ZTE Rectifier Settings

Para.Set > System Para


Parameter Settings Modified Value

1 Password 0000 0063

2 Battery Cap.1# 0 500AH

3 Battery Cap.2# 0 0AH

4 Battery Cap.3# 0 0AH

5 Battery Cap.4# 0 0AH

5 SMR Qty. 3

6 Spont.Alm.En. Enabled
7 Port Baudrate 9600 bps
Para.Set > Alam.Attr
1 Parameter Default Value Modified Value
Grade-
2 Ac Power off
Major/Relay-A5
Grade-
3 SMR Fan Faulty
Major/Relay-A2
Grade-
4 SMR Out Fuse
Major/Relay-A2
Grade-
5 SMR EEProm
Major/Relay-A2
Grade-
6 SMR Start Abr
Major/Relay-A2
Grade-
7 SMR Comm Fail
Major/Relay-A2
Grade-
8 Battery Voltage Low
Major/Relay-A4
Grade-
9 Door Alarm
Major/Relay-A1
Grade-
10 Battery loop brk
Major/Relay-A3
Grade-
11 LLVD1 Extend brk
Major/Relay-A3
Grade-
12 BLVD Extend brk
Major/Relay-A3
Local Set Parameter Default Value Modified Value
1 System Time
2 Language English
3 LCD Contrast 50%
Para.Set > Batt.Para
1 Parameter Default Value Modified Value
2 Work Mode Save

3 Float Voltage 53.5 V


4 Equalized Voltage 56.4 V
5 Equalized Period 90 Day
6 Chg.Curr.Coeff 0.2C10 0.200C10
7 Disconnect Mode Batt.Volt.
8 LLVD1 Enabled Enabled
9 LLVD2 Enabled Disabled
10 BLVD Enabled Enabled
11 LLVD1 Voltage 44 V 44.0V
12 LLVD2 Voltage 44.0 V 44.0V
13 BLVD Voltage 42 V 42.0V
Para.Set > Alam.Para
1 Parameter Default Value Modified Value
Battery Voltage
2 48.0V
L.Thre

Hardware connection
1 Parameter SIB Board Pin No

2 Ac Power off X16-NO5/COM-5

3 SMR Fan Faulty X14-NO2/COM2

4 SMR Out Fuse X14-NO2/COM2

5 SMR EEProm X14-NO2/COM2

6 SMR Start Abr X14-NO2/COM2

7 SMR Comm Fail X14-NO2/COM2

8 Battery Voltage Low X15-NO4/COM4

9 Door Alarm X14-NO1/COM1

10 Battery loop brk X15- NO3/COM3

11 LLVD1 Extend brk X15- NO3/COM3

12 BLVD Extend brk X15- NO3/COM3


Setting Requirement

Setting Requirement

Setting Requirement
The system activates and
deactivates SMRs.according to this
parameter.

Setting Requirement