KS 20-1

Universal Industrial Controller


• BluePort Front interface and BlueControl
software
• Maintenance manager and error list
• Start-up circuit and boost function
• Two switchable parameter sets
• Self-Tuning to the setpoint without oscillation
• Monitoring of heating current and output circuit
• 3-point controller for water, fan and oil cooling
• 16 x 16 segment profiler
• cULus

• 100 ms cycle time, i.e. also suitable APPLICATIONS parameters at setpoint. This function
for fast control loops does not require oscillation, and
•  Furnaces and ovens performs a minimal deviation of the
• 20ms as shortest pulse for very •  Burners and boilers process value.
fast / strong actuators (e.g. infrared •  Plastics processing
heater or water cooling •  Driers Display and operation
• Freely configurable analog output, •  Climatic chambers Clear information is given by indicator
e.g. as process value output •  Heat treatment plants LEDs in the front panel that displays
operating mode and I/O states. An
• Customer-specific linearization for DESCRIPTION F key switches the controller into
all sensors The universal temperature controller the several operation modes such
is intended for precise and cost- as manual, latched alarm reset or
• Extended temperature range up to effective control tasks in all branches activates the boost function directly.
60°C allows mounting close to the of industry. The unit can provide
process simple 2-point (on/off) control, Front interface and Engineering
• Easy 2-point or offset measurement continuous PID control, or 3-point Tools
correction stepping control. The process value It is possible to adjust parameters in
signal from a sensor is connected to seconds in KS 20-1 via BlueControl
• Emergency operation after sensor the universal input. A supplementary software with simulation function, the
break by means of the “output hold“ analog input is available for heating required set-up for a specific control
function current measurement or as an task can be determined without
external setpoint signal. a detailed study of the operating
• Logical combination of digital instructions.
outputs, e.g. for general alarm The function “start-up“ can be
• Programmer with 16 x 16 segments selected for increased lifetime of Additionally most adjustments can
and “end“ signal high performance electrical heating be made easily from the instrument
elements (e.g. hot runner moulds). front. (see page 7, BlueControl)
• RS 485 Modbus RTU interface
Password protection
• Built-in transmitter power supply Self-tuning during start-up and to If required, the various operating
• Splash-water proof front (IP 65) the setpoint levels can be protected with a
This function determines the optimum password to prevent unauthorized
settings for fast ramp to setpoint access.
with no overshoot. Using three-
point controller configuration, the
“cooling“ parameters are determined
separately, ensuring an optimum
performance matched to the process.

On a single keypress the controller


can determine the best PID control

1 KS 20-1 Datasheet
TECHNICAL DATA Table 1. Thermocouple ranges
INPUTS Thermocouple Range Accuracy Resolution (Ø)
L Fe-CuNi (DIN) -100...900°C -148...1652°F ≤2K 0.1 K
PROCESS VALUE INPUT INP1
J Fe-CuNi -100...1200°C -148...2192°F ≤2K 0.1 K
Resolution: > 14 bit K NiCr-Ni -100...1350°C -148...2462°F ≤2K 0.2 K
Decimal point: 0 to 3 decimals
Digital input filter: adjustable 0,000...9999 s N Nicrosil/Nisil -100...1300°C -148...2372°F ≤2K 0.2 K
Scanning cycle: 100 ms S PtRh-Pt 10% 0...1760°C 32...3200°F ≤2K 0.2 K
Measured value
R PtRh-Pt 13% 0...1760°C 32...3200°F ≤2K 0.2K
correction: 2-point or offset correction
T Cu-CuNi -200...400°C -328...752°F ≤2K 0.1 K
Thermocouples (Table 1) C W5%Re-W26%Re 0...2315°C 32...4199°F ≤2K 0.1 K
Input impedance: 1 MΩ D W3%Re-W25%Re 0...2315°C 32...4199°F ≤2K 0.1 K
Effect of source resistance: 1 V/Ω
 E NiCr-CuNi -100...-1000°C -148...1832°F ≤2K 0.1 K
Cold junction compensation B PtRh-Pt6% 0...1820°C 32...3308°F ≤3K 0.2 K
Max. additional error < 0.5 K
special -25...75 mV ≤1% 0.01%
Sensor break monitoring
Sensor current: ≤ 1 µA Table 2. Resistance transducers
Operating sense configurable (see page 4) Type Sensor current Range Accuracy Resolution (Ø)
Pt100 -200...850°C -328...1562°F ≤1K 0.1 K
Resistance thermometer
Connection: 3-wire Pt1000 0.2 mA -200...200°C -328...392°F ≤2K 0.1 K
Lead resistance: max. 30Ω
KTY 11-6* -50...150°C -58...302°F ≤2K 0.05 K
Input circuit monitor: Break and short circuit
*or special resistive input 0...4500 Ω (connecting as PT 100)

