (STORIOA) has two physical parts:
the FRUs if they are not listed in the serviceable event v The embedded storage adapter on the I/O
or if you are working the failing item list here. backplane.
Failing Item: v The Battery charger and carrier card.
v SIP4152
See symbolic FRU FEATCRD for the location codes of
v SASCABL the FRUs if they are not listed in the serviceable event
v SASEXP or if you are working the failing item list here.
v DEVBPLN
v STORIOA Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v FI01105 embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
2BD94101 2BD94101 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Temporary device bus fabric error
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SIP4152 v The dual battery charger and carrier card. To
determine which battery is connected to which
embedded IOA use the bus number of the IOA with
2BD94110 2BD94110
symbolic FRU CACHBAT.
Explanation: Unsupported enclosure function detected
See symbolic FRU FEATCRD for the location code of
Failing Item:
the dual battery charger and carrier card if it is not
v SIP3145 listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card) read the following: When working the FRUs from
or if you are working the failing item list here. the serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has two
Card type 57CF (embedded IOAs on DASD backplane physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card) read
symbolic FRU CACHBAT. the following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
Failing Item: symbolic FRU CACHBAT.
v CACHBAT
See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 2BD98141 2BD98141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter
Response: No action is required. This reference code
(STORIOA) has two physical parts:
is logged for information only.
v The embedded storage adapter on the I/O
backplane.
2BD98146 2BD98146
v The Battery charger and carrier card.
Explanation: Disk device detected recoverable error
See symbolic FRU FEATCRD for the location codes of
Failing Item:
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v FI01105
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v PTFSRCH v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2BD98157 2BD98157
See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error
the dual battery charger and carrier card if it is not
Response: The FRU list in the Service Action Log will listed in the serviceable event or if you are working the
vary based on the conditions this event was logged for. failing item list here.
Display the Service Action Log entry for this SRC. If Failing Item:
the Failing Item indicates an I/O adapter, then replace v SVCDOCS
the I/O adapter. If the Failing Item indicates
v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated 2BD98300 2BD98300
with this I/O adapter. Other resources attached to the
Explanation: IOA hardware error or PCI bus error
virtual I/O processor may then need to be Varied On.
Response: If you are working with one of the card
If you are replacing the I/O adapter and you are
types below, the adapter has mulitple physical parts.
working with one of the card types below, the adapter
Choose the card type to identify the physical parts of
has mulitple physical parts. Choose the card type to
the storage adapter.
identify the physical parts of the storage adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has
three physical parts:
three physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The RAID enablement card.
v The RAID enablement card.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v STORIOA Failing Item:
v ANYBRDG v PTFSRCH
v PTFSRCH v STORIOA
Explanation: Not valid condition in Licensed Internal Explanation: Missing Licensed Internal Code
Code Response: Ensure that the code necessary to support
Response: If you are working with one of the card this I/O adapter is loaded.
types below, the adapter has mulitple physical parts. If you are working with one of the card types below,
Choose the card type to identify the physical parts of the adapter has mulitple physical parts. Choose the
the storage adapter. card type to identify the physical parts of the storage
Card type 2BE1 (feature RAID enablement card for adapter.
embedded IOA) read the following: When working the Card type 2BE1 (feature RAID enablement card for
FRUs from the serviceable event or the failing item list embedded IOA) read the following: When working the
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2BD98400 2BD98400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
2BD98404 2BD98404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
2BD99001 2BD99001
2BD99000 2BD99000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
2BD99002 2BD99002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 2BD99008 2BD99008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 2BD99010 2BD99010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
2BD99026 2BD99026
Explanation: Disk unit not found at required physical
2BD99011 2BD99011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
2BD99020 2BD99020
2BD99027 2BD99027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
2BD99021 2BD99021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
2BD99028 2BD99028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
2BD99022 2BD99022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
2BD99032 2BD99032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
2BD99054 2BD99054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
2BD99070 2BD99070
2BD99040 2BD99040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
2BD99071 2BD99071
Explanation: Link from IOA to auxiliary or remote
2BD99041 2BD99041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
2BD99072 2BD99072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
2BD99042 2BD99042
2BD99073 2BD99073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP4140
Failing Item:
v NEXTLVL
2BD99074 2BD99074
2BD99051 2BD99051
2BD99075 2BD99075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP4149
2BD99052 2BD99052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
2BD99076 2BD99076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP4147 2BD99082 2BD99082
Explanation: Device error
2BD99081 2BD99081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
2BD99500 2BD99500
v STORIOA
Explanation: Internal program error in driver code.
Problem determination: IPL the IOP to retry the Explanation: Incomplete multipath connection
device identification process. If the error persists then
Response: Incomplete multipath connection between
contact your service provider.
device backplane and device.
Failing Item:
Failing Item:
v PTFSRCH
v SIP3146
2BE034FF 2BE034FF
2BE04050 2BE04050
Explanation: Format in progress
Explanation: Enclosure does not support required
Response: No action required. This reference code is multipath function
logged for information only.
Failing Item:
v SIP3148
2BE03601 2BE03601
Explanation: System log entry only. No service action 2BE04060 2BE04060
required.
Explanation: Multipath redundancy level reduced
Response: A redundant disk unit connection has
failed.
Failing Item:
v SIP4153
2BE04150 2BE04150
v SASCABL
Explanation: I/O adapter detected PCI bus error
v SASEXP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
2BE04061 2BE04061
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been If you are working with one of the card types below,
restored. No service action is required. the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
2BE04070 2BE04070
Card type 2BE1 (feature RAID enablement card for
Explanation: System log entry only. No service action embedded IOA) read the following: When working the
required. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
2BE04100 2BE04100 three physical parts:
v The embedded storage adapter on the I/O
Explanation: Device bus fabric error
backplane.
Response: For card type 2BE1 (feature RAID v The RAID enablement card.
enablement card for embedded IOA) read the
v The Battery charger and carrier card.
following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has three See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
1. The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
2. The RAID enablement card. card for embedded IOA) read the following: When
3. The Battery charger and carrier card. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
See symbolic FRU FEATCRD for the location codes of (STORIOA) has two physical parts:
the FRUs if they are not listed in the serviceable event v The embedded storage adapter on the I/O
or if you are working the failing item list here. backplane.
Failing Item: v The Battery charger and carrier card.
v SIP4152
See symbolic FRU FEATCRD for the location codes of
v SASCABL the FRUs if they are not listed in the serviceable event
v SASEXP or if you are working the failing item list here.
v DEVBPLN
v STORIOA Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v FI01105 embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
2BE04101 2BE04101 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Temporary device bus fabric error
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SIP4152 v The dual battery charger and carrier card. To
determine which battery is connected to which
embedded IOA use the bus number of the IOA with
2BE04110 2BE04110
symbolic FRU CACHBAT.
Explanation: Unsupported enclosure function detected
See symbolic FRU FEATCRD for the location code of
Failing Item:
the dual battery charger and carrier card if it is not
v SIP3145 listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card) read the following: When working the FRUs from
or if you are working the failing item list here. the serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has two
Card type 57CF (embedded IOAs on DASD backplane physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card) read
symbolic FRU CACHBAT. the following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
Failing Item: symbolic FRU CACHBAT.
v CACHBAT
See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 2BE08141 2BE08141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter
Response: No action is required. This reference code
(STORIOA) has two physical parts:
is logged for information only.
v The embedded storage adapter on the I/O
backplane.
2BE08146 2BE08146
v The Battery charger and carrier card.
Explanation: Disk device detected recoverable error
See symbolic FRU FEATCRD for the location codes of
Failing Item:
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v FI01105
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v PTFSRCH v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2BE08157 2BE08157
See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error
the dual battery charger and carrier card if it is not
Response: The FRU list in the Service Action Log will listed in the serviceable event or if you are working the
vary based on the conditions this event was logged for. failing item list here.
Display the Service Action Log entry for this SRC. If Failing Item:
the Failing Item indicates an I/O adapter, then replace v SVCDOCS
the I/O adapter. If the Failing Item indicates
v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated 2BE08300 2BE08300
with this I/O adapter. Other resources attached to the
Explanation: IOA hardware error or PCI bus error
virtual I/O processor may then need to be Varied On.
Response: If you are working with one of the card
If you are replacing the I/O adapter and you are
types below, the adapter has mulitple physical parts.
working with one of the card types below, the adapter
Choose the card type to identify the physical parts of
has mulitple physical parts. Choose the card type to
the storage adapter.
identify the physical parts of the storage adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has
three physical parts:
three physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The RAID enablement card.
v The RAID enablement card.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v STORIOA Failing Item:
v ANYBRDG v PTFSRCH
v PTFSRCH v STORIOA
Explanation: Not valid condition in Licensed Internal Explanation: Missing Licensed Internal Code
Code Response: Ensure that the code necessary to support
Response: If you are working with one of the card this I/O adapter is loaded.
types below, the adapter has mulitple physical parts. If you are working with one of the card types below,
Choose the card type to identify the physical parts of the adapter has mulitple physical parts. Choose the
the storage adapter. card type to identify the physical parts of the storage
Card type 2BE1 (feature RAID enablement card for adapter.
embedded IOA) read the following: When working the Card type 2BE1 (feature RAID enablement card for
FRUs from the serviceable event or the failing item list embedded IOA) read the following: When working the
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2BE08400 2BE08400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
2BE08404 2BE08404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
2BE09001 2BE09001
2BE09000 2BE09000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
2BE09002 2BE09002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 2BE09008 2BE09008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 2BE09010 2BE09010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
2BE09026 2BE09026
Explanation: Disk unit not found at required physical
2BE09011 2BE09011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
2BE09020 2BE09020
2BE09027 2BE09027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
2BE09021 2BE09021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
2BE09028 2BE09028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
2BE09022 2BE09022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
2BE09032 2BE09032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
2BE09054 2BE09054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
2BE09070 2BE09070
2BE09040 2BE09040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
2BE09071 2BE09071
Explanation: Link from IOA to auxiliary or remote
2BE09041 2BE09041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
2BE09072 2BE09072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
2BE09042 2BE09042
2BE09073 2BE09073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP4140
Failing Item:
v NEXTLVL
2BE09074 2BE09074
2BE09051 2BE09051
2BE09075 2BE09075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP4149
2BE09052 2BE09052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
2BE09076 2BE09076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP4147 2BE09082 2BE09082
Explanation: Device error
2BE09081 2BE09081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
2BE09500 2BE09500
v STORIOA
Explanation: Internal program error in driver code.
Problem determination: IPL the IOP to retry the Explanation: Incomplete multipath connection
device identification process. If the error persists then
Response: Incomplete multipath connection between
contact your service provider.
device backplane and device.
Failing Item:
Failing Item:
v PTFSRCH
v SIP3146
2BE134FF 2BE134FF
2BE14050 2BE14050
Explanation: Format in progress
Explanation: Enclosure does not support required
Response: No action required. This reference code is multipath function
logged for information only.
Failing Item:
v SIP3148
2BE13601 2BE13601
Explanation: System log entry only. No service action 2BE14060 2BE14060
required.
Explanation: Multipath redundancy level reduced
Response: A redundant disk unit connection has
failed.
Failing Item:
v SIP4153
2BE14150 2BE14150
v SASCABL
Explanation: I/O adapter detected PCI bus error
v SASEXP
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
2BE14061 2BE14061
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been If you are working with one of the card types below,
restored. No service action is required. the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
2BE14070 2BE14070
Card type 2BE1 (feature RAID enablement card for
Explanation: System log entry only. No service action embedded IOA) read the following: When working the
required. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
2BE14100 2BE14100 three physical parts:
v The embedded storage adapter on the I/O
Explanation: Device bus fabric error
backplane.
Response: For card type 2BE1 (feature RAID v The RAID enablement card.
enablement card for embedded IOA) read the
v The Battery charger and carrier card.
following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has three See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
1. The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
2. The RAID enablement card. card for embedded IOA) read the following: When
3. The Battery charger and carrier card. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
See symbolic FRU FEATCRD for the location codes of (STORIOA) has two physical parts:
the FRUs if they are not listed in the serviceable event v The embedded storage adapter on the I/O
or if you are working the failing item list here. backplane.
Failing Item: v The Battery charger and carrier card.
v SIP4152
See symbolic FRU FEATCRD for the location codes of
v SASCABL the FRUs if they are not listed in the serviceable event
v SASEXP or if you are working the failing item list here.
v DEVBPLN
v STORIOA Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v FI01105 embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
2BE14101 2BE14101 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Temporary device bus fabric error
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SIP4152 v The dual battery charger and carrier card. To
determine which battery is connected to which
embedded IOA use the bus number of the IOA with
2BE14110 2BE14110
symbolic FRU CACHBAT.
Explanation: Unsupported enclosure function detected
See symbolic FRU FEATCRD for the location code of
Failing Item:
the dual battery charger and carrier card if it is not
v SIP3145 listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card) read the following: When working the FRUs from
or if you are working the failing item list here. the serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has two
Card type 57CF (embedded IOAs on DASD backplane physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card) read
symbolic FRU CACHBAT. the following: When working the FRUs from the
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
Failing Item: symbolic FRU CACHBAT.
v CACHBAT
See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 2BE18141 2BE18141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter
Response: No action is required. This reference code
(STORIOA) has two physical parts:
is logged for information only.
v The embedded storage adapter on the I/O
backplane.
2BE18146 2BE18146
v The Battery charger and carrier card.
Explanation: Disk device detected recoverable error
See symbolic FRU FEATCRD for the location codes of
Failing Item:
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v FI01105
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v PTFSRCH v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2BE18157 2BE18157
See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error
the dual battery charger and carrier card if it is not
Response: The FRU list in the Service Action Log will listed in the serviceable event or if you are working the
vary based on the conditions this event was logged for. failing item list here.
Display the Service Action Log entry for this SRC. If Failing Item:
the Failing Item indicates an I/O adapter, then replace v SVCDOCS
the I/O adapter. If the Failing Item indicates
v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated 2BE18300 2BE18300
with this I/O adapter. Other resources attached to the
Explanation: IOA hardware error or PCI bus error
virtual I/O processor may then need to be Varied On.
Response: If you are working with one of the card
If you are replacing the I/O adapter and you are
types below, the adapter has mulitple physical parts.
working with one of the card types below, the adapter
Choose the card type to identify the physical parts of
has mulitple physical parts. Choose the card type to
the storage adapter.
identify the physical parts of the storage adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has
three physical parts:
three physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The RAID enablement card.
v The RAID enablement card.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v STORIOA Failing Item:
v ANYBRDG v PTFSRCH
v PTFSRCH v STORIOA
Explanation: Not valid condition in Licensed Internal Explanation: Missing Licensed Internal Code
Code Response: Ensure that the code necessary to support
Response: If you are working with one of the card this I/O adapter is loaded.
types below, the adapter has mulitple physical parts. If you are working with one of the card types below,
Choose the card type to identify the physical parts of the adapter has mulitple physical parts. Choose the
the storage adapter. card type to identify the physical parts of the storage
Card type 2BE1 (feature RAID enablement card for adapter.
embedded IOA) read the following: When working the Card type 2BE1 (feature RAID enablement card for
FRUs from the serviceable event or the failing item list embedded IOA) read the following: When working the
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
2BE18400 2BE18400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
2BE18404 2BE18404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
2BE19001 2BE19001
2BE19000 2BE19000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
2BE19002 2BE19002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 2BE19008 2BE19008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 2BE19010 2BE19010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
2BE19026 2BE19026
Explanation: Disk unit not found at required physical
2BE19011 2BE19011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
2BE19020 2BE19020
2BE19027 2BE19027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
2BE19021 2BE19021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
2BE19028 2BE19028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
2BE19022 2BE19022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
2BE19032 2BE19032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
2BE19054 2BE19054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
2BE19070 2BE19070
2BE19040 2BE19040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
2BE19071 2BE19071
Explanation: Link from IOA to auxiliary or remote
2BE19041 2BE19041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
2BE19072 2BE19072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
2BE19042 2BE19042
2BE19073 2BE19073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP4140
Failing Item:
v NEXTLVL
2BE19074 2BE19074
2BE19051 2BE19051
2BE19075 2BE19075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP4149
2BE19052 2BE19052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
2BE19076 2BE19076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP4147 2BE19082 2BE19082
Explanation: Device error
2BE19081 2BE19081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
2BE19500 2BE19500
v STORIOA
Explanation: Internal program error in driver code.
2BF3B9B0 2BF3B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
2BF4B9B0 2BF4B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
2C4CB9B0 2C4CB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
2C4DB9B0 2C4DB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
that you find in the serviceable event view. If you cannot locate an error log in the serviceable event view
that corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the 3494 Library Manager console for error indications. Refer to the 3494 service information to
resolve any error indications.
3. Attempt the failing operation again.
4. Does the operation complete successfully?
Yes: The problem has been corrected. This ends the procedure.
No: Look at the 4 rightmost characters of the Data display for Function 11, which represents the
unit reference code. Find the unit reference code in the following table.
34942311 34942311
Explanation: Library device requires operator
intervention
Response: Put the library into pause mode and
perform the intervention indicated on the library
manager console.
34942319 34942319
Explanation: Tape unit failure
Response: Use the tape unit service information to
analyze the failure.
Failing Item:
v FI00851
34942321 34942321
Explanation: Library enclosure environmental alert
was detected.
Response: Use the 3494 Tape Library Dataserver
Maintenance Information and follow the procedures for
analyzing a "LIBRARY PROBLEM - NO ERROR
MESSAGE."
Failing Item:
v LIB3494
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
35809210 35809210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
35809303 35809303
35809211 35809211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
35809304 35809304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
35809220 35809220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
35809310 35809310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
35809300 35809300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
35809321 35809321
35809500 35809500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
35809501 35809501
35809350 35809350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 35809800 35809800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
35809801 35809801
35809351 35809351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 35809802 35809802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
35809803 35809803
35809355 35809355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
35809899 35809899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
35809900 35809900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
35809901 35809901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
35929210 35929210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
35929303 35929303
35929211 35929211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
35929304 35929304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
35929220 35929220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
35929310 35929310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
35929300 35929300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
35929321 35929321
35929500 35929500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
35929501 35929501
35929350 35929350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 35929800 35929800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
35929801 35929801
35929351 35929351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 35929802 35929802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
35929803 35929803
35929355 35929355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
35929899 35929899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
35929900 35929900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
35929901 35929901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
43203010 43203010
43203110 43203110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4320FFF4 4320FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4320FFFA 4320FFFA
4320FFFB 4320FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4320FFFE 4320FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43223010 43223010
43223110 43223110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4322FFF4 4322FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4322FFFA 4322FFFA
4322FFFB 4322FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4322FFFE 4322FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43233010 43233010
43233110 43233110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4323FFF4 4323FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4323FFFA 4323FFFA
4323FFFB 4323FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4323FFFE 4323FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43253010 43253010
43253110 43253110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4325FFF4 4325FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4325FFFA 4325FFFA
4325FFFB 4325FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4325FFFE 4325FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43263010 43263010
43263110 43263110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4326FFF4 4326FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4326FFFA 4326FFFA
4326FFFB 4326FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4326FFFE 4326FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43273010 43273010
43273110 43273110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4327FFF4 4327FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4327FFFA 4327FFFA
4327FFFB 4327FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4327FFFE 4327FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43283010 43283010
43283110 43283110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4328FFF4 4328FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4328FFFA 4328FFFA
4328FFFB 4328FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4328FFFE 4328FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
43293010 43293010
43293110 43293110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
4329FFF4 4329FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 4329FFFA 4329FFFA
4329FFFB 4329FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
4329FFFE 4329FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
433B3100 433B3100 level of support.
433BFFF4 433BFFF4
433B4060 433B4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
433BFFF5 433BFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
433B4061 433B4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
433B4100 433B4100
433BFFF6 433BFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
433BFFFB 433BFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
433BFFFC 433BFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
433BFFFD 433BFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
433C3100 433C3100 level of support.
433CFFF4 433CFFF4
433C4060 433C4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
433CFFF5 433CFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
433C4061 433C4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
433C4100 433C4100
433CFFF6 433CFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
433CFFFB 433CFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
433CFFFC 433CFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
433CFFFD 433CFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
433D3100 433D3100 level of support.
433DFFF4 433DFFF4
433D4060 433D4060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
433DFFF5 433DFFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
433D4061 433D4061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
433D4100 433D4100
433DFFF6 433DFFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
433DFFFB 433DFFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
433DFFFC 433DFFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
433DFFFD 433DFFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
46859210 46859210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
46859303 46859303
46859211 46859211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
46859304 46859304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
46859220 46859220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
46859310 46859310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
46859300 46859300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
46859321 46859321
46859500 46859500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
46859501 46859501
46859350 46859350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 46859800 46859800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
46859801 46859801
46859351 46859351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 46859802 46859802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
46859803 46859803
46859355 46859355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
46859899 46859899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
46859900 46859900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
46859901 46859901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
4758B991 4758B991
Explanation: Tampering of cryptographic card
suspected.
Failing Item:
v IOA
v FI00130
v IOP
4758B992 4758B992
Explanation: Operating voltage and/or temperature
range limits exceeded.
Response: Correct any conditions in the physical
environment which may have caused the voltage
and/or temperature out-of-range error on the 4758
adapter card. After the conditions have been corrected,
vary off and then vary back on the 4758 device
description associated with the 4758 adapter card.
Failing Item:
v CARDTMP
4764B991 4764B991
Explanation: Tampering of cryptographic card
suspected.
Failing Item:
v IOA
v AJDG301
4764B992 4764B992
Explanation: Operating voltage and/or temperature
range limits exceeded.
Response: Correct any conditions in the physical
environment which may have caused the voltage
and/or temperature out-of-range error on the 4764 /
4765 adapter card. After the conditions have been
corrected, vary off and then vary back on the 4764 /
4765 device description associated with the 4764 / 4765
adapter card.
Failing Item:
v CARDTMP
4765B991 4765B991
Explanation: Tampering of cryptographic card
suspected.
Failing Item:
v IOA
v AJDG301
4765B992 4765B992
Explanation: Operating voltage and/or temperature
range limits exceeded.
Response: Correct any conditions in the physical
environment which may have caused the voltage
and/or temperature out-of-range error on the 4764 /
4765 adapter card. After the conditions have been
corrected, vary off and then vary back on the 4764 /
4765 device description associated with the 4764 / 4765
adapter card.
Failing Item:
v CARDTMP
Explanation: I/O processor resource not available Explanation: Windows initiated a warm boot
Explanation: A permanent I/O processor failure Explanation: A Windows fatal error occurred
occurred Failing Item:
Failing Item: v IOA
v FI00730 v FI00730
v IOA
48126502 48126502
48126223 48126223 Explanation: A Windows fatal error occurred
Explanation: A permanent I/O processor failure Failing Item:
occurred
v FI00730
v IOA
48126538 48126538
Explanation: A Virtual SCSI error was detected.
48126530 48126530
Failing Item:
Explanation: A Virtual SCSI error was detected.
v NTVSCSI
Failing Item:
v NTOPSYS
v NTVSCSI
v NTOPSYS
48126539 48126539
Explanation: A Virtual SCSI error was detected.
48126531 48126531
Failing Item:
Explanation: A Virtual SCSI error was detected.
v NTVSCSI
Failing Item:
v AS4NTDD
v NTVSCSI
v NTOPSYS
v AS4NTDD
v FI00730
v NTOPSYS
v FI00730
4812653A 4812653A
Explanation: A Virtual SCSI error was detected.
48126532 48126532
Failing Item:
Explanation: A Virtual SCSI error was detected.
v NTOPSYS
Failing Item:
v FI00730
v NTOPSYS
v AS4NTDD
v FI00730
v AS4NTDD
4812653B 4812653B
Explanation: A Virtual SCSI error was detected.
48126533 48126533
Failing Item:
Explanation: A Virtual SCSI error was detected.
v NTUSER
Failing Item:
v NTOPSYS
v NTUSER
v AS4NTDD
v NTOPSYS
v AS4NTDD
4812653C 4812653C
Explanation: A Virtual SCSI error was detected.
48126534 48126534
Failing Item:
Explanation: A Virtual SCSI error was detected.
v AS4NTDD
Failing Item:
v FI00730
v AS4NTDD
v NTOPSYS
v FI00730
v NTOPSYS
4812653D 4812653D
Explanation: A Virtual SCSI error was detected.
48126535 48126535
Failing Item:
Explanation: A Virtual SCSI error was detected.
v NTUSER
Failing Item:
v NTDEVDR
v NTUSER
v FI00730
v NTDEVDR
v FI00730
4812B904 4812B904
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v FI00730
v IOA
4812B960 4812B960
Explanation: I/O processor Licensed Internal Code
error
Failing Item:
v FI00730
v IOP
506D8401 506D8401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
506D8404 506D8404
Explanation: System log entry only, no service action
required
506DFFF4 506DFFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
506E8401 506E8401
Explanation: Removable media power fault
Failing Item:
v DEVBPLN
506E8404 506E8404
Explanation: System log entry only, no service action
required
506EFFF4 506EFFF4
Explanation: Device backplane problem
Failing Item:
v DEVBPLN
v STORIOA
v FI01140
v FI01106
509A8404 509A8404
Explanation: System log entry only, no service action
required
509AFFF4 509AFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
509D1515 509D1515
Explanation: A fatal error occurred on power supply 1
Failing Item:
v DISKPWR
v SASEXP
509D3002 509D3002
Explanation: Addressed device backplane failed to
respond to selection
Failing Item:
v SASEXP
v SASCABL
v STORIOA
509D3109 509D3109
Explanation: I/O adapter timed out a device
backplane command
Failing Item:
v SASEXP
v SASCABL
v STORIOA
509D7614 509D7614
Explanation: A fatal error occurred on fan 1
Failing Item:
v DISKFAN
509D8404 509D8404
Explanation: System log entry only, no service action
required
509DFFF4 509DFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
50A48404 50A48404
Explanation: System log entry only, no service action
required
50A4FFF4 50A4FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
50AD8404 50AD8404
Explanation: System log entry only, no service action
required
50ADFFF4 50ADFFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
50B176A4 50B176A4
Explanation: A fatal error occurred on fan 10
Failing Item:
v DISKFAN
50B176B4 50B176B4
Explanation: A fatal error occurred on fan 11
Failing Item:
v DISKFAN
50B176C4 50B176C4
Explanation: A fatal error occurred on fan 12
Failing Item:
v DISKFAN
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
56199210 56199210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
56199303 56199303
56199211 56199211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
56199304 56199304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
56199220 56199220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
56199310 56199310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
56199300 56199300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
56199321 56199321
56199500 56199500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
56199501 56199501
56199350 56199350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 56199800 56199800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
56199801 56199801
56199351 56199351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 56199802 56199802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
56199803 56199803
56199355 56199355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
56199899 56199899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
56199900 56199900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
56199901 56199901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
56389210 56389210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
56389303 56389303
56389211 56389211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
56389304 56389304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
56389220 56389220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
56389310 56389310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
56389300 56389300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
56389321 56389321
56389500 56389500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
56389501 56389501
56389350 56389350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 56389800 56389800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
56389801 56389801
56389351 56389351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 56389802 56389802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
56389803 56389803
56389355 56389355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
56389899 56389899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
56389900 56389900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
56389901 56389901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
56759210 56759210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
56759303 56759303
56759211 56759211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
56759304 56759304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
56759220 56759220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
56759310 56759310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
56759300 56759300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
56759321 56759321
56759500 56759500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
56759501 56759501
56759350 56759350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 56759800 56759800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
56759801 56759801
56759351 56759351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 56759802 56759802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
56759803 56759803
56759355 56759355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
56759899 56759899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
56759900 56759900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
56759901 56759901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
5700B9A0 5700B9A0
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
5700B9B0 5700B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDG301
v MA_BRDG
5701B9A0 5701B9A0
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
5701B9B0 5701B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDG301
v MA_BRDG
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 57022202 57022202
Explanation: Removable media error during IPL
57021307 57021307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 57023000 57023000
Explanation: A permanent I/O processor failure
57021310 57021310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
57023001 57023001
Explanation: Not valid condition in I/O Processor 57023022 57023022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
57023002 57023002 v STORIOA
Explanation: Addressed device failed to respond to
selection 57023023 57023023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
57023006 57023006
Explanation: System bus error 57023080 57023080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
57023102 57023102
57023120 57023120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 57023121 57023121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 57023150 57023150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
57023205 57023205
Explanation: Disk sector read error
57023142 57023142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
57023250 57023250
57026070 57026070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
57026071 57026071
57026075 57026075
57023401 57023401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
57026076 57026076
57023501 57023501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
57029041 57029041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
57029081 57029081
57029050 57029050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
5702BE00 5702BE00
Explanation: I/O processor detected a fault condition
5702B3E0 5702B3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
5702B3E1 5702B3E1
5702FF3D 5702FF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
5702B410 5702B410
5702FF6D 5702FF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
5702B411 5702B411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
5702B412 5702B412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
5702B935 5702B935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
Explanation: I/O processor detected a SCSI bus Response: Error occurred on SCSI bus 0.
configuration error Failing Item:
Response: Error occurred on SCSI bus 0. v IOPIP13
Failing Item: v FI01107
v IOPIP17 v STORIOA
v USER v FI01140
v FI01107 v DEVBPLN
v STORIOA
57033101 57033101
57033021 57033021 Explanation: I/O processor card detected interface
error
Explanation: I/O processor detected a SCSI bus
configuration error Response: Error occurred on SCSI bus 1.
Response: Error occurred on SCSI bus 1. Failing Item:
Failing Item: v IOPIP13
v IOPIP17 v FI01107
v USER v STORIOA
v FI01107 v FI01140
v STORIOA v DEVBPLN
Explanation: I/O processor detected a SCSI bus Explanation: I/O processor card detected interface
configuration error error
Response: Error occurred on SCSI bus 2. Response: Error occurred on SCSI bus 2.
v FI01140 v SVCDOCS
v DEVBPLN
57033140 57033140
57033103 57033103 Explanation: I/O Processor detected that the bus is
Explanation: I/O processor card detected interface now operational
error Response: This reference code and the 3120 reference
Response: Error occurred on SCSI bus 3. code that occurred before it require no service action,
since SCSI bus 0 is now operational.
Failing Item:
v IOPIP13
57033141 57033141
v FI01107
Explanation: I/O Processor detected that the bus is
v STORIOA
now operational
v FI01140
Response: This reference code and the 3121 reference
v DEVBPLN
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
57033120 57033120
Explanation: I/O Processor detected that the bus is 57033142 57033142
not operational
Explanation: I/O Processor detected that the bus is
Response: A device was added to SCSI bus 0 of the now operational
I/O Adapter and caused the bus to become not
Response: This reference code and the 3122 reference
operational. Remove the device.
code that occurred before it require no service action,
Failing Item: since SCSI bus 2 is now operational.
v SVCDOCS
57033143 57033143
57033121 57033121 Explanation: I/O Processor detected that the bus is
Explanation: I/O Processor detected that the bus is now operational
not operational Response: This reference code and the 3123 reference
Response: A device was added to SCSI bus 1 of the code that occurred before it require no service action,
I/O Adapter and caused the bus to become not since SCSI bus 3 is now operational.
operational. Remove the device.
Failing Item: 57033150 57033150
v ANYBRDG
5703FF6D 5703FF6D
Explanation: I/O processor detected a recoverable
system bus error
Failing Item:
v IOP
v ANYBUS
Explanation: A permanent I/O processor failure IPL the I/O processor, see Debug the resource. If an
occurred I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v FCIOA Failing Item:
v ANYBRDG v SVCDOCS
v OPT_CLN
5704FF3D 5704FF3D
57048151 57048151 Explanation: Recovered IOA error
Explanation: I/O processor Licensed Internal Code Failing Item:
error v FCIOA
Failing Item: v ANYBRDG
v AJDGP01 v OPT_CLN
v FCIOA
v IOP
v OPT_CLN
57048155 57048155
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
57048156 57048156
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v AJDGP01
v FCIOA
v OPT_CLN
57049091 57049091
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
IPL the I/O processor, see Debug the resource. If an
I/O processor reset and I/O processor IPL does not
resolve the problem, contact your next level of support.
Failing Item:
v SVCDOCS
57049092 57049092
Explanation: Incorrect hardware configuration change
has been detected.
Response: Reset the I/O processor and then IPL the
I/O processor. For information about how to reset and
5706B9B0 5706B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDGP01
5707B9B0 5707B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDGP01
Response: Error occurred on SCSI bus 0. Explanation: Impending cache battery pack failure
Response: v AUXIOA
Failing Item:
57088302 57088302
v PTFSRCH
v AUXIOA Explanation: Missing Licensed Internal Code
Response: Ensure that the code necessary to support
57088156 57088156 this I/O adapter is loaded.
57089071 57089071
Explanation: Link from IOA to auxiliary cache IOA
went operational
Response: No service action required.
57089072 57089072
Explanation: Link from IOA to auxiliary cache IOA
went non-operational
Response: No service action required.
57089073 57089073
Explanation: Disconnected, incompatible, or
non-operational storage IOA
Response:
Failing Item:
v IOPIP41
5708FF3D 5708FF3D
Explanation: I/O adapter detected recoverable error
Response:
Failing Item:
v AUXIOA
v ANYBRDG
Explanation: I/O processor detected a SCSI bus Response: Error occurred on SCSI bus 0.
configuration error Failing Item:
Response: Error occurred on SCSI bus 0. v IOPIP13
Failing Item: v FI01107
v IOPIP17 v STORIOA
v USER v FI01140
v FI01107 v DEVBPLN
v STORIOA
57093101 57093101
57093021 57093021 Explanation: I/O processor card detected interface
error
Explanation: I/O processor detected a SCSI bus
configuration error Response: Error occurred on SCSI bus 1.
Response: Error occurred on SCSI bus 1. Failing Item:
Failing Item: v IOPIP13
v IOPIP17 v FI01107
v USER v STORIOA
v FI01107 v FI01140
v STORIOA v DEVBPLN
Explanation: I/O processor detected a SCSI bus Explanation: I/O processor card detected interface
configuration error error
Response: Error occurred on SCSI bus 2. Response: Error occurred on SCSI bus 2.
v FI01140 v SVCDOCS
v DEVBPLN
57093140 57093140
57093103 57093103 Explanation: I/O Processor detected that the bus is
Explanation: I/O processor card detected interface now operational
error Response: This reference code and the 3120 reference
Response: Error occurred on SCSI bus 3. code that occurred before it require no service action,
since SCSI bus 0 is now operational.
Failing Item:
v IOPIP13
57093141 57093141
v FI01107
Explanation: I/O Processor detected that the bus is
v STORIOA
now operational
v FI01140
Response: This reference code and the 3121 reference
v DEVBPLN
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
57093120 57093120
Explanation: I/O Processor detected that the bus is 57093142 57093142
not operational
Explanation: I/O Processor detected that the bus is
Response: A device was added to SCSI bus 0 of the now operational
I/O Adapter and caused the bus to become not
Response: This reference code and the 3122 reference
operational. Remove the device.
code that occurred before it require no service action,
Failing Item: since SCSI bus 2 is now operational.
v SVCDOCS
57093143 57093143
57093121 57093121 Explanation: I/O Processor detected that the bus is
Explanation: I/O Processor detected that the bus is now operational
not operational Response: This reference code and the 3123 reference
Response: A device was added to SCSI bus 1 of the code that occurred before it require no service action,
I/O Adapter and caused the bus to become not since SCSI bus 3 is now operational.
operational. Remove the device.
Failing Item: 57093150 57093150
v ANYBRDG
5709FF6D 5709FF6D
Explanation: I/O processor detected a recoverable
system bus error
Failing Item:
v IOP
v ANYBUS
v AJDGP01 v USER
v IOP v FI01105
v FI01104
v BACKPLN 570B2202 570B2202
Explanation: Removable media error during IPL
570B1307 570B1307 Failing Item:
Explanation: I/O processor resource not available v FI00022
Failing Item: v FI01105
v AJDGP01
v AJDG301 570B3000 570B3000
Explanation: A permanent I/O processor failure
570B1310 570B1310 occurred
v FI01101 v IOPIP17
v IOP v USER
v MA_BRDG v FI01107
v STORIOA
570B3001 570B3001
Explanation: Not valid condition in I/O Processor 570B3022 570B3022
Licensed Internal Code Explanation: I/O processor detected a SCSI bus
Response: The Licensed Internal Code found a configuration error
condition that should not have occurred. Response: Error occurred on SCSI bus 2.
Failing Item: Failing Item:
v IOP v IOPIP17
v AJDGP01 v USER
v FI01107
570B3002 570B3002 v STORIOA
Explanation: Addressed device failed to respond to
selection 570B3023 570B3023
Failing Item: Explanation: I/O processor detected a SCSI bus
v IOPIP16 configuration error
v FI01105 Response: Error occurred on SCSI bus 3.
v STORIOA
Failing Item:
v FI01140
v IOPIP17
v FI01141
v USER
v FI01106
v FI01107
v STORIOA
570B3006 570B3006
Explanation: System bus error 570B3080 570B3080
Failing Item: Explanation: I/O processor Licensed Internal Code
v IOP error
v ANYBUS Failing Item:
v FI01101 v AJDGP01
Failing Item:
570B3102 570B3102
570B3120 570B3120
Explanation: I/O processor card detected interface
error Explanation: I/O Processor detected that the bus is
not operational
Response: Error occurred on SCSI bus 2.
Response: A device was added to SCSI bus 0 of the
Failing Item: I/O Adapter and caused the bus to become not
v IOPIP13 operational. Remove the device.
v FI01107 Failing Item:
v STORIOA v SVCDOCS
v FI01140
v DEVBPLN 570B3121 570B3121
Explanation: I/O Processor detected that the bus is
not operational
Response: A device was added to SCSI bus 1 of the
I/O Adapter and caused the bus to become not
Explanation: I/O Processor detected that the bus is Response: This reference code and the 3123 reference
not operational code that occurred before it require no service action,
since SCSI bus 3 is now operational.
Response: A device was added to SCSI bus 2 of the
I/O Adapter and caused the bus to become not
operational. Remove the device. 570B3150 570B3150
Explanation: I/O Processor detected that the bus is Explanation: Disk media format bad
now operational Failing Item:
Response: This reference code and the 3121 reference v FI01105
code that occurred before it require no service action,
since SCSI bus 1 is now operational.
570B3205 570B3205
Explanation: Disk sector read error
570B3142 570B3142
Response: Disk unit data may need to be reloaded,
Explanation: I/O Processor detected that the bus is
but the disk unit does not need to be replaced.
now operational
Failing Item:
Response: This reference code and the 3122 reference
code that occurred before it require no service action, v FI01105
570B3250 570B3250
570B6070 570B6070
Explanation: Disk unit requires initialization before
use. Explanation: A permanent I/O processor failure
occurred
Response: Perform a D-IPL and work on errors found
in the log. Failing Item:
v IOP
Failing Item:
v USER
570B6071 570B6071
570B6075 570B6075
570B3401 570B3401
Explanation: I/O processor resource not available
Explanation: Device backplane problem
Failing Item:
Failing Item:
v AJDGP01
v DEVBPLN
570B6076 570B6076
570B3501 570B3501
Explanation: I/O processor card detected media error
Explanation: I/O processor Licensed Internal Code
error Failing Item:
Failing Item: v MEDIA
v AJDGP01 v AJDGP01
v IOP v FI01105
Response: No action required. Protection will be Explanation: IOP resources not available due to
automatically restarted. previous problems.
Response: Power off the system and remove all new
570B9041 570B9041 or replacement disk units. IPL the system to DST. If
you cannot perform a type A or B IPL, perform a type
Explanation: Background array parity check detected D IPL from removable media.
and corrected errors
Look for Product Activity Log entries for other IOP
Response: Call your next level of support to report reference codes and take action on them.
the problem.
