Professional Documents
Culture Documents
Admapn059en 0916
Admapn059en 0916
system
2100 RPM resistance
8
curve
7 1900 RPM
6
1700 RPM
5
1500 RPM
4
1300 RPM
3 B A
1100 RPM
2
900 RPM
10.00 hp
15.00 hp
20.00 hp
1.50 hp
2.00 hp
3.00 hp
5.00 hp
7.50 hp
1
0
0 2500 5000 7500 10000 12500 15000 17500 20000 22500
airflow (cfm)
2 Trane Engineers Newsletter volume 45–3 providing insights for today’s HVAC system designer
best performance (predicted by the affinity Reliability and lower installed cost. The
laws) as shown in Figure 3. When position of the supply static pressure
Damper High- and Low-Limits
operated with a constant duct pressure sensor matters less when the system is
Note that VAV dampers do not operate setpoint, the fan consumes 3.2 run with fan pressure optimization because
in a linear fashion. As shown in Figure 2. horsepower at part-speed to deliver 6600 its setpoint is continually reset. This allows
Most airflow variation occurs between cfm (B). When the same fan is operated the sensor to be factory-tested and
20 and 80% open. For stable
operation,a more-linear portion of the
with fan pressure optimization to deliver installed at the outlet, which reduces
curve should be used for control. the same volume of air, it operates at a installed cost and increases reliability.
lower pressure and consumes 2.5
The system controller polls the VAV box horsepower (B'). In addition to reducing
controllers to determine the critical zone
Proper operation. Fan pressure
the energy consumed by the supply fan optimization and DDC control allow the
based upon the farthest-open VAV
damper. If this damper is less than 65% during part-load operation, there are other system and operators to identify, correct,
open (point A), the duct static pressure benefits. and/or ignore rogue zones. A rogue zone
setpoint is decreased; if it's more than
can prevent the duct static pressure from
75% open (point B), the setpoint is
increased; and if it's between 65% and Surge avoidance. When running at being reset downward because it requires
75% open, the duct pressure setpoint reduced speed and generating lower static nearly constant airflow. Sometimes, this
remains unchanged. pressure, the fan operates farther from the indicates one of several possible problems:
surge region compared to traditional duct
• undersized VAV box,
Figure 2. VAV damper position static pressure control.
versus airflow • obstruction in supply duct to zone
Acoustics. The fan itself generates less (such as crimped flex duct),
100% B noise at lower speed and the further-open • improperly located or malfunctioning
A
dampers produce less noise in each box. zone sensor.
airflow
7 1900 RPM
6 VAV system
VAV system1700 RPM
5 modulation
modulation curve with
R
1500 RPM
4 curve with fan pressure
constantP
1300 RPM optimization
3 duct A
1100 RPM
B
2 pressure
900 RPM
control B’
10.00 hp
15.00 hp
20.00 hp
1.50 hp
2.00 hp
3.00 hp
5.00 hp
7.50 hp
1
0
0 2500 5000 7500 10000 12500 15000 17500 20000 22500
airflow (cfm)
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 45–3 3
During operation, the system controller Figure 4. VAV damper position as a function of time
gathers data about the damper position.
100
Over time, this data can be plotted to help VAV 2-15
the building operator identify any potential 90
rogue zones. For example, consider the
damper positions (shown in Figure 4) 80
4 Trane Engineers Newsletter volume 45–3 providing insights for today’s HVAC system designer
compressor, reheat, and fan energy, and Figure 5. Supply-air- temperature reset based upon outdoor air dry-bulb
the impact on space humidity levels. temperature
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 45–3 5
damper is reported, the system can Figure 6. Supply-air-temperature reset based upon outdoor air temperature and
determine if it has reset too much and VAV damper position
respond by again lowering the SA
temperature setpoint.
SA temperature setpoint, °F
60
55°F but can be reset upward by as
much as 5 degrees to 60°F during cooler
59
outdoor temperatures. When the
outdoor air temperature is above 65°F, no 58
reset occurs and the system delivers
55°F air. The temperature at which reset reset based on
57
worst case zone
begins (below 65°F) can be adjusted to
suit the climate and installation. 56
55
Considerations for supply-air-
temperature reset. The economizer
high-limit shutoff setpoint temperature is 45 50 55 60 65 70 75
often used as the setpoint to begin SA outdoor dry-bulb temperature, °F
temperature reset.