Table 3. Current and voltage


Range Input resistance Accuracy Resolution (Ø)
0-10 Volt ≈ 110 KΩ ≤ 0.1 % 0.6 mV
0-20 mA 5 Ω (voltage requirement ≤ 1.0 V) ≤ 0.1 % 1.5 μA

Electrical Connections

2 KS 20-1 Datasheet
Current and voltage signals Start-up circuit
Span start, end of span: anywhere within
measuring range
Scaling: selectable -1999...9999
When the process is controlled towards the start-up setpoint, the output value
Linearization: 16 segments, adaptable is limited. The start-up setpoint is kept constant during the start-up holding
with BlueControl time. After that, the main setpoint SP is controlled. If a disturbance reduced
Decimal point: adjustable the process value, the start-up circuit is activated again.
Input circuit monitor: 12.5% below span start
(2mA, 1V)
Resolution: > 14 bit
Scanning cycle: 100 ms
Accuracy: Better 0.1%

CURRENT INPUT INP2

Heating current measurement


via current transformer
Measuring range: 0...30 mA AC
Scaling: adjustable
-1999..0,000..9999 A
Accuracy: 0.25%

Remote setpoint measurement


Input resistance: approx. 60Ω 
Span: configurable within
0 to 20mA
Scaling: adjustable -1999...9999
Input circuit monitor: 12.5% below span start Dual SSR - option 1-3 • Water cooling linear (heating = standard):
(4..20mA 2mA) Voltage 10 V into 500 Ω minimum To ensure a sufficient cooling effect,
the cooling function starts only after
Linear DC output option 1 & 3 reaching an adjustable temperature
CONTROL INPUT DI1 & DI2 value. The pulse length is adjustable too and
0/4mA...20 mA, configurable.
Signal range: 0...approx. 22 mA remains constant for all output values.
Configurable as direct or inverse switch or • Water cooling nonlinear (heating=standard):
push-button! Load: ≤ 500 Ω
Load effect: none The general function is described
Resolution: 0.1% above but the controller additionally takes
Connection of a potential-free contact in consideration that the water cooling is
suitable for switching “dry“ circuits. Error: 0.2%
usually much stronger than the heating
Switched voltage: 3.3 V (thus preventing unfavorable behavior when
Switched current: < 10mA 0-10 V
Signal range: 0...11 V changing from heating to cooling).
Load: ≥ 2K Ω
CONTROL INPUTS DI3 & DI4 Resolution: ≤ 0.1 % Setpoint functions
(OPTION) Error: ≤ 0.2 % • Adjustable setpoint gradient
0,01...9999 °C/min
Configurable as direct or inverse. Transmitter supply • Setpoint control
Output: 22 mA / ≥18 V • Setpoint/cascade control
Nominal voltage: 24 V DC, external • Program controller with 16 x 16 segments
(setpoint/section time)
OUTPUTS FUNCTIONS
Behaviour with sensor break
SURVEY OF THE OUTPUTS Control behaviour or short circuit:
• Signaler with adjustable switching differential
(ON/OFF controller)
• Control outputs switched off
• PID controller (2-point and continuous)
Output used for: • Switch-over to a safe output value
• Delta / Star / Off or 2-point controller
• Switch-over to a mean output value
with switch over from partial to full load
(PID controller)
Relay – option 1-3 • 2 x PID (heating/cooling)
Contacts: Potential free changeover • 3-point stepping controller
Max contact rating: 2A@ 250V 48…62Hz SPECIAL FUNCTIONS
Min contact rating: 6V, 1mA Two parameter sets for manual gain
Duty cycle: I = 1A/2A scheduling. Self-tuning control parameters Boost-Function
250,000/150,000 @ 250V or adjustable manually via front keys or The boost function provides a short-term
resisitive BlueControl software. increase of the setpoint, e.g. with hot
runner control, in order to clear nozzles
Dual relay – option 2 Behaviour with 2- and 3-point of “frozen” rests of material.
Contacts: 2 NO contacts with controllers
shared common • Standard behaviour: Start-up circuit
Max contact rating: 2A@ 250V 48…62Hz For precise matching of the required output For temperature control, e.g. with hot
Min contact rating: 6V, 1mA value at the output signal limits, the controller runners.
Duty cycle: I = 1A/2A changes the cycle times for heating and High-performance heating elements with
500,000/200,000 @ cooling automatically and continuously. magnesium oxide insulation must be
250V resisitive • With constant cycle times: heated slowly, to remove any humidity
The length of the shortest heating and cooling and to prevent destruction.
pulse is adjustable.
SSR - option 1-3
Voltage 10 V into 500 Ω minimum