Failing Item:
Failing Item:
v SVCDOCS
v AJDGP01
570B9081 570B9081
570B9050 570B9050
Explanation: I/O processor card detected device error
Explanation: Required cache data cannot be located
for a disk unit. Failing Item:
v FI01105
Failing Item:
v STORIOA
v IOPIP30
v IOP
570BBE00 570BBE00
Explanation: I/O processor detected a fault condition
570BB3E0 570BB3E0
Failing Item:
Explanation: I/O processor detected a fault condition
v AJDGP01
Failing Item:
v IOP
v IOP
v FI01104
v MA_BRDG
v MA_BRDG
570BB3E1 570BB3E1
570BFF3D 570BFF3D
Explanation: I/O processor detected a fault condition
Explanation: I/O adapter detected recoverable error
Failing Item:
Failing Item:
v IOP
v STORIOA
v MA_BRDG
v ANYBRDG
570BB410 570BB410
570BFF6D 570BFF6D
Explanation: A permanent I/O processor failure
Explanation: I/O processor detected a recoverable
occurred
system bus error
Failing Item:
Failing Item:
v STORIOA
v IOP
v ANYBUS
570BB411 570BB411
Explanation: A permanent I/O processor failure
occurred
Failing Item:
v STORIOA
570BB412 570BB412
Explanation: Tape/CD or disk bus interface error
occurred
Failing Item:
v IOPIP16
v FI01107
v FI01140
v STORIOA
v DEVTERM
570BB935 570BB935
Explanation: Unknown hardware detected
Failing Item:
v FI01101
v AJDGP01
v IOP
v MA_BRDG
v STORIOA
571A3140 571A3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
571A3103 571A3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 571A3141 571A3141
v FI01140
v DEVBPLN 571A3142 571A3142
Explanation: Bus is operational
571A3120 571A3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 571A3143 571A3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
571A4150 571A4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
571A3401 571A3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
571A3405 571A3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
571A34FF 571A34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
571A4160 571A4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
571A8008 571A8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 571A8009 571A8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
571A8100 571A8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 571A8130 571A8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
571A9002 571A9002
Explanation: Device error
571A8300 571A8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
571A8301 571A8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
571A9008 571A9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
571A8400 571A8400
571A9010 571A9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
571A8404 571A8404
v IOPIP31
Explanation: System log entry only. No service action
required.
571A9011 571A9011
571A9020 571A9020
571A9001 571A9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
571A9040 571A9040
571A9053 571A9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
571A9041 571A9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
571A9054 571A9054
571A9042 571A9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
571A9050 571A9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
571A9071 571A9071
Response:
Explanation: Link from IOA to auxiliary cache IOA
Failing Item: went operational
v IOPIP30 Response: No service action required.
Response:
571A9903 571A9903
Failing Item:
Explanation: Tape device information was logged.
v IOPIP16
Informational event, no service required.
v FI01105
v STORIOA
571AC000 571AC000
v FI01140
Explanation: System log entry only. No service action
v BACKPLN
required.
v FI01106
Response: No action is required. This reference code
is logged for information only.
571A9090 571A9090
Explanation: Disk unit has been modified after the 571AC100 571AC100
last known status.
Explanation: System log entry only. No service action
Response: Re-IPL the system. If any reference codes required.
are surfaced, use the new reference code to resolve the
problem. Response: No action is required. This reference code
is logged for information only.
If you cannot resolve the problem, contact your next
level of support.
571AC402 571AC402
Failing Item:
Explanation: Licensed Internal Code error
v SVCDOCS
Response: Ask your next level of support for
assistance.
571A9091 571A9091
Failing Item:
Explanation: Incorrect hardware configuration change
detected v PTFSRCH
571AFF6D 571AFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
v STORIOA
571B3140 571B3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
571B3103 571B3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 571B3141 571B3141
v FI01140
v DEVBPLN 571B3142 571B3142
Explanation: Bus is operational
571B3120 571B3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 571B3143 571B3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
571B4150 571B4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
571B3401 571B3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
571B3405 571B3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
571B34FF 571B34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
571B4160 571B4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
571B8008 571B8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 571B8009 571B8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
571B8100 571B8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 571B8130 571B8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
571B9002 571B9002
Explanation: Device error
571B8300 571B8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
571B8301 571B8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
571B9008 571B9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
571B8400 571B8400
571B9010 571B9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
571B8404 571B8404
v IOPIP31
Explanation: System log entry only. No service action
required.
571B9011 571B9011
571B9020 571B9020
571B9001 571B9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
571B9040 571B9040
571B9053 571B9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
571B9041 571B9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
571B9054 571B9054
571B9042 571B9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
571B9050 571B9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
571B9071 571B9071
Response:
Explanation: Link from IOA to auxiliary cache IOA
Failing Item: went operational
v IOPIP30 Response: No service action required.
Response:
571B9903 571B9903
Failing Item:
Explanation: Tape device information was logged.
v IOPIP16
Informational event, no service required.
v FI01105
v STORIOA
571BC000 571BC000
v FI01140
Explanation: System log entry only. No service action
v BACKPLN
required.
v FI01106
Response: No action is required. This reference code
is logged for information only.
571B9090 571B9090
Explanation: Disk unit has been modified after the 571BC100 571BC100
last known status.
Explanation: System log entry only. No service action
Response: Re-IPL the system. If any reference codes required.
are surfaced, use the new reference code to resolve the
problem. Response: No action is required. This reference code
is logged for information only.
If you cannot resolve the problem, contact your next
level of support.
571BC402 571BC402
Failing Item:
Explanation: Licensed Internal Code error
v SVCDOCS
Response: Ask your next level of support for
assistance.
571B9091 571B9091
Failing Item:
Explanation: Incorrect hardware configuration change
detected v PTFSRCH
571BFF6D 571BFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
v STORIOA
571E3140 571E3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
571E3103 571E3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 571E3141 571E3141
v FI01140
v DEVBPLN 571E3142 571E3142
Explanation: Bus is operational
571E3120 571E3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 571E3143 571E3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
571E4150 571E4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
571E3401 571E3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
571E3405 571E3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
571E34FF 571E34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
571E4160 571E4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
571E8008 571E8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 571E8009 571E8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
571E8100 571E8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 571E8130 571E8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
571E9002 571E9002
Explanation: Device error
571E8300 571E8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
571E8301 571E8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
571E9008 571E9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
571E8400 571E8400
571E9010 571E9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
571E8404 571E8404
v IOPIP31
Explanation: System log entry only. No service action
required.
571E9011 571E9011
571E9020 571E9020
571E9001 571E9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
571E9040 571E9040
571E9053 571E9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
571E9041 571E9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
571E9054 571E9054
571E9042 571E9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
571E9050 571E9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
571E9071 571E9071
Response:
Explanation: Link from IOA to auxiliary cache IOA
Failing Item: went operational
v IOPIP30 Response: No service action required.
Response:
571E9903 571E9903
Failing Item:
Explanation: Tape device information was logged.
v IOPIP16
Informational event, no service required.
v FI01105
v STORIOA
571EC000 571EC000
v FI01140
Explanation: System log entry only. No service action
v BACKPLN
required.
v FI01106
Response: No action is required. This reference code
is logged for information only.
571E9090 571E9090
Explanation: Disk unit has been modified after the 571EC100 571EC100
last known status.
Explanation: System log entry only. No service action
Response: Re-IPL the system. If any reference codes required.
are surfaced, use the new reference code to resolve the
problem. Response: No action is required. This reference code
is logged for information only.
If you cannot resolve the problem, contact your next
level of support.
571EC402 571EC402
Failing Item:
Explanation: Licensed Internal Code error
v SVCDOCS
Response: Ask your next level of support for
assistance.
571E9091 571E9091
Failing Item:
Explanation: Incorrect hardware configuration change
detected v PTFSRCH
571EFF6D 571EFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
v STORIOA
571F3140 571F3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
571F3103 571F3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 571F3141 571F3141
v FI01140
v DEVBPLN 571F3142 571F3142
Explanation: Bus is operational
571F3120 571F3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 571F3143 571F3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
571F4150 571F4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
571F3401 571F3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
571F3405 571F3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
571F34FF 571F34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
571F4160 571F4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
571F8008 571F8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 571F8009 571F8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
571F8100 571F8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 571F8130 571F8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
571F9002 571F9002
Explanation: Device error
571F8300 571F8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
571F8301 571F8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
571F9008 571F9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
571F8400 571F8400
571F9010 571F9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
571F8404 571F8404
v IOPIP31
Explanation: System log entry only. No service action
required.
571F9011 571F9011
571F9020 571F9020
571F9001 571F9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
571F9040 571F9040
571F9053 571F9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
571F9041 571F9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
571F9054 571F9054
571F9042 571F9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
571F9050 571F9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
571F9071 571F9071
Response:
Explanation: Link from IOA to auxiliary cache IOA
Failing Item: went operational
v IOPIP30 Response: No service action required.
Response:
571F9903 571F9903
Failing Item:
Explanation: Tape device information was logged.
v IOPIP16
Informational event, no service required.
v FI01105
v STORIOA
571FC000 571FC000
v FI01140
Explanation: System log entry only. No service action
v BACKPLN
required.
v FI01106
Response: No action is required. This reference code
is logged for information only.
571F9090 571F9090
Explanation: Disk unit has been modified after the 571FC100 571FC100
last known status.
Explanation: System log entry only. No service action
Response: Re-IPL the system. If any reference codes required.
are surfaced, use the new reference code to resolve the
problem. Response: No action is required. This reference code
is logged for information only.
If you cannot resolve the problem, contact your next
level of support.
571FC402 571FC402
Failing Item:
Explanation: Licensed Internal Code error
v SVCDOCS
Response: Ask your next level of support for
assistance.
571F9091 571F9091
Failing Item:
Explanation: Incorrect hardware configuration change
detected v PTFSRCH
571FFF6D 571FFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
572A8008 572A8008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 572A8009 572A8009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 572A8100 572A8100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
572A8300 572A8300
Explanation: IOA hardware error or PCI bus error 572A8301 572A8301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
572A8302 572A8302
572A8400 572A8400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
572A8404 572A8404
v STORIOA
Explanation: System log entry only. No service action
required.
572A9001 572A9001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
572A9020 572A9020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 572A9021 572A9021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
572A9031 572A9031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
572A9026 572A9026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 572A9032 572A9032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
572A9027 572A9027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
572A9040 572A9040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
572A9091 572A9091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
572A9092 572A9092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
572A9500 572A9500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
572A9903 572A9903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
572AC000 572AC000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
572B8008 572B8008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 572B8009 572B8009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 572B8100 572B8100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
572B8300 572B8300
Explanation: IOA hardware error or PCI bus error 572B8301 572B8301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
572B8302 572B8302
572B8400 572B8400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
572B8404 572B8404
v STORIOA
Explanation: System log entry only. No service action
required.
572B9001 572B9001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
572B9020 572B9020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 572B9021 572B9021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
572B9031 572B9031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
572B9026 572B9026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 572B9032 572B9032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
572B9027 572B9027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
572B9040 572B9040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
572B9091 572B9091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
572B9092 572B9092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
572B9500 572B9500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
572B9903 572B9903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
572BC000 572BC000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
572C8008 572C8008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 572C8009 572C8009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 572C8100 572C8100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
572C8300 572C8300
Explanation: IOA hardware error or PCI bus error 572C8301 572C8301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
572C8302 572C8302
572C8400 572C8400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
572C8404 572C8404
v STORIOA
Explanation: System log entry only. No service action
required.
572C9001 572C9001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
572C9020 572C9020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 572C9021 572C9021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
572C9031 572C9031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
572C9026 572C9026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 572C9032 572C9032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
572C9027 572C9027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
572C9040 572C9040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
572C9091 572C9091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
572C9092 572C9092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
572C9500 572C9500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
572C9903 572C9903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
572CC000 572CC000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
572F8008 572F8008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 572F8009 572F8009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 572F8100 572F8100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
572F8300 572F8300
Explanation: IOA hardware error or PCI bus error 572F8301 572F8301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
572F8302 572F8302
572F8400 572F8400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
572F8404 572F8404
v STORIOA
Explanation: System log entry only. No service action
required.
572F9001 572F9001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
572F9020 572F9020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 572F9021 572F9021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
572F9031 572F9031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
572F9026 572F9026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 572F9032 572F9032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
572F9027 572F9027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
572F9040 572F9040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
572F9091 572F9091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
572F9092 572F9092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
572F9500 572F9500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
572F9903 572F9903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
572FC000 572FC000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
573AB9B0 573AB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
573BA6E3 573BA6E3
Explanation: Ethernet adapter or network device
cabling error.
Failing Item:
v FI00722
v UJE40
v IOA
573BB100 573BB100
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
573BB200 573BB200
Explanation: I/O adapter hardware error detected
Failing Item:
v AJDG301
v IOA
573BB300 573BB300
Explanation: An I/O adapter hardware error was
detected.
Response: Work the Failing Item list from the
serviceable event view if it is available, otherwise use
this Failing Item list.
Problem determination: Varying off and then varying
on the resource may resolve the problem. If that does
not resolve the problem then have the service provider
work the problem.
Failing Item:
v IOA
v AJDG301
573CA6E3 573CA6E3
Explanation: Ethernet adapter or network device
cabling error.
Failing Item:
v FI00722
v UJE40
v IOA
573CB100 573CB100
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
573CB200 573CB200
Explanation: I/O adapter hardware error detected
Failing Item:
v AJDG301
v IOA
573CB300 573CB300
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
v STORIOA
573D3140 573D3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
573D3103 573D3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 573D3141 573D3141
v FI01140
v DEVBPLN 573D3142 573D3142
Explanation: Bus is operational
573D3120 573D3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 573D3143 573D3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
573D4150 573D4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
573D3401 573D3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
573D3405 573D3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
573D34FF 573D34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
573D4160 573D4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
573D8008 573D8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 573D8009 573D8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
573D8100 573D8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 573D8130 573D8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
573D9002 573D9002
Explanation: Device error
573D8300 573D8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
573D8301 573D8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
573D9008 573D9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
573D8400 573D8400
573D9010 573D9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
573D8404 573D8404
v IOPIP31
Explanation: System log entry only. No service action
required.
573D9011 573D9011
573D9020 573D9020
573D9001 573D9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
573D9040 573D9040
573D9053 573D9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
573D9041 573D9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
573D9054 573D9054
573D9042 573D9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
573D9050 573D9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
573D9071 573D9071
Response:
Explanation: Link from IOA to auxiliary cache IOA
Failing Item: went operational
v IOPIP30 Response: No service action required.
Response:
573D9903 573D9903
Failing Item:
Explanation: Tape device information was logged.
v IOPIP16
Informational event, no service required.
v FI01105
v STORIOA
573DC000 573DC000
v FI01140
Explanation: System log entry only. No service action
v BACKPLN
required.
v FI01106
Response: No action is required. This reference code
is logged for information only.
573D9090 573D9090
Explanation: Disk unit has been modified after the 573DC100 573DC100
last known status.
Explanation: System log entry only. No service action
Response: Re-IPL the system. If any reference codes required.
are surfaced, use the new reference code to resolve the
problem. Response: No action is required. This reference code
is logged for information only.
If you cannot resolve the problem, contact your next
level of support.
573DC402 573DC402
Failing Item:
Explanation: Licensed Internal Code error
v SVCDOCS
Response: Ask your next level of support for
assistance.
573D9091 573D9091
Failing Item:
Explanation: Incorrect hardware configuration change
detected v PTFSRCH
573DFF6D 573DFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
v STORIOA
573E3140 573E3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
573E3103 573E3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 573E3141 573E3141
v FI01140
v DEVBPLN 573E3142 573E3142
Explanation: Bus is operational
573E3120 573E3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 573E3143 573E3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
573E4150 573E4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
573E3401 573E3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
573E3405 573E3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
573E34FF 573E34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
573E4160 573E4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
573E8008 573E8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 573E8009 573E8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
573E8100 573E8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 573E8130 573E8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
573E9002 573E9002
Explanation: Device error
573E8300 573E8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
573E8301 573E8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
573E9008 573E9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
573E8400 573E8400
573E9010 573E9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
573E8404 573E8404
v IOPIP31
Explanation: System log entry only. No service action
required.
573E9011 573E9011
573E9020 573E9020
573E9001 573E9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
573E9040 573E9040
573E9053 573E9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
573E9041 573E9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
573E9054 573E9054
573E9042 573E9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
573E9050 573E9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
573E9071 573E9071
Response:
Explanation: Link from IOA to auxiliary cache IOA
Failing Item: went operational
v IOPIP30 Response: No service action required.
Response:
573E9903 573E9903
Failing Item:
Explanation: Tape device information was logged.
v IOPIP16
Informational event, no service required.
v FI01105
v STORIOA
573EC000 573EC000
v FI01140
Explanation: System log entry only. No service action
v BACKPLN
required.
v FI01106
Response: No action is required. This reference code
is logged for information only.
573E9090 573E9090
Explanation: Disk unit has been modified after the 573EC100 573EC100
last known status.
Explanation: System log entry only. No service action
Response: Re-IPL the system. If any reference codes required.
are surfaced, use the new reference code to resolve the
problem. Response: No action is required. This reference code
is logged for information only.
If you cannot resolve the problem, contact your next
level of support.
573EC402 573EC402
Failing Item:
Explanation: Licensed Internal Code error
v SVCDOCS
Response: Ask your next level of support for
assistance.
573E9091 573E9091
Failing Item:
Explanation: Incorrect hardware configuration change
detected v PTFSRCH
573EFF6D 573EFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
57469210 57469210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
57469303 57469303
57469211 57469211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
57469304 57469304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
57469220 57469220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
57469310 57469310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
57469300 57469300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
57469321 57469321
57469500 57469500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
57469501 57469501
57469350 57469350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 57469800 57469800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
57469801 57469801
57469351 57469351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 57469802 57469802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
57469803 57469803
57469355 57469355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
57469899 57469899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
57469900 57469900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
57469901 57469901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
574E8008 574E8008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 574E8009 574E8009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 574E8100 574E8100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
574E8300 574E8300
Explanation: IOA hardware error or PCI bus error 574E8301 574E8301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
574E8302 574E8302
574E8400 574E8400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
574E8404 574E8404
v STORIOA
Explanation: System log entry only. No service action
required.
574E9001 574E9001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
574E9020 574E9020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 574E9021 574E9021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
574E9031 574E9031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
574E9026 574E9026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 574E9032 574E9032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
574E9027 574E9027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
574E9040 574E9040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
574E9091 574E9091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
574E9092 574E9092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
574E9500 574E9500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
574E9903 574E9903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
574EC000 574EC000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
Response: Error occurred on SCSI bus 0. Explanation: Impending cache battery pack failure
Response: v AUXIOA
Failing Item:
574F8302 574F8302
v PTFSRCH
v AUXIOA Explanation: Missing Licensed Internal Code
Response: Ensure that the code necessary to support
574F8156 574F8156 this I/O adapter is loaded.
574F9071 574F9071
Explanation: Link from IOA to auxiliary cache IOA
went operational
Response: No service action required.
574F9072 574F9072
Explanation: Link from IOA to auxiliary cache IOA
went non-operational
Response: No service action required.
574F9073 574F9073
Explanation: Disconnected, incompatible, or
non-operational storage IOA
Response:
Failing Item:
v IOPIP41
574FFF3D 574FFF3D
Explanation: I/O adapter detected recoverable error
Response:
Failing Item:
v AUXIOA
v ANYBRDG
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
57559210 57559210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
57559303 57559303
57559211 57559211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
57559304 57559304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
57559220 57559220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
57559310 57559310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
57559300 57559300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
57559321 57559321
57559500 57559500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
57559501 57559501
57559350 57559350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 57559800 57559800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
57559801 57559801
57559351 57559351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 57559802 57559802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
57559803 57559803
57559355 57559355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
57559899 57559899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
57559900 57559900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
57559901 57559901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Response: Error occurred on SCSI bus 0. Explanation: Impending cache battery pack failure
Response: v AUXIOA
Failing Item:
575B8302 575B8302
v PTFSRCH
v AUXIOA Explanation: Missing Licensed Internal Code
Response: Ensure that the code necessary to support
575B8156 575B8156 this I/O adapter is loaded.
575B9071 575B9071
Explanation: Link from IOA to auxiliary cache IOA
went operational
Response: No service action required.
575B9072 575B9072
Explanation: Link from IOA to auxiliary cache IOA
went non-operational
Response: No service action required.
575B9073 575B9073
Explanation: Disconnected, incompatible, or
non-operational storage IOA
Response:
Failing Item:
v IOPIP41
575BFF3D 575BFF3D
Explanation: I/O adapter detected recoverable error
Response:
Failing Item:
v AUXIOA
v ANYBRDG
Explanation: I/O adapter detected recoverable bus SVCDOCS, then do NOT replace the I/O adapter. This
error is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated
Response: If this event appears in a serviceable event
with this I/O adapter.
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no Failing Item:
service action is required. v SVCDOCS
Failing Item:
v PRIMIOA 575C8300 575C8300
v AUXIOA Explanation: IOA hardware or PCI bus error
v BACKPLN
Failing Item:
v AUXIOA
575C8150 575C8150
v ANYBRDG
Explanation: A permanent failure occurred v PTFSRCH
Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service 575C8301 575C8301
action. Depending on the configuration of the system,
the Storage IOA may have been altered and/or the Explanation: Not valid condition in Licensed Internal
Storage IOA Cache may have been disabled to allow Code
attachment of OEM Storage that emulates a Load Failing Item:
Source drive. If this is the case, this error will be posted
each time the IOA is IPLed and it can be ignored. v PTFSRCH
v AUXIOA
Failing Item:
v AUXIOA
575C8302 575C8302
v ANYBRDG
Explanation: Missing Licensed Internal Code
575C8151 575C8151 Response: Ensure that the code necessary to support
this I/O adapter is loaded.
Explanation: Licensed Internal Code error
Failing Item:
Failing Item:
v SVCDOCS
v PTFSRCH
v AUXIOA
v AUXIOA
575C9055 575C9055
575C8155 575C8155
Explanation: Write cache data is available for attached
Explanation: A permanent failure occurred storage IOA
Failing Item: Response: No service action required.
v PTFSRCH
v AUXIOA 575C9071 575C9071
Explanation: Link from IOA to auxiliary cache IOA
575C8156 575C8156 went operational
Explanation: A permanent failure occurred Response: No service action required.
Failing Item:
v PTFSRCH 575C9072 575C9072
v AUXIOA Explanation: Link from IOA to auxiliary cache IOA
went non-operational
575C8157 575C8157 Response: No service action required.
Explanation: I/O adapter card error
Response: Display the Service Action Log entry for
this SRC. If the Failing Item indicates I/O adapter, then
replace the I/O adapter. If the Failing Item indicates
575C9073 575C9073
Explanation: Multiple I/O adapters connected in a not
valid configuration
Failing Item:
v SIP3140
575C9076 575C9076
Explanation: Missing remote I/O adapter
Failing Item:
v SIP3147
v PRIMIOA
v AUXIOA
v BACKPLN
575CFF3D 575CFF3D
Explanation: I/O adapter detected recoverable error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v AUXIOA
v ANYBRDG
5767B9B0 5767B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDGP01
5768B9B0 5768B9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDGP01
576AB9B0 576AB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
Explanation: A port failure was detected on port 0 v Check the Product Activity Log for other entries that
indicate interface problems and work those
Failing Item: problems.
v FCPORT v Check the device firmware level and apply the latest
v FCIOA PTFs.
v FCDEV v Check for LIC logs with major code 2E00. Contact
your next level of support with the information you
v OPT_CLN
have gathered.
Problem determination: IPL the IOP to retry the
576B3121 576B3121
device identification process. If the error persists then
Explanation: A port failure was detected on port 1 contact your service provider.
Failing Item: Failing Item:
v PTFSRCH
576B8300 576B8300
Explanation: IOA hardware error or PCI bus error
576B34FF 576B34FF
Failing Item:
Explanation: Format in progress
v FCIOA
Response: The device indicated that a format is in
v ANYBRDG
progress. When the format is complete, the device
should be usable. No action is required. This reference v PTFSRCH
code is logged for information only. v OPT_CLN
576B8131 576B8131
576B9903 576B9903
Explanation: Recovered Fibre Channel interface error
on port 1 Explanation: Tape device information was logged.
Informational event, no service required.
Response: No action required. This reference code is
logged for information only.
576BB000 576BB000
576BC000 576BC000
Explanation: System log entry only, no service action
required
Response: No action is required. This reference code
is logged for information only.
576BC402 576BC402
Explanation: Licensed Internal Code error
Failing Item:
v PTFSRCH
576CB940 576CB940
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDGP01
v MA_BRDG
576CB941 576CB941
Explanation: One of the ports on the IOA has failed.
Failing Item:
v FI00719
v AJDGP01
576DB9B0 576DB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
576EB9B0 576EB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v IOA
v AJDG301
576FB9A0 576FB9A0
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v FI00718
v AJDGP01
v MA_BRDG
576FB9B0 576FB9B0
Explanation: I/O adapter hardware error detected
Failing Item:
v FI00719
v AJDG301
v MA_BRDG
Explanation: A port failure was detected on port 0 v Check the Product Activity Log for other entries that
indicate interface problems and work those
Failing Item: problems.
v FCPORT v Check the device firmware level and apply the latest
v FCIOA PTFs.
v FCDEV v Check for LIC logs with major code 2E00. Contact
your next level of support with the information you
v OPT_CLN
have gathered.
Problem determination: IPL the IOP to retry the
57743121 57743121
device identification process. If the error persists then
Explanation: A port failure was detected on port 1 contact your service provider.
Failing Item: Failing Item:
v PTFSRCH
57748300 57748300
Explanation: IOA hardware error or PCI bus error
577434FF 577434FF
Failing Item:
Explanation: Format in progress
v FCIOA
Response: The device indicated that a format is in
v ANYBRDG
progress. When the format is complete, the device
should be usable. No action is required. This reference v PTFSRCH
code is logged for information only. v OPT_CLN
57748131 57748131
57749903 57749903
Explanation: Recovered Fibre Channel interface error
on port 1 Explanation: Tape device information was logged.
Informational event, no service required.
Response: No action required. This reference code is
logged for information only.
5774B000 5774B000
5774C000 5774C000
Explanation: System log entry only, no service action
required
Response: No action is required. This reference code
is logged for information only.
5774C402 5774C402
Explanation: Licensed Internal Code error
Failing Item:
v PTFSRCH
Explanation: A port failure was detected on port 0 v Check the Product Activity Log for other entries that
indicate interface problems and work those
Failing Item: problems.
v FCPORT v Check the device firmware level and apply the latest
v FCIOA PTFs.
v FCDEV v Check for LIC logs with major code 2E00. Contact
your next level of support with the information you
v OPT_CLN
have gathered.
Problem determination: IPL the IOP to retry the
577D3121 577D3121
device identification process. If the error persists then
Explanation: A port failure was detected on port 1 contact your service provider.
Failing Item: Failing Item:
v PTFSRCH
577D8300 577D8300
Explanation: IOA hardware error or PCI bus error
577D34FF 577D34FF
Failing Item:
Explanation: Format in progress
v FCIOA
Response: The device indicated that a format is in
v ANYBRDG
progress. When the format is complete, the device
should be usable. No action is required. This reference v PTFSRCH
code is logged for information only. v OPT_CLN
577D8131 577D8131
577D9903 577D9903
Explanation: Recovered Fibre Channel interface error
on port 1 Explanation: Tape device information was logged.
Informational event, no service required.
Response: No action required. This reference code is
logged for information only.
577DB000 577DB000
577DC000 577DC000
Explanation: System log entry only, no service action
required
Response: No action is required. This reference code
is logged for information only.
577DC402 577DC402
Explanation: Licensed Internal Code error
Failing Item:
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of v The embedded storage adapter on the I/O
the FRUs if they are not listed in the serviceable event backplane.
or if you are working the failing item list here. v The Battery charger and carrier card.
Card type 57CF (embedded IOAs on DASD backplane See symbolic FRU FEATCRD for the location codes of
with 2BC2 dual battery charger and carrier card for the the FRUs if they are not listed in the serviceable event
embedded IOAs) read the following: When working or if you are working the failing item list here.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) Card type 57CF (embedded IOAs on DASD backplane
have two physical parts: with 2BC2 dual battery charger and carrier card for the
v The embedded storage adapter on the DASD embedded IOAs) read the following: When working
backplane. the FRUs from the serviceable event or the failing item
v The dual battery charger and carrier card. To list here, the embedded storage adapters (STORIOA)
determine which battery is connected to which have two physical parts:
embedded IOA use the bus number of the IOA with v The embedded storage adapter on the DASD
symbolic FRU CACHBAT. backplane.
v The dual battery charger and carrier card. To
See symbolic FRU FEATCRD for the location code of determine which battery is connected to which
the dual battery charger and carrier card if it is not embedded IOA use the bus number of the IOA with
listed in the serviceable event or if you are working the symbolic FRU CACHBAT.
failing item list here.
Failing Item: See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
v BACKPLN
listed in the serviceable event or if you are working the
v STORIOA failing item list here.
Failing Item:
57B14160 57B14160
v BACKPLN
Explanation: I/O adapter detected and recovered a v STORIOA
PCI bus error
Response: If this event appears in a serviceable event 57B18008 57B18008
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no Explanation: A permanent cache battery pack failure
service action is required. occurred
If you are working with one of the card types below, Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the may not represent an error that requires a service
card type to identify the physical parts of the storage action. Depending on the configuration of the system,
adapter. the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
Card type 2BE1 (feature RAID enablement card for attachment of OEM Storage that emulates a Load
embedded IOA) read the following: When working the Source drive. If this is the case, this error will be posted
FRUs from the serviceable event or the failing item list each time the IOA is IPLed and it can be ignored.
here, the embedded storage adapter (STORIOA) has
three physical parts: If you are working with one of the card types below,
the adapter has mulitple physical parts. Choose the
v The embedded storage adapter on the I/O
card type to identify the physical parts of the storage
backplane.
adapter.
v The RAID enablement card.
Card type 2BE1 (feature RAID enablement card for
v The Battery charger and carrier card.
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
See symbolic FRU FEATCRD for the location codes of
here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event
three physical parts:
or if you are working the failing item list here.
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When v The RAID enablement card.
working the FRUs from the serviceable event or the v The Battery charger and carrier card.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
See symbolic FRU FEATCRD for the location codes of here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event three physical parts:
or if you are working the failing item list here. v The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
v The RAID enablement card.
card) read the following: When working the FRUs from
the serviceable event or the failing item list here, the v The Battery charger and carrier card.
embedded storage adapter (STORIOA) has two
physical parts: See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O
or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
See symbolic FRU FEATCRD for the location codes of working the FRUs from the serviceable event or the
the FRUs if they are not listed in the serviceable event failing item list here, the embedded storage adapter
or if you are working the failing item list here. (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane
backplane.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the v The Battery charger and carrier card.
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane.
Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card for the
determine which battery is connected to which embedded IOAs) read the following: When working
embedded IOA use the bus number of the IOA with the FRUs from the serviceable event or the failing item
symbolic FRU CACHBAT. list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location code of
v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not
backplane.
listed in the serviceable event or if you are working the
failing item list here. v The dual battery charger and carrier card. To
determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
v CACHBAT symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
v FEATCRD
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57B18009 57B18009 failing item list here.
Explanation: Impending cache battery pack failure Failing Item:
Failing Item: v PTFSRCH
v CACHBAT v STORIOA
Explanation: Licensed Internal Code error Explanation: IOA detected recoverable device bus
error
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts. Response: If this event appears in a serviceable event
Choose the card type to identify the physical parts of view, work with the failing item list found there. If this
the storage adapter. event does not appear in a serviceable event view, no
service action is required.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v SIP3150
v FI01105
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
57B18150 57B18150 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent failure occurred
Failing Item:
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v ANYBRDG
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
57B18151 57B18151
attachment of OEM Storage that emulates a Load
Source drive. If this is the case, this error will be posted Explanation: Licensed Internal Code error
each time the IOA is IPLed and it can be ignored.
Response: If you are working with one of the card
If you are working with one of the card types below, types below, the adapter has mulitple physical parts.
the adapter has mulitple physical parts. Choose the Choose the card type to identify the physical parts of
card type to identify the physical parts of the storage the storage adapter.
adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for embedded IOA) read the following: When working the
embedded IOA) read the following: When working the FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has three physical parts:
three physical parts: v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O backplane.
backplane. v The RAID enablement card.
v The RAID enablement card. v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
Card type 57CB (embedded IOA with 2BCF battery card for embedded IOA) read the following: When
card for embedded IOA) read the following: When working the FRUs from the serviceable event or the
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card for embedded IOA) read the following: When
the FRUs if they are not listed in the serviceable event
working the FRUs from the serviceable event or the
or if you are working the failing item list here.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of
have two physical parts:
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
v The dual battery charger and carrier card. To
Failing Item:
determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57B18302 57B18302
57B18301 57B18301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 2BE1 (feature RAID enablement card for
the FRUs if they are not listed in the serviceable event embedded IOA) read the following: When working the
or if you are working the failing item list here. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
Card type 57CB (embedded IOA with 2BCF battery three physical parts:
card for embedded IOA) read the following: When v The embedded storage adapter on the I/O
working the FRUs from the serviceable event or the backplane.
failing item list here, the embedded storage adapter
v The RAID enablement card.
(STORIOA) has two physical parts:
v The Battery charger and carrier card.
v The embedded storage adapter on the I/O
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here. card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working
v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item
backplane.
list here, the embedded storage adapters (STORIOA)
have two physical parts: v The Battery charger and carrier card.
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here.
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
v STORIOA determine which battery is connected to which
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57B18400 57B18400
Explanation: Licensed Internal Code error See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57B18404 57B18404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57B19001 57B19001
57B19000 57B19000
Explanation: Device configuration error
Explanation: Device error
Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
the storage adapter.
Failing Item:
57B19026 57B19026
v SIP3120
Explanation: Disk unit not found at required physical
location
57B19011 57B19011
Response: A previously exposed disk unit in an array
Explanation: Cache data belongs to devices other than
was not found at the required physical location.
those attached
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57B19027 57B19027
57B19020 57B19020
Explanation: Array not functional due to parity out of
Explanation: Two or more disk units missing from
synchronization
RAID-5 or RAID-6 array
Response: Array is or would become exposed and
Failing Item:
parity data is out of synchronization
v SIP3111
Failing Item:
v SIP3113
57B19021 57B19021
Explanation: Two or more disk units missing from
57B19028 57B19028
RAID-5 or RAID-6 array
Explanation: Maximum number of functional arrays
Failing Item:
has been exceeded
v SIP3111
Response: Reduce the number of arrays on this I/O
adapter. Either move all the devices in an array to
57B19022 57B19022 another I/O adapter that supports arrays, or stop an
Explanation: Two or more disk units missing from array on this I/O adapter.
RAID-5 or RAID-6 array Failing Item:
Failing Item: v SVCDOCS
v SIP3111
57B19029 57B19029
57B19023 57B19023 Explanation: Maximum number of functional array
Explanation: One or more array members not in members has been exceeded
required physical locations Response: Contact your next level of support.
Failing Item: Failing Item:
v SIP3112 v NEXTLVL
Failing Item:
57B19054 57B19054
v SIP3110
v FI02112 Explanation: IOA resources not available due to
previous problems
Card type 57CF (embedded IOAs on DASD backplane reference code to resolve the problem.
with 2BC2 dual battery charger and carrier card for the
If you cannot resolve the problem, contact your next
embedded IOAs) read the following: When working
level of support.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) Failing Item:
have two physical parts: v SVCDOCS
v The embedded storage adapter on the DASD
backplane.
57B19092 57B19092
v The dual battery charger and carrier card. To
determine which battery is connected to which Explanation: Disk unit requires initialization before
embedded IOA use the bus number of the IOA with use.
symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of v SIP3134
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the 57B19500 57B19500
failing item list here.
Explanation: Internal program error in driver code.
Failing Item:
Failing Item:
v FI01105
v PTFSRCH
v STORIOA
57B19903 57B19903
57B19083 57B19083
Explanation: Tape device information was logged.
Explanation: System log entry only. No service action
Informational event, no service required.
required.
57B1C000 57B1C000
57B19084 57B19084
Explanation: System log entry only. No service action
Explanation: System log entry only. No service action
required.
required.
Response: No action is required. This reference code
is logged for information only.
57B19090 57B19090
Explanation: Disk unit has been modified after the
57B1C402 57B1C402
last known status.
Explanation: Licensed Internal Code error
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this Response: Ask your next level of support for
I/O adapter. Other resources attached to the virtual assistance.
I/O processor may then need to be Varied On.
Failing Item:
If any reference codes are surfaced, use the new v PTFSRCH
reference code to resolve the problem.
If you cannot resolve the problem, contact your next 57B1FF3D 57B1FF3D
level of support.
Explanation: I/O adapter detected a recoverable error
Failing Item:
Response: If you are working with one of the card
v SVCDOCS
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57B19091 57B19091 the storage adapter.
Explanation: Incorrect hardware configuration change Card type 2BE1 (feature RAID enablement card for
detected embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Response: Use Hardware Service Manager to re-IPL
here, the embedded storage adapter (STORIOA) has
the virtual I/O processor that is associated with this
three physical parts:
I/O adapter. Other resources attached to the virtual
I/O processor may then need to be Varied On. v The embedded storage adapter on the I/O
backplane.
If any reference codes are surfaced, use the new
v The RAID enablement card.
Failing Item:
57B24080 57B24080
v SASCABL
Explanation: Storage controller thermal error. The
controller exceeded the maximum operating
temperature. 57B24150 57B24150
Problem determination: Verify that the storage Explanation: I/O adapter detected PCI bus error
controller is placed in a valid location for this type of Response: If this event appears in a serviceable event
controller and enclosure. Perform the procedure listed view, work with the failing item list found there. If this
in the failing items to determine the problem and event does not appear in a serviceable event view, no
corrective action. service action is required.
Failing Item: If you are working with one of the card types below,
v SIP3295 the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
57B24085 57B24085
Card type 2BE1 (feature RAID enablement card for
Explanation: Storage controller detected error. Contact
embedded IOA) read the following: When working the
your next level of support or hardware service provider
FRUs from the serviceable event or the failing item list
for more information before replacing any hardware.
here, the embedded storage adapter (STORIOA) has
Failing Item: three physical parts:
v NEXTLVL v The embedded storage adapter on the I/O
backplane.
57B24100 57B24100 v The RAID enablement card.
v The Battery charger and carrier card.
Explanation: Device bus fabric error
Failing Item: See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v SASCABL
v SASEXP Card type 57CB (embedded IOA with 2BCF battery
v DEVBPLN card for embedded IOA) read the following: When
v STORIOA working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
v FI01105
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
57B24101 57B24101 backplane.
Explanation: Temporary device bus fabric error v The Battery charger and carrier card.
Failing Item:
See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
57B24110 57B24110
Card type 57CF (embedded IOAs on DASD backplane
Explanation: Unsupported enclosure function detected with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
v SIP3145 list here, the embedded storage adapters (STORIOA)
have two physical parts:
57B24123 57B24123 v The embedded storage adapter on the DASD
backplane.
Explanation: Configuration error, invalid cable Vital
Product Data. The storage controller detected invalid v The dual battery charger and carrier card. To
VPD on the SAS cable. This is most likely caused by a determine which battery is connected to which
non IBM cable or a wrap plug. The system will embedded IOA use the bus number of the IOA with
continue to run. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of v The dual battery charger and carrier card. To
the dual battery charger and carrier card if it is not determine which battery is connected to which
listed in the serviceable event or if you are working the embedded IOA use the bus number of the IOA with
failing item list here. symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of
v BACKPLN the dual battery charger and carrier card if it is not
v STORIOA listed in the serviceable event or if you are working the
failing item list here.
