TCD - 070 48V Power Error


Point of Application ● DI120-150
Detection ● Speed CPU ● DI180-420

[Meaning] When +48[V] power falls down to +39.6[V] for 10 or more times [Actions to take]
in 10 seconds. 1. Check +48[V] power LED(LED1) in DOR-230 PCB, and
1) If LED(LED1) is OFF,
(1) Check any errors in output fuse of Power Source and, if disconnected,
replace with rated fuse.
[Diagram] => Check P48V side SIG Fuse(F3, F4) of power source for short.
(2) If no error is found in Fuse, turn OFF the control panel power and
measure the resistance values at both ends of DOR-230 PCB and
POLY-SW1. => If the resistance value is obtained by Mega-Ohm unit,
check if +48[V] and GND is short in DOR-230 PCB since Poly Switch has
operated because of over current.
* DOR-230 PCB : +48[V] => Connector PWS/2; GND => TP10
2) If LED(LED1) is ON,
(1) Check the contacting status of connector(MA) cable connecting
DOR-230(#1) PCB and DOC-200 PCB.
(2) Check the DC +48[V] input voltage in DOR-230 PCB.
=> Normally, it is within DC +48[V]±10%. But if one of 3 phases is
missing, DC +32[V]±10% voltage is detected as shown in left diagram.
This time, LED1 is ON in its Semi-brightness Mode.
[Figure] +48[V] Power Error Detecting Circuit in DOR-230 PCB
(3) Verify if TP12(V_SET) voltage in DOR-230 PCB is DC +6.63[V].
In the following, left shows DC+48[V] when power is normal and right shows the wave If different, set the variable resistance VR1 to DC +6.63[V] by rotating
form when one phase of input power is missing. adjust tap and check again if TCD 70 occurs again.
(4) Read the value of address 0x52 in F7DOR-230 PCB. If all input values
are 0x00, verify if 48V and 24V power are short or not & 48V power
and 24V power cable in DOR-230 PCB are not exchanged by each other.
(We experienced this status at the trial operation in PUSAN Office Building)
2. Check +5[V] and +15[V] voltage.
=> Must be at least +4.8[V], + 15[V]±10%
1) DOC-230 PCB : +5[V] => Connector MG/1, MG/6; GND => TP16
2) DOR-230 PCB : +5[V] => Connector SMP/1, SMP/6
+15[V] => Connector SMP/2
3. Check the PCB applied voltages (+48[V], +5[V], +15[V]) after
turning OFF-ON the control panel power.
=> If TCD 70 still occurs even though all voltages are normal, try replacing
PCB in sequence of DOR-230(#1) PCB and DOC-200 PCB.
Voltage : DC +48[V]± 10% Voltage : DC +32[V]± 10%
[Wave Form and Voltage When Normal] [Wave Form and Voltage When a Phase is Missing]
Note) Above voltage is the DC value measured by DIGITAL VOLT METER.