The amount of reset can vary as well. methodologies were evaluated using The optimal SA temperature schedule
Systems serving zones that require more energy modeling. Based on the results, from the study is reproduced as Figure 7.
cooling year-round (e.g. interior they stated: "it appears that it is best to
conference rooms) should limit the reset the supply air temperature upwards In both cases, it was found that keeping
amount of reset, while systems that until the outdoor air temperature exceeds the SA cold (rather than resetting upward)
serve zones with a mixture of heating 65°F or 70°F, then reduce the supply-air during warmer weather was more
and cooling typically benefit from higher temperature to [the minimum] in order to efficient. The CEC guideline concludes
SA temperatures. minimize fan energy and rely on the chiller that "the recommended control sequence
for cooling." [2] is to lead with supply temperature
Some designers might choose to setpoint reset in cool weather where
monitor indoor space humidity levels as This is reinforced by earlier research from reheat might dominate the equation and to
well. When space humidity rises above a Texas A&M University. In a study, they keep the chillers off as long as possible,
specific threshold, say 60 percent RH, found that resetting the SA temperature then return to a fixed low setpoint in
the SA temperature is reset downward upward during mild weather (below warmer weather when the chillers are
to increase the dehumidification approximately 72°F) was optimal for a likely to be on. During reset, employ a
performed by the cooling coil. Similarly, VAV system serving a 3-story building [3]. demand-based control that uses the
designers may choose to monitor warmest supply air temperature that
outdoor dew-point temperature to limit satisfies all of the zones in cooling."
or disable reset during humid weather.
For example, when the outdoor air dew- Figure 7. Optimal SA temperature schedule from Texas A&M University
point temperature is greater than 60°F,
the SA temperature might not be
62
allowed to reset upward to avoid adding
humid air to the spaces.
60
SA temperature setpoint, °F
6 Trane Engineers Newsletter volume 45–3 providing insights for today’s HVAC system designer
This is consistent with reset based upon
ASHRAE's Proposed Guideline 36 outdoor air temperature and VAV damper ASHRAE Standard 90.1 Requirements -
position, as shown in Figure 6. Supply Air Temperature Reset
In January 2014, ASHRAE authorized the
creation of Proposed Guideline 36, High This same approach is recommended in the ANSI/ASHRAE/IES Standard 90.1 has
Performance Sequences of Operation for prescriptively required SA temperature reset
HVAC Systems, with the purpose to
public review draft of ASHRAE Guideline 36
for multiple-zone systems for many years.
"provide uniform sequences of operation (see sidebar).
The requirements allow SA temperature to
for heating, ventilating, and air- be automatically reset in response to either
conditioning (HVAC) systems that are building load or outdoor air temperature.
intended to maximize HVAC system energy
Combining supply-air-temperature reset
efficiency and performance, provide and fan pressure optimization. Some
Section 6.5.3.4 of the 2013 version of the
control stability, and allow for real-time designers might choose to minimize fan standard requires the SA temperature be
fault detection and diagnostics." power by resetting duct pressure downward reset by at least "25 percent of the
first, then raising the SA temperature setpoint difference between the design SA
The proposed guideline would provide temperature and the design room air
"detailed sequences of operation" for later, as discussed in "Reset based upon VAV
temperature." The standard also permits
systems and "functional tests that when damper position." control of reset based upon zone humidity.
performed will confirm implementation of Finally, it suggests zones with constant
the sequences of operation." Others might choose to reset both SA internal loads be designed for the reset SA
temperature and static pressure setpoints temperature instead of the design SA
The first public review draft suggested that temperature.
during the occupied mode, the highest SA
simultaneously, as discussed in "Reset based
temperature for a VAV system should be upon outdoor air temperature and VAV
There are three exceptions to this
65°F in mild and dry climates and 60°F in damper position." In this case, both SA requirement:
humid climates. The authors warn that SA temperature reset and fan pressure
temperatures greater than 65°F "may lead 1. Installations in hot and humid climate
optimization might use the same control
to excessive fan energy that can offset the zones 1A, 2A, and 3A
mechanical cooling savings from point—VAV damper position—to determine
economizer operation." operation. Some SA temperature reset 2. Systems that prevent reheating,
strategies use the position of the VAV recooling, or mixing of heated and
The authors suggest when reset should dampers to determine when to end reset and cooled SA
occur for typical outdoor air dry-bulb
temperatures:
return the SA temperature to the design
3. Systems that source at least 75 percent
setpoint. On the other hand, fan pressure
• The minimum (coldest) SA temperature of the annual energy used for reheat
optimization attempts to keep at least one from site-recovered or site-solar energy
should be delivered whenever outdoor
temperatures are warmer than 70°F. VAV damper nearly wide open to reduce fan
energy. These two control loops using the So for instance, consider an installation at
• The maximum reset SA temperature Flamborough Head on the Yorkshire coast of
should be delivered whenever outdoor
same data could result in some conflicts
England where the climate is cool and
temperatures are cooler than 60°F. during operation, so careful programming of humid. Here, the design SA temperature is
the control loops is essential. 55°F and the space cooling setpoint
The proposed guideline also includes a temperature is 75°F. The amount of reset
description and example of trim and Determining when to reset and optimize one needs to be at least 5°F, which is 25 percent
respond setpoint reset logic. This logic of the difference of 20°F. In this case, the
system variable before another is complex.
allows requests to reset the SA controller should be programmed to reset
temperature or static pressure setpoints to The decision could be based upon weather
from 55°F to at least 60°F to comply.