57B24160 57B24160 Failing Item:
Explanation: I/O adapter detected and recovered a v BACKPLN
PCI bus error v STORIOA
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this 57B28008 57B28008
event does not appear in a serviceable event view, no
Explanation: A permanent cache battery pack failure
service action is required.
occurred
If you are working with one of the card types below,
Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the
may not represent an error that requires a service
card type to identify the physical parts of the storage
action. Depending on the configuration of the system,
adapter.
the Storage IOA may have been altered and/or the
Card type 2BE1 (feature RAID enablement card for Storage IOA Cache may have been disabled to allow
embedded IOA) read the following: When working the attachment of OEM Storage that emulates a Load
FRUs from the serviceable event or the failing item list Source drive. If this is the case, this error will be posted
here, the embedded storage adapter (STORIOA) has each time the IOA is IPLed and it can be ignored.
three physical parts:
If you are working with one of the card types below,
v The embedded storage adapter on the I/O the adapter has mulitple physical parts. Choose the
backplane. card type to identify the physical parts of the storage
v The RAID enablement card. adapter.
v The Battery charger and carrier card. Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
See symbolic FRU FEATCRD for the location codes of FRUs from the serviceable event or the failing item list
the FRUs if they are not listed in the serviceable event here, the embedded storage adapter (STORIOA) has
or if you are working the failing item list here. three physical parts:
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card) read the following: When working the FRUs from
the FRUs if they are not listed in the serviceable event
the serviceable event or the failing item list here, the
or if you are working the failing item list here.
embedded storage adapter (STORIOA) has two
physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane v The Battery charger and carrier card.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the See symbolic FRU FEATCRD for the location codes of
serviceable event or the failing item list here, the the FRUs if they are not listed in the serviceable event
embedded storage adapters (STORIOA) have two or if you are working the failing item list here.
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
Failing Item:
v CACHBAT See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 57B28141 57B28141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter Response: No action is required. This reference code
(STORIOA) has two physical parts: is logged for information only.
v The embedded storage adapter on the I/O
backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To Card type 57CF (embedded IOAs on DASD backplane
determine which battery is connected to which with 2BC2 dual battery charger and carrier card for the
embedded IOA use the bus number of the IOA with embedded IOAs) read the following: When working
symbolic FRU CACHBAT. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of have two physical parts:
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here.
v The dual battery charger and carrier card. To
Failing Item: determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
57B28157 57B28157 the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Explanation: I/O adapter card error failing item list here.
Response: The FRU list in the Service Action Log will Failing Item:
vary based on the conditions this event was logged for.
v SVCDOCS
Display the Service Action Log entry for this SRC. If v STORIOA
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates
SVCDOCS, then do NOT replace the I/O adapter. This 57B28300 57B28300
is a recoverable error. Use Hardware Service Manager
Explanation: IOA hardware error or PCI bus error
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the Response: If you are working with one of the card
virtual I/O processor may then need to be Varied On. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
If you are replacing the I/O adapter and you are
the storage adapter.
working with one of the card types below, the adapter
has mulitple physical parts. Choose the card type to Card type 2BE1 (feature RAID enablement card for
identify the physical parts of the storage adapter. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has
embedded IOA) read the following: When working the
three physical parts:
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CB (embedded IOA with 2BCF battery
failing item list here, the embedded storage adapter
card for embedded IOA) read the following: When
(STORIOA) has two physical parts:
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57B28302 57B28302
57B28301 57B28301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57B28400 57B28400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57B28404 57B28404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57B29001 57B29001
57B29000 57B29000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57B29002 57B29002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 57B29008 57B29008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 57B29010 57B29010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
57B29026 57B29026
Explanation: Disk unit not found at required physical
57B29011 57B29011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57B29020 57B29020
57B29027 57B29027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
57B29021 57B29021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
57B29028 57B29028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
57B29022 57B29022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
57B29032 57B29032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
57B29054 57B29054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
57B29070 57B29070
57B29040 57B29040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
57B29071 57B29071
Explanation: Link from IOA to auxiliary or remote
57B29041 57B29041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
57B29072 57B29072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
57B29042 57B29042
57B29073 57B29073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP3140
Failing Item:
v NEXTLVL
57B29074 57B29074
57B29051 57B29051
57B29075 57B29075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP3149
57B29052 57B29052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
57B29076 57B29076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP3147 57B29082 57B29082
Explanation: Device error
57B29081 57B29081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
57B29500 57B29500
v STORIOA
Explanation: Internal program error in driver code.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
57B38008 57B38008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 57B38009 57B38009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 57B38100 57B38100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
57B38300 57B38300
Explanation: IOA hardware error or PCI bus error 57B38301 57B38301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
57B38302 57B38302
57B38400 57B38400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
57B38404 57B38404
v STORIOA
Explanation: System log entry only. No service action
required.
57B39001 57B39001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
57B39020 57B39020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 57B39021 57B39021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
57B39031 57B39031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
57B39026 57B39026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 57B39032 57B39032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
57B39027 57B39027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
57B39040 57B39040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
57B39091 57B39091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
57B39092 57B39092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
57B39500 57B39500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
57B39903 57B39903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
57B3C000 57B3C000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
Failing Item:
57B44080 57B44080
v SASCABL
Explanation: Storage controller thermal error. The
controller exceeded the maximum operating
temperature. 57B44150 57B44150
Problem determination: Verify that the storage Explanation: I/O adapter detected PCI bus error
controller is placed in a valid location for this type of Response: If this event appears in a serviceable event
controller and enclosure. Perform the procedure listed view, work with the failing item list found there. If this
in the failing items to determine the problem and event does not appear in a serviceable event view, no
corrective action. service action is required.
Failing Item: If you are working with one of the card types below,
v SIP3295 the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
57B44085 57B44085
Card type 2BE1 (feature RAID enablement card for
Explanation: Storage controller detected error. Contact
embedded IOA) read the following: When working the
your next level of support or hardware service provider
FRUs from the serviceable event or the failing item list
for more information before replacing any hardware.
here, the embedded storage adapter (STORIOA) has
Failing Item: three physical parts:
v NEXTLVL v The embedded storage adapter on the I/O
backplane.
57B44100 57B44100 v The RAID enablement card.
v The Battery charger and carrier card.
Explanation: Device bus fabric error
Failing Item: See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v SASCABL
v SASEXP Card type 57CB (embedded IOA with 2BCF battery
v DEVBPLN card for embedded IOA) read the following: When
v STORIOA working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
v FI01105
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
57B44101 57B44101 backplane.
Explanation: Temporary device bus fabric error v The Battery charger and carrier card.
Failing Item:
See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
57B44110 57B44110
Card type 57CF (embedded IOAs on DASD backplane
Explanation: Unsupported enclosure function detected with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
v SIP3145 list here, the embedded storage adapters (STORIOA)
have two physical parts:
57B44123 57B44123 v The embedded storage adapter on the DASD
backplane.
Explanation: Configuration error, invalid cable Vital
Product Data. The storage controller detected invalid v The dual battery charger and carrier card. To
VPD on the SAS cable. This is most likely caused by a determine which battery is connected to which
non IBM cable or a wrap plug. The system will embedded IOA use the bus number of the IOA with
continue to run. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of v The dual battery charger and carrier card. To
the dual battery charger and carrier card if it is not determine which battery is connected to which
listed in the serviceable event or if you are working the embedded IOA use the bus number of the IOA with
failing item list here. symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of
v BACKPLN the dual battery charger and carrier card if it is not
v STORIOA listed in the serviceable event or if you are working the
failing item list here.
57B44160 57B44160 Failing Item:
Explanation: I/O adapter detected and recovered a v BACKPLN
PCI bus error v STORIOA
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this 57B48008 57B48008
event does not appear in a serviceable event view, no
Explanation: A permanent cache battery pack failure
service action is required.
occurred
If you are working with one of the card types below,
Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the
may not represent an error that requires a service
card type to identify the physical parts of the storage
action. Depending on the configuration of the system,
adapter.
the Storage IOA may have been altered and/or the
Card type 2BE1 (feature RAID enablement card for Storage IOA Cache may have been disabled to allow
embedded IOA) read the following: When working the attachment of OEM Storage that emulates a Load
FRUs from the serviceable event or the failing item list Source drive. If this is the case, this error will be posted
here, the embedded storage adapter (STORIOA) has each time the IOA is IPLed and it can be ignored.
three physical parts:
If you are working with one of the card types below,
v The embedded storage adapter on the I/O the adapter has mulitple physical parts. Choose the
backplane. card type to identify the physical parts of the storage
v The RAID enablement card. adapter.
v The Battery charger and carrier card. Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
See symbolic FRU FEATCRD for the location codes of FRUs from the serviceable event or the failing item list
the FRUs if they are not listed in the serviceable event here, the embedded storage adapter (STORIOA) has
or if you are working the failing item list here. three physical parts:
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card) read the following: When working the FRUs from
the FRUs if they are not listed in the serviceable event
the serviceable event or the failing item list here, the
or if you are working the failing item list here.
embedded storage adapter (STORIOA) has two
physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane v The Battery charger and carrier card.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the See symbolic FRU FEATCRD for the location codes of
serviceable event or the failing item list here, the the FRUs if they are not listed in the serviceable event
embedded storage adapters (STORIOA) have two or if you are working the failing item list here.
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
Failing Item:
v CACHBAT See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 57B48141 57B48141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter Response: No action is required. This reference code
(STORIOA) has two physical parts: is logged for information only.
v The embedded storage adapter on the I/O
backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To Card type 57CF (embedded IOAs on DASD backplane
determine which battery is connected to which with 2BC2 dual battery charger and carrier card for the
embedded IOA use the bus number of the IOA with embedded IOAs) read the following: When working
symbolic FRU CACHBAT. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of have two physical parts:
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here.
v The dual battery charger and carrier card. To
Failing Item: determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
57B48157 57B48157 the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Explanation: I/O adapter card error failing item list here.
Response: The FRU list in the Service Action Log will Failing Item:
vary based on the conditions this event was logged for.
v SVCDOCS
Display the Service Action Log entry for this SRC. If v STORIOA
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates
SVCDOCS, then do NOT replace the I/O adapter. This 57B48300 57B48300
is a recoverable error. Use Hardware Service Manager
Explanation: IOA hardware error or PCI bus error
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the Response: If you are working with one of the card
virtual I/O processor may then need to be Varied On. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
If you are replacing the I/O adapter and you are
the storage adapter.
working with one of the card types below, the adapter
has mulitple physical parts. Choose the card type to Card type 2BE1 (feature RAID enablement card for
identify the physical parts of the storage adapter. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has
embedded IOA) read the following: When working the
three physical parts:
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CB (embedded IOA with 2BCF battery
failing item list here, the embedded storage adapter
card for embedded IOA) read the following: When
(STORIOA) has two physical parts:
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57B48302 57B48302
57B48301 57B48301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57B48400 57B48400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57B48404 57B48404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57B49001 57B49001
57B49000 57B49000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57B49002 57B49002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 57B49008 57B49008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 57B49010 57B49010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
57B49026 57B49026
Explanation: Disk unit not found at required physical
57B49011 57B49011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57B49020 57B49020
57B49027 57B49027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
57B49021 57B49021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
57B49028 57B49028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
57B49022 57B49022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
57B49032 57B49032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
57B49054 57B49054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
57B49070 57B49070
57B49040 57B49040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
57B49071 57B49071
Explanation: Link from IOA to auxiliary or remote
57B49041 57B49041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
57B49072 57B49072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
57B49042 57B49042
57B49073 57B49073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP3140
Failing Item:
v NEXTLVL
57B49074 57B49074
57B49051 57B49051
57B49075 57B49075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP3149
57B49052 57B49052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
57B49076 57B49076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP3147 57B49082 57B49082
Explanation: Device error
57B49081 57B49081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
57B49500 57B49500
v STORIOA
Explanation: Internal program error in driver code.
See symbolic FRU FEATCRD for the location codes of v The embedded storage adapter on the I/O
the FRUs if they are not listed in the serviceable event backplane.
or if you are working the failing item list here. v The Battery charger and carrier card.
Card type 57CF (embedded IOAs on DASD backplane See symbolic FRU FEATCRD for the location codes of
with 2BC2 dual battery charger and carrier card for the the FRUs if they are not listed in the serviceable event
embedded IOAs) read the following: When working or if you are working the failing item list here.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) Card type 57CF (embedded IOAs on DASD backplane
have two physical parts: with 2BC2 dual battery charger and carrier card for the
v The embedded storage adapter on the DASD embedded IOAs) read the following: When working
backplane. the FRUs from the serviceable event or the failing item
v The dual battery charger and carrier card. To list here, the embedded storage adapters (STORIOA)
determine which battery is connected to which have two physical parts:
embedded IOA use the bus number of the IOA with v The embedded storage adapter on the DASD
symbolic FRU CACHBAT. backplane.
v The dual battery charger and carrier card. To
See symbolic FRU FEATCRD for the location code of determine which battery is connected to which
the dual battery charger and carrier card if it is not embedded IOA use the bus number of the IOA with
listed in the serviceable event or if you are working the symbolic FRU CACHBAT.
failing item list here.
Failing Item: See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
v BACKPLN
listed in the serviceable event or if you are working the
v STORIOA failing item list here.
Failing Item:
57B54160 57B54160
v BACKPLN
Explanation: I/O adapter detected and recovered a v STORIOA
PCI bus error
Response: If this event appears in a serviceable event 57B58008 57B58008
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no Explanation: A permanent cache battery pack failure
service action is required. occurred
If you are working with one of the card types below, Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the may not represent an error that requires a service
card type to identify the physical parts of the storage action. Depending on the configuration of the system,
adapter. the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
Card type 2BE1 (feature RAID enablement card for attachment of OEM Storage that emulates a Load
embedded IOA) read the following: When working the Source drive. If this is the case, this error will be posted
FRUs from the serviceable event or the failing item list each time the IOA is IPLed and it can be ignored.
here, the embedded storage adapter (STORIOA) has
three physical parts: If you are working with one of the card types below,
the adapter has mulitple physical parts. Choose the
v The embedded storage adapter on the I/O
card type to identify the physical parts of the storage
backplane.
adapter.
v The RAID enablement card.
Card type 2BE1 (feature RAID enablement card for
v The Battery charger and carrier card.
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
See symbolic FRU FEATCRD for the location codes of
here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event
three physical parts:
or if you are working the failing item list here.
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When v The RAID enablement card.
working the FRUs from the serviceable event or the v The Battery charger and carrier card.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
See symbolic FRU FEATCRD for the location codes of here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event three physical parts:
or if you are working the failing item list here. v The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
v The RAID enablement card.
card) read the following: When working the FRUs from
the serviceable event or the failing item list here, the v The Battery charger and carrier card.
embedded storage adapter (STORIOA) has two
physical parts: See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O
or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
See symbolic FRU FEATCRD for the location codes of working the FRUs from the serviceable event or the
the FRUs if they are not listed in the serviceable event failing item list here, the embedded storage adapter
or if you are working the failing item list here. (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane
backplane.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the v The Battery charger and carrier card.
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane.
Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card for the
determine which battery is connected to which embedded IOAs) read the following: When working
embedded IOA use the bus number of the IOA with the FRUs from the serviceable event or the failing item
symbolic FRU CACHBAT. list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location code of
v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not
backplane.
listed in the serviceable event or if you are working the
failing item list here. v The dual battery charger and carrier card. To
determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
v CACHBAT symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
v FEATCRD
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57B58009 57B58009 failing item list here.
Explanation: Impending cache battery pack failure Failing Item:
Failing Item: v PTFSRCH
v CACHBAT v STORIOA
Explanation: Licensed Internal Code error Explanation: IOA detected recoverable device bus
error
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts. Response: If this event appears in a serviceable event
Choose the card type to identify the physical parts of view, work with the failing item list found there. If this
the storage adapter. event does not appear in a serviceable event view, no
service action is required.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v SIP3150
v FI01105
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
57B58150 57B58150 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent failure occurred
Failing Item:
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v ANYBRDG
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
57B58151 57B58151
attachment of OEM Storage that emulates a Load
Source drive. If this is the case, this error will be posted Explanation: Licensed Internal Code error
each time the IOA is IPLed and it can be ignored.
Response: If you are working with one of the card
If you are working with one of the card types below, types below, the adapter has mulitple physical parts.
the adapter has mulitple physical parts. Choose the Choose the card type to identify the physical parts of
card type to identify the physical parts of the storage the storage adapter.
adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for embedded IOA) read the following: When working the
embedded IOA) read the following: When working the FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has three physical parts:
three physical parts: v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O backplane.
backplane. v The RAID enablement card.
v The RAID enablement card. v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
Card type 57CB (embedded IOA with 2BCF battery card for embedded IOA) read the following: When
card for embedded IOA) read the following: When working the FRUs from the serviceable event or the
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card for embedded IOA) read the following: When
the FRUs if they are not listed in the serviceable event
working the FRUs from the serviceable event or the
or if you are working the failing item list here.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of
have two physical parts:
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
v The dual battery charger and carrier card. To
Failing Item:
determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57B58302 57B58302
57B58301 57B58301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 2BE1 (feature RAID enablement card for
the FRUs if they are not listed in the serviceable event embedded IOA) read the following: When working the
or if you are working the failing item list here. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
Card type 57CB (embedded IOA with 2BCF battery three physical parts:
card for embedded IOA) read the following: When v The embedded storage adapter on the I/O
working the FRUs from the serviceable event or the backplane.
failing item list here, the embedded storage adapter
v The RAID enablement card.
(STORIOA) has two physical parts:
v The Battery charger and carrier card.
v The embedded storage adapter on the I/O
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here. card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working
v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item
backplane.
list here, the embedded storage adapters (STORIOA)
have two physical parts: v The Battery charger and carrier card.
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here.
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
v STORIOA determine which battery is connected to which
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57B58400 57B58400
Explanation: Licensed Internal Code error See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57B58404 57B58404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57B59001 57B59001
57B59000 57B59000
Explanation: Device configuration error
Explanation: Device error
Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
the storage adapter.
Failing Item:
57B59026 57B59026
v SIP3120
Explanation: Disk unit not found at required physical
location
57B59011 57B59011
Response: A previously exposed disk unit in an array
Explanation: Cache data belongs to devices other than
was not found at the required physical location.
those attached
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57B59027 57B59027
57B59020 57B59020
Explanation: Array not functional due to parity out of
Explanation: Two or more disk units missing from
synchronization
RAID-5 or RAID-6 array
Response: Array is or would become exposed and
Failing Item:
parity data is out of synchronization
v SIP3111
Failing Item:
v SIP3113
57B59021 57B59021
Explanation: Two or more disk units missing from
57B59028 57B59028
RAID-5 or RAID-6 array
Explanation: Maximum number of functional arrays
Failing Item:
has been exceeded
v SIP3111
Response: Reduce the number of arrays on this I/O
adapter. Either move all the devices in an array to
57B59022 57B59022 another I/O adapter that supports arrays, or stop an
Explanation: Two or more disk units missing from array on this I/O adapter.
RAID-5 or RAID-6 array Failing Item:
Failing Item: v SVCDOCS
v SIP3111
57B59029 57B59029
57B59023 57B59023 Explanation: Maximum number of functional array
Explanation: One or more array members not in members has been exceeded
required physical locations Response: Contact your next level of support.
Failing Item: Failing Item:
v SIP3112 v NEXTLVL
Failing Item:
57B59054 57B59054
v SIP3110
v FI02112 Explanation: IOA resources not available due to
previous problems
Card type 57CF (embedded IOAs on DASD backplane reference code to resolve the problem.
with 2BC2 dual battery charger and carrier card for the
If you cannot resolve the problem, contact your next
embedded IOAs) read the following: When working
level of support.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) Failing Item:
have two physical parts: v SVCDOCS
v The embedded storage adapter on the DASD
backplane.
57B59092 57B59092
v The dual battery charger and carrier card. To
determine which battery is connected to which Explanation: Disk unit requires initialization before
embedded IOA use the bus number of the IOA with use.
symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of v SIP3134
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the 57B59500 57B59500
failing item list here.
Explanation: Internal program error in driver code.
Failing Item:
Failing Item:
v FI01105
v PTFSRCH
v STORIOA
57B59903 57B59903
57B59083 57B59083
Explanation: Tape device information was logged.
Explanation: System log entry only. No service action
Informational event, no service required.
required.
57B5C000 57B5C000
57B59084 57B59084
Explanation: System log entry only. No service action
Explanation: System log entry only. No service action
required.
required.
Response: No action is required. This reference code
is logged for information only.
57B59090 57B59090
Explanation: Disk unit has been modified after the
57B5C402 57B5C402
last known status.
Explanation: Licensed Internal Code error
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this Response: Ask your next level of support for
I/O adapter. Other resources attached to the virtual assistance.
I/O processor may then need to be Varied On.
Failing Item:
If any reference codes are surfaced, use the new v PTFSRCH
reference code to resolve the problem.
If you cannot resolve the problem, contact your next 57B5FF3D 57B5FF3D
level of support.
Explanation: I/O adapter detected a recoverable error
Failing Item:
Response: If you are working with one of the card
v SVCDOCS
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57B59091 57B59091 the storage adapter.
Explanation: Incorrect hardware configuration change Card type 2BE1 (feature RAID enablement card for
detected embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Response: Use Hardware Service Manager to re-IPL
here, the embedded storage adapter (STORIOA) has
the virtual I/O processor that is associated with this
three physical parts:
I/O adapter. Other resources attached to the virtual
I/O processor may then need to be Varied On. v The embedded storage adapter on the I/O
backplane.
If any reference codes are surfaced, use the new
v The RAID enablement card.
Explanation: I/O adapter detected recoverable bus SVCDOCS, then do NOT replace the I/O adapter. This
error is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated
Response: If this event appears in a serviceable event
with this I/O adapter.
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no Failing Item:
service action is required. v SVCDOCS
Failing Item:
v PRIMIOA 57B78300 57B78300
v AUXIOA Explanation: IOA hardware or PCI bus error
v BACKPLN
Failing Item:
v AUXIOA
57B78150 57B78150
v ANYBRDG
Explanation: A permanent failure occurred v PTFSRCH
Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service 57B78301 57B78301
action. Depending on the configuration of the system,
the Storage IOA may have been altered and/or the Explanation: Not valid condition in Licensed Internal
Storage IOA Cache may have been disabled to allow Code
attachment of OEM Storage that emulates a Load Failing Item:
Source drive. If this is the case, this error will be posted
each time the IOA is IPLed and it can be ignored. v PTFSRCH
v AUXIOA
Failing Item:
v AUXIOA
57B78302 57B78302
v ANYBRDG
Explanation: Missing Licensed Internal Code
57B78151 57B78151 Response: Ensure that the code necessary to support
this I/O adapter is loaded.
Explanation: Licensed Internal Code error
Failing Item:
Failing Item:
v SVCDOCS
v PTFSRCH
v AUXIOA
v AUXIOA
57B79055 57B79055
57B78155 57B78155
Explanation: Write cache data is available for attached
Explanation: A permanent failure occurred storage IOA
Failing Item: Response: No service action required.
v PTFSRCH
v AUXIOA 57B79071 57B79071
Explanation: Link from IOA to auxiliary cache IOA
57B78156 57B78156 went operational
Explanation: A permanent failure occurred Response: No service action required.
Failing Item:
v PTFSRCH 57B79072 57B79072
v AUXIOA Explanation: Link from IOA to auxiliary cache IOA
went non-operational
57B78157 57B78157 Response: No service action required.
Explanation: I/O adapter card error
Response: Display the Service Action Log entry for
this SRC. If the Failing Item indicates I/O adapter, then
replace the I/O adapter. If the Failing Item indicates
57B79073 57B79073
Explanation: Multiple I/O adapters connected in a not
valid configuration
Failing Item:
v SIP3140
57B79076 57B79076
Explanation: Missing remote I/O adapter
Failing Item:
v SIP3147
v PRIMIOA
v AUXIOA
v BACKPLN
57B7FF3D 57B7FF3D
Explanation: I/O adapter detected recoverable error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v AUXIOA
v ANYBRDG
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
57B88008 57B88008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 57B88009 57B88009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 57B88100 57B88100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
57B88300 57B88300
Explanation: IOA hardware error or PCI bus error 57B88301 57B88301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
57B88302 57B88302
57B88400 57B88400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
57B88404 57B88404
v STORIOA
Explanation: System log entry only. No service action
required.
57B89001 57B89001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
57B89020 57B89020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 57B89021 57B89021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
57B89031 57B89031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
57B89026 57B89026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 57B89032 57B89032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
57B89027 57B89027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
57B89040 57B89040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
57B89091 57B89091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
57B89092 57B89092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
57B89500 57B89500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
57B89903 57B89903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
57B8C000 57B8C000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
Failing Item:
57C33000 57C33000
v DISKPWR
v DEVBPLN Explanation: A permanent failure occurred
v SASEXP Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57C31515 57C31515
the storage adapter.
Explanation: A fatal error occurred on power supply 1
Card type 2BE1 (feature RAID enablement card for
Problem determination: This SRC can be the result of embedded IOA) read the following: When working the
a loss of utility power, battery back up or UPS power FRUs from the serviceable event or the failing item list
to the I/O storage unit. The unit and power supply here, the embedded storage adapter (STORIOA) has
that detected the problem are in the FRU list of the three physical parts:
serviceable event. Before starting a repair action for this v The embedded storage adapter on the I/O
problem verify that utility power, BBU or UPS to the backplane.
unit was not interrupted at the time the SRC was
v The RAID enablement card.
logged. If there was an interruption to power at about
the same time then no service is required and this v The Battery charger and carrier card.
problem can be closed.
See symbolic FRU FEATCRD for the location codes of
Failing Item: the FRUs if they are not listed in the serviceable event
v DISKPWR or if you are working the failing item list here.
v DEVBPLN
Card type 57CB (embedded IOA with 2BCF battery
v SASEXP
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
57C31521 57C31521 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: A non-fatal error occurred on power
supply 2 v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v DISKPWR
v DEVBPLN See symbolic FRU FEATCRD for the location codes of
v SASEXP the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Failing Item:
57C34100 57C34100
v SIP3146
Explanation: Device bus fabric error
Failing Item:
v SIP3152
v SASCABL
57C34150 57C34150
v SASEXP
Explanation: I/O adapter detected PCI bus error
v DEVBPLN
v STORIOA Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
v FI01105
event does not appear in a serviceable event view, no
service action is required.
57C34101 57C34101
If you are working with one of the card types below,
Explanation: Temporary device bus fabric error the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
Failing Item: adapter.
v SIP3152
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
57C34102 57C34102 FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
Explanation: Internal device bus fabric performance
three physical parts:
degradation.
v The embedded storage adapter on the I/O
Failing Item: backplane.
v SIP3254 v The RAID enablement card.
v The Battery charger and carrier card.
57C34110 57C34110
See symbolic FRU FEATCRD for the location codes of
Explanation: Unsupported enclosure function detected
the FRUs if they are not listed in the serviceable event
Failing Item: or if you are working the failing item list here.
v SIP3145
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
57C34120 57C34120 working the FRUs from the serviceable event or the
Explanation: SAS cable VPD cannot be read. failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Failing Item:
v The embedded storage adapter on the I/O
v SASCABL backplane.
v The Battery charger and carrier card.
57C34121 57C34121
See symbolic FRU FEATCRD for the location codes of
Explanation: SAS cable is missing.
the FRUs if they are not listed in the serviceable event
Failing Item: or if you are working the failing item list here.
v SASCABL
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
57C34123 57C34123 embedded IOAs) read the following: When working
Explanation: Configuration error, invalid cable Vital the FRUs from the serviceable event or the failing item
Product Data. The storage controller detected invalid list here, the embedded storage adapters (STORIOA)
VPD on the SAS cable. This is most likely caused by a have two physical parts:
non IBM cable or a wrap plug. The system will v The embedded storage adapter on the DASD
continue to run. backplane.
Problem determination: Verify that wrap plugs have v The dual battery charger and carrier card. To
been removed and the cable is an IBM part. If the determine which battery is connected to which
problem persists contact your next level of support. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
Failing Item:
v SASCABL See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
See symbolic FRU FEATCRD for the location codes of Response: Under a certain configuration, this SRC
the FRUs if they are not listed in the serviceable event may not represent an error that requires a service
or if you are working the failing item list here. action. Depending on the configuration of the system,
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
Card type 57CB (embedded IOA with 2BCF battery
attachment of OEM Storage that emulates a Load
card for embedded IOA) read the following: When
Source drive. If this is the case, this error will be posted
working the FRUs from the serviceable event or the
each time the IOA is IPLed and it can be ignored.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: If you are working with one of the card types below,
v The embedded storage adapter on the I/O the adapter has mulitple physical parts. Choose the
backplane. card type to identify the physical parts of the storage
adapter.
v The Battery charger and carrier card.
Card type 2BE1 (feature RAID enablement card for
See symbolic FRU FEATCRD for the location codes of embedded IOA) read the following: When working the
the FRUs if they are not listed in the serviceable event FRUs from the serviceable event or the failing item list
or if you are working the failing item list here. here, the embedded storage adapter (STORIOA) has
three physical parts:
Card type 57CF (embedded IOAs on DASD backplane v The embedded storage adapter on the I/O
with 2BC2 dual battery charger and carrier card for the backplane.
embedded IOAs) read the following: When working
v The RAID enablement card.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CB (embedded IOA with 2BCF battery
embedded IOA use the bus number of the IOA with card) read the following: When working the FRUs from
symbolic FRU CACHBAT. the serviceable event or the failing item list here, the
embedded storage adapter (STORIOA) has two
physical parts:
v The embedded storage adapter on the I/O Card type 57CB (embedded IOA with 2BCF battery
backplane. card for embedded IOA) read the following: When
v The Battery charger and carrier card. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
See symbolic FRU FEATCRD for the location codes of (STORIOA) has two physical parts:
the FRUs if they are not listed in the serviceable event v The embedded storage adapter on the I/O
or if you are working the failing item list here. backplane.
v The Battery charger and carrier card.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card) read See symbolic FRU FEATCRD for the location codes of
the following: When working the FRUs from the the FRUs if they are not listed in the serviceable event
serviceable event or the failing item list here, the or if you are working the failing item list here.
embedded storage adapters (STORIOA) have two
physical parts: Card type 57CF (embedded IOAs on DASD backplane
v The embedded storage adapter on the DASD with 2BC2 dual battery charger and carrier card for the
backplane. embedded IOAs) read the following: When working
v The dual battery charger and carrier card. To the FRUs from the serviceable event or the failing item
determine which battery is connected to which list here, the embedded storage adapters (STORIOA)
embedded IOA use the bus number of the IOA with have two physical parts:
symbolic FRU CACHBAT. v The embedded storage adapter on the DASD
backplane.
See symbolic FRU FEATCRD for the location code of v The dual battery charger and carrier card. To
the dual battery charger and carrier card if it is not determine which battery is connected to which
listed in the serviceable event or if you are working the embedded IOA use the bus number of the IOA with
failing item list here. symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of
v CACHBAT
the dual battery charger and carrier card if it is not
v STORIOA listed in the serviceable event or if you are working the
v FEATCRD failing item list here.
Failing Item:
57C38009 57C38009 v PTFSRCH
Explanation: Impending cache battery pack failure v STORIOA
Failing Item:
v CACHBAT 57C38130 57C38130
Explanation: IOA detected recoverable device bus
57C38100 57C38100 error
Explanation: Licensed Internal Code error Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Response: If you are working with one of the card event does not appear in a serviceable event view, no
types below, the adapter has mulitple physical parts. service action is required.
Choose the card type to identify the physical parts of
the storage adapter. Failing Item:
v SIP3150
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list 57C38140 57C38140
here, the embedded storage adapter (STORIOA) has
Explanation: IOA detected recoverable device bus
three physical parts:
error
v The embedded storage adapter on the I/O
backplane. Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
v The RAID enablement card.
event does not appear in a serviceable event view, no
v The Battery charger and carrier card. service action is required.
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v SIP3150
or if you are working the failing item list here.
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of
have two physical parts:
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
v The dual battery charger and carrier card. To
Failing Item:
determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57C38302 57C38302
57C38301 57C38301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
Failing Item: v The dual battery charger and carrier card. To
v SVCDOCS determine which battery is connected to which
embedded IOA use the bus number of the IOA with
v STORIOA
symbolic FRU CACHBAT.
57C38400 57C38400 See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Explanation: Licensed Internal Code error
listed in the serviceable event or if you are working the
Failing Item: failing item list here.
v PTFSRCH Failing Item:
v FI01105
57C38404 57C38404 v STORIOA
Explanation: System log entry only. No service action
required. 57C39001 57C39001
Explanation: Device configuration error
57C39000 57C39000
Failing Item:
Explanation: Device error
v NEXTLVL
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
57C39002 57C39002
Choose the card type to identify the physical parts of
the storage adapter. Explanation: Device error
Card type 2BE1 (feature RAID enablement card for Failing Item:
embedded IOA) read the following: When working the v NEXTLVL
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
three physical parts: 57C39008 57C39008
v The embedded storage adapter on the I/O Explanation: I/O card does not support functions
backplane. expected by devices
v The RAID enablement card. Failing Item:
v The Battery charger and carrier card. v SIP3130
57C39026 57C39026
57C39011 57C39011
Explanation: Disk unit not found at required physical
Explanation: Cache data belongs to devices other than location
those attached
Response: A previously exposed disk unit in an array
Failing Item: was not found at the required physical location.
v NEXTLVL
Failing Item:
v NEXTLVL
57C39020 57C39020
Explanation: Two or more disk units missing from 57C39027 57C39027
RAID-5 or RAID-6 array
Explanation: Array not functional due to parity out of
Failing Item: synchronization
v SIP3111
Response: Array is or would become exposed and
parity data is out of synchronization
57C39021 57C39021
Failing Item:
Explanation: Two or more disk units missing from v SIP3113
RAID-5 or RAID-6 array
Failing Item: 57C39028 57C39028
v SIP3111
Explanation: Maximum number of functional arrays
has been exceeded
57C39022 57C39022
Response: Reduce the number of arrays on this I/O
Explanation: Two or more disk units missing from adapter. Either move all the devices in an array to
RAID-5 or RAID-6 array another I/O adapter that supports arrays, or stop an
array on this I/O adapter.
Failing Item:
v SIP3111 Failing Item:
v SVCDOCS
57C39023 57C39023
57C39029 57C39029
Explanation: One or more array members not in
required physical locations Explanation: Maximum number of functional array
members has been exceeded
Failing Item:
v SIP3112 Response: Contact your next level of support.
Failing Item:
57C39024 57C39024 v NEXTLVL
Explanation: Array member physical location conflicts
with another array 57C39030 57C39030
Failing Item: Explanation: Array no longer protected due to
v NEXTLVL missing or failed disk unit
Failing Item:
57C39025 57C39025 v SIP3110
Explanation: Incompatible device v FI02112
57C39052 57C39052
57C39032 57C39032
Explanation: Cache data exists for one or more
Explanation: A disk unit in an array is missing or modified devices
failed
Response: Contact your next level of support.
Response: The array is still protected, but the disk
unit should be replaced. Failing Item:
v NEXTLVL
Failing Item:
v SIP3110
57C39054 57C39054
v FI02112
Explanation: IOA resources not available due to
previous problems
57C39040 57C39040
Failing Item:
Explanation: Re-synchronization of array parity was
initiated v SIP3121
57C39072 57C39072
57C39042 57C39042
Explanation: Link from IOA to auxiliary or remote
Explanation: Background parity check corrected errors
IOA is non-operational
on disk unit
Response: No service action required.
Response: Call your next level of support to report
the problem.
57C39073 57C39073
Failing Item:
v NEXTLVL Explanation: Multiple I/O adapters connected in a not
valid configuration
57C39082 57C39082
57C39081 57C39081
Explanation: Device error
Explanation: Device error
Response: If you are working with one of the card
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
Choose the card type to identify the physical parts of
the storage adapter.
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has
three physical parts:
three physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The RAID enablement card.
v The RAID enablement card.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
list here, the embedded storage adapters (STORIOA)
have two physical parts:
have two physical parts:
v The embedded storage adapter on the DASD
v The embedded storage adapter on the DASD
backplane.
backplane.
57C39083 57C39083
57C39903 57C39903
Explanation: System log entry only. No service action
Explanation: Tape device information was logged.
required.
Informational event, no service required.
57C39084 57C39084
57C3C000 57C3C000
Explanation: System log entry only. No service action
Explanation: System log entry only. No service action
required.
required.
Response: No action is required. This reference code
57C39090 57C39090
is logged for information only.
Explanation: Disk unit has been modified after the
last known status.
57C3C402 57C3C402
Response: Use Hardware Service Manager to re-IPL
Explanation: Licensed Internal Code error
the virtual I/O processor that is associated with this
I/O adapter. Other resources attached to the virtual Response: Ask your next level of support for
I/O processor may then need to be Varied On. assistance.
If any reference codes are surfaced, use the new Failing Item:
reference code to resolve the problem. v PTFSRCH
If you cannot resolve the problem, contact your next
level of support. 57C3FF3D 57C3FF3D
Failing Item: Explanation: I/O adapter detected a recoverable error
v SVCDOCS
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
57C39091 57C39091 Choose the card type to identify the physical parts of
the storage adapter.
Explanation: Incorrect hardware configuration change
detected Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
Response: Use Hardware Service Manager to re-IPL
FRUs from the serviceable event or the failing item list
the virtual I/O processor that is associated with this
here, the embedded storage adapter (STORIOA) has
I/O adapter. Other resources attached to the virtual
three physical parts:
I/O processor may then need to be Varied On.
v The embedded storage adapter on the I/O
If any reference codes are surfaced, use the new backplane.
reference code to resolve the problem.
v The RAID enablement card.
If you cannot resolve the problem, contact your next v The Battery charger and carrier card.
level of support.
Failing Item: See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
v SVCDOCS
or if you are working the failing item list here.
57C3FFF4 57C3FFF4
Explanation: Device backplane problem
Failing Item:
v SASEXP
v SASCABL
v STORIOA
v DEVBPLN
Failing Item:
57C44080 57C44080
v SASCABL
Explanation: Storage controller thermal error. The
controller exceeded the maximum operating
temperature. 57C44150 57C44150
Problem determination: Verify that the storage Explanation: I/O adapter detected PCI bus error
controller is placed in a valid location for this type of Response: If this event appears in a serviceable event
controller and enclosure. Perform the procedure listed view, work with the failing item list found there. If this
in the failing items to determine the problem and event does not appear in a serviceable event view, no
corrective action. service action is required.
Failing Item: If you are working with one of the card types below,
v SIP3295 the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
57C44085 57C44085
Card type 2BE1 (feature RAID enablement card for
Explanation: Storage controller detected error. Contact
embedded IOA) read the following: When working the
your next level of support or hardware service provider
FRUs from the serviceable event or the failing item list
for more information before replacing any hardware.
here, the embedded storage adapter (STORIOA) has
Failing Item: three physical parts:
v NEXTLVL v The embedded storage adapter on the I/O
backplane.
57C44100 57C44100 v The RAID enablement card.
v The Battery charger and carrier card.
Explanation: Device bus fabric error
Failing Item: See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v SASCABL
v SASEXP Card type 57CB (embedded IOA with 2BCF battery
v DEVBPLN card for embedded IOA) read the following: When
v STORIOA working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
v FI01105
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
57C44101 57C44101 backplane.
Explanation: Temporary device bus fabric error v The Battery charger and carrier card.
Failing Item:
See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
57C44110 57C44110
Card type 57CF (embedded IOAs on DASD backplane
Explanation: Unsupported enclosure function detected with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
v SIP3145 list here, the embedded storage adapters (STORIOA)
have two physical parts:
57C44123 57C44123 v The embedded storage adapter on the DASD
backplane.
