Establishement UNIFORTUNE 

BUILDING

Address 612 ELCANO STREET BINONDO METRO MANILA

Peak Load Current Test

Instrument Wheeler Digital Clamp Meter Date March 10, 2019 Time 6:00:00 PM to 7:00 PM


Model HD‐3311

Item No. Meter No. Unit No. Location CKT Breaker conductor Pole Volts Amps Single Phase Remarks
Grnd Flr Amp/Trip mm2 L1 L2
1 106FA005708 618 Right DB 60 14 2 220 19.2 20 Passed

2 330ZN65024 616 Right DB 60 14 2 220 13.6 14.5 Passed

3 33SYN57913 614 Right DB 60 14 2 220 8.7 9 Passed

4 107BA131918 612‐A Right DB 60 14 2 220 16.2 16.7 Passed

5 33HZN68687 201 Right DB 125 22 2 220 3.6 3.8 Passed

6 33JZN74685 202 Right DB 125 22 2 220 11 11.3 Passed

7 33SUN36692 203 Right DB 150 30 2 220 21 21.3 Passed

8 33HZN68058 301 Right DB 125 22 2 220 14 14.1 Passed

9 33HZN68686 302 Right DB 125 22 2 220 7.6 7.9 Passed

10 33HZN69432 303 Right DB 150 30 2 220 3.4 3 Passed

11 33HZN69428 902 Left DB 200 38 2 220 31 31.1 Passed

12 33IZN32414 803 Left DB 150 30 2 220 17 17 Passed

13 33IZN32416 802 Left DB 125 22 2 220 6 5.9 Passed

14 33IZN32462 801 Left DB 125 22 2 220 18 17.9 Passed

15 111BA042825 603 Left DB 150 30 2 220 11 11 Passed

16 33GZN15713 702 Left DB 125 22 2 220 4 4.2 Passed

17 33IZN32415 701 Left DB 125 22 2 220 16.2 16.7 Passed

18 111BA042660 703 Left DB 150 30 2 220 21.5 21.3 Passed

19 116BAG011697 602 Left DB 125 22 2 220 15.3 15.6 Passed

20 105BA131546 601 Left DB 125 22 2 220 22.3 22 Passed

21 111BA042804 503 Left DB 150 30 2 220 24.9 24.7 Passed

22 33IZN32460 502 Left DB 125 22 2 220 10.7 10.5 Passed

23 33IZN32459 501 Left DB 125 22 2 220 5.3 5.9 Passed

24 33GZN46976 403 Left DB 150 30 2 220 1.6 1.5 Passed

25 33GZN46977 402 Left DB 125 22 2 220 12.7 12.4 Passed

26 33GZN46975 401 Left DB 125 22 2 220 8.7 8.9 Passed


***************************************************Nothing Follows**************************************************

REMARKS           PASSED

RECOMMENDATION          RECOMMENDED FOR ANNUAL TESTING

CONDUCTED BY WITNESSED BY:
MANNY M. QUIBINIT
March 10, 2019
RME REG. NO. 0051284