This document describes a TCD-078 error that occurs when the computed floor table sum value in EEPROM does not match the stored value. There are several potential causes and solutions outlined: 1) The error can occur on initial power-up if floor heights were not set, 2) Improper DIP switch settings could corrupt data, 3) The EEPROM chip may not be fully inserted, and 4) Measuring floor heights again should resolve the error by recomputing and storing the correct sum value. Replacing the EEPROM chip or DOC-200 PCB may be needed if the error persists after troubleshooting steps.
This document describes a TCD-078 error that occurs when the computed floor table sum value in EEPROM does not match the stored value. There are several potential causes and solutions outlined: 1) The error can occur on initial power-up if floor heights were not set, 2) Improper DIP switch settings could corrupt data, 3) The EEPROM chip may not be fully inserted, and 4) Measuring floor heights again should resolve the error by recomputing and storing the correct sum value. Replacing the EEPROM chip or DOC-200 PCB may be needed if the error persists after troubleshooting steps.
This document describes a TCD-078 error that occurs when the computed floor table sum value in EEPROM does not match the stored value. There are several potential causes and solutions outlined: 1) The error can occur on initial power-up if floor heights were not set, 2) Improper DIP switch settings could corrupt data, 3) The EEPROM chip may not be fully inserted, and 4) Measuring floor heights again should resolve the error by recomputing and storing the correct sum value. Replacing the EEPROM chip or DOC-200 PCB may be needed if the error persists after troubleshooting steps.
Point of Application ● DI120-150 Detection ○ Speed CPU ● DI180-420 [Meaning] When the value obtained by computing floor table sum value in [Actions to take] EEPROM at one second interval is not identical with the SUM value memorized in EEPROM. 1. TCD 78 may occur at the first of powering ON at site because floor height table is all cleared when going out [Diagram] from the factory. Be sure to perform floor height measuring operation before high-speed operation. EEPROM(AT28C256) 0x1200 0x0000 Floor Height 1 2. Check the DIP switch(No.2 of SW4) status in DOC-200 PCB. Car SPEC . (Switch should be set to Write Protect side.) 0x1200 . Floor Height Table Data If it is set to Flash Write, ROM data may have been . 0x1700 Car SPEC Floor Height N destroyed when powering ON or OFF. 0x1308 (This time, measure the floor height again) 0x4000 미정의 영역 Unidentified Area NPLEX SPEC 3. Verify if EEPROM(U22) Socket is properly inserted. 0x1600 Pay attention to pin No. when inserting pin. Floor Height Table SUM 0x1604 Be careful of pin bend or electrostatics. 0x7FFC EEPROM CHECK 미정의 영역 Unidentified Area 0x7FFF SUM DATA(4BYTE) 0x1700 4. Measure the floor height again. For switch(No.2 of SW4) setting, follow the floor SUM A of Floor Height 1~Floor Floor Height Table SUM B height measuring sequence specified in installation Height N of SPEC ROM Recorded in SPEC ROM and maintenance manual.
5. After floor height measurement is completed, floor
Are SUM A and No height table sum value will be automatically computed SUM B Identical? by the program and recorded in EEPROM. Yes If TCD 78 error still exists even after floor height is completely measured, error may be coming from TCD 78 CLEAR TCD 78 SET EEPROM(U22) error. So, replace EEPROM and measure the floor height again.
6. If the problem exists even after above checks, try