Explanation: Configuration error, invalid cable Vital
Product Data. The storage controller detected invalid v The dual battery charger and carrier card. To
VPD on the SAS cable. This is most likely caused by a determine which battery is connected to which
non IBM cable or a wrap plug. The system will embedded IOA use the bus number of the IOA with
continue to run. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of v The dual battery charger and carrier card. To
the dual battery charger and carrier card if it is not determine which battery is connected to which
listed in the serviceable event or if you are working the embedded IOA use the bus number of the IOA with
failing item list here. symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of
v BACKPLN the dual battery charger and carrier card if it is not
v STORIOA listed in the serviceable event or if you are working the
failing item list here.
57C44160 57C44160 Failing Item:
Explanation: I/O adapter detected and recovered a v BACKPLN
PCI bus error v STORIOA
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this 57C48008 57C48008
event does not appear in a serviceable event view, no
Explanation: A permanent cache battery pack failure
service action is required.
occurred
If you are working with one of the card types below,
Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the
may not represent an error that requires a service
card type to identify the physical parts of the storage
action. Depending on the configuration of the system,
adapter.
the Storage IOA may have been altered and/or the
Card type 2BE1 (feature RAID enablement card for Storage IOA Cache may have been disabled to allow
embedded IOA) read the following: When working the attachment of OEM Storage that emulates a Load
FRUs from the serviceable event or the failing item list Source drive. If this is the case, this error will be posted
here, the embedded storage adapter (STORIOA) has each time the IOA is IPLed and it can be ignored.
three physical parts:
If you are working with one of the card types below,
v The embedded storage adapter on the I/O the adapter has mulitple physical parts. Choose the
backplane. card type to identify the physical parts of the storage
v The RAID enablement card. adapter.
v The Battery charger and carrier card. Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
See symbolic FRU FEATCRD for the location codes of FRUs from the serviceable event or the failing item list
the FRUs if they are not listed in the serviceable event here, the embedded storage adapter (STORIOA) has
or if you are working the failing item list here. three physical parts:
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card) read the following: When working the FRUs from
the FRUs if they are not listed in the serviceable event
the serviceable event or the failing item list here, the
or if you are working the failing item list here.
embedded storage adapter (STORIOA) has two
physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane v The Battery charger and carrier card.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the See symbolic FRU FEATCRD for the location codes of
serviceable event or the failing item list here, the the FRUs if they are not listed in the serviceable event
embedded storage adapters (STORIOA) have two or if you are working the failing item list here.
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
Failing Item:
v CACHBAT See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 57C48141 57C48141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter Response: No action is required. This reference code
(STORIOA) has two physical parts: is logged for information only.
v The embedded storage adapter on the I/O
backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To Card type 57CF (embedded IOAs on DASD backplane
determine which battery is connected to which with 2BC2 dual battery charger and carrier card for the
embedded IOA use the bus number of the IOA with embedded IOAs) read the following: When working
symbolic FRU CACHBAT. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of have two physical parts:
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here.
v The dual battery charger and carrier card. To
Failing Item: determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
57C48157 57C48157 the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Explanation: I/O adapter card error failing item list here.
Response: The FRU list in the Service Action Log will Failing Item:
vary based on the conditions this event was logged for.
v SVCDOCS
Display the Service Action Log entry for this SRC. If v STORIOA
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates
SVCDOCS, then do NOT replace the I/O adapter. This 57C48300 57C48300
is a recoverable error. Use Hardware Service Manager
Explanation: IOA hardware error or PCI bus error
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the Response: If you are working with one of the card
virtual I/O processor may then need to be Varied On. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
If you are replacing the I/O adapter and you are
the storage adapter.
working with one of the card types below, the adapter
has mulitple physical parts. Choose the card type to Card type 2BE1 (feature RAID enablement card for
identify the physical parts of the storage adapter. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has
embedded IOA) read the following: When working the
three physical parts:
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CB (embedded IOA with 2BCF battery
failing item list here, the embedded storage adapter
card for embedded IOA) read the following: When
(STORIOA) has two physical parts:
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57C48302 57C48302
57C48301 57C48301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57C48400 57C48400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57C48404 57C48404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57C49001 57C49001
57C49000 57C49000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57C49002 57C49002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 57C49008 57C49008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 57C49010 57C49010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
57C49026 57C49026
Explanation: Disk unit not found at required physical
57C49011 57C49011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57C49020 57C49020
57C49027 57C49027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
57C49021 57C49021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
57C49028 57C49028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
57C49022 57C49022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
57C49032 57C49032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
57C49054 57C49054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
57C49070 57C49070
57C49040 57C49040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
57C49071 57C49071
Explanation: Link from IOA to auxiliary or remote
57C49041 57C49041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
57C49072 57C49072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
57C49042 57C49042
57C49073 57C49073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP3140
Failing Item:
v NEXTLVL
57C49074 57C49074
57C49051 57C49051
57C49075 57C49075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP3149
57C49052 57C49052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
57C49076 57C49076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP3147 57C49082 57C49082
Explanation: Device error
57C49081 57C49081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
57C49500 57C49500
v STORIOA
Explanation: Internal program error in driver code.
Failing Item:
57C64080 57C64080
v SASCABL
Explanation: Storage controller thermal error. The
controller exceeded the maximum operating
temperature. 57C64150 57C64150
Problem determination: Verify that the storage Explanation: I/O adapter detected PCI bus error
controller is placed in a valid location for this type of Response: If this event appears in a serviceable event
controller and enclosure. Perform the procedure listed view, work with the failing item list found there. If this
in the failing items to determine the problem and event does not appear in a serviceable event view, no
corrective action. service action is required.
Failing Item: If you are working with one of the card types below,
v SIP3295 the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
57C64085 57C64085
Card type 2BE1 (feature RAID enablement card for
Explanation: Storage controller detected error. Contact
embedded IOA) read the following: When working the
your next level of support or hardware service provider
FRUs from the serviceable event or the failing item list
for more information before replacing any hardware.
here, the embedded storage adapter (STORIOA) has
Failing Item: three physical parts:
v NEXTLVL v The embedded storage adapter on the I/O
backplane.
57C64100 57C64100 v The RAID enablement card.
v The Battery charger and carrier card.
Explanation: Device bus fabric error
Failing Item: See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v SASCABL
v SASEXP Card type 57CB (embedded IOA with 2BCF battery
v DEVBPLN card for embedded IOA) read the following: When
v STORIOA working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
v FI01105
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
57C64101 57C64101 backplane.
Explanation: Temporary device bus fabric error v The Battery charger and carrier card.
Failing Item:
See symbolic FRU FEATCRD for the location codes of
v SIP3152 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
57C64110 57C64110
Card type 57CF (embedded IOAs on DASD backplane
Explanation: Unsupported enclosure function detected with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
v SIP3145 list here, the embedded storage adapters (STORIOA)
have two physical parts:
57C64123 57C64123 v The embedded storage adapter on the DASD
backplane.
Explanation: Configuration error, invalid cable Vital
Product Data. The storage controller detected invalid v The dual battery charger and carrier card. To
VPD on the SAS cable. This is most likely caused by a determine which battery is connected to which
non IBM cable or a wrap plug. The system will embedded IOA use the bus number of the IOA with
continue to run. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of v The dual battery charger and carrier card. To
the dual battery charger and carrier card if it is not determine which battery is connected to which
listed in the serviceable event or if you are working the embedded IOA use the bus number of the IOA with
failing item list here. symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of
v BACKPLN the dual battery charger and carrier card if it is not
v STORIOA listed in the serviceable event or if you are working the
failing item list here.
57C64160 57C64160 Failing Item:
Explanation: I/O adapter detected and recovered a v BACKPLN
PCI bus error v STORIOA
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this 57C68008 57C68008
event does not appear in a serviceable event view, no
Explanation: A permanent cache battery pack failure
service action is required.
occurred
If you are working with one of the card types below,
Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the
may not represent an error that requires a service
card type to identify the physical parts of the storage
action. Depending on the configuration of the system,
adapter.
the Storage IOA may have been altered and/or the
Card type 2BE1 (feature RAID enablement card for Storage IOA Cache may have been disabled to allow
embedded IOA) read the following: When working the attachment of OEM Storage that emulates a Load
FRUs from the serviceable event or the failing item list Source drive. If this is the case, this error will be posted
here, the embedded storage adapter (STORIOA) has each time the IOA is IPLed and it can be ignored.
three physical parts:
If you are working with one of the card types below,
v The embedded storage adapter on the I/O the adapter has mulitple physical parts. Choose the
backplane. card type to identify the physical parts of the storage
v The RAID enablement card. adapter.
v The Battery charger and carrier card. Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
See symbolic FRU FEATCRD for the location codes of FRUs from the serviceable event or the failing item list
the FRUs if they are not listed in the serviceable event here, the embedded storage adapter (STORIOA) has
or if you are working the failing item list here. three physical parts:
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card) read the following: When working the FRUs from
the FRUs if they are not listed in the serviceable event
the serviceable event or the failing item list here, the
or if you are working the failing item list here.
embedded storage adapter (STORIOA) has two
physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane v The Battery charger and carrier card.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the See symbolic FRU FEATCRD for the location codes of
serviceable event or the failing item list here, the the FRUs if they are not listed in the serviceable event
embedded storage adapters (STORIOA) have two or if you are working the failing item list here.
physical parts:
v The embedded storage adapter on the DASD Card type 57CF (embedded IOAs on DASD backplane
backplane. with 2BC2 dual battery charger and carrier card for the
v The dual battery charger and carrier card. To embedded IOAs) read the following: When working
determine which battery is connected to which the FRUs from the serviceable event or the failing item
embedded IOA use the bus number of the IOA with list here, the embedded storage adapters (STORIOA)
symbolic FRU CACHBAT. have two physical parts:
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location code of backplane.
the dual battery charger and carrier card if it is not v The dual battery charger and carrier card. To
listed in the serviceable event or if you are working the determine which battery is connected to which
failing item list here. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
Failing Item:
v CACHBAT See symbolic FRU FEATCRD for the location code of
v STORIOA the dual battery charger and carrier card if it is not
v FEATCRD listed in the serviceable event or if you are working the
failing item list here.
Card type 57CB (embedded IOA with 2BCF battery 57C68141 57C68141
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Explanation: IOA detected recoverable device error
failing item list here, the embedded storage adapter Response: No action is required. This reference code
(STORIOA) has two physical parts: is logged for information only.
v The embedded storage adapter on the I/O
backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To Card type 57CF (embedded IOAs on DASD backplane
determine which battery is connected to which with 2BC2 dual battery charger and carrier card for the
embedded IOA use the bus number of the IOA with embedded IOAs) read the following: When working
symbolic FRU CACHBAT. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of have two physical parts:
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here.
v The dual battery charger and carrier card. To
Failing Item: determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
57C68157 57C68157 the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Explanation: I/O adapter card error failing item list here.
Response: The FRU list in the Service Action Log will Failing Item:
vary based on the conditions this event was logged for.
v SVCDOCS
Display the Service Action Log entry for this SRC. If v STORIOA
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates
SVCDOCS, then do NOT replace the I/O adapter. This 57C68300 57C68300
is a recoverable error. Use Hardware Service Manager
Explanation: IOA hardware error or PCI bus error
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the Response: If you are working with one of the card
virtual I/O processor may then need to be Varied On. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
If you are replacing the I/O adapter and you are
the storage adapter.
working with one of the card types below, the adapter
has mulitple physical parts. Choose the card type to Card type 2BE1 (feature RAID enablement card for
identify the physical parts of the storage adapter. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has
embedded IOA) read the following: When working the
three physical parts:
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CB (embedded IOA with 2BCF battery
failing item list here, the embedded storage adapter
card for embedded IOA) read the following: When
(STORIOA) has two physical parts:
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57C68302 57C68302
57C68301 57C68301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item backplane.
list here, the embedded storage adapters (STORIOA)
v The Battery charger and carrier card.
have two physical parts:
v The embedded storage adapter on the DASD See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here. v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
determine which battery is connected to which
v STORIOA
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57C68400 57C68400
See symbolic FRU FEATCRD for the location code of
Explanation: Licensed Internal Code error
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57C68404 57C68404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57C69001 57C69001
57C69000 57C69000 Explanation: Device configuration error
Explanation: Device error Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57C69002 57C69002
the storage adapter.
Explanation: Device error
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v NEXTLVL
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O 57C69008 57C69008
backplane. Explanation: I/O card does not support functions
v The RAID enablement card. expected by devices
v The Battery charger and carrier card. Failing Item:
v SIP3130
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. 57C69010 57C69010
Explanation: Cache data associated with attached
Card type 57CB (embedded IOA with 2BCF battery devices cannot be found
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the Failing Item:
v SIP3120
57C69026 57C69026
Explanation: Disk unit not found at required physical
57C69011 57C69011
location
Explanation: Cache data belongs to devices other than
Response: A previously exposed disk unit in an array
those attached
was not found at the required physical location.
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57C69020 57C69020
57C69027 57C69027
Explanation: Two or more disk units missing from
Explanation: Array not functional due to parity out of
RAID-5 or RAID-6 array
synchronization
Failing Item:
Response: Array is or would become exposed and
v SIP3111 parity data is out of synchronization
Failing Item:
57C69021 57C69021
v SIP3113
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
57C69028 57C69028
Failing Item:
Explanation: Maximum number of functional arrays
v SIP3111 has been exceeded
Response: Reduce the number of arrays on this I/O
57C69022 57C69022 adapter. Either move all the devices in an array to
Explanation: Two or more disk units missing from another I/O adapter that supports arrays, or stop an
RAID-5 or RAID-6 array array on this I/O adapter.
v SIP3111 v SVCDOCS
Explanation: One or more array members not in Explanation: Maximum number of functional array
required physical locations members has been exceeded
Failing Item:
57C69032 57C69032
v NEXTLVL
Explanation: A disk unit in an array is missing or
failed
57C69054 57C69054
Response: The array is still protected, but the disk
unit should be replaced. Explanation: IOA resources not available due to
previous problems
Failing Item:
Failing Item:
v SIP3110
v SIP3121
v FI02112
57C69070 57C69070
57C69040 57C69040
Explanation: System log entry only. No service action
Explanation: Re-synchronization of array parity was
required.
initiated
Response: No action required.
57C69071 57C69071
Explanation: Link from IOA to auxiliary or remote
57C69041 57C69041
IOA is operational
Explanation: Background array parity check detected
Response: No service action required.
and corrected errors
Response: Call your next level of support to report
57C69072 57C69072
the problem.
Explanation: Link from IOA to auxiliary or remote
Failing Item:
IOA is non-operational
v NEXTLVL
Response: No service action required.
57C69042 57C69042
57C69073 57C69073
Explanation: Background parity check corrected errors
on disk unit Explanation: Multiple I/O adapters connected in a not
valid configuration
Response: Call your next level of support to report
the problem. Failing Item:
v SIP3140
Failing Item:
v NEXTLVL
57C69074 57C69074
57C69051 57C69051
57C69075 57C69075
Explanation: Cache data exists for one or more
missing or failed devices Explanation: Incomplete multipath connection
between IOA and remote IOA
Failing Item:
Failing Item:
v SIP3132
v SIP3149
57C69052 57C69052
Explanation: Cache data exists for one or more
modified devices
Response: Contact your next level of support.
Failing Item:
57C69076 57C69076
v FI01105
Explanation: Missing auxiliary IOA or remote IOA
v STORIOA
Failing Item:
v SIP3147 57C69082 57C69082
Explanation: Device error
57C69081 57C69081
Response: If you are working with one of the card
Explanation: Device error types below, the adapter has mulitple physical parts.
Response: If you are working with one of the card Choose the card type to identify the physical parts of
types below, the adapter has mulitple physical parts. the storage adapter.
Choose the card type to identify the physical parts of Card type 2BE1 (feature RAID enablement card for
the storage adapter. embedded IOA) read the following: When working the
Card type 2BE1 (feature RAID enablement card for FRUs from the serviceable event or the failing item list
embedded IOA) read the following: When working the here, the embedded storage adapter (STORIOA) has
FRUs from the serviceable event or the failing item list three physical parts:
here, the embedded storage adapter (STORIOA) has v The embedded storage adapter on the I/O
three physical parts: backplane.
v The embedded storage adapter on the I/O v The RAID enablement card.
backplane. v The Battery charger and carrier card.
v The RAID enablement card.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
Card type 57CB (embedded IOA with 2BCF battery working the FRUs from the serviceable event or the
card for embedded IOA) read the following: When failing item list here, the embedded storage adapter
working the FRUs from the serviceable event or the (STORIOA) has two physical parts:
failing item list here, the embedded storage adapter v The embedded storage adapter on the I/O
(STORIOA) has two physical parts: backplane.
v The embedded storage adapter on the I/O v The Battery charger and carrier card.
backplane.
v The Battery charger and carrier card. See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
See symbolic FRU FEATCRD for the location codes of or if you are working the failing item list here.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Card type 57CF (embedded IOAs on DASD backplane embedded IOAs) read the following: When working
with 2BC2 dual battery charger and carrier card for the the FRUs from the serviceable event or the failing item
embedded IOAs) read the following: When working list here, the embedded storage adapters (STORIOA)
the FRUs from the serviceable event or the failing item have two physical parts:
list here, the embedded storage adapters (STORIOA) v The embedded storage adapter on the DASD
have two physical parts: backplane.
v The embedded storage adapter on the DASD v The dual battery charger and carrier card. To
backplane. determine which battery is connected to which
v The dual battery charger and carrier card. To embedded IOA use the bus number of the IOA with
determine which battery is connected to which symbolic FRU CACHBAT.
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
See symbolic FRU FEATCRD for the location code of listed in the serviceable event or if you are working the
the dual battery charger and carrier card if it is not failing item list here.
listed in the serviceable event or if you are working the Failing Item:
failing item list here.
v FI01105
57C69500 57C69500
v STORIOA
Explanation: Internal program error in driver code.
v The embedded storage adapter on the I/O contact your service provider.
backplane.
Failing Item:
v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event 57C734FF 57C734FF
or if you are working the failing item list here.
Explanation: Format in progress
Card type 57CF (embedded IOAs on DASD backplane Response: No action required. This reference code is
with 2BC2 dual battery charger and carrier card). When logged for information only.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapters
57C73601 57C73601
(STORIOA) have two physical parts:
v The embedded storage adapter on the DASD Explanation: System log entry only. No service action
backplane. required.
v The dual battery charger and carrier card. To
determine which battery is connected to which 57C74010 57C74010
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Explanation: Configuration error
Response: Incorrect connection between cascaded
See symbolic FRU FEATCRD for the location code of enclosures.
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the Failing Item:
failing item list here. v SIP3142
Failing Item:
v SIP4050 57C74020 57C74020
v SIP4053 v DEVBPLN
v SASCABL v STORIOA
v SASEXP v FI01105
Explanation: Multipath redundancy level increased Explanation: Temporary device bus fabric error
Explanation: System log entry only. No service action Explanation: Unsupported enclosure function detected
required.
Failing Item:
v SIP3145
57C74100 57C74100
Explanation: Device bus fabric error 57C74150 57C74150
Response: If you are working with one of the card Explanation: I/O adapter detected PCI bus error
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of Response: If this event appears in a serviceable event
the storage adapter. view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Card type 57CB (embedded IOA with 2BCF battery service action is required.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the If you are working with one of the card types below,
failing item list here, the embedded storage adapter the adapter has mulitple physical parts. Choose the
(STORIOA) has two physical parts: card type to identify the physical parts of the storage
adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
v The Battery charger and carrier card. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
See symbolic FRU FEATCRD for the location codes of here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event three physical parts:
or if you are working the failing item list here. v The embedded storage adapter on the I/O
backplane.
Card type 57CF (embedded IOAs on DASD backplane v The RAID enablement card.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location codes of v The RAID enablement card.
the FRUs if they are not listed in the serviceable event v The Battery charger and carrier card.
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
Card type 57CB (embedded IOA with 2BCF battery the FRUs if they are not listed in the serviceable event
card for embedded IOA) read the following: When or if you are working the failing item list here.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter Card type 57CB (embedded IOA with 2BCF battery
(STORIOA) has two physical parts: card for embedded IOA) read the following: When
v The embedded storage adapter on the I/O working the FRUs from the serviceable event or the
backplane. failing item list here, the embedded storage adapter
v The Battery charger and carrier card. (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of backplane.
the FRUs if they are not listed in the serviceable event v The Battery charger and carrier card.
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
Card type 57CF (embedded IOAs on DASD backplane the FRUs if they are not listed in the serviceable event
with 2BC2 dual battery charger and carrier card for the or if you are working the failing item list here.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
v The dual battery charger and carrier card. To have two physical parts:
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
Failing Item: the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
v BACKPLN
failing item list here.
v STORIOA
Failing Item:
v BACKPLN
57C74160 57C74160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
57C78008 57C78008
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this Explanation: A permanent cache battery pack failure
event does not appear in a serviceable event view, no occurred
service action is required. Response: Under a certain configuration, this SRC
If you are working with one of the card types below, may not represent an error that requires a service
the adapter has mulitple physical parts. Choose the action. Depending on the configuration of the system,
card type to identify the physical parts of the storage the Storage IOA may have been altered and/or the
adapter. Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has If you are working with one of the card types below,
three physical parts: the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
v The embedded storage adapter on the I/O
adapter.
backplane.
Card type 57CF (embedded IOAs on DASD backplane v The embedded storage adapter on the I/O
with 2BC2 dual battery charger and carrier card) read backplane.
the following: When working the FRUs from the v The Battery charger and carrier card.
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the DASD or if you are working the failing item list here.
backplane.
Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To
with 2BC2 dual battery charger and carrier card for the
determine which battery is connected to which
embedded IOAs) read the following: When working
embedded IOA use the bus number of the IOA with
the FRUs from the serviceable event or the failing item
symbolic FRU CACHBAT.
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here. v The dual battery charger and carrier card. To
determine which battery is connected to which
Failing Item:
embedded IOA use the bus number of the IOA with
v CACHBAT symbolic FRU CACHBAT.
v STORIOA
v FEATCRD See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57C78009 57C78009 failing item list here.
Explanation: Impending cache battery pack failure Failing Item:
Failing Item: v PTFSRCH
v CACHBAT v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O If you are replacing the I/O adapter and you are
backplane. working with one of the card types below, the adapter
v The RAID enablement card. has mulitple physical parts. Choose the card type to
identify the physical parts of the storage adapter.
v The Battery charger and carrier card.
Card type 2BE1 (feature RAID enablement card for
See symbolic FRU FEATCRD for the location codes of embedded IOA) read the following: When working the
the FRUs if they are not listed in the serviceable event FRUs from the serviceable event or the failing item list
or if you are working the failing item list here. here, the embedded storage adapter (STORIOA) has
three physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The embedded storage adapter on the I/O
card for embedded IOA) read the following: When backplane.
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the
v The embedded storage adapter on the DASD
failing item list here.
backplane.
Failing Item: v The dual battery charger and carrier card. To
v PTFSRCH determine which battery is connected to which
v STORIOA embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57C78157 57C78157 See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Response: The FRU list in the Service Action Log will failing item list here.
vary based on the conditions this event was logged for.
Failing Item:
Display the Service Action Log entry for this SRC. If v SVCDOCS
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the
virtual I/O processor may then need to be Varied On.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
Failing Item: v The dual battery charger and carrier card. To
determine which battery is connected to which
v SVCDOCS
embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
57C79008 57C79008
57C79025 57C79025
Explanation: I/O card does not support functions
expected by devices Explanation: Incompatible device
57C79027 57C79027
57C79020 57C79020
Explanation: Array not functional due to parity out of
Explanation: Two or more disk units missing from synchronization
RAID-5 or RAID-6 array
Response: Array is or would become exposed and
Failing Item: parity data is out of synchronization
v SIP3111
Failing Item:
v SIP3113
57C79021 57C79021
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
Failing Item:
v SIP3111
Explanation: Multiple I/O adapters connected in a not Card type 57CF (embedded IOAs on DASD backplane
valid configuration with 2BC2 dual battery charger and carrier card for the
Response: Multiple I/O adapters not capable of embedded IOAs) read the following: When working
similar functions or controlling the same set of devices. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
Failing Item: have two physical parts:
v SIP4041 v The embedded storage adapter on the DASD
backplane.
57C79075 57C79075 v The dual battery charger and carrier card. To
determine which battery is connected to which
Explanation: Incomplete multipath connection embedded IOA use the bus number of the IOA with
between IOA and remote IOA symbolic FRU CACHBAT.
Failing Item:
v SIP4049 See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57C79076 57C79076 failing item list here.
Explanation: Missing auxiliary IOA or remote IOA Failing Item:
Failing Item: v FI01105
v SIP4047 v STORIOA
Response: If you are working with one of the card Response: If you are working with one of the card
types below, the adapter has mulitple physical parts. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of Choose the card type to identify the physical parts of
the storage adapter. the storage adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
57C7FF3D 57C7FF3D
Explanation: I/O adapter detected a recoverable error
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O
backplane.
v The RAID enablement card.
v The Battery charger and carrier card.
v The embedded storage adapter on the I/O contact your service provider.
backplane.
Failing Item:
v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event 57CB34FF 57CB34FF
or if you are working the failing item list here.
Explanation: Format in progress
Card type 57CF (embedded IOAs on DASD backplane Response: No action required. This reference code is
with 2BC2 dual battery charger and carrier card). When logged for information only.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapters
57CB3601 57CB3601
(STORIOA) have two physical parts:
v The embedded storage adapter on the DASD Explanation: System log entry only. No service action
backplane. required.
v The dual battery charger and carrier card. To
determine which battery is connected to which 57CB4010 57CB4010
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Explanation: Configuration error
Response: Incorrect connection between cascaded
See symbolic FRU FEATCRD for the location code of enclosures.
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the Failing Item:
failing item list here. v SIP3142
Failing Item:
v SIP4050 57CB4020 57CB4020
v SIP4053 v DEVBPLN
v SASCABL v STORIOA
v SASEXP v FI01105
Explanation: Multipath redundancy level increased Explanation: Temporary device bus fabric error
Explanation: System log entry only. No service action Explanation: Unsupported enclosure function detected
required.
Failing Item:
v SIP3145
57CB4100 57CB4100
Explanation: Device bus fabric error 57CB4150 57CB4150
Response: If you are working with one of the card Explanation: I/O adapter detected PCI bus error
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of Response: If this event appears in a serviceable event
the storage adapter. view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Card type 57CB (embedded IOA with 2BCF battery service action is required.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the If you are working with one of the card types below,
failing item list here, the embedded storage adapter the adapter has mulitple physical parts. Choose the
(STORIOA) has two physical parts: card type to identify the physical parts of the storage
adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
v The Battery charger and carrier card. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
See symbolic FRU FEATCRD for the location codes of here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event three physical parts:
or if you are working the failing item list here. v The embedded storage adapter on the I/O
backplane.
Card type 57CF (embedded IOAs on DASD backplane v The RAID enablement card.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location codes of v The RAID enablement card.
the FRUs if they are not listed in the serviceable event v The Battery charger and carrier card.
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
Card type 57CB (embedded IOA with 2BCF battery the FRUs if they are not listed in the serviceable event
card for embedded IOA) read the following: When or if you are working the failing item list here.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter Card type 57CB (embedded IOA with 2BCF battery
(STORIOA) has two physical parts: card for embedded IOA) read the following: When
v The embedded storage adapter on the I/O working the FRUs from the serviceable event or the
backplane. failing item list here, the embedded storage adapter
v The Battery charger and carrier card. (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of backplane.
the FRUs if they are not listed in the serviceable event v The Battery charger and carrier card.
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
Card type 57CF (embedded IOAs on DASD backplane the FRUs if they are not listed in the serviceable event
with 2BC2 dual battery charger and carrier card for the or if you are working the failing item list here.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
v The dual battery charger and carrier card. To have two physical parts:
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
Failing Item: the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
v BACKPLN
failing item list here.
v STORIOA
Failing Item:
v BACKPLN
57CB4160 57CB4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
57CB8008 57CB8008
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this Explanation: A permanent cache battery pack failure
event does not appear in a serviceable event view, no occurred
service action is required. Response: Under a certain configuration, this SRC
If you are working with one of the card types below, may not represent an error that requires a service
the adapter has mulitple physical parts. Choose the action. Depending on the configuration of the system,
card type to identify the physical parts of the storage the Storage IOA may have been altered and/or the
adapter. Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has If you are working with one of the card types below,
three physical parts: the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
v The embedded storage adapter on the I/O
adapter.
backplane.
Card type 57CF (embedded IOAs on DASD backplane v The embedded storage adapter on the I/O
with 2BC2 dual battery charger and carrier card) read backplane.
the following: When working the FRUs from the v The Battery charger and carrier card.
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the DASD or if you are working the failing item list here.
backplane.
Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To
with 2BC2 dual battery charger and carrier card for the
determine which battery is connected to which
embedded IOAs) read the following: When working
embedded IOA use the bus number of the IOA with
the FRUs from the serviceable event or the failing item
symbolic FRU CACHBAT.
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here. v The dual battery charger and carrier card. To
determine which battery is connected to which
Failing Item:
embedded IOA use the bus number of the IOA with
v CACHBAT symbolic FRU CACHBAT.
v STORIOA
v FEATCRD See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57CB8009 57CB8009 failing item list here.
Explanation: Impending cache battery pack failure Failing Item:
Failing Item: v PTFSRCH
v CACHBAT v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O If you are replacing the I/O adapter and you are
backplane. working with one of the card types below, the adapter
v The RAID enablement card. has mulitple physical parts. Choose the card type to
identify the physical parts of the storage adapter.
v The Battery charger and carrier card.
Card type 2BE1 (feature RAID enablement card for
See symbolic FRU FEATCRD for the location codes of embedded IOA) read the following: When working the
the FRUs if they are not listed in the serviceable event FRUs from the serviceable event or the failing item list
or if you are working the failing item list here. here, the embedded storage adapter (STORIOA) has
three physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The embedded storage adapter on the I/O
card for embedded IOA) read the following: When backplane.
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the
v The embedded storage adapter on the DASD
failing item list here.
backplane.
Failing Item: v The dual battery charger and carrier card. To
v PTFSRCH determine which battery is connected to which
v STORIOA embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57CB8157 57CB8157 See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Response: The FRU list in the Service Action Log will failing item list here.
vary based on the conditions this event was logged for.
Failing Item:
Display the Service Action Log entry for this SRC. If v SVCDOCS
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the
virtual I/O processor may then need to be Varied On.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
Failing Item: v The dual battery charger and carrier card. To
determine which battery is connected to which
v SVCDOCS
embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
57CB9008 57CB9008
57CB9025 57CB9025
Explanation: I/O card does not support functions
expected by devices Explanation: Incompatible device
57CB9027 57CB9027
57CB9020 57CB9020
Explanation: Array not functional due to parity out of
Explanation: Two or more disk units missing from synchronization
RAID-5 or RAID-6 array
Response: Array is or would become exposed and
Failing Item: parity data is out of synchronization
v SIP3111
Failing Item:
v SIP3113
57CB9021 57CB9021
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
Failing Item:
v SIP3111
Explanation: Multiple I/O adapters connected in a not Card type 57CF (embedded IOAs on DASD backplane
valid configuration with 2BC2 dual battery charger and carrier card for the
Response: Multiple I/O adapters not capable of embedded IOAs) read the following: When working
similar functions or controlling the same set of devices. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
Failing Item: have two physical parts:
v SIP4041 v The embedded storage adapter on the DASD
backplane.
57CB9075 57CB9075 v The dual battery charger and carrier card. To
determine which battery is connected to which
Explanation: Incomplete multipath connection embedded IOA use the bus number of the IOA with
between IOA and remote IOA symbolic FRU CACHBAT.
Failing Item:
v SIP4049 See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57CB9076 57CB9076 failing item list here.
Explanation: Missing auxiliary IOA or remote IOA Failing Item:
Failing Item: v FI01105
v SIP4047 v STORIOA
Response: If you are working with one of the card Response: If you are working with one of the card
types below, the adapter has mulitple physical parts. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of Choose the card type to identify the physical parts of
the storage adapter. the storage adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
57CBFF3D 57CBFF3D
Explanation: I/O adapter detected a recoverable error
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O
backplane.
v The RAID enablement card.
v The Battery charger and carrier card.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The RAID enablement card.
card for embedded IOA) read the following: When v The Battery charger and carrier card.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter See symbolic FRU FEATCRD for the location codes of
(STORIOA) has two physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card) read the following: When working the FRUs from
See symbolic FRU FEATCRD for the location codes of the serviceable event or the failing item list here, the
the FRUs if they are not listed in the serviceable event embedded storage adapter (STORIOA) has two
or if you are working the failing item list here. physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane backplane.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item See symbolic FRU FEATCRD for the location codes of
list here, the embedded storage adapters (STORIOA) the FRUs if they are not listed in the serviceable event
have two physical parts: or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane. Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card) read
determine which battery is connected to which the following: When working the FRUs from the
embedded IOA use the bus number of the IOA with serviceable event or the failing item list here, the
symbolic FRU CACHBAT. embedded storage adapters (STORIOA) have two
physical parts:
See symbolic FRU FEATCRD for the location code of v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not backplane.
listed in the serviceable event or if you are working the v The dual battery charger and carrier card. To
failing item list here. determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
v BACKPLN
v STORIOA See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
57CC8008 57CC8008 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent cache battery pack failure
occurred Failing Item:
v CACHBAT
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v FEATCRD
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load 57CC8009 57CC8009
Source drive. If this is the case, this error will be posted Explanation: Impending cache battery pack failure
each time the IOA is IPLed and it can be ignored.
Failing Item:
If you are working with one of the card types below,
v CACHBAT
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter. 57CC8100 57CC8100
Card type 2BE1 (feature RAID enablement card for Explanation: Licensed Internal Code error
embedded IOA) read the following: When working the
Response: If you are working with one of the card
FRUs from the serviceable event or the failing item list
types below, the adapter has mulitple physical parts.
here, the embedded storage adapter (STORIOA) has
Choose the card type to identify the physical parts of
three physical parts:
the storage adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v SVCDOCS v STORIOA
v STORIOA v ANYBRDG
v PTFSRCH
57CC8300 57CC8300
Explanation: IOA hardware error or PCI bus error 57CC8301 57CC8301
Response: If you are working with one of the card Explanation: Not valid condition in Licensed Internal
types below, the adapter has mulitple physical parts. Code
Choose the card type to identify the physical parts of Response: If you are working with one of the card
the storage adapter. types below, the adapter has mulitple physical parts.
Card type 2BE1 (feature RAID enablement card for Choose the card type to identify the physical parts of
embedded IOA) read the following: When working the the storage adapter.
FRUs from the serviceable event or the failing item list Card type 2BE1 (feature RAID enablement card for
here, the embedded storage adapter (STORIOA) has embedded IOA) read the following: When working the
three physical parts: FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has FRUs from the serviceable event or the failing item list
three physical parts: here, the embedded storage adapter (STORIOA) has
v The embedded storage adapter on the I/O three physical parts:
backplane. v The embedded storage adapter on the I/O
v The RAID enablement card. backplane.
v The Battery charger and carrier card. v The RAID enablement card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Card type 57CB (embedded IOA with 2BCF battery
working the FRUs from the serviceable event or the card for embedded IOA) read the following: When
failing item list here, the embedded storage adapter working the FRUs from the serviceable event or the
(STORIOA) has two physical parts: failing item list here, the embedded storage adapter
v The embedded storage adapter on the I/O (STORIOA) has two physical parts:
backplane. v The embedded storage adapter on the I/O
v The Battery charger and carrier card. backplane.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event See symbolic FRU FEATCRD for the location codes of
or if you are working the failing item list here. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Card type 57CF (embedded IOAs on DASD backplane
embedded IOAs) read the following: When working with 2BC2 dual battery charger and carrier card for the
the FRUs from the serviceable event or the failing item embedded IOAs) read the following: When working
list here, the embedded storage adapters (STORIOA) the FRUs from the serviceable event or the failing item
have two physical parts: list here, the embedded storage adapters (STORIOA)
v The embedded storage adapter on the DASD have two physical parts:
backplane. v The embedded storage adapter on the DASD
v The dual battery charger and carrier card. To backplane.
determine which battery is connected to which v The dual battery charger and carrier card. To
embedded IOA use the bus number of the IOA with determine which battery is connected to which
symbolic FRU CACHBAT. embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not See symbolic FRU FEATCRD for the location code of
listed in the serviceable event or if you are working the the dual battery charger and carrier card if it is not
failing item list here. listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
v PTFSRCH Failing Item:
v STORIOA v SVCDOCS
v STORIOA
57CC8302 57CC8302
57CC8400 57CC8400
Explanation: Missing Licensed Internal Code
Explanation: Licensed Internal Code error
Response: Ensure that the code necessary to support
this I/O adapter is loaded. Failing Item:
If you are working with one of the card types below, v PTFSRCH
the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
v FI01105
57CC8404 57CC8404
v STORIOA
Explanation: System log entry only. No service action
required.
57CC9001 57CC9001
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v NEXTLVL
or if you are working the failing item list here.
57CC9020 57CC9020
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the Explanation: Two or more disk units missing from
embedded IOAs) read the following: When working RAID-5 or RAID-6 array
the FRUs from the serviceable event or the failing item
Failing Item:
list here, the embedded storage adapters (STORIOA)
have two physical parts: v SIP3111
v The embedded storage adapter on the DASD
backplane. 57CC9021 57CC9021
v The dual battery charger and carrier card. To Explanation: Two or more disk units missing from
determine which battery is connected to which RAID-5 or RAID-6 array
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Failing Item:
v SIP3111
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
failing item list here.
Failing Item:
Failing Item:
57CC9031 57CC9031
v SIP3110
v FI02112 Explanation: Automatic rebuild initiated for array
Response: Either a previous rebuild was interrupted
57CC9026 57CC9026 and was automatically restarted, or a hot spare disk
unit was used to automatically rebuild the array. Look
Explanation: Disk unit not found at required physical for other reference codes and take action on them.
location
Response: A previously exposed disk unit in an array 57CC9032 57CC9032
was not found at the required physical location.
Explanation: A disk unit in an array is missing or
Failing Item: failed
v NEXTLVL
Response: The array is still protected, but the disk
unit should be replaced.
57CC9027 57CC9027
Failing Item:
Explanation: Array not functional due to parity out of v SIP3110
synchronization
v FI02112
Response: Array is or would become exposed and
parity data is out of synchronization
57CC9040 57CC9040
Failing Item:
Explanation: Re-synchronization of array parity was
v SIP3113 initiated
Response: No action required.
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v FI01105 v FI01105
v STORIOA v STORIOA
If you cannot resolve the problem, contact your next Explanation: I/O adapter detected a recoverable error
level of support. Response: If you are working with one of the card
Failing Item: types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
v SVCDOCS
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
57CC9091 57CC9091
embedded IOA) read the following: When working the
Explanation: Incorrect hardware configuration change FRUs from the serviceable event or the failing item list
detected here, the embedded storage adapter (STORIOA) has
three physical parts:
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this v The embedded storage adapter on the I/O
I/O adapter. Other resources attached to the virtual backplane.
I/O processor may then need to be Varied On. v The RAID enablement card.
If any reference codes are surfaced, use the new v The Battery charger and carrier card.
reference code to resolve the problem.
See symbolic FRU FEATCRD for the location codes of
If you cannot resolve the problem, contact your next the FRUs if they are not listed in the serviceable event
level of support. or if you are working the failing item list here.
Failing Item:
Card type 57CB (embedded IOA with 2BCF battery
v SVCDOCS
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
57CC9092 57CC9092 failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Explanation: Disk unit requires initialization before
use. v The embedded storage adapter on the I/O
backplane.
