TCD - 082 DOR-230 PCB #3 Signal Input Error


Point of Application ● DI120-150
Detection ○ Speed CPU ● DI180-420
[Meaning]
When input port values read at 10ms interval in [Actions to take]
DOR-230 PCB(#1~#4) are not identical for 5 or more consecutive
times and lasts for 50ms. 1. Check connector contacting status by DOR-230 PCB.
[Diagram] PORT 1: INA
PORT 2: INB
PORT 3: INC
TCD NO PCB No. PCB Selection S/W Input Port ADDRESS
80 DOR-230(#1) PORT 1 0x5000 0000
SW1 2. Check the PCB selection switch status by DOR-230 PCB No..
PORT 2 0x5000 0400 (Setting should be as same as shown in the left diagram.)
SW2
PORT 3 0x5000 0800
81 DOR-230(#2) PORT 1 0x5000 2000 3. Check the connection status of PCB Connector(MA) cable
SW1
PORT 2 0x5000 2400 since there could be an error in PCB connection status and
SW2 DOR-230 PCB, DOC-200 PCB, or other PCBs.
PORT 3 0x5000 2800
82 DOR-230(#3) PORT 1 0x5000 4000
SW1 4. Visually check defects for input port HIC(MIA-E02) in DOR-230
PORT 2 0x5000 4400
SW2 PCB where the error occurs.
PORT 3 0x5000 4800
83 DOR-230(#4) PORT 1 0x5000 6000 5. Check the DC +48[V] voltage supplied to external devices(e.g.
SW1
PORT 2 0x5000 6400 relay, etc.) which is connected to input port in DOR-230 where
SW2
PORT 3 0x5000 6800 the error occurs.

6. Check the DC +5[V], +15[V], +24[V] voltage for PCB.


1) Check the voltage applied to DOR-230 PCB.
(1) DC +5[V] : Connector SMP/1, SMP/6
(2) DC +15[V] : Connector SMP/2
(3) DC +24[V] : Connector PWS/1
(4) GND : TP10(Location : Between Connector INC and OUT)
2) Check the voltage applied to DOC-230 PCB PCB.
(1) +5[V] => Connector MG/1, MG/6
(2) GND => TP16(Location : Just above Connector MG)

7. If TCD 80 ~ 83 error exists even after above checks,


1) Try replacing the DOR-230 PCB where the error occurs.
2) If the error has nothing to do with DOR-230 PCB,
try replacing DOC-200 PCB.