BUR-8191
general
technical data
1)
gas flow rate V/t min. 32 mi.N.³/h 31 m³/h
1)
max. 100 mi.N.³/h 104 m³/h
gas flow pressure* p d min. 5 mbarg (min. gas flow)
max. 50 mbarg (max. gas flow)
methane concentration max. 75 vol.%
calorific value H i max. 7,5 kWh/mi.N.³ 1)
combustion rate P th min. 237 kW
max. 750 kW
safety switch p min 4 mbarg
average combustion temperature T C appr. 800 °C
open flame
x enclosed flame
burner type atmospheric injection burner
safety guidelines ATEX, fail-safe
flare control x external/ potential-free contact (static signal)
x local (manual)
x gas pressure (automatic)
gas temperature T appr. 25 °C
min. 0 °C
max. 60 °C
distance to buildings D min. 5-10 m
gas flow-velocity v max. 20 m/s
Ex group medium IIA1
ATEX zone medium none (not explosive)
dimensions
materials
scope of delivery