Failing Item:
v The Battery charger and carrier card.
v SIP3134
See symbolic FRU FEATCRD for the location codes of
57CC9500 57CC9500 the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
Explanation: Internal program error in driver code.
Failing Item: Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
v PTFSRCH
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
57CC9903 57CC9903 list here, the embedded storage adapters (STORIOA)
have two physical parts:
Explanation: Tape device information was logged.
Informational event, no service required. v The embedded storage adapter on the DASD
backplane.
v The dual battery charger and carrier card. To
57CCC000 57CCC000 determine which battery is connected to which
Explanation: System log entry only. No service action embedded IOA use the bus number of the IOA with
required. symbolic FRU CACHBAT.
v The embedded storage adapter on the I/O Card type 2BE1 (feature RAID enablement card for
backplane. embedded IOA) read the following: When working the
v The RAID enablement card. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
v The Battery charger and carrier card. three physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. v The RAID enablement card.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When See symbolic FRU FEATCRD for the location codes of
working the FRUs from the serviceable event or the the FRUs if they are not listed in the serviceable event
failing item list here, the embedded storage adapter or if you are working the failing item list here.
(STORIOA) has two physical parts:
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v BACKPLN v PTFSRCH
v STORIOA v STORIOA
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of
have two physical parts:
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
v The dual battery charger and carrier card. To
Failing Item:
determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57CD8302 57CD8302
57CD8301 57CD8301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
Failing Item: v The dual battery charger and carrier card. To
v SVCDOCS determine which battery is connected to which
embedded IOA use the bus number of the IOA with
v STORIOA
symbolic FRU CACHBAT.
57CD8400 57CD8400 See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Explanation: Licensed Internal Code error
listed in the serviceable event or if you are working the
Failing Item: failing item list here.
v PTFSRCH Failing Item:
v FI01105
57CD8404 57CD8404 v STORIOA
Explanation: System log entry only. No service action
required. 57CD9001 57CD9001
Explanation: Device configuration error
57CD9000 57CD9000
Failing Item:
Explanation: Device error
v NEXTLVL
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
57CD9002 57CD9002
Choose the card type to identify the physical parts of
the storage adapter. Explanation: Device error
Card type 2BE1 (feature RAID enablement card for Failing Item:
embedded IOA) read the following: When working the v NEXTLVL
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
three physical parts: 57CD9008 57CD9008
v The embedded storage adapter on the I/O Explanation: I/O card does not support functions
backplane. expected by devices
v The RAID enablement card. Failing Item:
v The Battery charger and carrier card. v SIP3130
57CD9026 57CD9026
57CD9011 57CD9011
Explanation: Disk unit not found at required physical
Explanation: Cache data belongs to devices other than location
those attached
Response: A previously exposed disk unit in an array
Failing Item: was not found at the required physical location.
v NEXTLVL
Failing Item:
v NEXTLVL
57CD9020 57CD9020
Explanation: Two or more disk units missing from 57CD9027 57CD9027
RAID-5 or RAID-6 array
Explanation: Array not functional due to parity out of
Failing Item: synchronization
v SIP3111
Response: Array is or would become exposed and
parity data is out of synchronization
57CD9021 57CD9021
Failing Item:
Explanation: Two or more disk units missing from v SIP3113
RAID-5 or RAID-6 array
Failing Item: 57CD9028 57CD9028
v SIP3111
Explanation: Maximum number of functional arrays
has been exceeded
57CD9022 57CD9022
Response: Reduce the number of arrays on this I/O
Explanation: Two or more disk units missing from adapter. Either move all the devices in an array to
RAID-5 or RAID-6 array another I/O adapter that supports arrays, or stop an
array on this I/O adapter.
Failing Item:
v SIP3111 Failing Item:
v SVCDOCS
57CD9023 57CD9023
57CD9029 57CD9029
Explanation: One or more array members not in
required physical locations Explanation: Maximum number of functional array
members has been exceeded
Failing Item:
v SIP3112 Response: Contact your next level of support.
Failing Item:
57CD9024 57CD9024 v NEXTLVL
Explanation: Array member physical location conflicts
with another array 57CD9030 57CD9030
Failing Item: Explanation: Array no longer protected due to
v NEXTLVL missing or failed disk unit
Failing Item:
57CD9025 57CD9025 v SIP3110
Explanation: Incompatible device v FI02112
57CD9052 57CD9052
57CD9032 57CD9032
Explanation: Cache data exists for one or more
Explanation: A disk unit in an array is missing or modified devices
failed
Response: Contact your next level of support.
Response: The array is still protected, but the disk
unit should be replaced. Failing Item:
v NEXTLVL
Failing Item:
v SIP3110
57CD9054 57CD9054
v FI02112
Explanation: IOA resources not available due to
previous problems
57CD9040 57CD9040
Failing Item:
Explanation: Re-synchronization of array parity was
initiated v SIP3121
57CD9072 57CD9072
57CD9042 57CD9042
Explanation: Link from IOA to auxiliary or remote
Explanation: Background parity check corrected errors
IOA is non-operational
on disk unit
Response: No service action required.
Response: Call your next level of support to report
the problem.
57CD9073 57CD9073
Failing Item:
v NEXTLVL Explanation: Multiple I/O adapters connected in a not
valid configuration
57CD9082 57CD9082
57CD9081 57CD9081
Explanation: Device error
Explanation: Device error
Response: If you are working with one of the card
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
Choose the card type to identify the physical parts of
the storage adapter.
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has
three physical parts:
three physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The RAID enablement card.
v The RAID enablement card.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O
backplane.
backplane.
v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
list here, the embedded storage adapters (STORIOA)
have two physical parts:
have two physical parts:
v The embedded storage adapter on the DASD
v The embedded storage adapter on the DASD
backplane.
backplane.
57CD9083 57CD9083
57CD9903 57CD9903
Explanation: System log entry only. No service action
Explanation: Tape device information was logged.
required.
Informational event, no service required.
57CD9084 57CD9084
57CDC000 57CDC000
Explanation: System log entry only. No service action
Explanation: System log entry only. No service action
required.
required.
Response: No action is required. This reference code
57CD9090 57CD9090
is logged for information only.
Explanation: Disk unit has been modified after the
last known status.
57CDC402 57CDC402
Response: Use Hardware Service Manager to re-IPL
Explanation: Licensed Internal Code error
the virtual I/O processor that is associated with this
I/O adapter. Other resources attached to the virtual Response: Ask your next level of support for
I/O processor may then need to be Varied On. assistance.
If any reference codes are surfaced, use the new Failing Item:
reference code to resolve the problem. v PTFSRCH
If you cannot resolve the problem, contact your next
level of support. 57CDFF3D 57CDFF3D
Failing Item: Explanation: I/O adapter detected a recoverable error
v SVCDOCS
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
57CD9091 57CD9091 Choose the card type to identify the physical parts of
the storage adapter.
Explanation: Incorrect hardware configuration change
detected Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
Response: Use Hardware Service Manager to re-IPL
FRUs from the serviceable event or the failing item list
the virtual I/O processor that is associated with this
here, the embedded storage adapter (STORIOA) has
I/O adapter. Other resources attached to the virtual
three physical parts:
I/O processor may then need to be Varied On.
v The embedded storage adapter on the I/O
If any reference codes are surfaced, use the new backplane.
reference code to resolve the problem.
v The RAID enablement card.
If you cannot resolve the problem, contact your next v The Battery charger and carrier card.
level of support.
Failing Item: See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
v SVCDOCS
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of v The embedded storage adapter on the I/O
the FRUs if they are not listed in the serviceable event backplane.
or if you are working the failing item list here. v The Battery charger and carrier card.
Card type 57CF (embedded IOAs on DASD backplane See symbolic FRU FEATCRD for the location codes of
with 2BC2 dual battery charger and carrier card for the the FRUs if they are not listed in the serviceable event
embedded IOAs) read the following: When working or if you are working the failing item list here.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) Card type 57CF (embedded IOAs on DASD backplane
have two physical parts: with 2BC2 dual battery charger and carrier card for the
v The embedded storage adapter on the DASD embedded IOAs) read the following: When working
backplane. the FRUs from the serviceable event or the failing item
v The dual battery charger and carrier card. To list here, the embedded storage adapters (STORIOA)
determine which battery is connected to which have two physical parts:
embedded IOA use the bus number of the IOA with v The embedded storage adapter on the DASD
symbolic FRU CACHBAT. backplane.
v The dual battery charger and carrier card. To
See symbolic FRU FEATCRD for the location code of determine which battery is connected to which
the dual battery charger and carrier card if it is not embedded IOA use the bus number of the IOA with
listed in the serviceable event or if you are working the symbolic FRU CACHBAT.
failing item list here.
Failing Item: See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
v BACKPLN
listed in the serviceable event or if you are working the
v STORIOA failing item list here.
Failing Item:
57CE4160 57CE4160
v BACKPLN
Explanation: I/O adapter detected and recovered a v STORIOA
PCI bus error
Response: If this event appears in a serviceable event 57CE8008 57CE8008
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no Explanation: A permanent cache battery pack failure
service action is required. occurred
If you are working with one of the card types below, Response: Under a certain configuration, this SRC
the adapter has mulitple physical parts. Choose the may not represent an error that requires a service
card type to identify the physical parts of the storage action. Depending on the configuration of the system,
adapter. the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
Card type 2BE1 (feature RAID enablement card for attachment of OEM Storage that emulates a Load
embedded IOA) read the following: When working the Source drive. If this is the case, this error will be posted
FRUs from the serviceable event or the failing item list each time the IOA is IPLed and it can be ignored.
here, the embedded storage adapter (STORIOA) has
three physical parts: If you are working with one of the card types below,
the adapter has mulitple physical parts. Choose the
v The embedded storage adapter on the I/O
card type to identify the physical parts of the storage
backplane.
adapter.
v The RAID enablement card.
Card type 2BE1 (feature RAID enablement card for
v The Battery charger and carrier card.
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
See symbolic FRU FEATCRD for the location codes of
here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event
three physical parts:
or if you are working the failing item list here.
v The embedded storage adapter on the I/O
Card type 57CB (embedded IOA with 2BCF battery backplane.
card for embedded IOA) read the following: When v The RAID enablement card.
working the FRUs from the serviceable event or the v The Battery charger and carrier card.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
See symbolic FRU FEATCRD for the location codes of here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event three physical parts:
or if you are working the failing item list here. v The embedded storage adapter on the I/O
backplane.
Card type 57CB (embedded IOA with 2BCF battery
v The RAID enablement card.
card) read the following: When working the FRUs from
the serviceable event or the failing item list here, the v The Battery charger and carrier card.
embedded storage adapter (STORIOA) has two
physical parts: See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the I/O
or if you are working the failing item list here.
backplane.
v The Battery charger and carrier card. Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When
See symbolic FRU FEATCRD for the location codes of working the FRUs from the serviceable event or the
the FRUs if they are not listed in the serviceable event failing item list here, the embedded storage adapter
or if you are working the failing item list here. (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
Card type 57CF (embedded IOAs on DASD backplane
backplane.
with 2BC2 dual battery charger and carrier card) read
the following: When working the FRUs from the v The Battery charger and carrier card.
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The embedded storage adapter on the DASD
backplane.
Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To with 2BC2 dual battery charger and carrier card for the
determine which battery is connected to which embedded IOAs) read the following: When working
embedded IOA use the bus number of the IOA with the FRUs from the serviceable event or the failing item
symbolic FRU CACHBAT. list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location code of
v The embedded storage adapter on the DASD
the dual battery charger and carrier card if it is not
backplane.
listed in the serviceable event or if you are working the
failing item list here. v The dual battery charger and carrier card. To
determine which battery is connected to which
Failing Item: embedded IOA use the bus number of the IOA with
v CACHBAT symbolic FRU CACHBAT.
v STORIOA
See symbolic FRU FEATCRD for the location code of
v FEATCRD
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57CE8009 57CE8009 failing item list here.
Explanation: Impending cache battery pack failure Failing Item:
Failing Item: v PTFSRCH
v CACHBAT v STORIOA
Explanation: Licensed Internal Code error Explanation: IOA detected recoverable device bus
error
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts. Response: If this event appears in a serviceable event
Choose the card type to identify the physical parts of view, work with the failing item list found there. If this
the storage adapter. event does not appear in a serviceable event view, no
service action is required.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the Failing Item:
FRUs from the serviceable event or the failing item list v SIP3150
v FI01105
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
57CE8150 57CE8150 listed in the serviceable event or if you are working the
failing item list here.
Explanation: A permanent failure occurred
Failing Item:
Response: Under a certain configuration, this SRC
may not represent an error that requires a service v STORIOA
action. Depending on the configuration of the system, v ANYBRDG
the Storage IOA may have been altered and/or the
Storage IOA Cache may have been disabled to allow
57CE8151 57CE8151
attachment of OEM Storage that emulates a Load
Source drive. If this is the case, this error will be posted Explanation: Licensed Internal Code error
each time the IOA is IPLed and it can be ignored.
Response: If you are working with one of the card
If you are working with one of the card types below, types below, the adapter has mulitple physical parts.
the adapter has mulitple physical parts. Choose the Choose the card type to identify the physical parts of
card type to identify the physical parts of the storage the storage adapter.
adapter.
Card type 2BE1 (feature RAID enablement card for
Card type 2BE1 (feature RAID enablement card for embedded IOA) read the following: When working the
embedded IOA) read the following: When working the FRUs from the serviceable event or the failing item list
FRUs from the serviceable event or the failing item list here, the embedded storage adapter (STORIOA) has
here, the embedded storage adapter (STORIOA) has three physical parts:
three physical parts: v The embedded storage adapter on the I/O
v The embedded storage adapter on the I/O backplane.
backplane. v The RAID enablement card.
v The RAID enablement card. v The Battery charger and carrier card.
v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of
See symbolic FRU FEATCRD for the location codes of the FRUs if they are not listed in the serviceable event
the FRUs if they are not listed in the serviceable event or if you are working the failing item list here.
or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery
Card type 57CB (embedded IOA with 2BCF battery card for embedded IOA) read the following: When
card for embedded IOA) read the following: When working the FRUs from the serviceable event or the
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter v The Battery charger and carrier card.
(STORIOA) has two physical parts:
v The embedded storage adapter on the I/O See symbolic FRU FEATCRD for the location codes of
backplane. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
v The Battery charger and carrier card.
Card type 57CB (embedded IOA with 2BCF battery
See symbolic FRU FEATCRD for the location codes of
card for embedded IOA) read the following: When
the FRUs if they are not listed in the serviceable event
working the FRUs from the serviceable event or the
or if you are working the failing item list here.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts:
Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
See symbolic FRU FEATCRD for the location code of
have two physical parts:
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
v The dual battery charger and carrier card. To
Failing Item:
determine which battery is connected to which
v PTFSRCH embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v STORIOA v PTFSRCH
v ANYBRDG v STORIOA
v PTFSRCH
57CE8302 57CE8302
57CE8301 57CE8301 Explanation: Missing Licensed Internal Code
Explanation: Not valid condition in Licensed Internal Response: Ensure that the code necessary to support
Code this I/O adapter is loaded.
Response: If you are working with one of the card If you are working with one of the card types below,
types below, the adapter has mulitple physical parts. the adapter has mulitple physical parts. Choose the
Choose the card type to identify the physical parts of card type to identify the physical parts of the storage
the storage adapter. adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 2BE1 (feature RAID enablement card for
the FRUs if they are not listed in the serviceable event embedded IOA) read the following: When working the
or if you are working the failing item list here. FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
Card type 57CB (embedded IOA with 2BCF battery three physical parts:
card for embedded IOA) read the following: When v The embedded storage adapter on the I/O
working the FRUs from the serviceable event or the backplane.
failing item list here, the embedded storage adapter
v The RAID enablement card.
(STORIOA) has two physical parts:
v The Battery charger and carrier card.
v The embedded storage adapter on the I/O
backplane.
See symbolic FRU FEATCRD for the location codes of
v The Battery charger and carrier card. the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event Card type 57CB (embedded IOA with 2BCF battery
or if you are working the failing item list here. card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the
Card type 57CF (embedded IOAs on DASD backplane failing item list here, the embedded storage adapter
with 2BC2 dual battery charger and carrier card for the (STORIOA) has two physical parts:
embedded IOAs) read the following: When working
v The embedded storage adapter on the I/O
the FRUs from the serviceable event or the failing item
backplane.
list here, the embedded storage adapters (STORIOA)
have two physical parts: v The Battery charger and carrier card.
v The embedded storage adapter on the DASD
See symbolic FRU FEATCRD for the location codes of
backplane.
the FRUs if they are not listed in the serviceable event
v The dual battery charger and carrier card. To or if you are working the failing item list here.
determine which battery is connected to which
embedded IOA use the bus number of the IOA with Card type 57CF (embedded IOAs on DASD backplane
symbolic FRU CACHBAT. with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working
See symbolic FRU FEATCRD for the location code of the FRUs from the serviceable event or the failing item
the dual battery charger and carrier card if it is not list here, the embedded storage adapters (STORIOA)
listed in the serviceable event or if you are working the have two physical parts:
failing item list here.
v The embedded storage adapter on the DASD
Failing Item: backplane.
v SVCDOCS v The dual battery charger and carrier card. To
v STORIOA determine which battery is connected to which
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57CE8400 57CE8400
Explanation: Licensed Internal Code error See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item: listed in the serviceable event or if you are working the
v PTFSRCH failing item list here.
Failing Item:
57CE8404 57CE8404 v FI01105
Explanation: System log entry only. No service action v STORIOA
required.
57CE9001 57CE9001
57CE9000 57CE9000
Explanation: Device configuration error
Explanation: Device error
Failing Item:
Response: If you are working with one of the card v NEXTLVL
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
the storage adapter.
Failing Item:
57CE9026 57CE9026
v SIP3120
Explanation: Disk unit not found at required physical
location
57CE9011 57CE9011
Response: A previously exposed disk unit in an array
Explanation: Cache data belongs to devices other than
was not found at the required physical location.
those attached
Failing Item:
Failing Item:
v NEXTLVL
v NEXTLVL
57CE9027 57CE9027
57CE9020 57CE9020
Explanation: Array not functional due to parity out of
Explanation: Two or more disk units missing from
synchronization
RAID-5 or RAID-6 array
Response: Array is or would become exposed and
Failing Item:
parity data is out of synchronization
v SIP3111
Failing Item:
v SIP3113
57CE9021 57CE9021
Explanation: Two or more disk units missing from
57CE9028 57CE9028
RAID-5 or RAID-6 array
Explanation: Maximum number of functional arrays
Failing Item:
has been exceeded
v SIP3111
Response: Reduce the number of arrays on this I/O
adapter. Either move all the devices in an array to
57CE9022 57CE9022 another I/O adapter that supports arrays, or stop an
Explanation: Two or more disk units missing from array on this I/O adapter.
RAID-5 or RAID-6 array Failing Item:
Failing Item: v SVCDOCS
v SIP3111
57CE9029 57CE9029
57CE9023 57CE9023 Explanation: Maximum number of functional array
Explanation: One or more array members not in members has been exceeded
required physical locations Response: Contact your next level of support.
Failing Item: Failing Item:
v SIP3112 v NEXTLVL
Failing Item:
57CE9054 57CE9054
v SIP3110
v FI02112 Explanation: IOA resources not available due to
previous problems
Card type 57CF (embedded IOAs on DASD backplane reference code to resolve the problem.
with 2BC2 dual battery charger and carrier card for the
If you cannot resolve the problem, contact your next
embedded IOAs) read the following: When working
level of support.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) Failing Item:
have two physical parts: v SVCDOCS
v The embedded storage adapter on the DASD
backplane.
57CE9092 57CE9092
v The dual battery charger and carrier card. To
determine which battery is connected to which Explanation: Disk unit requires initialization before
embedded IOA use the bus number of the IOA with use.
symbolic FRU CACHBAT.
Failing Item:
See symbolic FRU FEATCRD for the location code of v SIP3134
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the 57CE9500 57CE9500
failing item list here.
Explanation: Internal program error in driver code.
Failing Item:
Failing Item:
v FI01105
v PTFSRCH
v STORIOA
57CE9903 57CE9903
57CE9083 57CE9083
Explanation: Tape device information was logged.
Explanation: System log entry only. No service action
Informational event, no service required.
required.
57CEC000 57CEC000
57CE9084 57CE9084
Explanation: System log entry only. No service action
Explanation: System log entry only. No service action
required.
required.
Response: No action is required. This reference code
is logged for information only.
57CE9090 57CE9090
Explanation: Disk unit has been modified after the
57CEC402 57CEC402
last known status.
Explanation: Licensed Internal Code error
Response: Use Hardware Service Manager to re-IPL
the virtual I/O processor that is associated with this Response: Ask your next level of support for
I/O adapter. Other resources attached to the virtual assistance.
I/O processor may then need to be Varied On.
Failing Item:
If any reference codes are surfaced, use the new v PTFSRCH
reference code to resolve the problem.
If you cannot resolve the problem, contact your next 57CEFF3D 57CEFF3D
level of support.
Explanation: I/O adapter detected a recoverable error
Failing Item:
Response: If you are working with one of the card
v SVCDOCS
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
57CE9091 57CE9091 the storage adapter.
Explanation: Incorrect hardware configuration change Card type 2BE1 (feature RAID enablement card for
detected embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
Response: Use Hardware Service Manager to re-IPL
here, the embedded storage adapter (STORIOA) has
the virtual I/O processor that is associated with this
three physical parts:
I/O adapter. Other resources attached to the virtual
I/O processor may then need to be Varied On. v The embedded storage adapter on the I/O
backplane.
If any reference codes are surfaced, use the new
v The RAID enablement card.
v The embedded storage adapter on the I/O contact your service provider.
backplane.
Failing Item:
v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event 57CF34FF 57CF34FF
or if you are working the failing item list here.
Explanation: Format in progress
Card type 57CF (embedded IOAs on DASD backplane Response: No action required. This reference code is
with 2BC2 dual battery charger and carrier card). When logged for information only.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapters
57CF3601 57CF3601
(STORIOA) have two physical parts:
v The embedded storage adapter on the DASD Explanation: System log entry only. No service action
backplane. required.
v The dual battery charger and carrier card. To
determine which battery is connected to which 57CF4010 57CF4010
embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. Explanation: Configuration error
Response: Incorrect connection between cascaded
See symbolic FRU FEATCRD for the location code of enclosures.
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the Failing Item:
failing item list here. v SIP3142
Failing Item:
v SIP4050 57CF4020 57CF4020
v SIP4053 v DEVBPLN
v SASCABL v STORIOA
v SASEXP v FI01105
Explanation: Multipath redundancy level increased Explanation: Temporary device bus fabric error
Explanation: System log entry only. No service action Explanation: Unsupported enclosure function detected
required.
Failing Item:
v SIP3145
57CF4100 57CF4100
Explanation: Device bus fabric error 57CF4150 57CF4150
Response: If you are working with one of the card Explanation: I/O adapter detected PCI bus error
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of Response: If this event appears in a serviceable event
the storage adapter. view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Card type 57CB (embedded IOA with 2BCF battery service action is required.
card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the If you are working with one of the card types below,
failing item list here, the embedded storage adapter the adapter has mulitple physical parts. Choose the
(STORIOA) has two physical parts: card type to identify the physical parts of the storage
adapter.
v The embedded storage adapter on the I/O
backplane. Card type 2BE1 (feature RAID enablement card for
v The Battery charger and carrier card. embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
See symbolic FRU FEATCRD for the location codes of here, the embedded storage adapter (STORIOA) has
the FRUs if they are not listed in the serviceable event three physical parts:
or if you are working the failing item list here. v The embedded storage adapter on the I/O
backplane.
Card type 57CF (embedded IOAs on DASD backplane v The RAID enablement card.
with 2BC2 dual battery charger and carrier card for the v The Battery charger and carrier card.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location codes of v The RAID enablement card.
the FRUs if they are not listed in the serviceable event v The Battery charger and carrier card.
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
Card type 57CB (embedded IOA with 2BCF battery the FRUs if they are not listed in the serviceable event
card for embedded IOA) read the following: When or if you are working the failing item list here.
working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter Card type 57CB (embedded IOA with 2BCF battery
(STORIOA) has two physical parts: card for embedded IOA) read the following: When
v The embedded storage adapter on the I/O working the FRUs from the serviceable event or the
backplane. failing item list here, the embedded storage adapter
v The Battery charger and carrier card. (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O
See symbolic FRU FEATCRD for the location codes of backplane.
the FRUs if they are not listed in the serviceable event v The Battery charger and carrier card.
or if you are working the failing item list here.
See symbolic FRU FEATCRD for the location codes of
Card type 57CF (embedded IOAs on DASD backplane the FRUs if they are not listed in the serviceable event
with 2BC2 dual battery charger and carrier card for the or if you are working the failing item list here.
embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
v The dual battery charger and carrier card. To have two physical parts:
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
Failing Item: the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
v BACKPLN
failing item list here.
v STORIOA
Failing Item:
v BACKPLN
57CF4160 57CF4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
57CF8008 57CF8008
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this Explanation: A permanent cache battery pack failure
event does not appear in a serviceable event view, no occurred
service action is required. Response: Under a certain configuration, this SRC
If you are working with one of the card types below, may not represent an error that requires a service
the adapter has mulitple physical parts. Choose the action. Depending on the configuration of the system,
card type to identify the physical parts of the storage the Storage IOA may have been altered and/or the
adapter. Storage IOA Cache may have been disabled to allow
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has If you are working with one of the card types below,
three physical parts: the adapter has mulitple physical parts. Choose the
card type to identify the physical parts of the storage
v The embedded storage adapter on the I/O
adapter.
backplane.
Card type 57CF (embedded IOAs on DASD backplane v The embedded storage adapter on the I/O
with 2BC2 dual battery charger and carrier card) read backplane.
the following: When working the FRUs from the v The Battery charger and carrier card.
serviceable event or the failing item list here, the
embedded storage adapters (STORIOA) have two See symbolic FRU FEATCRD for the location codes of
physical parts: the FRUs if they are not listed in the serviceable event
v The embedded storage adapter on the DASD or if you are working the failing item list here.
backplane.
Card type 57CF (embedded IOAs on DASD backplane
v The dual battery charger and carrier card. To
with 2BC2 dual battery charger and carrier card for the
determine which battery is connected to which
embedded IOAs) read the following: When working
embedded IOA use the bus number of the IOA with
the FRUs from the serviceable event or the failing item
symbolic FRU CACHBAT.
list here, the embedded storage adapters (STORIOA)
have two physical parts:
See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not v The embedded storage adapter on the DASD
listed in the serviceable event or if you are working the backplane.
failing item list here. v The dual battery charger and carrier card. To
determine which battery is connected to which
Failing Item:
embedded IOA use the bus number of the IOA with
v CACHBAT symbolic FRU CACHBAT.
v STORIOA
v FEATCRD See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57CF8009 57CF8009 failing item list here.
Explanation: Impending cache battery pack failure Failing Item:
Failing Item: v PTFSRCH
v CACHBAT v STORIOA
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The RAID enablement card. v The RAID enablement card.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CB (embedded IOA with 2BCF battery Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When card for embedded IOA) read the following: When
working the FRUs from the serviceable event or the working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: (STORIOA) has two physical parts:
v The embedded storage adapter on the I/O v The embedded storage adapter on the I/O
backplane. backplane.
v The Battery charger and carrier card. v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. or if you are working the failing item list here.
Card type 57CF (embedded IOAs on DASD backplane Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the with 2BC2 dual battery charger and carrier card for the
embedded IOAs) read the following: When working embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) list here, the embedded storage adapters (STORIOA)
have two physical parts: have two physical parts:
v The embedded storage adapter on the DASD v The embedded storage adapter on the DASD
backplane. backplane.
v The dual battery charger and carrier card. To v The dual battery charger and carrier card. To
determine which battery is connected to which determine which battery is connected to which
embedded IOA use the bus number of the IOA with embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT. symbolic FRU CACHBAT.
See symbolic FRU FEATCRD for the location code of See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the listed in the serviceable event or if you are working the
failing item list here. failing item list here.
Failing Item: Failing Item:
v PTFSRCH v PTFSRCH
v STORIOA v STORIOA
v The embedded storage adapter on the I/O If you are replacing the I/O adapter and you are
backplane. working with one of the card types below, the adapter
v The RAID enablement card. has mulitple physical parts. Choose the card type to
identify the physical parts of the storage adapter.
v The Battery charger and carrier card.
Card type 2BE1 (feature RAID enablement card for
See symbolic FRU FEATCRD for the location codes of embedded IOA) read the following: When working the
the FRUs if they are not listed in the serviceable event FRUs from the serviceable event or the failing item list
or if you are working the failing item list here. here, the embedded storage adapter (STORIOA) has
three physical parts:
Card type 57CB (embedded IOA with 2BCF battery v The embedded storage adapter on the I/O
card for embedded IOA) read the following: When backplane.
working the FRUs from the serviceable event or the v The RAID enablement card.
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v The Battery charger and carrier card.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA) v The Battery charger and carrier card.
have two physical parts:
See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD
the FRUs if they are not listed in the serviceable event
backplane.
or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the
v The embedded storage adapter on the DASD
failing item list here.
backplane.
Failing Item: v The dual battery charger and carrier card. To
v PTFSRCH determine which battery is connected to which
v STORIOA embedded IOA use the bus number of the IOA with
symbolic FRU CACHBAT.
57CF8157 57CF8157 See symbolic FRU FEATCRD for the location code of
Explanation: I/O adapter card error the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
Response: The FRU list in the Service Action Log will failing item list here.
vary based on the conditions this event was logged for.
Failing Item:
Display the Service Action Log entry for this SRC. If v SVCDOCS
the Failing Item indicates an I/O adapter, then replace
the I/O adapter. If the Failing Item indicates v STORIOA
SVCDOCS, then do NOT replace the I/O adapter. This
is a recoverable error. Use Hardware Service Manager
to re-IPL the virtual I/O processor that is associated
with this I/O adapter. Other resources attached to the
virtual I/O processor may then need to be Varied On.
See symbolic FRU FEATCRD for the location codes of Card type 57CB (embedded IOA with 2BCF battery
the FRUs if they are not listed in the serviceable event card for embedded IOA) read the following: When
or if you are working the failing item list here. working the FRUs from the serviceable event or the
failing item list here, the embedded storage adapter
Card type 57CF (embedded IOAs on DASD backplane (STORIOA) has two physical parts:
with 2BC2 dual battery charger and carrier card for the v The embedded storage adapter on the I/O
embedded IOAs) read the following: When working backplane.
the FRUs from the serviceable event or the failing item v The Battery charger and carrier card.
list here, the embedded storage adapters (STORIOA)
have two physical parts: See symbolic FRU FEATCRD for the location codes of
v The embedded storage adapter on the DASD the FRUs if they are not listed in the serviceable event
backplane. or if you are working the failing item list here.
v The dual battery charger and carrier card. To
determine which battery is connected to which Card type 57CF (embedded IOAs on DASD backplane
embedded IOA use the bus number of the IOA with with 2BC2 dual battery charger and carrier card for the
symbolic FRU CACHBAT. embedded IOAs) read the following: When working
the FRUs from the serviceable event or the failing item
See symbolic FRU FEATCRD for the location code of list here, the embedded storage adapters (STORIOA)
the dual battery charger and carrier card if it is not have two physical parts:
listed in the serviceable event or if you are working the v The embedded storage adapter on the DASD
failing item list here. backplane.
Failing Item: v The dual battery charger and carrier card. To
determine which battery is connected to which
v SVCDOCS
embedded IOA use the bus number of the IOA with
v STORIOA symbolic FRU CACHBAT.
57CF9008 57CF9008
57CF9025 57CF9025
Explanation: I/O card does not support functions
expected by devices Explanation: Incompatible device
57CF9027 57CF9027
57CF9020 57CF9020
Explanation: Array not functional due to parity out of
Explanation: Two or more disk units missing from synchronization
RAID-5 or RAID-6 array
Response: Array is or would become exposed and
Failing Item: parity data is out of synchronization
v SIP3111
Failing Item:
v SIP3113
57CF9021 57CF9021
Explanation: Two or more disk units missing from
RAID-5 or RAID-6 array
Failing Item:
v SIP3111
Explanation: Multiple I/O adapters connected in a not Card type 57CF (embedded IOAs on DASD backplane
valid configuration with 2BC2 dual battery charger and carrier card for the
Response: Multiple I/O adapters not capable of embedded IOAs) read the following: When working
similar functions or controlling the same set of devices. the FRUs from the serviceable event or the failing item
list here, the embedded storage adapters (STORIOA)
Failing Item: have two physical parts:
v SIP4041 v The embedded storage adapter on the DASD
backplane.
57CF9075 57CF9075 v The dual battery charger and carrier card. To
determine which battery is connected to which
Explanation: Incomplete multipath connection embedded IOA use the bus number of the IOA with
between IOA and remote IOA symbolic FRU CACHBAT.
Failing Item:
v SIP4049 See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
listed in the serviceable event or if you are working the
57CF9076 57CF9076 failing item list here.
Explanation: Missing auxiliary IOA or remote IOA Failing Item:
Failing Item: v FI01105
v SIP4047 v STORIOA
Response: If you are working with one of the card Response: If you are working with one of the card
types below, the adapter has mulitple physical parts. types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of Choose the card type to identify the physical parts of
the storage adapter. the storage adapter.
Card type 2BE1 (feature RAID enablement card for Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has here, the embedded storage adapter (STORIOA) has
three physical parts: three physical parts:
57CFFF3D 57CFFF3D
Explanation: I/O adapter detected a recoverable error
Response: If you are working with one of the card
types below, the adapter has mulitple physical parts.
Choose the card type to identify the physical parts of
the storage adapter.
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
FRUs from the serviceable event or the failing item list
here, the embedded storage adapter (STORIOA) has
three physical parts:
v The embedded storage adapter on the I/O
backplane.
v The RAID enablement card.
v The Battery charger and carrier card.
Explanation: A port failure was detected on port 0 v Check the Product Activity Log for other entries that
indicate interface problems and work those
Failing Item: problems.
v FCPORT v Check the device firmware level and apply the latest
v FCIOA PTFs.
v FCDEV v Check for LIC logs with major code 2E00. Contact
your next level of support with the information you
v OPT_CLN
have gathered.
Problem determination: IPL the IOP to retry the
57FC3121 57FC3121
device identification process. If the error persists then
Explanation: A port failure was detected on port 1 contact your service provider.
Failing Item: Failing Item:
v PTFSRCH
57FC8300 57FC8300
Explanation: IOA hardware error or PCI bus error
57FC34FF 57FC34FF
Failing Item:
Explanation: Format in progress
v FCIOA
Response: The device indicated that a format is in
v ANYBRDG
progress. When the format is complete, the device
should be usable. No action is required. This reference v PTFSRCH
code is logged for information only. v OPT_CLN
57FC8131 57FC8131
57FC9903 57FC9903
Explanation: Recovered Fibre Channel interface error
on port 1 Explanation: Tape device information was logged.
Informational event, no service required.
Response: No action required. This reference code is
logged for information only.
57FCB000 57FCB000
57FCC000 57FCC000
Explanation: System log entry only, no service action
required
Response: No action is required. This reference code
is logged for information only.
57FCC402 57FCC402
Explanation: Licensed Internal Code error
Failing Item:
v PTFSRCH
v STORIOA
57FF3140 57FF3140
v FI01140
Explanation: Bus is operational
v DEVBPLN
Response: This reference code and the 3120 reference
code that occurred before it require no service action
57FF3103 57FF3103
because SCSI bus 0 is now operational.
Explanation: Interface error
Response: Error occurred on SCSI bus 3. 57FF3141 57FF3141
v FI01140
v DEVBPLN 57FF3142 57FF3142
Explanation: Bus is operational
57FF3120 57FF3120 Response: This reference code and the 3122 reference
Explanation: Bus is not operational code that occurred before it require no service action
because SCSI bus 2 is now operational.
Response: Adding a device to SCSI bus 0 of the I/O
Adapter caused the bus to become not operational.
Remove the device. 57FF3143 57FF3143
Response: NOTE: If external devices are attached Explanation: System log entry only. No service action
check EXTSCSI and DEVTERM first. required.
Failing Item:
57FF4150 57FF4150
v FI02112
v STORIOA Explanation: I/O adapter detected PCI bus error
v FI01106 Response: If this event appears in a serviceable event
v FI01140 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
57FF3401 57FF3401
If you are working with one of the card types below,
Explanation: Device backplane problem the adapter has mulitple physical parts. Choose the
Failing Item: card type to identify the physical parts of the storage
adapter.
v DEVBPLN
Card type 2BE1 (feature RAID enablement card for
embedded IOA) read the following: When working the
57FF3405 57FF3405 FRUs from the serviceable event or the failing item list
Explanation: An error occurred during task here, the embedded storage adapter (STORIOA) has
initialization for a removable media device. This SRC is three physical parts:
logged when an error occurs and the removable media v The embedded storage adapter on the I/O
device driver cannot determine the device type or backplane.
model. v The RAID enablement card.
Response: Perform the following: v The Battery charger and carrier card.
v Check the Product Activity Log for other entries that
indicate interface problems and work those See symbolic FRU FEATCRD for the location codes of
problems. the FRUs if they are not listed in the serviceable event
v Check the device firmware level and apply the latest or if you are working the failing item list here.
PTFs.
Card type 57CB (embedded IOA with 2BCF battery
v Check for LIC logs with major code 2E00. Contact
card for embedded IOA) read the following: When
your next level of support with the information you
working the FRUs from the serviceable event or the
have gathered.
failing item list here, the embedded storage adapter
Problem determination: IPL the IOP to retry the (STORIOA) has two physical parts:
device identification process. If the error persists then v The embedded storage adapter on the I/O
contact your service provider. backplane.
Failing Item: v The Battery charger and carrier card.
v PTFSRCH
See symbolic FRU FEATCRD for the location codes of
the FRUs if they are not listed in the serviceable event
57FF34FF 57FF34FF or if you are working the failing item list here.
Explanation: A device on this adapter is being
formatted. Wait for the formatting to complete. Card type 57CF (embedded IOAs on DASD backplane
with 2BC2 dual battery charger and carrier card for the
Failing Item: embedded IOAs) read the following: When working
v SVCDOCS
the FRUs from the serviceable event or the failing item Card type 57CF (embedded IOAs on DASD backplane
list here, the embedded storage adapters (STORIOA) with 2BC2 dual battery charger and carrier card for the
have two physical parts: embedded IOAs) read the following: When working
v The embedded storage adapter on the DASD the FRUs from the serviceable event or the failing item
backplane. list here, the embedded storage adapters (STORIOA)
have two physical parts:
v The dual battery charger and carrier card. To
determine which battery is connected to which v The embedded storage adapter on the DASD
embedded IOA use the bus number of the IOA with backplane.
symbolic FRU CACHBAT. v The dual battery charger and carrier card. To
determine which battery is connected to which
See symbolic FRU FEATCRD for the location code of embedded IOA use the bus number of the IOA with
the dual battery charger and carrier card if it is not symbolic FRU CACHBAT.
listed in the serviceable event or if you are working the
failing item list here. See symbolic FRU FEATCRD for the location code of
the dual battery charger and carrier card if it is not
Failing Item:
listed in the serviceable event or if you are working the
v BACKPLN failing item list here.
v STORIOA
Failing Item:
v BACKPLN
57FF4160 57FF4160
v STORIOA
Explanation: I/O adapter detected and recovered a
PCI bus error
57FF8008 57FF8008
Response: If this event appears in a serviceable event
Explanation: A permanent cache battery pack failure
view, work with the failing item list found there. If this
occurred
event does not appear in a serviceable event view, no
service action is required. Response: NOTE: Under a certain configuration, this
SRC may not represent an error that requires a service
If you are working with one of the card types below,
action. Depending on the configuration of the system,
the adapter has mulitple physical parts. Choose the
the Storage IOA may have been altered and/or the
card type to identify the physical parts of the storage
Storage IOA Cache may have been disabled to allow
adapter.
attachment of OEM Storage that emulates a Load
Card type 2BE1 (feature RAID enablement card for Source drive. If this is the case, this error will be posted
embedded IOA) read the following: When working the each time the IOA is IPLed and it can be ignored.