3 KS 20-1 Datasheet
Modbus Master Modbus Master function supports setpoint changes e.g. in extruder
The KS 20-1 can be configured as applications
Modbus Master.
This enables it to transmit user-specified
signals or parameters cyclically to all
connected Slave controllers.

For example, the following applications


are possible:

• Setpoint shifting relative to the


setpoint adjusted in the Slave (see
picture)
• matching of control parameters, limit
contacts, etc.
• Limiting the output value (override
control OVC)

LIMIT SIGNALLING FUNCTIONS

Max., Min. or Max./Min. monitoring with MAINTENANCE MANAGER POWER SUPPLY


adjustable hysteresis.
• Display of error signals, warnings, and Depending on version:
Signals which can be monitored: latched limit messages in the error list.
• Process value • Signals are latched, and can be reset
• Control deviation
AC SUPPLY
manually.
• Control deviation with suppression • Possible signals in the error list:
during start-up or setpoint changes Voltage: 90...260 VAC
• Effective setpoint Frequency: 48...62 Hz
• Output signal Y Sensor break, short circuit, reversed polarity Power consumption approx. 7 VA
• Control deviation always compared to
Heating current alarm
internal setpoint SP even if SP2 or UNIVERSAL SUPPLY 24 V UC
SP.E is activated. Control loop alarm
Fault during self-tuning AC voltage: 20,4...26,4 VAC
Functions Latched limit messages Frequency: 48...62 Hz
• Input signal monitoring DC voltage: 18...31 V DC
• Input signal monitoring with latch (reset via Re-calibration warning Power consumption: approx: 7 VA (W)
front key or digital input) (If the adjusted operating hours are
Several limit signals or alarms can be exceeded a message is displayed)
OR-linked before being output.
BEHAVIOUR WITH POWER
Maintenance interval of actuator FAILURE
(If the adjusted switching cycles are
ALARMS exceeded a message is displayed)
Configuration, parameters and adjusted
Internal fault (RAM, EEPROM, ...) setpoints, control mode:
Heating current alarm
• Overload and short circuit Non-volatile storage in EEPROM
• Open circuit and short circuit OPERATION AND DISPLAY
BluePort INTERFACE
Limit value adjustable 0...9999 A Display
Process value: LED with 7 segments, 10,5 mm
Connection of PC via PC adapter (see
Control loop alarm Lower display: LED with 7 segments, 7,8 mm
“Accessories“). The BlueControl software is
• Automatic detection if there is no response of used to configure, set parameters, and operate
the process to a change of output value. Operating functions the KS 20-1.
The functions of the F-key are configurable:
Sensor break or short circuit BUS INTERFACE (OPTION 3 & A)
• Depending on selected input type, the Function F
• input signal is monitored for break and Galvanically isolated
• short circuit. Remote (no front operation) x
Physical: RS485
SP.2 (2nd setpoint) x Protocol: Modbus RTU
Y.2 (2nd output value) x Transmission speed: 2400, 4800,
9600, 19.200
SP.E (external setpoint) x bits/s
Manual operation x Address range: 00...99
Number of controllers per bus: 32
C.OFF (controller function off) x
Lock of manual key x Repeaters must be used to connect more
controllers.
Reset of latched limits and error list x
Boost x
Parameter set ½ x
Programmer run/stop x

Several functions can be combined e.g.