be sent to the central controller. Each zone conditions, building loads, HVAC system type, Because this is a coastal location, the
and request type can be assigned an and so on. Designers should consider designers may choose to monitor indoor
importance multiplier greater than one to evaluating options through energy modeling, humidity and discontinue reset when indoor
increase the rank of the specific zone relative humidity surpasses a threshold-
within the algorithms. Rogue zones are
then coordinate strategies with the controls
perhaps 60 percent RH.
identified using the request-hours data vendor, programmer, and building operators.
point. The default logic triggers an alarm
indicating a rogue zone when a specific
zone has run hours exceeding 40 and
request-hours greater than 70 percent. ASHRAE Standard 90.1 Requirements -
Conclusion Fan Pressure Optimization
Fan pressure optimization and supply-air ASHRAE Standard 90.1 has prescriptively
required the static pressure setpoint to be
temperature reset are both energy
reset for VAV systems when the system
conservation measures, prescriptively uses DDC controls and a central/system
required by ASHRAE Standard 90.1 (see controller for many years. Section 6.5.3.2.3
sidebar). They can be implemented relatively of the 2013 version also requires:
easily with modern controls. Both have been • System controls must monitor damper
used simultaneously to significantly reduce position or "other indicator of need for
the energy usage and operational cost of static pressure"
multiple-zone VAV systems. Not using one or • Automatic detection of rogue zones and
both should be the exception. Too often notification of these to the system
energy savings is left on the table. operator
providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 45–3 7
www.Trane.com/bookstore
References
Learn HVAC design strategies and earn credit
[1] Stanke, D., "VAV System Optimization Critical
Zone Reset," Trane Engineers Newsletter, vol.
20, no. 2, 1991.
Upcoming Trane Engineers Newsletter
[2] California Energy Commission, "Advanced LIVE Program!
Variable Air Volume System Design Guide," Acoustics in HVAC Outdoor
2003.
Applications. This program reviews the
[3] G. Wei, M. Liu and D. Claridge, "Optimize the analysis steps required to avoid noise
Supply Air Temperature Reset Schedule for a complaints caused by outdoor HVAC
Single-Duct VAV System," in Proceedings of the equipment. Topics include equipment and
Twelfth Symposium on Improving Building sound attenuation selection, equipment
Systems in Hot and Humid Climates, San
Antonio, 2000.
location, sound ordinances, barrier walls,
reflective surfaces and sound power to
[4] E. Sturm, "Airside Economizers and ASHRAE sound pressure conversion calculations.
Standard 90.1-2013." Trane Engineers Earn continuing education credit on- Contact your local Trane office for event
Newsletter, vol. 44-2, 2015.
demand for LEED® . 60 or 90-minute details.
[5] ANSI/ASHRAE/IES, Standard 90.1-2013 Energy on-demand programs are available free of Review past programs by visiting
Standard for Buildings Except Low-Rise charge. All courses are available at www.trane.com/ENL.
Residential Buildings (I-P Edition), Atlanta: www.trane.com/continuingeducation.
ASHRAE, 2013. The latest release of TRACE™ 700
[6] ANSI/ASHRAE/IES, Proposed Guideline 36, Air conditioning clinics. A series of focuses on updating and adding to the
High Performance Sequences of Operation for educational presentations that teach standard libraries included in the program.
HVAC Systems. Atlanta: ASHRAE, 2016. HVAC fundamentals, equipment, and Check out the latest release which
[7] J. Murphy, "Reaping the Benefits of Optimized
systems. The series includes full-color features the following
Control," The BOMA Magazine, p. 48, student workbooks, which can be
September/October 2013. purchased individually. Approved by the • ASHRAE Standard 90.1-2013
American Institute of Architects for 1.5 libraries. Previously the TRACE library
[8] Taylor Engineering, "Advanced Variable Air
(Health, Safety and Welfare) learning included equipment and constructions
Volume System Design Guide," 2007.
units per clinic. Contact your local Trane for 90.1–2004, 2007, and 2010. This
office to sign up for training in your area. has now been expanded to include
90.1-2013 equipment and
Application manuals. Comprehensive constructions to support the LEED v5.
reference guides that can increase your
• CVHS Library Trane Series S
working knowledge of commercial HVAC
CenTraVac™ chiller is now available
systems. Topics range from component
as cooling equipment library in the
combinations and innovative design
program. This can be found in the
concepts to system control strategies,
water-cooled chiller category.
industry issues, and fundamentals.
Remember, you can still import Trane
Visit www.trane.com/bookstore for a equipment selections from TOPSS®
complete list of manuals and to place into TRACE.
your order.
Visit www.Trane.com/TRACE to view
version details or download a free 30-day
trial.
Trane, Trane believes the facts and suggestions presented here to be accurate. However, final design and
A business of Ingersoll Rand application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.
For more information, contact your local Trane
TM ® The following are registered trademarks of United States Green Building Council: LEED
office or e-mail us at comfort@trane.com
TM ® The following are registered trademarks of Trane: TRACE and CenTraVac