FRUs from the serviceable event or the failing item list
Failing Item:
here, the embedded storage adapter (STORIOA) has
three physical parts: v CACHBAT
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The RAID enablement card. 57FF8009 57FF8009
v The Battery charger and carrier card. Explanation: Impending cache battery pack failure
See symbolic FRU FEATCRD for the location codes of Failing Item:
the FRUs if they are not listed in the serviceable event v CACHBAT
or if you are working the failing item list here.
57FF8100 57FF8100
Card type 57CB (embedded IOA with 2BCF battery
card for embedded IOA) read the following: When Explanation: Licensed Internal Code error
working the FRUs from the serviceable event or the
Failing Item:
failing item list here, the embedded storage adapter
(STORIOA) has two physical parts: v PTFSRCH
v The embedded storage adapter on the I/O v STORIOA
backplane.
v The Battery charger and carrier card. 57FF8130 57FF8130
Explanation: IOA detected recoverable device bus
See symbolic FRU FEATCRD for the location codes of
error
the FRUs if they are not listed in the serviceable event
or if you are working the failing item list here. Response: An error occurred on SCSI bus 0. No action
v SVCDOCS
57FF9002 57FF9002
Explanation: Device error
57FF8300 57FF8300
Response:
Explanation: IOA hardware error or PCI bus error
Failing Item:
Failing Item:
v IOPIP16
v STORIOA
v FI01105
v ANYBRDG
v STORIOA
v PTFSRCH
v FI01140
v BACKPLN
57FF8301 57FF8301
v FI01106
Explanation: Not valid condition in Licensed Internal
Code
57FF9008 57FF9008
Failing Item:
Explanation: I/O card does not support functions
v PTFSRCH
expected by devices
v STORIOA
Response:
57FF8400 57FF8400
57FF9010 57FF9010
Explanation: Licensed Internal Code error
Explanation: Cache data associated with attached
Failing Item: devices cannot be found
v PTFSRCH
Response:
Failing Item:
57FF8404 57FF8404
v IOPIP31
Explanation: System log entry only. No service action
required.
57FF9011 57FF9011
57FF9020 57FF9020
57FF9001 57FF9001
Explanation: Array not functional due to present
Explanation: Device configuration error
hardware configuration.
Response:
Response:
Failing Item:
Failing Item:
v IOPIP33
v IOPIP20
57FF9040 57FF9040
57FF9053 57FF9053
Explanation: Array protection temporarily suspended
Explanation: IOA resources not available due to
Response: No action required. Protection will be previous problems
automatically restarted.
Response: Take action on other reference codes which
have surfaced.
57FF9041 57FF9041
If you cannot get to SST or DST, and cannot perform a
Explanation: Background array parity check detected type A or B IPL, perform a type D IPL from removable
and corrected errors media. Look for Product Activity Log entries for other
reference codes and take action on them.
Response: Call your next level of support to report
the problem. Failing Item:
Failing Item: v SVCDOCS
v PTFSRCH
57FF9054 57FF9054
57FF9042 57FF9042 Explanation: IOA resources not available due to
previous problems
Explanation: An array parity error has been detected
and corrected Response: Power off the system and remove all new
or replacement disk units. IPL the system to DST. If
Response: Call your next level of support to report
you cannot perform a type A or B IPL, perform a type
the problem.
D IPL from removable media.
Failing Item:
Look for Product Activity Log entries for other
v NEXTLVL reference codes and take action on them.
Failing Item:
57FF9050 57FF9050
v SVCDOCS
Explanation: Required cache data cannot be located
for a disk unit.
57FF9070 57FF9070
Response:
Explanation: System log entry only. No service action
Failing Item: required.
v IOPIP30
57FF9071 57FF9071
57FF9051 57FF9051 Explanation: Link from IOA to auxiliary cache IOA
Explanation: Cache data exists for a missing or failed went operational
device Response: No service action required.
Response: If all configured units are missing, a 9054
reference code may appear in the product activity log.
If so, perform the action indicated for the 9054
reference code.
57FF9092 57FF9092
57FF9073 57FF9073
Explanation: Disk unit requires initialization before
Explanation: Incompatible or non-operational use.
auxiliary cache IOA attached
Response:
Response:
Failing Item:
Failing Item:
v IOPIP26
v IOPIP40
57FF9500 57FF9500
57FF9081 57FF9081
Explanation: Internal program error in driver code.
Explanation: Device error
Failing Item:
Failing Item:
v PTFSRCH
v FI01105
v STORIOA
57FF9902 57FF9902
Explanation: System log entry only. No service action
57FF9082 57FF9082
required.
Explanation: Device error
Response: 57FF9903 57FF9903
Failing Item: Explanation: Tape device information was logged.
v IOPIP16 Informational event, no service required.
v FI01105
v STORIOA 57FFC000 57FFC000
v FI01140 Explanation: System log entry only. No service action
v BACKPLN required.
v FI01106 Response: No action is required. This reference code
is logged for information only.
57FF9090 57FF9090
57FFC100 57FFC100
Explanation: Disk unit has been modified after the
last known status. Explanation: System log entry only. No service action
required.
Response: Re-IPL the system. If any reference codes
are surfaced, use the new reference code to resolve the Response: No action is required. This reference code
problem. is logged for information only.
If you cannot resolve the problem, contact your next
level of support. 57FFC402 57FFC402
Failing Item: Explanation: Licensed Internal Code error
v SVCDOCS Response: Ask your next level of support for
assistance.
57FF9091 57FF9091 Failing Item:
Explanation: Incorrect hardware configuration change v PTFSRCH
detected
Response: Re-IPL the system. If any reference codes
are surfaced, use the new reference code to resolve the
problem.
57FFFF3D 57FFFF3D
Explanation: I/O adapter detected a recoverable error
Failing Item:
v STORIOA
v ANYBRDG
57FFFF6D 57FFFF6D
Explanation: Recoverable system bus error
Failing Item:
v STORIOA
v ANYBRDG
v PTFSRCH
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
58B03100 58B03100 level of support.
58B0FFF4 58B0FFF4
58B04060 58B04060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
58B0FFF5 58B0FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
58B04061 58B04061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
58B04100 58B04100
58B0FFF6 58B0FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
58B0FFFB 58B0FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
58B0FFFC 58B0FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
58B0FFFD 58B0FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
58B23100 58B23100 level of support.
58B2FFF4 58B2FFF4
58B24060 58B24060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
58B2FFF5 58B2FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
58B24061 58B24061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
58B24100 58B24100
58B2FFF6 58B2FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
58B2FFFB 58B2FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
58B2FFFC 58B2FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
58B2FFFD 58B2FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
58B33100 58B33100 level of support.
58B3FFF4 58B3FFF4
58B34060 58B34060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
58B3FFF5 58B3FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
58B34061 58B34061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
58B34100 58B34100
58B3FFF6 58B3FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
58B3FFFB 58B3FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
58B3FFFC 58B3FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
58B3FFFD 58B3FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
58B43100 58B43100 level of support.
58B4FFF4 58B4FFF4
58B44060 58B44060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
58B4FFF5 58B4FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
58B44061 58B44061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
58B44100 58B44100
58B4FFF6 58B4FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
58B4FFFB 58B4FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
58B4FFFC 58B4FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
58B4FFFD 58B4FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
58B53100 58B53100 level of support.
58B5FFF4 58B5FFF4
58B54060 58B54060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
58B5FFF5 58B5FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
58B54061 58B54061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
58B54100 58B54100
58B5FFF6 58B5FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
58B5FFFB 58B5FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
58B5FFFC 58B5FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
58B5FFFD 58B5FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Response: No action required. This reference code is Explanation: Device Licensed Internal Code
logged for information only. Response: The device is not supported with the level
of code currently on the system. Contact your next
58B63100 58B63100 level of support.
58B6FFF4 58B6FFF4
58B64060 58B64060
Explanation: Disk device problem
Explanation: Multipath redundancy level reduced
Failing Item:
Response: A redundant disk unit connection has
failed. v DISKDRV
v STORIOA
Failing Item:
v SIP3153
58B6FFF5 58B6FFF5
v SASCABL
v SASEXP Explanation: Disk sector read error
Response: If this event appears in a serviceable event
58B64061 58B64061 view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
Explanation: Multipath redundancy level increased service action is required.
Response: A redundant disk unit connection has been Failing Item:
restored. No service action is required.
v DISKDRV
58B64100 58B64100
58B6FFF6 58B6FFF6
Explanation: Device bus fabric error
Explanation: Disk device detected recoverable error
Failing Item:
Response: If this event appears in a serviceable event
v SIP3152 view, work with the failing item list found there. If this
v SASCABL event does not appear in a serviceable event view, no
v SASEXP service action is required.
58B6FFFB 58B6FFFB
Explanation: SAS bus reset occurred
Response: No action required. This reference code is
logged for information only.
58B6FFFC 58B6FFFC
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
58B6FFFD 58B6FFFD
Explanation: Soft device bus error.
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v SIP3250
v DISKDRV
v STORIOA
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
59079210 59079210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
59079303 59079303
59079211 59079211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
59079304 59079304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
59079220 59079220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
59079310 59079310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
59079300 59079300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
59079321 59079321
59079500 59079500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
59079501 59079501
59079350 59079350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 59079800 59079800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
59079801 59079801
59079351 59079351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 59079802 59079802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
59079803 59079803
59079355 59079355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
59079899 59079899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
59079900 59079900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
59079901 59079901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
62589210 62589210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
62589303 62589303
62589211 62589211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
62589304 62589304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
62589220 62589220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
62589310 62589310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
62589300 62589300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
62589321 62589321
62589500 62589500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
62589501 62589501
62589350 62589350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 62589800 62589800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
62589801 62589801
62589351 62589351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 62589802 62589802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
62589803 62589803
62589355 62589355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
62589899 62589899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
62589900 62589900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
62589901 62589901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
62799210 62799210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
62799303 62799303
62799211 62799211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
62799304 62799304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
62799220 62799220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
62799310 62799310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
62799300 62799300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
62799321 62799321
62799500 62799500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
62799501 62799501
62799350 62799350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 62799800 62799800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
62799801 62799801
62799351 62799351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 62799802 62799802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
62799803 62799803
62799355 62799355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
62799899 62799899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
62799900 62799900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
62799901 62799901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6320C302 6320C302
6320C100 6320C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6320C303 6320C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6320C110 6320C110
Explanation: SCSI command timeout occurred 6320C332 6320C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6320C333 6320C333
Explanation: Incompatible media
6320C210 6320C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6320CFF6 6320CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6321C302 6321C302
6321C100 6321C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6321C303 6321C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6321C110 6321C110
Explanation: SCSI command timeout occurred 6321C332 6321C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6321C333 6321C333
Explanation: Incompatible media
6321C210 6321C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6321CFF6 6321CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
632BCFC5 632BCFC5
Explanation: Error reading virtual optical volume
632CC002 632CC002
632CC023 632CC023
Explanation: SCSI Selection or Reselection timeout
occurred Explanation: Unable to determine all device
capabilities or device characteristics are not supported
Response: Refer to the hosting partition for problem with the current LIC. Writes will be blocked for this
analysis. device. If a write is attempted, the device will be
marked failed.
632CC010 632CC010 Response: No action is required. This reference code
Explanation: Undefined sense key returned by device is logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6330C302 6330C302
6330C100 6330C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6330C303 6330C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6330C110 6330C110
Explanation: SCSI command timeout occurred 6330C332 6330C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6330C333 6330C333
Explanation: Incompatible media
6330C210 6330C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6330CFF6 6330CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6331C302 6331C302
6331C100 6331C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6331C303 6331C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6331C110 6331C110
Explanation: SCSI command timeout occurred 6331C332 6331C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6331C333 6331C333
Explanation: Incompatible media
6331C210 6331C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6331CFF6 6331CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6333C302 6333C302
6333C100 6333C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6333C303 6333C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6333C110 6333C110
Explanation: SCSI command timeout occurred 6333C332 6333C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6333C333 6333C333
Explanation: Incompatible media
6333C210 6333C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6333CFF6 6333CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6336C302 6336C302
6336C100 6336C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6336C303 6336C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6336C110 6336C110
Explanation: SCSI command timeout occurred 6336C332 6336C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6336C333 6336C333
Explanation: Incompatible media
6336C210 6336C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6336CFF6 6336CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
Notes:
1. If the system is available, use online diagnostic tests when possible.
2. Use the Hardware Service Manager (HSM) verify function (via DST or SST) and verify that the unit is
operating correctly.
3. Search the problem log (WRKPRB) for a recent optical storage entry that might assist in analyzing the
problem. The WRKPRB entry will provide a reference code that can be found in the following table.
If the system is available, attempt the failing operation again with an optical media that is known to be
good. Does the operation complete successfully?
Yes: The original optical media may be defective, or the problem may be intermittent. Attempt the
failing operation again with the original optical media to verify. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for word 1. These 8 characters are the
reference code. Find the reference code in the following table.
6337C302 6337C302
6337C100 6337C100
Explanation: Media or device error occurred
Explanation: SCSI Bus error occurred
Response: The device encountered an 'out of spare
Failing Item:
sectors' condition when writing to the media. The
v FI00870 media can no longer be written to but is still readable.
v CNVTCRD
Clean the optical drive and the media contained in the
v FI01106 drive.
v STORIOA
v MEDIA 6337C303 6337C303
v FI01141
Explanation: Media had an unknown format
v FI01140
Response: No action required. This reference code is
logged for information only.
6337C110 6337C110
Explanation: SCSI command timeout occurred 6337C332 6337C332
Failing Item: Explanation: Media or device error occurred
v FI00870
Response: The device encountered an 'out of spare
v CNVTCRD sectors' condition when writing to the media. The
v FI01106 media can no longer be written to but is still readable.
v STORIOA Clean the optical drive and the media contained in the
v MEDIA drive.
v FI01141
v FI01140 6337C333 6337C333
Explanation: Incompatible media
6337C210 6337C210
Response: Perform the following:
Explanation: Unxpected device condition 1. Verify that the disk has a supported format.
Response: The device successfully recovered from a 2. If the format is supported, clean the disk and
temporary error. attempt the failing operation again.
No action is required. This reference code is logged for
information only.
6337CFF6 6337CFF6
Explanation: Device successfully recovered from a
temporary error
Response: No action is required. This reference code
is logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63829210 63829210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63829303 63829303
63829211 63829211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63829304 63829304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63829220 63829220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63829310 63829310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63829300 63829300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63829321 63829321
63829500 63829500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63829501 63829501
63829350 63829350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63829800 63829800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63829801 63829801
63829351 63829351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63829802 63829802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63829803 63829803
63829355 63829355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63829899 63829899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63829900 63829900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63829901 63829901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63839210 63839210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63839303 63839303
63839211 63839211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63839304 63839304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63839220 63839220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63839310 63839310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63839300 63839300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63839321 63839321
63839500 63839500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63839501 63839501
63839350 63839350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63839800 63839800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63839801 63839801
63839351 63839351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63839802 63839802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63839803 63839803
63839355 63839355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63839899 63839899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63839900 63839900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63839901 63839901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63849210 63849210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63849303 63849303
63849211 63849211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63849304 63849304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63849220 63849220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63849310 63849310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63849300 63849300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63849321 63849321
63849500 63849500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63849501 63849501
63849350 63849350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63849800 63849800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63849801 63849801
63849351 63849351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63849802 63849802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63849803 63849803
63849355 63849355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63849899 63849899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63849900 63849900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63849901 63849901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63869210 63869210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63869303 63869303
63869211 63869211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63869304 63869304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63869220 63869220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63869310 63869310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63869300 63869300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63869321 63869321
63869500 63869500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63869501 63869501
63869350 63869350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63869800 63869800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63869801 63869801
63869351 63869351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63869802 63869802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63869803 63869803
63869355 63869355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63869899 63869899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63869900 63869900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63869901 63869901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63879210 63879210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63879303 63879303
63879211 63879211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63879304 63879304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63879220 63879220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63879310 63879310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63879300 63879300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63879321 63879321
63879500 63879500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63879501 63879501
63879350 63879350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63879800 63879800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63879801 63879801
63879351 63879351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63879802 63879802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63879803 63879803
63879355 63879355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63879899 63879899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63879900 63879900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63879901 63879901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63A09210 63A09210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63A09303 63A09303
63A09211 63A09211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63A09304 63A09304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63A09220 63A09220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63A09310 63A09310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63A09300 63A09300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63A09321 63A09321
63A09500 63A09500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63A09501 63A09501
63A09350 63A09350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63A09800 63A09800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63A09801 63A09801
63A09351 63A09351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63A09802 63A09802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63A09803 63A09803
63A09355 63A09355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63A09899 63A09899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63A09900 63A09900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63A09901 63A09901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
63A19210 63A19210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
63A19303 63A19303
63A19211 63A19211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
63A19304 63A19304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
63A19220 63A19220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
63A19310 63A19310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
63A19300 63A19300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
63A19321 63A19321
63A19500 63A19500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
63A19501 63A19501
63A19350 63A19350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 63A19800 63A19800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63A19801 63A19801
63A19351 63A19351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 63A19802 63A19802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
63A19803 63A19803
63A19355 63A19355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
63A19899 63A19899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
63A19900 63A19900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
63A19901 63A19901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
66073010 66073010
66073110 66073110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
6607FFF4 6607FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 6607FFFA 6607FFFA
6607FFFB 6607FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
6607FFFE 6607FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
67133010 67133010
67133110 67133110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
6713FFF4 6713FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 6713FFFA 6713FFFA
6713FFFB 6713FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
6713FFFE 6713FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
67143010 67143010
67143110 67143110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
6714FFF4 6714FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 6714FFFA 6714FFFA
6714FFFB 6714FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
6714FFFE 6714FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
67173010 67173010
67173110 67173110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
6717FFF4 6717FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 6717FFFA 6717FFFA
6717FFFB 6717FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
6717FFFE 6717FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
67183010 67183010
67183110 67183110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
6718FFF4 6718FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 6718FFFA 6718FFFA
6718FFFB 6718FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
6718FFFE 6718FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
67193010 67193010
67193110 67193110
Explanation: Disk device returned wrong response to
IOA Explanation: Disk bus interface error occurred
Explanation: A device replacement has occurred Explanation: Device or IOA Licensed Internal Code
Response: No action required. This reference code is Response: The device does not support a needed
logged for information only. attribute and is running with degraded performance.
Contact your next level of support.
Explanation: Disk media format not valid Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
Failing Item: event does not appear in a serviceable event view, no
v DISKDRV service action is required.
Failing Item:
6719FFF4 6719FFF4 v DISKDRV
Explanation: Disk device problem
Failing Item: 6719FFFA 6719FFFA
6719FFFB 6719FFFB
Explanation: SCSI bus reset occurred
Response: No action required. This reference code is
logged for information only.
6719FFFE 6719FFFE
Explanation: Temporary disk bus error
Response: If this event appears in a serviceable event
view, work with the failing item list found there. If this
event does not appear in a serviceable event view, no
service action is required.
Failing Item:
v DISKDRV
v STORIOA
v FI01106
v FI01140
Explanation: Synchronous-data-link-control
6A590C90 6A590C90
send-receive test failed
Explanation: Communications adapter card X.21 test
Failing Item:
failed
v FI00719
Failing Item:
v FI00718
v FI00719
v FI00718
6A590C50 6A590C50
Explanation: Binary synchronous control send-receive
6A590CA1 6A590CA1
test failed
Explanation: Communications adapter card test failed
Failing Item:
v FI00719 Failing Item:
v FI00718 v FI00719
v FI00718
6A590C53 6A590C53
6A590CC0 6A590CC0
Explanation: Binary synchronous control send-receive
test failed Explanation: Communications adapter card test failed
Failing Item: Failing Item:
v FI00719 v FI00719
v FI00718 v FI00718
6A59FFFF 6A59FFFF
6A590C70 6A590C70
Explanation: User suspected problem
Explanation: Communications adapter card test failed
Failing Item:
Failing Item:
v USER
v FI00719
v FI00718
6A590C80 6A590C80
Explanation: Communications adapter card test failed
Failing Item:
v FI00719
v FI00718
Failing Item:
v PTFSRCH
6B259903 6B259903
Explanation: Tape device information was logged.
Informational event, no service required.
Note: Use this table to handle reference codes that might be displayed during a type D IPL to install the
operating system. If you are not performing a type D IPL of the operating system, consult any error logs
found in the serviceable event view. If you cannot locate an error log in the serviceable event view that
corresponds with the failure, run a verification test for the tape unit.
1. Verify that the device has power.
2. Check the device for any error indications. Refer to the device service information to resolve any error
indications.
3. Clean the recording head in the tape device.
4. Attempt the failing operation again. Does the operation complete successfully?
Yes: You have corrected the problem. This ends the procedure.
No: Look at the 8 rightmost characters of the Data display for Function 11, which represent the
reference code. Find the reference code in the following list.
72079210 72079210 Refer to the tape unit service information for possible
information on diagnositic tests that can be run to
Explanation: Illegal or unsupported tape unit response isolate between hardware and media failures.
Failing Item: Failing Item:
v FI00871 v MEDIA
v FI01112 v FI00871
v PTFSRCH
72079303 72079303
72079211 72079211
Explanation: Gateway device failure
Explanation: Gateway device detected a bus protocol
Response: Use the gateway device service
error
documenation to analyze the problem.
Response: Use the gateway device service
Failing Item:
documentation to analyze the problem.
v FCGATE
Failing Item:
v FCGATE
72079304 72079304
v FCIOA
Explanation: Tape unit failure
v FI00871
v ANYFC Response: Before exchanging any parts, do the
following:
v FCCABLE
1. Ensure that the EKM server is operational and
v FI00872
properly configured.
v DEVTERM
2. Ensure that the mounted cartridge is in the EKM
server database.
72079220 72079220
Failing Item:
Explanation: Hardware configuration change detected v USER
Response: The tape device or tape library device has v FI00871
reported a configuration change that requires the I/O
processor to be reset. Reset the I/O processor before
72079310 72079310
using the device.
Explanation: Licensed Internal Code for the tape unit
is not correct
72079300 72079300
Failing Item:
Explanation: Tape unit failure
v PTFSRCH
Failing Item:
v FI00871
v FI00871
72079321 72079321
72079500 72079500
Explanation: Gateway device Licensed Internal Code
Explanation: Licensed Internal Code error
error
Response: If the system is operational, perform a
Response: Use the gateway device service
dump of the I/O processor data.
documenation to analyze the problem.
Failing Item:
Failing Item:
v PTFSRCH
v FCCODE
72079501 72079501
72079350 72079350
Explanation: Licensed Internal Code error
Explanation: Tape unit detected a read or write error
on tape medium Failing Item:
Response: A permanent read or write error occurred. v PTFSRCH
Clean the tape unit and retry the operation.
If cleaning the tape unit does not correct the problem, 72079800 72079800
exchange the tape media. Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
72079801 72079801
72079351 72079351 Explanation: System successfully recovered from
temporary I/O error
Explanation: Tape with excessive error rate was
mounted in tape device. Response: No action required. This reference code is
logged for information only.
Response: The tape unit detected that the mounted
tape cartridge has a history of excessive read and write
errors. It is recommended that you exchange the tape 72079802 72079802
cartridge.
Explanation: System successfully recovered from
Failing Item: temporary I/O error
v MEDIA Response: No action required. This reference code is
v TAPCLN logged for information only.
v FI00871
72079803 72079803
72079355 72079355 Explanation: System successfully recovered from
Explanation: The data format is incorrect; the tape temporary I/O error
cannot be read Response: No action required. This reference code is
Response: The tape unit has detected that the data logged for information only.
format on the tape media is not supported or that the
tape media is defective. Do the following before
exchanging any parts:
1. Initialize the tape to a different format.
2. Clean the tape unit.
72079899 72079899
Explanation: Problem analysis completed, the problem
has been corrected.
Response: This reference code is used for ending
Online Problem Analysis when no problem was found
or the problem was corrected.
72079900 72079900
Explanation: Licensed Internal Code for tape unit was
not upgraded
Response: The I/O processor loading of Licensed
Internal Code (LIC) to the programmable tape unit was
not completed.
The tape unit will continue to operate with the
previous LIC. You may do either of the following:
v Wait for next IPL when the system will attempt to
load the LIC for the tape drive again.
v Perform TUPIP04 to reset the IOP and the tape unit.
When the IOP is reset, if the device has the wrong
level of LIC, the IOP will attempt to load the new
LIC.
Failing Item:
v USER
72079901 72079901
Explanation: Tape performance statistics logged
Response: No action required. This reference code is
logged for information only.
A181D000 A181D000
Explanation: The hypervisor did not respond to a
ROLE or FAILOVER message. If the system hangs on
this progress code, perform isolation procedure
FSPSPC1.
A181D001 A181D001
Explanation: The hypervisor did not post an Xdown
interrupt when a reset/reload occurred. If the system
hangs on this progress code, perform isolation
procedure FSPSPC1.
A1A3C100 A1A3C100
Explanation: Invalid operational mode for remote
power on (wake onLAN)
Response: Check the service processor settings for
remote power on. If the system hangs on this progress
code, perform isolation procedure FSPSPC1.
Failing Item:
A2002426 A2002426
v SLOTUSE
Explanation: A problem occurred during the IPL of a
partition.
A2002300 A2002300
Response: The partition ID is in extended word one
Explanation: A problem occurred during the IPL of a
as LP=xxx in decimal format. The platform LIC for this
partition.
partition attempted an operation. There was a failure.
Response: The partition ID is in extended word one Contact your next level of support.
as LP=xxx in decimal format. A slot that was needed
Failing Item:
for the partition was unavailable. See the Symbolic FRU
SLOTUSE for more information on the cause of this v NEXTLVL
error.
Failing Item: A2002475 A2002475
v SLOTUSE Explanation: A problem occurred during the IPL of a
partition.
A2002310 A2002310 Response: The partition ID is in extended word one
as LP=xxx in decimal format. A slot that was needed
Explanation: A problem occurred during the IPL of a
for the partition was either empty or the device in the
partition.
slot has failed. See the Symbolic FRU SLOTUSE for
Response: The partition ID is in extended word one more information on the cause of this error.
as LP=xxx in decimal format. The platform LIC for this
If you have a RAID enablement card (CCIN 5709) on
partition attempted an operation. There was a failure.
your system, it will disable an embedded SCSI adapter.
Contact your next level of support.
If that embedded slot is called out in the error, you can
Failing Item: safely ignore this error.
v NEXTLVL Failing Item:
v SLOTUSE
A2002320 A2002320
Explanation: A problem occurred during the IPL of a A2002477 A2002477
partition.
Explanation: A problem occurred during the IPL of a
Response: The partition ID is in extended word one partition.
as LP=xxx in decimal format. The platform LIC for this
Response: No service action required.
partition attempted an operation. There was a failure.
Contact your next level of support.
A2002479 A2002479
Failing Item:
v NEXTLVL Explanation: A problem occurred during the IPL of a
partition.
A2D03001 A2D03001
A2008080 A2008080
Explanation: User-initiated RSCDUMP of RPA
Explanation: System log entry only, no service action partition's PFW content.
required
Response: No service action required.
Response: No service action required.
A2D03002 A2D03002
A2008108 A2008108
Explanation: User-initiated RSCDUMP of IBM i
Explanation: A problem occurred during the IPL of a partition's SLIC bootloader and PFW content.
partition.
Response: No service action required.
A2009010 A2009010
Explanation: A problem occurred during the IPL of a
partition.
A2009020 A2009020
Explanation: A problem occurred during the IPL of a
partition.
A2009030 A2009030
Explanation: A problem occurred during the IPL of a
partition.
A200B07B A200B07B
Explanation: System log entry only, no service action
required
Response: No service action required.
A200C220 A200C220
Explanation: A problem occurred during the IPL of a
partition.
A6000105 A6000105 Explanation: The system ASP has run out of disk
storage.
Explanation: More than one request to terminate the
system was issued Response: The out of storage condition in the system
ASP can be caused by an allocation failure in some
Failing Item: other system software. This could be a looping
v LICIP08 condition that continues to allocate storage. Contact
v AJDG301 your service representative for assistance with the Main
Storage Dump.
A6000106 A6000106
A6000231 A6000231
Explanation: Terminate Immediate data is not valid
v AJDG301
A6001104 A6001104
Explanation: Failure reading media or not install
A6001724 A6001724
media
Explanation: An attempt to create a segment failed
Response: Determine that correct install media is
loaded. If correct install media is installed, media could Response: The create could fail for two reasons:
be corrupt. Obtain another copy of the install media v A code problem. Perform the procedure indicated in
and re-attempt the install. If the install still fails, contact the failing item list.
your service representative.
v No free auxiliary storage on the system. Add
additional DASD if the create failed because no
A6001201 A6001201 auxiliary storage was available.
Explanation: Critical database segment could not be Failing Item:
created v LICIP08
Failing Item: v AJDG301
v LICIP08
v AJDG301 A6001730 A6001730
Explanation: An IPL is needed to restore system
A6001204 A6001204 performance
Explanation: Error in constraint enforcement Response: Licensed Internal Code has detected a
condition that is impacting system performance. System
Failing Item:
operation can continue, but system performance may
v LICIP08 be noticeably reduced until the next IPL.
v AJDG301
Look at the Product Activity Log entry, and find the
value at offset x'000180'. If the value equals x'00000122',
A6001210 A6001210 the error was caused by too much processor memory
being installed.
Explanation: Object not found in the in-use table
For more information, contact IBM Service Support.
Failing Item:
v LICIP08 Failing Item:
v AJDG301 v UPLF1
Explanation: Error in critical code sequence Explanation: LPAR service function directed a Main
Storage Dump.
Failing Item:
Response: Copy the current main storage dump to
v LICIP08
media. For more information on how to copy a Main
v AJDG301 Storage Dump, refer to Copying a main storage dump.
Failing Item:
A6001219 A6001219
v AJDG301
Explanation: A back leveled driver has been detected
Failing Item: A60041FC A60041FC
v LICIP08 Explanation: Installation of LIC failed
v AJDG301
Response: Words 12 and 13 of this SRC contain
additional diagnostic information.
A6001604 A6001604
Install LIC using physical media.
Explanation: Not able to create APPN task
To determine what caused the failure, collect SRC
Response: An error occurred during task creation information and contact your next level of support.
which requires a power off of the system.
Failing Item:
Failing Item: v SVCDOCS
v LICIP08
For more information on how to perform a Main Explanation: Insufficient space in the ASP to store a
Storage Dump, refer to Copying a main storage dump. platform dump
Response: The platform produced dump data, and the
A6004402 A6004402 Main Storage Dump (MSD) Manager was configured to
automatically copy the dump to an Auxiliary Storage
Explanation: Missing DASD units. Pool (ASP), but there was not sufficient free space
available in the ASP. The dump will be lost if the
Response: Copy the current main storage dump to
system power is lost. Manually copy the current
media. Then exit the Main Storage Dump Manager.
platform dump from the platform by performing one of
For more information on how to perform a Main the following:
Storage Dump, refer to Copying a main storage dump. v Make room in the designated ASP and then use the
MSD Manager to copy the current platform dump to
A6004403 A6004403 ASP.
v Use the MSD Manager to delete other dump copies,
Explanation: Storage Management failed to reach full
then copy the current platform dump to ASP.
paging.
v Use the MSD Manager to copy the current platform
Response: Copy the current main storage dump to dump to a different ASP.
media.
v Use the MSD Manager to copy the current platform
For more information on how to perform a Main dump to media.
Storage Dump, refer to Copying a main storage dump.
A6004422 A6004422
A6004404 A6004404
Explanation: A platform dump is saved in MSD
Explanation: Auto copy failed or not attempted. Manager
Response: Copy the current main storage dump. If Response: The platform produced dump data. The
copying to system ASP, existing copies may need to be dump data was copied to the Main Storage Dump
deleted or renamed. Then exit the Main Storage Dump (MSD) Manager.
Manager.
Failing Item:
For more information on how to perform a Main v PLDUMP
Storage Dump, refer to Copying a main storage dump.
Contact your service provider. Response: Correct any Processor Capacity card or
SPCN failures.
Failing Item:
Failing Item:
v AJDG301
v CTLPNCD
A6004710 A6004710
A6004730 A6004730
Explanation: Processor On Demand error detected.
Explanation: Processor On Demand error detected.
Response: SPCN communication failure during
Processor On Demand. Response: Processor On Demand standby processors
are in use.
Look in the Product Activity Log for other SPCN errors
and perform the actions indicated for those errors. Contact your service provider.
v SPNLCRD v AJDG301
Explanation: Processor On Demand error detected. Explanation: Processor On Demand error detected.
Response: Correct any Processor Capacity card or Response: The Processor On Demand Trial Activation
SPCN failures. period is not valid. Contact your next level of support.
v CTLPNCD v AJDG301
Explanation: Incorrect Processor Capacity Card Explanation: Processor On Demand error detected.
installed. Response: Contact your service provider.
Response: The Processor Capacity Card is the failing Failing Item:
v AJDG301
v AJDG301
A6004740 A6004740
v FI00380
Explanation: Processor On Demand error detected.
Response: The Processor On Demand Activation code A6005003 A6005003
just entered is not valid.
Explanation: Service program failed
Contact your next level of support.
Response: The ASCII system console failed to
Failing Item: respond.
v AJDG301
Failing Item:
v FI00320
A6004741 A6004741
v FI00602
Explanation: Processor On Demand error detected. v USER
Response: An invalid Processor On Demand v AJDG301
Activation code has been entered more than 5 v FI00380
consecutive times. Contact your service provider.
Failing Item: A6005004 A6005004
v AJDG301
Explanation: DST console failed to respond
Response: The system console failed to respond.
A6004745 A6004745
Failing Item:
Explanation: Processor Capacity card replaced on
activated POD system. v RTRIP02
v FI00320
Response: Contact IBM Support to order a
replacement Processor On Demand activation code. v FI00602
v USER
A6004747 A6004747 v AJDG301
v FI00380
Explanation: 1 hour left in POD 14 day Trial
Activation Period.
A6005005 A6005005
Response: If a new activation code was purchased, it
should be entered now. Otherwise, the system will Explanation: Service program failed
revert back to its previous activation state at the end of
the Trial Activation Period. Response: The workstation adapter system console
failed to respond.
v AJDG301
A6005090 A6005090
v FI00380
Explanation: System startup failed in unattended IPL
mode
A6005008 A6005008
Response: Perform the following:
Explanation: DST console failed to respond
v If reference code A6xx5090 is displayed on the
Response: control panel for more than 10 minutes, perform the
procedure indicated in the failing item list.
Failing Item:
v For reference code B6xx5090, perform the procedure
v OPCIP03 indicated in the failing item list.
v FI00719
Failing Item:
v LICIP11
A6005010 A6005010
v FI00580
Explanation: IPL service function ended abnormally v FI00500
Failing Item: v FI00301
v LICIP04 v FI00021
v AJDG301 v FI00065
v AJDG301
A6005014 A6005014
Explanation: DST status. The Storage Management A6005092 A6005092
Dual Path Information Screen option to dump data to a Explanation: System is in DASD migration mode
PAL has completed successfully.
Response: Install Licensed Internal Code and Upgrade
Load Source was specified but the key is not in the
A6005015 A6005015 manual position. Change the key position to manual
Explanation: DST error. An error has occurred and perform a system IPL.
gathering data for the Storage Management Dual Path
Information Screen option to dump data to a PAL. A6005094 A6005094
Contact your next level of support or hardware service
provider. Explanation: IASP detected a failure during the vary
on operation
Failing Item:
v NEXTLVL Failing Item:
v LICIP12
A6005082 A6005082
A60050FF A60050FF
Explanation: DST lost contact with the console
Explanation: DST unrecoverable program error
Response: A service program lost contact with the
system console. Failing Item:
Failing Item: v LICIP03
v RTRIP03 v AJDG301
v AJDG301 v FI00380
v USER
A6005120 A6005120
A6005083 A6005083 Explanation: System LIC detected a program
exception
Explanation: IPL service function ended abnormally
Response: System LIC detected a programming
Response: A service program lost contact with the problem. If performance or other system degradation is
system console. occurring, the system may be operating with reduced
Failing Item: resources.
v TWSIP01 Check the Product activity log for related entries. If this
v AJDG301 reference code is logged with an error class of
Informational, then no action is required.
v USER
Response: System LIC detected an IOP programming Explanation: I/O processor failure
problem for which an IOP dump may have been Failing Item:
initiated.
v FI01112
Failing Item: v FI01107
v LICIP01
v FI00130 A600512D A600512D
v AJDG301
Explanation: An IOP dump was initiated
v FI00131
Response: Copy the IOP dump entry and any related
entries from the Product Activity Log to suitable media,
A6005123 A6005123 and give to an IBM service representative.
Explanation: LIC program exception occurred
Response: System LIC detected an interface problem A600512E A600512E
with the IOP or an IOP programming problem for Explanation: LIC program exception occurred
which an IOP and main storage dump may have been
initiated. Response: The system was in a D IPL mode when the
problem was detected. A main storage dump was not
Failing Item: taken.
v LICIP01
Failing Item:
v FI00130
v LICIP01
v AJDG301
v AJDG301
v FI00131
v FI00130
A6005126 A6005126
A6005192 A6005192
Explanation: Addressed device failed to respond to
Explanation: Insufficient entitled memory for the I/O
selection
configuration
Failing Item:
Response: Use the hardware management console to
v DISKDRV increase the entitled memory capacity of the partition
v STORIOA and restart the I/O adapter. To restart a storage I/O
v DISKTRY adapter, use Hardware Service Manager to re-IPL the
virtual I/O processor that is associated with this I/O
A6005194 A6005194
A6005275 A6005275
Explanation: Insufficient entitled memory for the I/O
configuration Explanation: The system issued a reset/reload to the
IOP.
Response: Use the hardware management console to
increase the entitled memory capacity of the partition Response: System Licensed Internal Code detected
and restart the partition. that an IOP Reset/Reload has occurred, and that the
IOP successfully recovered.
Failing Item:
Users who were signed on to a Workstation device
v SVCDOCS
under the IOP will need to sign back on. Any
LAN/WAN communications lines under the IOP will
A6005206 A6005206 need to be restarted. Tape/Optical devices under the
IOP may need to be varied back on.
Explanation: System LIC detected a missing IOP LIC
code load To determine the cause of the IOP Reset/Reload, check
the Product Activity Log for additional entries logged
Response: System LIC detected a missing IOP LIC with the same System Log ID, and perform any actions
code load during IPL of the IOP. This indicates that indicated for those errors.
either the IOP code load is not installed on the system
Load Source device or that system LIC was unable to
successfully read that load from the Load Source A6005276 A6005276
device.
Explanation: IOP Reset was issued
Failing Item:
Response: LIC has detected a problem with the
v LICIP01 Service Processor IOP and has reset it but has not
v USER initiated reload of the Service Processor.
If the Load Source is mirrored, some system operations
A6005209 A6005209 may be able to continue normally. However, some
system service operations have been suspended and the
Explanation: System LIC detected an IOP timeout system should be scheduled for power down as soon
during IOP IPL as possible.
Response: Verify that all IOP cable connections are Failing Item:
secure, and check tape and other non-disk devices and
media to verify that they are in a ready state. v RTRIP08
v AJGLD01
Failing Item:
v AJDG301
v LICIP01
v FI00021
v USER
v FI00130
v AJDG301
Explanation: LIC program exception occurred Response: Check the primary partition Product
Activity Log for system memory entries from
Response: LPAR configuration data does not match approximately the same time. Perform the actions
current system configuration. The system will not IPL indicated for those entries.
past DST until the problem is corrected.
