● Run CPU

TCD - 078 EEPROM FLOOR HEIGHT TABLE SUM ERROR


Point of Application ● DI120-150
Detection ○ Speed CPU ● DI180-420
[Meaning] When the value obtained by computing floor table sum value in [Actions to take]
EEPROM at one second interval is not identical with the SUM value
memorized in EEPROM. 1. TCD 78 may occur at the first of powering ON at site
because floor height table is all cleared when going out
[Diagram] from the factory. Be sure to perform floor height
measuring operation before high-speed operation.
EEPROM(AT28C256)
0x1200
0x0000 Floor Height 1 2. Check the DIP switch(No.2 of SW4) status in DOC-200 PCB.
Car SPEC
. (Switch should be set to Write Protect side.)
0x1200 .
Floor Height Table Data If it is set to Flash Write, ROM data may have been
.
0x1700
Car SPEC Floor Height N destroyed when powering ON or OFF.
0x1308 (This time, measure the floor height again)
0x4000
미정의 영역
Unidentified Area
NPLEX SPEC 3. Verify if EEPROM(U22) Socket is properly inserted.
0x1600 Pay attention to pin No. when inserting pin.
Floor Height Table SUM
0x1604 Be careful of pin bend or electrostatics.
0x7FFC EEPROM CHECK 미정의 영역
Unidentified Area
0x7FFF SUM DATA(4BYTE) 0x1700 4. Measure the floor height again.
For switch(No.2 of SW4) setting, follow the floor
SUM A of Floor Height 1~Floor Floor Height Table SUM B height measuring sequence specified in installation
Height N of SPEC ROM Recorded in SPEC ROM
and maintenance manual.

5. After floor height measurement is completed, floor


Are SUM A and
No
height table sum value will be automatically computed
SUM B Identical? by the program and recorded in EEPROM.
Yes
If TCD 78 error still exists even after floor height is
completely measured, error may be coming from
TCD 78 CLEAR TCD 78 SET
EEPROM(U22) error. So, replace EEPROM and measure the
floor height again.

6. If the problem exists even after above checks, try


replacing DOC-200 PCB.