data sheet

specification
BUR-8191

general

flare type LTU 0,8


medium sewage biogas
operation condition emergency flare
offer no. 11-1076 Rev. 02

technical data

1)
gas flow rate V/t min. 32 mi.N.³/h 31 m³/h
1)
max. 100 mi.N.³/h 104 m³/h
gas flow pressure* p d min. 5 mbarg (min. gas flow)
max. 50 mbarg (max. gas flow)
methane concentration max. 75 vol.%
calorific value H i max. 7,5 kWh/mi.N.³ 1)
combustion rate P th min. 237 kW
max. 750 kW
safety switch p min 4 mbarg
average combustion temperature T C appr. 800 °C
open flame
x enclosed flame
burner type atmospheric injection burner
safety guidelines ATEX, fail-safe
flare control x external/ potential-free contact (static signal)
x local (manual)
x gas pressure (automatic)
gas temperature T appr. 25 °C
min. 0 °C
max. 60 °C
distance to buildings D min. 5-10 m
gas flow-velocity v max. 20 m/s
Ex group medium IIA1
ATEX zone medium none (not explosive)

dimensions

connection piping (flange) DN 50


PN 10 acc. to ISO 7005
height (from top of basement) H g 7000 mm
combustion-chamber height H b 4000 mm
combustion-chamber diameter d 508 mm
total weight appr. 500 kg

materials

combustion chamber stainless steel 1.4571 or the like


gas piping stainless steel 1.4404 or the like
burner stainless steel 1.4841 or the like (heat resistant)
stainless steel 1.4571 or the like
flare skid steel galvanized
x stainless steel 1.4301 or the like
fittings according to supplier
switchboard stainless steel 1.4301 or the like
*at nozzle plus pressure drop in gas train, minimum pressure ignition 25 mbarg
1)
standard cubic meters, standard conditions: 0 °C, 1 013 mbar

bb/ 16.06.2011 Page 1/ 2


data sheet
scope of delivery

scope of delivery

flare unit x combustion chamber


x flare skid
x identification plate
ignition x burner control unit acc. to EN 298
x ignition electrode
x flame sensor
x ignition transformer 7,5 kV
direct ignition
x reduced ignition burner (ball valve, pressure regulator)
ignition burner (ball valve, solenoid valve, pressure regulator, flame arrestor)

ignition burner can be used as a pilot burner as well


gas piping pneumatic* slam shut valve (t<1 sec)
x motorized slam shut valve (t<1 sec**)
x flame arrestor acc. to EN ISO 16852:2010
temperature monitoring of the flame arrestor (PT100)
x manual butterfly valve (ball valve)
x condensate tank with ball valve
x pressure switch ON
pressure switch OFF
x safety pressure switch
x pressure gauge
special equipment insulation and heating of the piping
redundant slam shut valve
valve tightness control acc. to EN 298
fittings in Ex
identification labels for fittings
switchboard x switchboard outside with heating
x 115V/60Hz, approx. 350 W
x system configuration: TN-S acc. to IEC 60364-1:2005-11
cabinet light with door contact
x safety lock
processing of the pressure switches Ex ia (switch amplifier)
selection/deselection x remote start (potential-free contact as a static signal)
(remote signal) x gasholder level (2 potential-free contacts for min. and max.)
x remote reset
selector switches x flare operation: off/manual/auto
x automatic operation: pressure/remote/pressure+remote (key-switch)
pilot burner operation: on/off
status messages x operation
(potential-free contact + x failure
telltale light) failure of valve tightness control
documentation 1 paper format
1 digital on CD
x manual with maintenance plan
x flare drawing
x basement plan
basement statics (verifiable calculations)
x certificate for flame arrestor
x principle drawing
x CE certificate of conformity
fixation x screw anchor
*compressed air (6 bar, quality 4.3.2 according ISO 8573-1:2010) to be supplied by customer
**with electrical drive poss. larger

bb/ 16.06.2011 Page 2/ 2