Following is a list of problems which may have caused A6005342 A6005342
this SRC to be reported:
Explanation: Secondary partition not running at
v Non-configured disk unit which was previously a
optimum.
load source on a partitioned system.
v Load Source configuration data does not match Response: Check the Primary partition's Product
partition for which it is being used. Activity Log for system processor entries from
approximately the same time. Perform the actions
v Load Source configuration data does not match
indicated for those entries.
system serial number for which it is being used.
v Load Source configuration data is newer than
primary partition configuration data. A6005343 A6005343
Failing Item:
A6006907 A6006907
v SIIOADP
Explanation: High Speed Link (HSL) I/O bridge
v OPT_CLN
failure
Response: LIC detected invalid data in the HSL I/O
A6006909 A6006909
bridge VPD. The bridge and HSL loop may not have
become operational. Explanation: High Speed Link (HSL) I/O bridge
failure
For this reference code the failing item list presented in
the Service Action Log (SAL), or serviceable event view Response: LIC detected invalid data in the I/O bus
you are working with, can be different from the failing VPD. The bus and resources associated with it may not
item list documented here. That is due to the be operational.
differences in system models and features installed.
For this reference code the failing item list presented in
If the Service Action Log (SAL) or serviceable event the Service Action Log (SAL), or serviceable event view
view on the hardware management console, is available you are working with, can be different from the failing
then use the failing item list presented there for item list documented here. That is due to the
servicing this reference code. differences in system models and features installed.
If a serviceable event view is not available then use the If the Service Action Log (SAL) or serviceable event
failing item list documented here. By following the viewer on the hardware management console is
procedures in the symbolic FRUs listed here you will available then use the failing item list presented there
isolate to the correct FRU list based on system model for servicing this reference code.
and features installed.
If a serviceable event view is not available then use the
NOTE: A fiber optic cleaning kit may be required for failing item list documented here. By following the
optical HSL connections. procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model
Failing Item:
and features installed.
v SIIOADP
If the serviceable event view only indicated a frame or
v OPT_CLN
enclosure see the locations section for the frame or
enclosure type. The location of the HSL I/O Bridge will
A6006908 A6006908 be given in the locations tables.
Explanation: High Speed Link (HSL) I/O bridge NOTE: A fiber optic cleaning kit may be required for
failure optical HSL connections.
Response: LIC data in the I/O bus VPD could not be Failing Item:
accessed. The I/O Bus identified in the SRC may not v SIIOADP
have become operational.
v OPT_CLN
If there is a B6xx 6906 reference code, close this
problem in the serviceable event view you are working
A600690A A600690A
with and work the 6906 error.
Explanation: Associated adapter not found in this
For this reference code the failing item list presented in
partition
the Service Action Log (SAL), or serviceable event view
you are working with, can be different from the failing Failing Item:
item list documented here. That is due to the v LICIP16
differences in system models and features installed.
If the Service Action Log or serviceable event view on A6006910 A6006910
the hardware management console or service processor
is available then use the failing item list presented there Explanation: I/O processor failure
for servicing this reference code.
Response: An I/O processor timed out, returned bad
If a serviceable event view is not available then use the status, or is not following the system bus protocol.
failing item list documented here. By following the
Failing Item:
procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model v LICIP07
and features installed. v FI00310
NOTE: A fiber optic cleaning kit may be required for v FI00318
optical HSL connections. v FI00065
v FI00130
A6006960 A6006960 See SLOTERR symbolic FRU for the list of messages
and a further description of the problem detected by
Explanation: Multi-adapter bridge card slot error, do Licensed Internal Code.
not use card slot
For this reference code the failing item list presented in
Response: Slot unavailable due to 64 bit card in the Service Action Log (SAL), or serviceable event view
adjacent slot. you are working with, can be different from the failing
One of the messages documented with the symbolic item list documented here. That is due to the
FRU will describe the problem. See SLOTERR symbolic differences in system models and features installed.
FRU for a list of messages and corrective actions. If the Service Action Log, or serviceable event view on
Failing Item: the hardware management console is available then use
the failing item list presented there for servicing this
v SLOTERR reference code.
If a serviceable event view is not available then use the
A6006961 A6006961 failing item list documented here. By following the
Explanation: Multi-adapter bridge card slot error, do procedures in the symbolic FRUs listed here you will
not use card slot isolate to the correct FRU list based on system model
and features installed.
Response: LED control failure, do not use slot.
Failing Item:
The card location is not available for use. The Failing
v SLOTERR
Item with the card slot error is in the Failing Item list
for this reference code. v MASBUS
The card location is not available for use. The Failing Failing Item:
Item with the card slot error is in the Failing Item list v MABRCFG
for this reference code.
See SLOTERR symbolic FRU for the list of messages A6006965 A6006965
and a further description of the problem detected by
Licensed Internal Code. Explanation: Multi-adapter bridge configuration
change or error
For this reference code the failing item list presented in
the Service Action Log (SAL), or serviceable event Response: Card type not supported in this slot.
viewer you are working with, can be different from the An I/O processor or I/O adapter card type is installed
failing item list documented here. That is due to the in the location indicated in word 7 of the SRC. The
differences in system models and features installed. card type is not supported in that slot under the
If the Service Action Log or serviceable event viewer on multi-adapter bridge. The card is unavailable.
the hardware management console is available then use See MABRCFG symbolic FRU for the list of messages, a
the failing item list presented there for servicing this further description of the problem detected by Licensed
reference code. Internal Code and the corrective action.
If serviceable event view is not available then use the Failing Item:
failing item list documented here. By following the
procedures in the symbolic FRUs listed here you will v MABRCFG
isolate to the correct FRU list based on system model
and features installed. A6006966 A6006966
Failing Item: Explanation: Multi-adapter bridge configuration
v SLOTERR change or error
v MASBUS Response: I/O processor removed from multi-adapter
bridge card slot.
A6006964 A6006964 On the previous IPL an I/O processor was in the card
Explanation: Multi-adapter bridge configuration location specified in word 7 of the SRC. The I/O
change or error processor was not detected on this IPL.
Response: One of several errors or configuration See MABRCFG symbolic FRU for the list of messages, a
problems has occurred under a Multi-adapter bridge. If further description of the problem detected by Licensed
you are using the Service Action Log (SAL), or the Internal Code and the corrective action.
serviceable event viewer on the hardware management Failing Item:
console or the service processor, then the correct FRU,
v MABRCFG
description and card position(s) will be listed. Use the
FRUs and descriptions in the serviceable event view
you are working with to determine the problem. A6006967 A6006967
If you do not have access to the Service Action Log, or Explanation: Multi-adapter bridge configuration
serviceable event view on the hardware management change or error
console or service processor, then word 4 of the SRC
Response: I/O adapter unavailable due to moved I/O
has more information. Examine the last 4 digits in word
processor card.
4 to determine the problem by comparing them to the
list below and using the FRU(s) listed here. The I/O adapter specified in word 7 of the SRC is not
1. xxxx2022 - IOP found in slots owned by a Linux available. On the previous IPL there was an I/O
partition. The Multi-adapter Bridge and PCI Bridge processor card the adapter was assigned to. The I/O
set that it controls are assigned to a Linux partition. processor was not detected on this IPL.
The IOP found in the SLOT indicated by the DSA in See MABRCFG symbolic FRU for the list of messages, a
word 7 will not be configured. further description of the problem detected by Licensed
2. xxxx2014 - I/O adapters were found under the Internal Code and the corrective action.
Multi-adapter Bridge but there is no IOP to support
them. The adapters cannot be used. Failing Item:
3. xxxx2015 - An card type was found that cannot be v MABRCFG
supported in the card position where it is located.
Failing Item: NOTE: This SRC can occur for the PCI bus resource on
a PCI bus in an I/O expansion unit when the unit is
v MABRCFG powered off for a concurrent maintenance action.
If the Service Action Log, or serviceable event view on
A600696A A600696A the hardware management console or service processor,
Explanation: Card slot test failed is available then use the failing item list presented there
for servicing this reference code.
Failing Item:
If a serviceable event view is not available then use the
v LICIP14
failing item list documented here.
v FI00131
NOTE: A fiber optic cleaning kit may be required for
v BACKPLN
optical HSL connections.
Failing Item:
A600696B A600696B
v SI_PHB
Explanation: Card slot could not be validated
v PRI_PCI
Response: This can be caused by "PCI error injection v MA_BRDG
policy" being set to "YES" and an I/O Processor being
v MABIP03
installed on the same Multi-adapter bridge domain as
the I/O Adapter. Do one of the following: v BRDGSET
v OPT_CLN
-- Using the hardware management console or a
customer PC with a Web browser access the Advanced
System Management Interface (ASMI) and disable PCI A6006971 A6006971
error injection policy.
Explanation: High Speed Link (HSL) resource failure
OR
Response: A failure occurred in a multi-adapter
-- Vary off the I/O Adapter. Using Hardware Service bridge or on the bus to the card location it controls.
If a serviceable event view is available, use the failing of or the removal of an I/O adapter.
item list presented there for servicing this reference
Failing Item:
code.
v MABRCFG
If a serviceable event view is not available, use the
failing item list documented here.
A6006975 A6006975
Failing Item:
Explanation: The system issued a reset/reload to the
v MABIP02
service processor.
v MA_BRDG
Response: Service processor error.
v MASBUS
v PIOCARD Failing Item:
v AJDGP01
A6006972 A6006972
A6006976 A6006976
Explanation: High Speed Link (HSL) resource failure
Explanation: Service processor failure.
Response: Multi-adapter Bridge (MaB) failure
detected. Response: For this reference code the failing item list
presented in the Service Action Log (SAL), or
For this reference code the failing item list presented in
serviceable event view you are working with, can be
the Service Action Log (SAL), or serviceable event
different from the failing item list documented here.
viewer you are working with, can be different from the
That is due to the differences in system models and
failing item list documented here. That is due to the
features installed.
differences in system models and features installed.
If the Service Action Log (SAL) or a serviceable event
If the Service Action Log (SAL) or serviceable event
viewer on the hardware management console is
viewer on the hardware management console is
available then use the failing item list presented there
available then use the failing item list presented there
for servicing this reference code.
for servicing this reference code.
If a serviceable event viewer is not available then use
If a serviceable event view is not available then use the
the failing item list documented here. By following the
failing item list documented here. By following the
procedures in the symbolic FRUs listed here you will
procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model
isolate to the correct FRU list based on system model
and features installed.
and features installed.
Failing Item:
Failing Item:
v SVCPROC
v MA_BRDG
A6006980 A6006980
A6006973 A6006973
Explanation: Network Interface Controller / IO Hub
Explanation: High Speed Link (HSL) resource failure
failure.
Response: Multi-adapter Bridge has detected a
Response: For Power5 and newer servers, service this
problem in the card installed in the location specified in
error using the B7006980 service information.
word 7 of the SRC. Use the FRU list in the Service
Otherwise, continue with this information.
Action Log (SAL), or serviceable event view you are
working with. If you are working from this document's The FRU list displayed in the Service Action Log (SAL)
FRU list use the Symbolic FRU BRDGSET to determine or serviceable event view you are working with, may
the failing items. vary from the failing item list given in this document.
Use the FRU list in the serviceable event view if it is
Failing Item:
available to you.
v BRDGSET
NOTE: A fiber optic cleaning kit may be required for
v SIIOADP
optical HSL connections.
v MA_BRDG
Failing Item:
v SICNTRL
A6006974 A6006974
v OPT_CLN
Explanation: Multi-adapter bridge configuration
change or error
Response: PCI I/O processor rejected the assignment
This error can appear as a serviceable event when a NOTE: A fiber optic cleaning kit may be required for
tower, or I/O unit or another system in the loop did optical HSL connections.
not complete powering on before LIC on this system
Failing Item:
checked this loop for errors. Search the Product
Activity Log (PAL) for the last B6xx 6985 SRC logged v SIRSTAT
for this loop and use FRU SIRSTAT to determine if this v HSL_LNK
error requires service. If the last entry indicates the v SIIOADP
loop is functioning (determined by FRU SIRSTAT) then
no service action is required, close this problem v SICNTRL
v OPT_CLN
There may be multiple B6xx 6985 logs with xxxx 3205
in word 4 errors for the same loop resource in the
serviceable event view. This is caused by retry and A6006986 A6006986
recovery attempts. If there is a B6xx 6985 with xxxx
Explanation: System bus error
3206 or xxxx 3208 in word 4 after the above B6xx 6985
entries in the PAL, then the recovery efforts were Response: For Power5 and newer servers, service this
successful. If this is the case, close all the B6xx 6985 error using the B7006986 service information.
entries for that loop resource in the serviceable event Otherwise, continue with this information.
view.
During IPL, system LIC detected an HSL I/O bridge
1. If you find a B6xx 6981 in the serviceable event that was already initialized. The bridge should have
view then close that problem and go to step 2. been in a flushed and uninitialized state after powering
Otherwise perform the following: on. There is a problem with SPCN components that
v Perform RIOIP06 to determine if any other prevented the tower from powering off after a previous
systems are connected to this loop and return power off was issued. The tower will not be configured
here. (HSL_LNK or HSLxxxx FRU in the Service for this IPL.
Action Log (SAL) entry, or serviceable event view
This reference code is equivalent to 1xxx 90F0. When
you are working with, indicates the loop
referring to the "CBLALL" symbolic FRU in the Failing
number.) If there are other system(s) then
Item list, perform the "CBLALL" procedure using
continue with the steps that follow, otherwise go
reference code "90F0".
to step 2.
v Check for HSL failures on the other system(s) Word 5 of the SRC identifies the frame. Determine the
before replacing parts. HSL failures are frame by breaking down word 5:
serviceable event entries with HSL I/O Bridge Word 5 -> xxxx xxNN where: NN is the frame number
and Network Interface Controller (NIC) in hexadecimal format.
resources. Ignore B6xx 6982 and B6xx 6984
entries. If there are HSL failures on other Failing Item:
system(s) then continue with the steps that v TWRCARD
follow, otherwise go to step 2.
v CBLALL
v Repair the problems on the other systems and
return to this step. After making repairs on the
other system(s) check the Product Activity Log A6006987 A6006987
(PAL) of this system for a B6xx 6985 logged after Explanation: High Speed Link (HSL) connection
the repairs you made on the other system(s). If failure
you find one then continue with the steps that
follow, otherwise go to step 2. Response: For Power5 and newer servers, service this
error using the B7006987 service information.
v For the B6xx 6985 log you found, use FRU
Otherwise, continue with this information.
SIRSTAT to determine if the loop is now
complete. If the loop is complete then this Failures are occurring on the HSL link.
problem has been resolved. Use RIOIP01 to verify
that the loop is now working properly. There may be B6xx 6982 errors logged on the same
Otherwise, go to step 2. loop and about the same time as this error. Close those
errors and continue to correct the problem by working
2. Use the serviceable event's FRU list when it is this error.
available.
v If there is a cable FRU in the serviceable event entry:
If this SRC appears in the Service Action Log (SAL),
or the serviceable event view you are using, with 1. If the connection is copper and either end has a
the Symbolic FRU HSL_LNK or HSLxxxx listed as a loose connection, re-seat the cable. To do this,
FRU, then perform problem isolation procedure disconnect the connection and wait a minimum
RIOIP01. Otherwise exchange the FRUs listed in the of 30 seconds. Then reconnect the cable and
serviceable event view. complete the tightening process in at most 30
seconds. Repeat the process at the other end of
v REM_SYS
A60069C9 A60069C9
v LOC_SYS
Explanation: HSL Opticonnect abnormal disconnect
from other sys. or partition.
A60069C8 A60069C8
Response: The local system or partition disconnected
Explanation: HSL Opticonnect abnormal disconnect from a remote system or partition due to an failure in a
from other sys. or partition. LIC virtualized bus unit. LIC will attempt to recover
Response: The local system or partition disconnected from the error. Possible causes are:
from a remote system or partition due to an v LIC problem where the local bus unit is off line.
unexpected event or failure. All of the HSL v LIC problem where the remote bus unit is off line.
OptiConnect connections on this loop will be in a failed
state. LIC will attempt to recover from the error. Examine the Service Action Log (SAL), or serviceable
Intervention at the local or remote system or partition event view you are using, on the local system or
may be required. Possible causes are: partition for HSL Opticonnect failures that occurred at
v time out of a critical message approximately the same time this error occurred.
v LIC code / table problem
Examine the remote system or partition for problems.
v Network deadlock detected
Examine the Service Action Log (SAL), or the
serviceable event view you are using, on the remote
The problem may be with:
system or partition for HSL Opticonnect problems that
v The local system or partition occurred at approximately the same time this error
v The remote system or partition occurred.
Examine the Service Action Log (SAL), or serviceable Collect all the Product Activity Log information for this
event view you are using, on the local system or failure on all systems and partitions on this HSL loop.
partition for HSL failures on the same HSL loop, or Be sure to record all words in the SRCs. Contact your
with the Network Interface Controller at approximately next level of support with the information you have
the same time this error occurred. collected.
Failing Item:
Examine the remote system or partition for problems.
Examine the Service Action Log (SAL), or serviceable v AJDG301
event view you are using, on the remote system or v REM_SYS
partition for problems on the same HSL loop or with v LOC_SYS
the Network Interface Controller at approximately the
same time this error occurred.
A60069CF A60069CF
Correct any problems you find with the remote and Explanation: HSL Opticonnect abnormal disconnect
local systems or partitions that happened at from other sys. or partition.
approximately the same time and involve HSL
Opticonnect or HSL loop components or Network Response: LIC internal error. All systems participating
Interface Controllers. in HSL OptiConnect will be disconnected. The system
must be re-IPL'd to recover. Before re-IPL'ing the
If there are no problems with the remote system or system initiate a main store dump.
partition and there are no problems with the local After getting the dump, examine the Service Action
system or partition then collect all the Product Activity Log (SAL), or serviceable event view you are using, on
Log information for this failure on all systems or the local system or partition for HSL Opticonnect
partitions. Be sure to record all words in the SRCs. failures that occurred at approximately the same time
Contact your next level of support. this error occurred.
Failing Item: Examine the remote systems or partitions for problems.
v REM_SYS Examine the Service Action Log (SAL), or serviceable
v LOC_SYS event view you are using, on the remote systems or
partitions for HSL Opticonnect problems that occurred
v AJDG301 at approximately the same time this error occurred.
Collect all the Product Activity Log information for this
failure on all systems and partitions on this HSL loop.
Be sure to record all words in the SRCs. Contact your
next level of support with the information you have
collected.
Failing Item:
A60069DD A60069DD
v AJDG301
Explanation: The HEA connection to the Ethernet
switch has been restored
A60069D0 A60069D0
Response: System log entry only, no service action
Explanation: Bus Expansion Adapter card failed required.
Response: Contact your next level of support.
Failing Item: A60069DE A60069DE
Explanation: Host Ethernet Adapter (HEA) failure Response: Contact your next level of support.
A60069DB A60069DB
A60069F0 A60069F0
Explanation: LIC failure
Explanation: Bus Expansion Adapter failed
Response: A Licensed Internal Code error occurred.
Response: Contact your next level of support.
The partition will continue to run with this Host
Ethernet Adapter (HEA) disabled. Perform a partition Failing Item:
dump and then IPL the partition to recover the HEA. v NEXTLVL
Send the partition dump to your next level of support.
Failing Item: A60069F8 A60069F8
v SVCDOCS
Explanation: Bus Expansion Adapter failed
Response: Contact your next level of support.
A60069DC A60069DC
Failing Item:
Explanation: The HEA is not connected to the
Ethernet switch v NEXTLVL
A600CFFC A600CFFC
A600FDC5 A600FDC5
Explanation: Optical library device condition not
expected Explanation: LIC program failed and data was
captured
Response: The optical disk drive addressing within
the optical library is incorrect. This error is likely to be Response: This reference code indicates first failure
the result of faulty cabling or switch setting following data capture (FFDC) data was collected for a problem
service to an optical library. reported by licensed internal code.
Contact your hardware service provider. The user should dial IBM Software Support for
assistance.
Failing Item:
Failing Item:
v OPTLCBL
v UG3AS
v DRVSWCH
A6xx0000 A6xx0000
A600CFFD A600CFFD
Explanation: Operating system status code
Explanation: Optical drive failure
Response: This reference code is for information only.
Failing Item:
It is shown in the Product activity log as a side effect of
v OPTLDRV a condition that was detected by LIC.
Normally, no action should be taken as a result of
A600CFFF A600CFFF information reference codes. However, to isolate the
Explanation: Media determined to be bad in Optical root cause, use these suggestions:
library 1. Examine the date and time of the informational
reference code.
A600F103 A600F103 2. Determine if any other reference codes have been
logged at or before the same date and time.
Explanation: Main storage dump must be copied for 3. Begin the service approach based on these other
service logged errors.
Failing Item:
v LICIP01 A6xx0102 A6xx0102
Explanation: A machine check occurred during IPL
A600F104 A600F104
Response: Words 2 to 9 of this SRC contain additional
Explanation: LPAR service function directed a Main diagnostic information. Record SRC words 1 through 9
Storage Dump. before attempting to IPL again and report the problem
to your Software Service Provider.
Response: The Hypervisor terminated a partition with
an unresponsive Operating System. A Main Store
Dump must be done for service. Call your next level of A6xx0103 A6xx0103
support when the dump is complete.
Explanation: Main storage dump must be copied for
Failing Item: service
v LICIP01 Failing Item:
v LICIP01
A600F105 A600F105
Explanation: Licensed Internal Code detected error
Failing Item:
v NEXTLVL
A6xx0106 A6xx0106
A6xx0231 A6xx0231
Explanation: Terminate Immediate data is not valid
Explanation: Disk sanitize action completed
Failing Item: successfully
v LICIP08
Response: No service action required. This entry is
v AJDG301 logged for information only.
v LICIP13
A6xx0307 A6xx0307
v FI00580
Explanation: LIC exception code detected a problem
v FI00500
v FI00302 Response: Component Specific Exception Handler
recursion is detected in an IBM i Operating System
v FI00301
process.
v AJDG301
Failing Item:
v LICIP08
A6xx0266 A6xx0266
v AJDG301
Explanation: Contact was lost with the device
indicated
A6xx0308 A6xx0308
Response: Do not power off the system.
Explanation: LIC exception code detected a problem
Perform the procedure indicated in the failing item list.
Response: Component Specific Exception Handler
Failing Item: recursion is detected in an IBM i Operating System
v LICIP13 process.
v FI00580 Failing Item:
v FI00500 v LICIP08
v FI00302 v AJDG301
v FI00301
v AJDG301 A6xx0317 A6xx0317
Explanation: Traceback for code not found
A6xx0299 A6xx0299
Failing Item:
Explanation: Informational LIC state SRC.
v LICIP08
v AJDG301
A6xx0302 A6xx0302
Explanation: Recursion in exception handler A6xx0323 A6xx0323
Failing Item: Explanation: LIC exception code detected a problem
v LICIP08
Failing Item:
v AJDG301
v LICIP08
v AJDG301
A6xx0304 A6xx0304
Explanation: Component specific exception handler A6xx0324 A6xx0324
return code not valid
Explanation: LIC exception code detected a problem
Failing Item:
Failing Item:
v LICIP08
v LICIP08
v AJDG301
v AJDG301
A6xx0305 A6xx0305
A6xx0325 A6xx0325
Explanation: Exception while storage management
lock is held Explanation: LIC exception code detected a problem
A6xx0607 A6xx0607
A6xx0446 A6xx0446
Explanation: Maximum stack size exceeded in process
Explanation: Error during machine termination or task
Failing Item: Failing Item:
v LICIP08 v LICIP08
v AJDG301 v AJDG301
v AJDG301
A6xx1104 A6xx1104
A6xx0901 A6xx0901 Explanation: Failure reading media or not install
media
Explanation: The LinkLoader has found its bad flag
ON Response: Determine that correct install media is
loaded. If correct install media is installed, media could
Response: This reference code is usually the result of be corrupt. Obtain another copy of the install media
a system termination while the LinkLoader is and re-attempt the install. If the install still fails, contact
performing its work. your service representative.
Reinstall the Licensed Internal Code by using Utilities
to install and restore IBM i Licensed Internal Code. A6xx1201 A6xx1201
Explanation: Critical database segment could not be
A6xx0902 A6xx0902 created
Explanation: Unable to perform programmed IPL Failing Item:
Response: The LinkLoader was not successful in v LICIP08
performing a programmed IPL. v AJDG301
Perform a system IPL. If the problem persists, examine
the main storage dump and determine the reason for A6xx1204 A6xx1204
the failure of the programmed IPL.
Explanation: Error in constraint enforcement
Failing Item:
v LICIP08
v AJDG301
Explanation: An attempt to create a segment failed Response: A main store dump was initiated. Words 12
and 13 of this SRC contain additional diagnostic
Response: The create could fail for two reasons: information.
v A code problem. Perform the procedure indicated in
To recover the partition using the previously installed
the failing item list.
LIC, perform a B-mode IPL. You can then re-try the
v No free auxiliary storage on the system. Add installation of LIC. Otherwise, install LIC using
additional DASD if the create failed because no physical media.
auxiliary storage was available.
To determine what caused this failure, collect SRC
Failing Item: information and main store dump and contact your
v LICIP08 next level of support.
v AJDG301 Failing Item:
v SVCDOCS
A6xx1730 A6xx1730
Explanation: An IPL is needed to restore system A6xx4401 A6xx4401
performance
Explanation: Missing DASD units.
Response: Licensed Internal Code has detected a
Response: Copy the current main storage dump to
condition that is impacting system performance. System
media.
operation can continue, but system performance may
be noticeably reduced until the next IPL. For more information on how to perform a Main
Storage Dump, refer to Copying a main storage dump.
Look at the Product Activity Log entry, and find the
A6xx4745 A6xx4745
A6xx4715 A6xx4715
Explanation: Processor Capacity card replaced on
Explanation: Processor On Demand error detected. activated POD system.
Response: Correct any Processor Capacity card or Response: Contact IBM Support to order a
SPCN failures. replacement Processor On Demand activation code.
Failing Item:
v CTLPNCD
v AJDG301
A6xx4747 A6xx4747
v FI00380
Explanation: 1 hour left in POD 14 day Trial
Activation Period.
A6xx5005 A6xx5005
Response: If a new activation code was purchased, it
should be entered now. Otherwise, the system will Explanation: Service program failed
revert back to its previous activation state at the end of Response: The workstation adapter system console
the Trial Activation Period. failed to respond.
Failing Item:
A6xx5001 A6xx5001
v WSAIP01
Explanation: DST received no response from a work v FI00320
station controller
v FI00602
Response: The workstation I/O processor for the v USER
system or partition console did not respond.
v AJDG301
Failing Item: v FI00380
v RTRIP01
v FI00380 A6xx5007 A6xx5007
v AJDG301
Explanation: Service program failed
A6xx5008 A6xx5008
A6xx5003 A6xx5003
Explanation: DST console failed to respond
Explanation: Service program failed
Response:
Response: The ASCII system console failed to
respond. Failing Item:
Failing Item: v OPCIP03
v FI00320 v FI00719
v FI00602
v USER A6xx5010 A6xx5010
A6xx5090 A6xx5090 Check the Product activity log for related entries. If this
reference code is logged with an error class of
Explanation: System startup failed in unattended IPL Informational, then no action is required.
mode
Otherwise, perform the procedure indicated in the
Response: Perform the following: failing item list.
v If reference code A6xx5090 is displayed on the
Failing Item:
control panel for more than 10 minutes, perform the
procedure indicated in the failing item list. v LICIP01
v For reference code B6xx5090, perform the procedure v AJDG301
indicated in the failing item list. v FI00130
Failing Item:
v LICIP11 A6xx5121 A6xx5121
v FI00580 Explanation: LIC program exception occurred
v FI00500 Response: System LIC detected a programming
v FI00301 problem for which a main storage dump may have
v FI00021 been initiated. Collect the dump if available.
v FI00065 A problem log entry may be generated for this refcode.
v AJDG301 Failing Item:
v LICIP01
v AJDG301
A6xx5192 A6xx5192
A6xx5126 A6xx5126
Explanation: Insufficient entitled memory for the I/O
Explanation: Addressed device failed to respond to configuration
selection
Response: Use the hardware management console to
Failing Item: increase the entitled memory capacity of the partition
v DISKDRV and restart the I/O adapter. To restart a storage I/O
v STORIOA adapter, use Hardware Service Manager to re-IPL the
virtual I/O processor that is associated with this I/O
v DISKTRY
adapter. To restart a communications I/O adapter, vary
v FI01106 the line off and vary it on using the vary configuration
v FI01140 (VRYCFG) command.
v FI01141 Failing Item:
v DEVTERM v SVCDOCS
v BACKPLN
A6xx5193 A6xx5193
A6xx5127 A6xx5127
Explanation: Virtual adapter not supported in a
Explanation: IOP timed out a disk command shared memory partition
Response: Verify that all IOP cable connections are Failing Item:
secure, and check tape and other non-disk devices and v RTRIP08
media to verify that they are in a ready state. v AJGLD01
Failing Item: v AJDG301
v LICIP01 v FI00021
v USER
v FI00130 A6xx5310 A6xx5310
v AJDG301 Explanation: LIC program exception occurred
Response: System LIC detected a logical partition
A6xx5219 A6xx5219 configuration data consistency error. Copy the Product
Explanation: LIC program exception occurred Activity Log data for this error and any related entries
and contact your next level of hardware service
Response: An IOP signaled to system LIC that it had support.
entered a critical internal state. LIC automatically
attempted to restart the IOP. Failing Item:
v LPARSUP
This reference code is logged for information only. No
action is required.
A6xx5311 A6xx5311
Failing Item:
v FI00310 Explanation: LIC program exception occurred
Failing Item:
A6xx5343 A6xx5343
v LPRIP01
v LPARSUP Explanation: Secondary partition not running at
optimum.
A6xx5340 A6xx5340 Check the Release Delta from the Primary partition
"Display Partition Release Level" screen.
Explanation: Secondary partition not running at
optimum. Check the LPAR documentation for the release level of
the Primary partition and determine what the
Response: Check the Primary partition's Product supported Release Delta is.
Activity Log for system processor entries from
approximately the same time. Perform the actions
indicated for those entries. A6xx5380 A6xx5380
Explanation: LIC program exception occurred
A6xx5341 A6xx5341 Response: Record the Product Activity Log (PAL) hex
Explanation: Secondary partition not running at data for this SRC or print the PAL entry.
optimum. Contact your next level of support.
Response: Check the primary partition Product Failing Item:
Activity Log for system memory entries from
v LPARSUP
approximately the same time. Perform the actions
indicated for those entries.
v NEXTLVL
A6xx5390 A6xx5390
Explanation: LIC program exception occurred
A6xx6905 A6xx6905
Response: Record the Product Activity Log (PAL) hex
Explanation: Optical bus failed
data for this SRC or print the PAL entry.
Response: Contact your next level of support.
Contact your next level of support.
Failing Item:
Failing Item:
v NEXTLVL
v LPARSUP
A6xx6906 A6xx6906
A6xx5505 A6xx5505
Explanation: High Speed Link (HSL) I/O bridge
Explanation: The copying of DASD log data to the
failure
IOP log was successful
Response: LIC could not access part of the HSL I/O
Response: IOP log data can be copied to a spool file
bridge VPD. The bridge and HSL loop may be
for examination by the development lab.
prevented from becoming operational.
For this reference code the failing item list presented in
A6xx5555 A6xx5555
the Service Action Log (SAL), or serviceable event
Explanation: SLIC I/O DASD subsystem error viewer you are working with, can be different from the
recovery in progress. failing item list documented here. That is due to the
differences in system models and features installed.
A6xx5600 A6xx5600 If the Service Action Log (SAL) or serviceable event
view on the hardware management console is available
Explanation: Unrecoverable read error
then use the failing item list presented there for
Response: VPD data could not be read. servicing this reference code.
Look for other errors implicating hardware. There is no If a serviceable event view is not available then use the
way to know what VPD read has failed, but the failing item list documented here. By following the
resource is not usable and should generate an error. procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model
If no such error occurred, call your next level of and features installed.
support.
NOTE: A fiber optic cleaning kit may be required for
Failing Item: optical HSL connections.
v SVCDOCS
Failing Item:
v SIIOADP
A6xx6900 A6xx6900
v OPT_CLN
Explanation: System bus error
Response: Contact your next level of support. A6xx6907 A6xx6907
Failing Item: Explanation: High Speed Link (HSL) I/O bridge
v NEXTLVL failure
Response: LIC detected invalid data in the HSL I/O
A6xx6901 A6xx6901 bridge VPD. The bridge and HSL loop may not have
become operational.
Explanation: Bus Expansion Adapter card failed
For this reference code the failing item list presented in
Response: Contact your next level of support. the Service Action Log (SAL), or serviceable event view
Failing Item: you are working with, can be different from the failing
item list documented here. That is due to the
v NEXTLVL
differences in system models and features installed.
If the Service Action Log (SAL) or serviceable event
A6xx6902 A6xx6902
view on the hardware management console, is available
Explanation: Bus Expansion Adapter card failed then use the failing item list presented there for
servicing this reference code.
Response: Contact your next level of support.
If a serviceable event view is not available then use the
Failing Item:
failing item list documented here. By following the viewer on the hardware management console is
procedures in the symbolic FRUs listed here you will available then use the failing item list presented there
isolate to the correct FRU list based on system model for servicing this reference code.
and features installed.
If a serviceable event view is not available then use the
NOTE: A fiber optic cleaning kit may be required for failing item list documented here. By following the
optical HSL connections. procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model
Failing Item:
and features installed.
v SIIOADP
If the serviceable event view only indicated a frame or
v OPT_CLN
enclosure see the locations section for the frame or
enclosure type. The location of the HSL I/O Bridge will
A6xx6908 A6xx6908 be given in the locations tables.
Explanation: High Speed Link (HSL) I/O bridge NOTE: A fiber optic cleaning kit may be required for
failure optical HSL connections.
Response: LIC data in the I/O bus VPD could not be Failing Item:
accessed. The I/O Bus identified in the SRC may not v SIIOADP
have become operational.
v OPT_CLN
If there is a B6xx 6906 reference code, close this
problem in the serviceable event view you are working
A6xx690A A6xx690A
with and work the 6906 error.
Explanation: Associated adapter not found in this
For this reference code the failing item list presented in
partition
the Service Action Log (SAL), or serviceable event view
you are working with, can be different from the failing Failing Item:
item list documented here. That is due to the v LICIP16
differences in system models and features installed.
If the Service Action Log or serviceable event view on A6xx6910 A6xx6910
the hardware management console or service processor
is available then use the failing item list presented there Explanation: I/O processor failure
for servicing this reference code. Response: An I/O processor timed out, returned bad
If a serviceable event view is not available then use the status, or is not following the system bus protocol.
failing item list documented here. By following the Failing Item:
procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model v LICIP07
and features installed. v FI00310
NOTE: A fiber optic cleaning kit may be required for v FI00318
optical HSL connections. v FI00065
Failing Item: v FI00130
v SIIOADP v AJDG301
v OPT_CLN
A6xx6938 A6xx6938
A6xx6909 A6xx6909 Explanation: Not valid system configuration detected
Explanation: High Speed Link (HSL) I/O bridge Response: This system model does not allow a
failure configuration of more than three (non-OptiConnect)
I/O Processors.
Response: LIC detected invalid data in the I/O bus
VPD. The bus and resources associated with it may not Power down the system and remove the extra
be operational. (non-OptiConnect) I/O Processor(s) so that there are
three or less. Restart the system.
For this reference code the failing item list presented in
the Service Action Log (SAL), or serviceable event view
you are working with, can be different from the failing
item list documented here. That is due to the
differences in system models and features installed.
If the Service Action Log (SAL) or serviceable event
Failing Item:
A6xx6944 A6xx6944
v SLOTERR
Explanation: Missing or failed I/O processor cards
v MASBUS
Response: A system bus appears to be empty. If the
bus is not empty, two I/O processors in consecutive
A6xx6962 A6xx6962
slots may be missing or broken. If there are broken I/O
processors, then another more serious SRC has Explanation: Multi-adapter bridge card slot error, do
occurred. Otherwise find the bus number for this not use card slot
failure from the Product activity log and use the system
configuration list to verify the configuration of the I/O Response: Power control failure, do not use slot.
processors on that bus. If there is a Linux partition in the system, any IOPs
Failing Item: plugged into slots owned by a Linux partition will not
power on. This error will be logged. Correct the
v FI00317 situation by removing the IOP cards.
v FI00316
The card location is not available for use. The Failing
v AJDG301 Item with the card slot error is in the Failing Item list
for this reference code.
A6xx6960 A6xx6960 See SLOTERR symbolic FRU for the list of messages
Explanation: Multi-adapter bridge card slot error, do and a further description of the problem detected by
not use card slot Licensed Internal Code.
Response: Slot unavailable due to 64 bit card in For this reference code the failing item list presented in
adjacent slot. the Service Action Log (SAL), or serviceable event view
you are working with, can be different from the failing
One of the messages documented with the symbolic item list documented here. That is due to the
FRU will describe the problem. See SLOTERR symbolic differences in system models and features installed.
FRU for a list of messages and corrective actions.
If the Service Action Log, or serviceable event view on
Failing Item: the hardware management console is available then use
v SLOTERR the failing item list presented there for servicing this
reference code.
A6xx6961 A6xx6961 If a serviceable event view is not available then use the
failing item list documented here. By following the
Explanation: Multi-adapter bridge card slot error, do
procedures in the symbolic FRUs listed here you will
not use card slot
isolate to the correct FRU list based on system model
Response: LED control failure, do not use slot. and features installed.
The card location is not available for use. The Failing Failing Item:
Item with the card slot error is in the Failing Item list v SLOTERR
for this reference code.
v MASBUS
See SLOTERR symbolic FRU for the list of messages
and a further description of the problem detected by
A6xx6963 A6xx6963
Licensed Internal Code.
Explanation: Multi-adapter bridge card slot error, do
For this reference code the failing item list presented in
not use card slot
the Service Action Log (SAL), or serviceable event view
you are working with, can be different from the failing Response: Power control failure, do not use slot.
item list documented here. That is due to the
The card location is not available for use. The Failing
differences in system models and features installed.
Item with the card slot error is in the Failing Item list
If the Service Action Log or a serviceable event viewer for this reference code.
on the hardware management console is available for
See SLOTERR symbolic FRU for the list of messages
this problem then use the failing item list presented
and a further description of the problem detected by
there for servicing this reference code.
Licensed Internal Code.
If a serviceable event view is not available then use the
For this reference code the failing item list presented in
failing item list documented here. By following the
the Service Action Log (SAL), or serviceable event
procedures in the symbolic FRUs listed here you will
viewer you are working with, can be different from the
isolate to the correct FRU list based on system model
failing item list documented here. That is due to the
and features installed.
differences in system models and features installed.
If the Service Action Log or serviceable event viewer on card type is not supported in that slot under the
the hardware management console is available then use multi-adapter bridge. The card is unavailable.
the failing item list presented there for servicing this
See MABRCFG symbolic FRU for the list of messages, a
reference code.
further description of the problem detected by Licensed
If serviceable event view is not available then use the Internal Code and the corrective action.
failing item list documented here. By following the
Failing Item:
procedures in the symbolic FRUs listed here you will
isolate to the correct FRU list based on system model v MABRCFG
and features installed.
Failing Item: A6xx6966 A6xx6966
v SLOTERR Explanation: Multi-adapter bridge configuration
v MASBUS change or error
Response: I/O processor removed from multi-adapter
A6xx6964 A6xx6964 bridge card slot.