SP.2 and parameter set switch-over
(gain scheduling) with only one key.

4 KS 20-1 Datasheet
ENVIRONMENTAL CONDITIONS BlueControl, versions and functionality

Protection modes
Functionality Mini Basic Expert
Front panel: IP 65 Parameter and configuration setting yes yes yes
Housing: IP 20 Controller and loop simulation yes yes yes
Terminals: IP 20
Download: transfer of a configuration to the controller yes yes yes
Permissible temperatures Online mode / visualization SIM only yes yes
Defining an application specific linearization yes yes yes
For specified accuracy: 0...60°C
Warm-up time: < 15 minutes Configuration in the extended operating level yes yes yes
Temperature effect: < 100ppm/K Upload: reading a configuration from the controller SIM only yes yes
For storage: -20...70°C
Basic diagnostic functions no no yes
Humidity Saving data file and configuration no yes yes
Printer function no yes yes
75% yearly average, no condensation
Online documentation, help yes yes yes
Electromagnetic compatibility Implementation of measurement value correction yes yes yes
Data acquisition and trend display SIM only yes yes
Complies with EN 61 326-1
Wizard function yes yes yes
GENERAL Extended simulation no yes yes
Programeditor: KS 90-1 no no yes
Housing
The “Universal BlueControl©” Software comprises all functions of the Expert-version.
Material: ABS AF BO5 All BluePort devices can be triggered via this software.
Flammability class: UL 94 VO, self-
extinguishing specific parameters can be changed. A PC adapter (see “Accessories“) is required
for connecting the controller.
Plug-in module, inserted from the front Safety relevant parameters are invisible and
cannot be modified! Updates and demo software can be
Safety tests downloaded from:
Simulation
The built-in simulation serves to test the www.West-CS.com
Complies with EN 61010-1
Over voltage category II controller settings, but can also be used
Contamination class 2 for general training and observing the
Working voltage range 300 VAC interaction between controller and control
Protection class II loop.

Certifications Software requirements:


Windows: Windows 2000, XP, VISTA, WIN7,
cULus-certification - Applied for. WIN8.

Terminals Configurations that can only be


implemented via the BlueControl
5mm Combicon software (not via the front-panel keys):

Mounting • Customer-specific linearizations

Panel mounting with quick release fixing • Enable “forcing“ for inputs/outputs.
mounting clamp (supplied). Forcing allows to write the analog and digital
inputs and outputs via Modbus interface.
Mounting position: not critical
Weight: 0.2 kg • Adjustment of limits for operating
hours and switching cycles

• Switch-over to 60 Hz mains frequency


ACCESSORY EQUIPMENT
• Master/slave configuration
BlueControl (Engineering Tool)
• Disable operator actions and operating
PC-based program for configuring, setting levels, plus password definition
parameters, and operating (commissioning)
the KS 20-1 controller. • Prevent automatic optimization of cycle times
T1, T2
All the settings are saved, and can be printed
on demand. Hardware requirements:
A powerful data acquisition module is
available, complete with trend graphics.

Visibility mask
The BlueControl software can be used
to hide any parameters in the instrument. Only

5 KS 20-1 Datasheet
Product Ordering Code (provisional)
Model Code KS20 - 1 x x - x x x x x x - 03
Model Type
1/16 Din Universal Industrial Controller
Supply Voltage
100-240V AC 0
24VAC 50/60Hz or 18 to 30VDC 1
Heater Current / Transmitter Power Supply
TPS T
HC / mA H
Option 1
Relay (switch over) R
Single SSR A
Dual SSR Y
Linear mA/VDC Output L
Option 2
Not fitted 0
Relay (switch over) R
Dual Relay D
Single SSR A
Dual SSR Y
Option 3
Not fitted 0
Relay (switch over) R
Single SSR A
Dual SSR Y
Linear mA/VDC Output L
RS485 C
Option A
Not fitted 0
RS485 C
Dual Isolated digital input B
Language
No Manual 0
German (Full or Concise Manual) 1
English (Full or Concise Manual) 2
French (Full or Concise Manual) 3
Italian (Concise Manual Only) 4
Spanish (Concise Manual Only) 5
Packing Options
Single pack with concise manual 0
Single pack with full manual 5

For more details on the complete product range from West Control Solutions please visit www.isotron.eu.