Explanation: Multi-adapter bridge configuration On the previous IPL an I/O processor was in the card
change or error location specified in word 7 of the SRC. The I/O
processor was not detected on this IPL.
Response: One of several errors or configuration
problems has occurred under a Multi-adapter bridge. If See MABRCFG symbolic FRU for the list of messages, a
you are using the Service Action Log (SAL), or the further description of the problem detected by Licensed
serviceable event viewer on the hardware management Internal Code and the corrective action.
console or the service processor, then the correct FRU, Failing Item:
description and card position(s) will be listed. Use the
FRUs and descriptions in the serviceable event view v MABRCFG
you are working with to determine the problem.
If you do not have access to the Service Action Log, or A6xx6967 A6xx6967
serviceable event view on the hardware management Explanation: Multi-adapter bridge configuration
console or service processor, then word 4 of the SRC change or error
has more information. Examine the last 4 digits in word
4 to determine the problem by comparing them to the Response: I/O adapter unavailable due to moved I/O
list below and using the FRU(s) listed here. processor card.
1. xxxx2022 - IOP found in slots owned by a Linux The I/O adapter specified in word 7 of the SRC is not
partition. The Multi-adapter Bridge and PCI Bridge available. On the previous IPL there was an I/O
set that it controls are assigned to a Linux partition. processor card the adapter was assigned to. The I/O
The IOP found in the SLOT indicated by the DSA in processor was not detected on this IPL.
word 7 will not be configured.
See MABRCFG symbolic FRU for the list of messages, a
2. xxxx2014 - I/O adapters were found under the further description of the problem detected by Licensed
Multi-adapter Bridge but there is no IOP to support Internal Code and the corrective action.
them. The adapters cannot be used.
Failing Item:
3. xxxx2015 - An card type was found that cannot be
supported in the card position where it is located. v MABRCFG
See MABRCFG symbolic FRU for the list of messages, a A6xx6968 A6xx6968
further description of the problem detected by Licensed
Internal Code and the corrective action. Explanation: Multi-adapter bridge configuration
change or error
Failing Item:
Response: IOA removed from multi-adapter bridge
v MABRCFG
slot.
On the previous IPL an I/O adapter was in the card
A6xx6965 A6xx6965
slot specified in word 7 of the SRC. That I/O adapter
Explanation: Multi-adapter bridge configuration was not detected on this IPL.
change or error
See MABRCFG symbolic FRU for the list of messages, a
Response: Card type not supported in this slot. further description of the problem detected by Licensed
Internal Code and the corrective action.
An I/O processor or I/O adapter card type is installed
in the location indicated in word 7 of the SRC. The Failing Item:
v MABRCFG
A6xx6970 A6xx6970
Explanation: High Speed Link (HSL) resource failure
A6xx6969 A6xx6969
Response: A system PCI bus failure was detected.
Explanation: Multi-adapter bridge configuration
Word 7 of the SRC contains the bus number.
change or error
This failure can occur when a tower in an HSL loop is
Response: I/O adapter replaced by I/O processor
powered off using concurrent maintenance. If this is the
card.
case, close this problem.
On the previous IPL there was an I/O adapter in the
This error is most likely in the hardware that makes up
location specified in word 7 of the SRC. This IPL LIC
the PCI bus, the PCI bus side of the HSL I/O bridge or
detected that the IOA was replaced by an IOP in that
the multi-adapter bridge. In some cases it may be
location.
caused by a failing IOP in the multi-adapter bridge's
See MABRCFG symbolic FRU for the list of messages, a domain. When an IOP is causing the problem, the
further description of the problem detected by Licensed failing IOP cannot be identified.
Internal Code and the corrective action.
NOTE: This SRC can occur for the PCI bus resource on
Failing Item: a PCI bus in an I/O expansion unit when the unit is
v MABRCFG powered off for a concurrent maintenance action.
If the Service Action Log, or serviceable event view on
A6xx696A A6xx696A the hardware management console or service processor,
is available then use the failing item list presented there
Explanation: Card slot test failed for servicing this reference code.
Failing Item: If a serviceable event view is not available then use the
v LICIP14 failing item list documented here.
v FI00131 NOTE: A fiber optic cleaning kit may be required for
v BACKPLN optical HSL connections.
Failing Item:
A6xx696B A6xx696B v SI_PHB
Explanation: Card slot could not be validated v PRI_PCI
v MA_BRDG
Response: This can be caused by "PCI error injection
policy" being set to "YES" and an I/O Processor being v MABIP03
installed on the same Multi-adapter bridge domain as v BRDGSET
the I/O Adapter. Do one of the following: v OPT_CLN
-- Using the hardware management console or a
customer PC with a Web browser access the Advanced A6xx6971 A6xx6971
System Management Interface (ASMI) and disable PCI
error injection policy. Explanation: High Speed Link (HSL) resource failure
OR Response: A failure occurred in a multi-adapter
bridge or on the bus to the card location it controls.
-- Vary off the I/O Adapter. Using Hardware Service
manager in SST/DST, locate the I/O Adapter resource. If a serviceable event view is available, use the failing
Using concurrent maintenance on the associated item list presented there for servicing this reference
packaging resource, remove the I/O Adapter and code.
install it in a location that does not have I/O Processors
If a serviceable event view is not available, use the
on the same Multi-adapter bridge domain.
failing item list documented here.
OR
Failing Item:
-- Vary off the I/O Adapter. Use the concurrent v MABIP02
maintenance option in Hardware Service Manager in
v MA_BRDG
SST/DST to power off all I/O Processors located on the
same multi-adapter bridge domain as the I/O Adapter. v MASBUS
Use concurrent maintenance to power off and power v PIOCARD
on the I/O Adapter. Then use concurrent maintenance
to power on the I/O Processors located on the same
multi-adapter bridge domain as the I/O Adapter.
Response: PCI I/O processor rejected the assignment Explanation: High Speed Link (HSL) I/O bridge
of or the removal of an I/O adapter. failure
Failing Item: Response: For Power5 and newer servers, service this
error using the B7006981 service information.
v MABRCFG
Otherwise, continue with this information.
Cycle power on the frame identified as the frame with
A6xx6975 A6xx6975
failed HSL I/O Bridge prior to replacing FRUs.
Explanation: The system issued a reset/reload to the
The FRU list displayed in the Service Action Log (SAL),
service processor.
or serviceable event view you are using, may vary from
Response: Service processor error. the failing item list given in this document. Use the
FRU list in the serviceable event view if it is available
Failing Item: to you.
v AJDGP01
If you find either a B6xx 6982 or B6xx 6984 SRC logged
at approximately the same time as this SRC then they description may already indicate the configuration
were caused by the same failure. If you find a 6982 problem.
SRC logged at approximately the same time then close
Failing Item:
this problem and service the 6982 SRC. The failing item
listed for this SRC is one of the failing items listed for v SIRGCFG
B6xx 6982. If the serviceable event view's entry for this
SRC has a location listed then record the location for A6xx6984 A6xx6984
use in servicing the 6982 SRC.
Explanation: High Speed Link (HSL) loop status
NOTE: This SRC can occur for the HSL I/O Bridge message
resource in an I/O expansion unit when the unit is
powered off for a concurrent maintenance action. Response: For Power5 and newer servers, service this
error using the B7006984 service information.
NOTE: A fiber optic cleaning kit may be required for Otherwise, continue with this information.
optical HSL connections.
An HSL loop has switched to its alternate path. This is
Failing Item: an informational SRC only.
v SIIOADP
Word 7 of the SRC contains the loop number in the
v OPT_CLN leftmost 4 digits. The loop number is in hexadecimal
format. You must convert the hexadecimal loop number
A6xx6982 A6xx6982 into decimal format to recognize the loop number in
HSM.
Explanation: High Speed Link (HSL) connection
failure This SRC can be caused by a tower on the HSL loop
powering off.
Response: For Power5 and newer servers, service this
error using the B7006982 service information. This SRC may also appear in the Service Action Log
Otherwise, continue with this information. (SAL), or serviceable event viewer you are using, with
a B6xx 6982 or B6xx 6981 logged at approximately the
If this SRC is not in the Service Action Log (SAL) or same time. In that case the other SRC is reporting a
serviceable event view you are using, then it is failure and this SRC is reporting that the alternate HSL
informational or statistical only. It does not require a path is now being used. Service the other SRC if
service action. present.
Otherwise, this is a connection failure on an HSL link.
Perform the procedure indicated in the failing item list. A6xx6985 A6xx6985
Failing Item: Explanation: High Speed Link (HSL) loop status
v RIOIP09 message
v HSL_LNK Response: For Power5 and newer servers, service this
v SIIOADP error using the B7006985 service information.
v SICNTRL Otherwise, continue with this information.
v REM_NIC If this SRC is not in the Service Action Log (SAL), or
v OPT_CLN serviceable event view you are using, then it is
informational. Use FRU SIRSTAT to determine what
this SRC means. Otherwise, continue with the
A6xx6983 A6xx6983 following steps:
Explanation: An invalid High Speed Link (HSL) This error can appear as a serviceable event when a
configuration was detected tower, or I/O unit or another system in the loop did
Response: For Power5 and newer servers, service this not complete powering on before LIC on this system
error using the B7006983 service information. checked this loop for errors. Search the Product
Otherwise, continue with this information. Activity Log (PAL) for the last B6xx 6985 SRC logged
for this loop and use FRU SIRSTAT to determine if this
An HSL loop has an invalid configuration. Word 4 of error requires service. If the last entry indicates the
the SRC contains the program return code (PRC) which loop is functioning (determined by FRU SIRSTAT) then
identifies the problem with the loop's configuration. no service action is required, close this problem
Use the PRC and the FRU listed below to determine
the problem. There may be multiple B6xx 6985 logs with xxxx 3205
in word 4 errors for the same loop resource in the
If you are using the Service Action Log (SAL) or serviceable event view. This is caused by retry and
serviceable event view you are working with, the FRU recovery attempts. If there is a B6xx 6985 with xxxx
3206 or xxxx 3208 in word 4 after the above B6xx 6985
A6xx6991 A6xx6991
A6xx69B8 A6xx69B8
Explanation: Service processor failure.
Explanation: Bus hardware configuration problem
Failing Item:
Response: Contact your next level of support.
v AJDGP01
Failing Item:
v NEXTLVL
A6xx6992 A6xx6992
Explanation: Service processor failure.
A6xx69C1 A6xx69C1
Failing Item:
Explanation: A failure occurred communicating with
v AJDGP01 another LPAR or system participating in Opti-connect
with this LPAR or system. Starting with IBM i release
A6xx6993 A6xx6993 7.1 this event will be logged in the Product Activity
Log but it will not be in the Service Action Log or the
Explanation: Service processor failure. Problem Log. This event normally occurs when the
Response: A failure occurred with the service other LPAR or system is powered off. If both LPARs or
processor hardware or the service processor LIC. systems are running and have no Opti-connect errors
then this event is indicating a possible problem with
The FRU list displayed in the Service Action Log (SAL), Opti-connect.
or serviceable event view you are working with, may
vary from the failing item list given in this document. Response: Contact your next level of support if you
Use the FRU list in the serviceable event view if it is suspect an Opti-connect problem. Otherwise this is a
available to you. tracking event.
v SVCPROC v NEXTLVL
v AJDGP01
A6xx69C2 A6xx69C2
A6xx6994 A6xx6994 Explanation: HSL Opticonnect normal connect to
another sys. or partition.
Explanation: Service processor failure.
Response: This reference code is informational only.
Response: The FRU list displayed in the Service
Action Log (SAL) or serviceable event view you are HSL OptiConnect has established connection normally.
working with, may vary from the failing item list given The local system or partition is participating in HSL
in this document. Use the FRU list in the serviceable Opticonnect with other systems or partitions on the
event view if it is available to you. same HSL loop.
Failing Item:
Response: The local system or partition disconnected If there was not a complete HSL loop before this error
from a remote system or partition due to an then a failure or power down in an HSL component
unexpected event or failure. The problem is most likely between the local system or partition and the remote
with the remote system or partition. Intervention at the system or partition could have caused this error. Check
remote system is most likely required. Examine both for SRCs with FRUs like: HSL cables, HSL I/O bridge
the local and remote HSL OptiConnected systems or or a power problem in an expansion I/O tower or unit
partitions for problems on this HSL loop. on this loop.
Possible reasons include: A fatal error in software or Examine the SAL or serviceable event view you are
hardware in the remote system or partition or a power working with on the local system or partition for
failure in the remote system. failures on the same loop, or with the Network
Interface Controller at approximately the same time.
If there was not a complete HSL loop before this error
occurred then a failure or power down in an HSL Examine the remote system or partition for problems.
component between the local system or partition and Correct any HSL or NIC problems you find with the
the remote system or partition could have caused this remote and local systems or partitions.
error. Check for a problem with: an HSL cable, HSL If there are no problems with the remote system or
I/O bridge or a power problem in an expansion I/O partition and there are no problems with the local
tower or unit on this loop. system or partition then collect all the Product Activity
Examine the Service Action Log (SAL), or serviceable Log (PAL) information for this failure on both systems.
event view you are using on the local system or Be sure to record all words in the SRC. Contact your
partition for HSL failures on the same HSL loop at next level of support.
approximately the same time this error occurred. Failing Item:
Examine the remote system or partition for problems. If v REM_SYS
the remote system or partition is powered on and IPL'd v LOC_SYS
then examine the Service Action Log (SAL), or
serviceable event view you are using, on the remote
system or partition for problems on the same HSL loop A6xx69C8 A6xx69C8
at approximately the same time this error occurred. Explanation: HSL Opticonnect abnormal disconnect
Correct any problems you find with the remote and from other sys. or partition.
local systems or partitions that happened at Response: The local system or partition disconnected
approximately the same time and involve HSL from a remote system or partition due to an
Opticonnect or HSL loop components or Network unexpected event or failure. All of the HSL
OptiConnect connections on this loop will be in a failed Examine the remote system or partition for problems.
state. LIC will attempt to recover from the error. Examine the Service Action Log (SAL), or the
Intervention at the local or remote system or partition serviceable event view you are using, on the remote
may be required. Possible causes are: system or partition for HSL Opticonnect problems that
v time out of a critical message occurred at approximately the same time this error
occurred.
v LIC code / table problem
v Network deadlock detected Collect all the Product Activity Log information for this
failure on all systems and partitions on this HSL loop.
The problem may be with: Be sure to record all words in the SRCs. Contact your
v The local system or partition next level of support with the information you have
v The remote system or partition collected.
Failing Item:
Examine the Service Action Log (SAL), or serviceable v AJDG301
event view you are using, on the local system or
partition for HSL failures on the same HSL loop, or v REM_SYS
with the Network Interface Controller at approximately v LOC_SYS
the same time this error occurred.
A6xx69CF A6xx69CF
Examine the remote system or partition for problems.
Examine the Service Action Log (SAL), or serviceable Explanation: HSL Opticonnect abnormal disconnect
event view you are using, on the remote system or from other sys. or partition.
partition for problems on the same HSL loop or with
Response: LIC internal error. All systems participating
the Network Interface Controller at approximately the
in HSL OptiConnect will be disconnected. The system
same time this error occurred.
must be re-IPL'd to recover. Before re-IPL'ing the
system initiate a main store dump.
Correct any problems you find with the remote and
local systems or partitions that happened at After getting the dump, examine the Service Action
approximately the same time and involve HSL Log (SAL), or serviceable event view you are using, on
Opticonnect or HSL loop components or Network the local system or partition for HSL Opticonnect
Interface Controllers. failures that occurred at approximately the same time
this error occurred.
If there are no problems with the remote system or Examine the remote systems or partitions for problems.
partition and there are no problems with the local Examine the Service Action Log (SAL), or serviceable
system or partition then collect all the Product Activity event view you are using, on the remote systems or
Log information for this failure on all systems or partitions for HSL Opticonnect problems that occurred
partitions. Be sure to record all words in the SRCs. at approximately the same time this error occurred.
Contact your next level of support.
Collect all the Product Activity Log information for this
Failing Item: failure on all systems and partitions on this HSL loop.
v REM_SYS Be sure to record all words in the SRCs. Contact your
v LOC_SYS next level of support with the information you have
collected.
v AJDG301
Failing Item:
A6xx69C9 A6xx69C9 v AJDG301
Response: The local system or partition disconnected Explanation: Bus Expansion Adapter card failed
from a remote system or partition due to an failure in a Response: Contact your next level of support.
LIC virtualized bus unit. LIC will attempt to recover
from the error. Possible causes are: Failing Item:
v LIC problem where the local bus unit is off line. v NEXTLVL
v LIC problem where the remote bus unit is off line.
A6xx69DC A6xx69DC
A6xx69F8 A6xx69F8
Explanation: The HEA is not connected to the
Ethernet switch Explanation: Bus Expansion Adapter failed
Response: The Host Ethernet Adapter (HEA) is not Response: Contact your next level of support.
connected to the Ethernet switch. If the HEA Failing Item:
connection is not needed, no service action is required.
v NEXTLVL
If the HEA connection is needed, verify that the cable is
connected and the switch is powered on. After
A6xx7001 A6xx7001
repairing the problem, verify that the connection has
been restored. Explanation: ISDN call in rejected
Failing Item:
A6xx69DD A6xx69DD v UG3LB
Explanation: The HEA connection to the Ethernet
switch has been restored A6xx7004 A6xx7004
Response: System log entry only, no service action Explanation: TCP/IP informational error
required.
Response: This reference code is logged when the
TCP/IP Attribute Log Protocol Errors is set, and the
TCP/IP System LIC silently discards an in bound
datagram. Silently discard is defined to mean discard
the received datagram without reporting an error to the
originating host device. Examples of such datagrams
A6xx7202 A6xx7202
A6xx7704 A6xx7704
Explanation: Utility power restored
Explanation: General failure detected by HRI
Response: This reference code is for information only. component.
The Uninterruptible Power System (UPS) is reporting
Failing Item:
that utility power has been restored.
v AJDG301
A6xx7203 A6xx7203
A6xx7777 A6xx7777
Explanation: A battery low condition was detected
Explanation: Hardware configuration change detected
Response: This reference code is for information only.
The Uninterruptible Power System (UPS) is reporting a Response: A hardware resource is missing. The
battery low condition. resource reported in to the system on a previous IPL,
but has not reported in on the current IPL. This could
occur for several different reasons.
A6xx7204 A6xx7204
1. It could be a normal situation where the resource is
Explanation: Uninterruptible Power System reported a currently powered off. In this case, when the
bypass active resource is powered back on, it will no longer be
missing.
Response: This reference code is for information only.
The Uninterruptible Power System (UPS) is reporting a 2. The hardware resource could also be missing if it
bypass is active. has been removed from the system, for example, a
tape drive that was replaced with a different tape
drive. The service representative should use the
A6xx7205 A6xx7205 Hardware service manager to remove the entry for
this resource.
Explanation: Battery low condition was reset
3. The resource may not have reported in on this IPL
Response: This reference code is for information only. because it is failing. Perform problem analysis to
The Uninterruptible Power System (UPS) is no longer determine why the resource is failing.
reporting a battery low condition.
A6xxCFFC A6xxCFFC
A6xxFDC5 A6xxFDC5
Explanation: Optical library device condition not
expected Explanation: LIC program failed and data was
captured
Response: The optical disk drive addressing within
the optical library is incorrect. This error is likely to be Response: This reference code indicates first failure
the result of faulty cabling or switch setting following data capture (FFDC) data was collected for a problem
service to an optical library. reported by licensed internal code.
Contact your hardware service provider. The user should dial IBM Software Support for
assistance.
Failing Item:
Failing Item:
v OPTLCBL
v UG3AS
v DRVSWCH
A6xxCFFD A6xxCFFD
Explanation: Optical drive failure
Failing Item:
v OPTLDRV
A6xxCFFF A6xxCFFF
Explanation: Media determined to be bad in Optical
library
A6xxF103 A6xxF103
Explanation: Main storage dump must be copied for
service
Failing Item:
v LICIP01
A6xxF104 A6xxF104
Explanation: LPAR service function directed a Main
Storage Dump.
Response: The Hypervisor terminated a partition with
an unresponsive Operating System. A Main Store
Dump must be done for service. Call your next level of
support when the dump is complete.
Failing Item:
v LICIP01
A6xxF105 A6xxF105
Explanation: Licensed Internal Code detected error
Failing Item:
v NEXTLVL
Failing Item:
A700173A A700173A
v NEXTLVL
Explanation: A VPD collection overflow occurred
A7001160 A7001160 Response: Look for and resolve other errors in the
serviceable event view. If that does not resolve the
Explanation: Service processor failure
problem, check for firmware updates and install them,
Response: Work with the FRU list in the serviceable if available. If that does not resolve the problem,
event view if there is one, otherwise use the FRU list contact your next level of support.
documented here to determine the parts to exchange.
Failing Item:
The platform encountered an error communicating with v SVCDOCS
the service processor. The platform code attempts a
graceful shutdown of partitions and powers off the
server after a certain time, or when the last partition A700173C A700173C
indicates shutdown, whichever comes first. Explanation: Generic Asset Protection Event. No
Failing Item: service action is required.
v LICCODE Response:
v SVCPROC Problem determination:
v PSI_LNK
A7003000 A7003000
Explanation: User-initiated PHYP-generated Demand function is required, re-IPL the system. If that
SYSDUMP. does not correct the problem, contact your next level of
support.
Response: No service action required.
Failing Item:
A7003003 A7003003 v LICCODE
Work with the FRU list in the serviceable event view if Failing Item:
there is one, otherwise use the FRU list documented v SVCDOCS
here to determine the parts to exchange. v CAPACTY
Failing Item:
v CAPACTY A7004712 A7004712
Explanation: Platform LIC detected the VPD card is
A7004703 A7004703 missing
Explanation: Platform LIC failure Response: A problem occurred when initializing,
reading, or using system VPD.
Response: A problem occurred when initializing,
reading, or using system VPD. The Capacity on Work with the FRU list in the serviceable event view if
Demand function is not available. If Capacity on there is one, otherwise use the FRU list documented
here to determine the parts to exchange. you have obtained a valid WWPN value, go to ASM
and select: System_Configuration->
Failing Item:
Program_Vital_Product_Data-> System_Keywords. On
v CAPACTY the System_Keyword menu, enter the value for the
'WN' keyword.
A7004713 A7004713 Failing Item:
Explanation: Platform LIC detected an error v SVCDOCS
Explanation: Platform LIC detected an error Explanation: Platform LIC detected an error
Response: A problem occurred when initializing, Response: The system has been running with full
reading, or using system VPD during concurrent Capacity on Demand resources activated. In one hour,
maintenance. the system will terminate and unlicensed resources will
no longer be available. To prevent the system from
Look for errors with SRCs of the form B1xxxxxx in the terminating, enter an activation code of all zeroes. Then
Serviceable Event View. Work those errors first. If that obtain the proper activation codes for the resources
does not correct the problem, replace the VPD card. being used or allocate fewer resources in the LPAR
configuration.
Work with the FRU list in the serviceable event view if
there is one, otherwise use the FRU list documented Failing Item:
here to determine the parts to exchange. v SVCDOCS
Failing Item:
v SVCDOCS A7004733 A7004733
v CAPACTY Explanation: Platform LIC failure
Response: The Capacity on Demand function is not
A7004716 A7004716 available. If Capacity on Demand function is required,
Explanation: User intervention required re-IPL the system. If that does not correct the problem,
contact your next level of support.
Response: The Capacity on Demand activation code
recovery period has been started. Either obtain more
capacity by obtaining new activation codes or allocate A7004740 A7004740
fewer resources in the LPAR configuration. Explanation: Platform LIC detected an error
Failing Item: Response: An incorrect activation code has been
v SVCDOCS detected. Resources associated with this activation code
v LPARCFG have been disabled. Enter a valid activation code.
Explanation: The World Wide Port Name (WWPN) Explanation: Platform LIC detected an error
Prefix is not valid. Response: The number of allowable attempts to enter
Response: Contact your hardware service provider to a valid activation code has been exceeded. The system
obtain a valid World-Wide Port Name (WWPN). Once will continue to run, but a system IPL is required in
order to retry entering a valid activation code. have been used to set AMM to "ON" for the system.
However, at IPL time, the system does not have a valid
license for AMM. The customer needs to contact IBM
A7004742 A7004742
or a Partner Sales representative to purchase and enter
Explanation: Platform LIC detected an error an Activation Code for this feature. If this is not
possible, then turn off the system; use FSP or HMC
Response: A communications problem with the interfaces to turn AMM "OFF"; and re-IPL.
service processor occurred. No Capacity on Demand
changes can be made, but you can continue to run with Failing Item:
the current Capacity on Demand resources. v SVCDOCS
Look for errors with SRCs of the form B1xxxxxx or
B7xx69xx in the Serviceable Event View. Work those A7004750 A7004750
errors first. If that does not correct the problem, re-IPL
the system. If that does not correct the problem, contact Explanation: A Capacity on Demand change has been
your next level of support. detected
A7004788 A7004788
A7004747 A7004747
Explanation: System log entry only, no service action
Explanation: User intervention required
required
Response: One hour remains until the On/Off
Response: The data obtained from the system is not
Capacity on Demand request expires. Permanently
what was expected. The IPL will continue. Should other
activate the temporary Capacity on Demand resources,
errors occur, contact your next level of support.
enter a new On/Off Capacity on Demand request for
the temporary resources, or remove all temporary
resources from partitions before the request expires. A70047C1 A70047C1
Failing Item: Explanation: Capacity on Demand data mismatch
v SVCDOCS Response: The data obtained from the system is not
what was expected. The system will perform a slow
A7004748 A7004748 IPL in order to obtain the correct data. If other errors
occur, contact your next level of support.
Explanation: User intervention required
Response: One hour remains until the Utility Capacity A70047CB A70047CB
on Demand enablement expires. In order to reactivate
temporary resources, a new Utility Capacity on Explanation: Fast system IPL changed to slow system
Demand enablement code is required. IPL
Failing Item: Response: The data obtained from the system is not
what was expected. The system will perform a slow
v SVCDOCS
IPL in order to obtain the correct data. If other errors
occur, contact your next level of support.
A7004749 A7004749
Explanation: User intervention required A70047CD A70047CD
Response: One hour remains until the Trial Customer Explanation: Platform LIC detected an error
on Demand activation expires. Obtain a permanent
Response: The server detected a not valid Capacity
activation code or remove all temporary resources from
On Demand activation and terminated the system. The
partitions before the request expires.
allocated resources for the system might exceed those
Failing Item: that are available for use.
v SVCDOCS Failing Item:
v SVCDOCS
A700474A A700474A
Explanation: System has Active Memory Mirroring
(AMM) ON, but is not licensed for AMM use
Problem determination: The FSP or HMC interfaces
A70047FF A70047FF
Explanation: System log entry only, no service action
required
Response: The Capacity on Demand History Log has
been written to the error log. No service action is
required.
A700C2AC A700C2AC
Explanation: System log entry only, no service action
required
Response: The Capacity on Demand License
acceptance has completed.
No corrective action is required.
Failing Item:
v SVCDOCS
A7013003 A7013003
Explanation: Partition-initiated PHYP-content
RSCDUMP.
Response: No service action required.
Note: Click the failing item in the FRU list only when you experience a hang condition on an attention
code. For example, a hang condition occurs when your server performs a requested action but the SRC in
the control panel display does not change for several minutes and the partition firmware appears to be
hung.
Explanation: Waiting for serial connection to the Explanation: A keyboard was not found
service processor to be established
AA06000B AA06000B
AA00E175 AA00E175 Explanation: The system or partition was not able to
Explanation: The I/O configuration exceeds the find an operating system on any of the devices in the
recommended size. Some operating systems might boot list.
crash when using this configuration.
Failing Item: AA06000C AA06000C
v FWFLASH Explanation: The media specified in a device in the
bootlist was not bootable
AA00E1A8 AA00E1A8
AA06000D AA06000D
Explanation: The system is booting to the open
firmware prompt Explanation: The media in the device in the bootlist
not found under the I/O adapter specified by the boot
Failing Item:
list.
v FWFLASH
AA06000E AA06000E
AA00E1A9 AA00E1A9
Explanation: The adapter specified in the boot list is
Explanation: The system is booting to the SMS menus not present or not functioning.
Failing Item:
v FWFLASH AA060010 AA060010
Explanation: The FAT filesystem on the bootdisk is
AA00E1B0 AA00E1B0 configured in a way that may cause a boot failure.
Explanation: Waiting for the user to select language
and keyboard. AA060011 AA060011
Explanation: The firmware did not find the operating
AA00E1B1 AA00E1B1 system image and is was unable to detect at least one
hard disk in the boot list. Firmware is now retrying the
Explanation: Waiting for the user to accept or decline
entries in the boot list. This often occurs when the boot
the license agreement.
disk enclosure is not yet fully initialized or if the boot
disk belongs to a server partition.
AA00E1F3 AA00E1F3
Problem determination: This error might occur before
AA170211 AA170211
Explanation: Setenv/$Setenv parameter error - value
contains a null character
Failing Item:
v FWFLASH
AA170212 AA170212
Explanation: Setenv/$Setenv parameter error: name is
null or too long. The name length is limited to 31
characters.
Failing Item:
v FWFLASH
AA190001 AA190001
Explanation: The server firmware function to get and
set the time-of-day reported an error.
The manufacturer may not offer the products, services, or features discussed in this document in other
countries. Consult the manufacturer's representative for information on the products and services
currently available in your area. Any reference to the manufacturer's product, program, or service is not
intended to state or imply that only that product, program, or service may be used. Any functionally
equivalent product, program, or service that does not infringe any intellectual property right of the
manufacturer may be used instead. However, it is the user's responsibility to evaluate and verify the
operation of any product, program, or service.
The manufacturer may have patents or pending patent applications covering subject matter described in
this document. The furnishing of this document does not grant you any license to these patents. You can
send license inquiries, in writing, to the manufacturer.
The following paragraph does not apply to the United Kingdom or any other country where such
provisions are inconsistent with local law: THIS INFORMATION IS PROVIDED “AS IS” WITHOUT
WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO,
THE IMPLIED WARRANTIES OF NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE. Some states do not allow disclaimer of express or implied warranties in certain
transactions, therefore, this statement may not apply to you.
This information could include technical inaccuracies or typographical errors. Changes are periodically
made to the information herein; these changes will be incorporated in new editions of the publication.
The manufacturer may make improvements and/or changes in the product(s) and/or the program(s)
described in this publication at any time without notice.
Any references in this information to websites not owned by the manufacturer are provided for
convenience only and do not in any manner serve as an endorsement of those websites. The materials at
those websites are not part of the materials for this product and use of those websites is at your own risk.
The manufacturer may use or distribute any of the information you supply in any way it believes
appropriate without incurring any obligation to you.
Any performance data contained herein was determined in a controlled environment. Therefore, the
results obtained in other operating environments may vary significantly. Some measurements may have
been made on development-level systems and there is no guarantee that these measurements will be the
same on generally available systems. Furthermore, some measurements may have been estimated through
extrapolation. Actual results may vary. Users of this document should verify the applicable data for their
specific environment.
Information concerning products not produced by this manufacturer was obtained from the suppliers of
those products, their published announcements or other publicly available sources. This manufacturer has
not tested those products and cannot confirm the accuracy of performance, compatibility or any other
claims related to products not produced by this manufacturer. Questions on the capabilities of products
not produced by this manufacturer should be addressed to the suppliers of those products.
All statements regarding the manufacturer's future direction or intent are subject to change or withdrawal
without notice, and represent goals and objectives only.
The manufacturer's prices shown are the manufacturer's suggested retail prices, are current and are
subject to change without notice. Dealer prices may vary.
This information contains examples of data and reports used in daily business operations. To illustrate
them as completely as possible, the examples include the names of individuals, companies, brands, and
products. All of these names are fictitious and any similarity to the names and addresses used by an
actual business enterprise is entirely coincidental.
If you are viewing this information in softcopy, the photographs and color illustrations may not appear.
The drawings and specifications contained herein shall not be reproduced in whole or in part without the
written permission of the manufacturer.
The manufacturer has prepared this information for use with the specific machines indicated. The
manufacturer makes no representations that it is suitable for any other purpose.
The manufacturer's computer systems contain mechanisms designed to reduce the possibility of
undetected data corruption or loss. This risk, however, cannot be eliminated. Users who experience
unplanned outages, system failures, power fluctuations or outages, or component failures must verify the
accuracy of operations performed and data saved or transmitted by the system at or near the time of the
outage or failure. In addition, users must establish procedures to ensure that there is independent data
verification before relying on such data in sensitive or critical operations. Users should periodically check
the manufacturer's support websites for updated information and fixes applicable to the system and
related software.
This product is not intended to be connected directly or indirectly by any means whatsoever to interfaces
of public telecommunications networks.
Trademarks
IBM, the IBM logo, and ibm.com are trademarks or registered trademarks of International Business
Machines Corp., registered in many jurisdictions worldwide. Other product and service names might be
trademarks of IBM or other companies. A current list of IBM trademarks is available on the Web at
Copyright and trademark information at www.ibm.com/legal/copytrade.shtml.
INFINIBAND, InfiniBand Trade Association, and the INFINIBAND design marks are trademarks and/or
service marks of the INFINIBAND Trade Association.
Linux is a registered trademark of Linus Torvalds in the United States, other countries, or both.
Java and all Java-based trademarks and logos are trademarks or registered trademarks of Oracle and/or
its affiliates.
UNIX is a registered trademark of The Open Group in the United States and other countries.
Other product and service names might be trademarks of IBM or other companies.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference, in which case the user will be
required to correct the interference at his own expense.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission
limits. IBM is not responsible for any radio or television interference caused by using other than
recommended cables and connectors or by unauthorized changes or modifications to this equipment.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
This product is in conformity with the protection requirements of EU Council Directive 2004/108/EC on
the approximation of the laws of the Member States relating to electromagnetic compatibility. IBM cannot
accept responsibility for any failure to satisfy the protection requirements resulting from a
non-recommended modification of the product, including the fitting of non-IBM option cards.
This product has been tested and found to comply with the limits for Class A Information Technology
Equipment according to European Standard EN 55022. The limits for Class A equipment were derived for
commercial and industrial environments to provide reasonable protection against interference with
licensed communication equipment.
Warning: This is a Class A product. In a domestic environment, this product may cause radio
interference, in which case the user may be required to take adequate measures.
Notices 1301
VCCI Statement - Japan
The following is a summary of the VCCI Japanese statement in the box above:
This is a Class A product based on the standard of the VCCI Council. If this equipment is used in a
domestic environment, radio interference may occur, in which case, the user may be required to take
corrective actions.
Declaration: This is a Class A product. In a domestic environment this product may cause radio
interference in which case the user may need to perform practical action.
Warning: This is a Class A product. In a domestic environment this product may cause radio interference
in which case the user will be required to take adequate measures.
Dieses Produkt entspricht den Schutzanforderungen der EU-Richtlinie 2004/108/EG zur Angleichung der
Rechtsvorschriften über die elektromagnetische Verträglichkeit in den EU-Mitgliedsstaaten und hält die
Grenzwerte der EN 55022 Klasse A ein.
Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu
betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM
übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne
Zustimmung von IBM verändert bzw. wenn Erweiterungskomponenten von Fremdherstellern ohne
Empfehlung von IBM gesteckt/eingebaut werden.
Notices 1303
EN 55022 Klasse A Geräte müssen mit folgendem Warnhinweis versehen werden:
"Warnung: Dieses ist eine Einrichtung der Klasse A. Diese Einrichtung kann im Wohnbereich
Funk-Störungen verursachen; in diesem Fall kann vom Betreiber verlangt werden, angemessene
Maßnahmen zu ergreifen und dafür aufzukommen."
Deutschland: Einhaltung des Gesetzes über die elektromagnetische Verträglichkeit von Geräten
Dieses Produkt entspricht dem “Gesetz über die elektromagnetische Verträglichkeit von Geräten
(EMVG)“. Dies ist die Umsetzung der EU-Richtlinie 2004/108/EG in der Bundesrepublik Deutschland.
Zulassungsbescheinigung laut dem Deutschen Gesetz über die elektromagnetische Verträglichkeit von
Geräten (EMVG) (bzw. der EMC EG Richtlinie 2004/108/EG) für Geräte der Klasse A
Dieses Gerät ist berechtigt, in Übereinstimmung mit dem Deutschen EMVG das EG-Konformitätszeichen
- CE - zu führen.
Verantwortlich für die Einhaltung der EMV Vorschriften ist der Hersteller:
International Business Machines Corp.
New Orchard Road
Armonk, New York 10504
Tel: 914-499-1900
Generelle Informationen:
Das Gerät erfüllt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse A.
Class B Notices
The following Class B statements apply to features designated as electromagnetic compatibility (EMC)
Class B in the feature installation information.
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation.
If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference
by one or more of the following measures:
v Reorient or relocate the receiving antenna.
v Increase the separation between the equipment and receiver.
v Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
v Consult an IBM-authorized dealer or service representative for help.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission
limits. Proper cables and connectors are available from IBM-authorized dealers. IBM is not responsible for
any radio or television interference caused by unauthorized changes or modifications to this equipment.
Unauthorized changes or modifications could void the user's authority to operate this equipment.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
This product is in conformity with the protection requirements of EU Council Directive 2004/108/EC on
the approximation of the laws of the Member States relating to electromagnetic compatibility. IBM cannot
accept responsibility for any failure to satisfy the protection requirements resulting from a
non-recommended modification of the product, including the fitting of non-IBM option cards.
This product has been tested and found to comply with the limits for Class B Information Technology
Equipment according to European Standard EN 55022. The limits for Class B equipment were derived for
typical residential environments to provide reasonable protection against interference with licensed
communication equipment.
Notices 1305
VCCI Statement - Japan
Um dieses sicherzustellen, sind die Geräte wie in den Handbüchern beschrieben zu installieren und zu
betreiben. Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden. IBM
übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen, wenn das Produkt ohne
Zustimmung von IBM verändert bzw. wenn Erweiterungskomponenten von Fremdherstellern ohne
Empfehlung von IBM gesteckt/eingebaut werden.
Deutschland: Einhaltung des Gesetzes über die elektromagnetische Verträglichkeit von Geräten
Dieses Produkt entspricht dem “Gesetz über die elektromagnetische Verträglichkeit von Geräten
(EMVG)“. Dies ist die Umsetzung der EU-Richtlinie 2004/108/EG in der Bundesrepublik Deutschland.
Zulassungsbescheinigung laut dem Deutschen Gesetz über die elektromagnetische Verträglichkeit von
Geräten (EMVG) (bzw. der EMC EG Richtlinie 2004/108/EG) für Geräte der Klasse B
Dieses Gerät ist berechtigt, in Übereinstimmung mit dem Deutschen EMVG das EG-Konformitätszeichen
- CE - zu führen.
Verantwortlich für die Einhaltung der EMV Vorschriften ist der Hersteller:
International Business Machines Corp.
New Orchard Road
Armonk, New York 10504
Tel: 914-499-1900
Generelle Informationen:
Das Gerät erfüllt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse B.
Personal Use: You may reproduce these publications for your personal, noncommercial use provided that
all proprietary notices are preserved. You may not distribute, display or make derivative works of these
publications, or any portion thereof, without the express consent of the manufacturer.
Commercial Use: You may reproduce, distribute and display these publications solely within your
enterprise provided that all proprietary notices are preserved. You may not make derivative works of
these publications, or reproduce, distribute or display these publications or any portion thereof outside
your enterprise, without the express consent of the manufacturer.
Except as expressly granted in this permission, no other permissions, licenses or rights are granted, either
express or implied, to the publications or any information, data, software or other intellectual property
contained therein.
Notices 1307
The manufacturer reserves the right to withdraw the permissions granted herein whenever, in its