Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

International Journal of Refrigeration 27 (2004) 761–773

www.elsevier.com/locate/ijrefrig

Propane heat pump with low refrigerant charge:


design and laboratory tests
Primal Fernando*, Björn Palm, Per Lundqvist, Eric Granryd
Division of Applied Thermodynamics and Refrigeration, Department of Energy Technology,
Royal Institute of Technology (KTH), SE-100 44 Stockholm, Sweden
Received 12 January 2004; received in revised form 28 June 2004; accepted 30 June 2004

Abstract
Independently of the choice of refrigerant, environmental and or safety issues can be minimised by reducing the amount of
refrigerant charge per heat pump or refrigeration system. In the investigation reported here, a laboratory test rig was built,
simulating a water-to-water heat pump with a heating capacity of 5 kW. The system was designed to minimize the charge of
refrigerant mainly by use of mini-channel aluminium heat exchangers. It was shown that the system could be run with 200 g of
propane at typical Swedish operating conditions without reduction of the COP compared to a traditional design. Additional
charge reduction is possible by selecting proper compressor lubrication oils or by using a compressor with less lubrication oil.
q 2004 Elsevier Ltd and IIR. All rights reserved.

Keywords: Heat pump; Water-water; Refrigerant charge; Propane; Design; Experiment

Pompe à chaleur à propane et à faible charge:


conception et essais en laboratoire
Mots clés: Pompe à chaleur; Eau-eau; Charge en frigorigène; Propane; Conception; Expérimentation

1. Introduction pumps annually in Sweden is at the same level as for the rest
of Europe. The main reason for this large interest is the cold
Sweden has several relatively big (for European climate in combination with low price of electricity at the
standards) production units of heat pumps. The Swedish consumer level, being, per kWh, comparable to the price of
heat pump market is also traditionally larger than other oil. Several countries, however, foresee a strong increase in
European markets. The number of installed and sold heat sales of heat pumps within coming years. Swedish heat
pumps generally have good reputation for high quality.
Fig. 1 shows the number of heat pumps installed per year
* Corresponding author. Tel.: C46-8-790-8941; fax: C46-8-20-
in Sweden [1]. The number of installed heat pumps started
30-07. to increase rapidly in 1995. The number of heat pumps
E-mail addresses: primal@energy.kth.se (P. Fernando), bpalm represent in the figure in year 2003 is only up to the month of
@energy.kth.se (B. Palm), perlundq@energy.kth.se (P. Lundqvist), August. The vast majority of them are installed in single-
granryd@energy.kth.se (E. Granryd). family houses. The most common type is an indirect (brine
0140-7007/$35.00 q 2004 Elsevier Ltd and IIR. All rights reserved.
doi:10.1016/j.ijrefrig.2004.06.012
762 P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773

Nomenclature
A heat transfer area (m2) c,in condenser inlet
A-BH-25 average temperature of the borehole, 25 m deep c,out condenser outlet
(8C) c,dsh,r condenser de-superheat region
A-BH-50 average temperature of the borehole, 50 m deep c,sc,r condenser sub-cool region
(8C) c,tp,r condenser two-phase region
A-ut average outside temperature (8C) c,sl condenser, saturated liquid
COP coefficient of performance, heating c,sg condenser, saturated gas
cp specific heat capacity (J kgK1 KK1) c,sc condenser, sub-cooled liquid
C-170 charge 170 g e evaporator
C-201 charge 201 g e,in evaporator inlet
C-240 charge 240 g e,out evaporator outlet
C-265 charge 265 g e,sh,r evaporator superheat region
GWP green house warming potential e,tp,r evaporator two phase region
h refrigerant enthalpy (J kgK1) e,sg at evaporator saturated gas
LMTD log mean temperature difference (K) e,sh at evaporator super heat
m mass flow rate (kg sK1) g glycol
M-BH-25 minimum temperature of the borehole, 25 m g,out glycol outlet
deep (8C) g,in glycol inlet
M-BH-50 minimum temperature of the borehole, 50 m g,sg glycol at refrigerant saturated gas
deep (8C) min minimum
M-ut minimum outside temperature (8C) r refrigerant
M-Br-in minimum brine inlet temperature (8C) r,sh refrigerant, superheated gas
ODP ozone depletion potential r,sg refrigerant, saturated gas
Q heat capacity (W) r,in,e refrigerant inlet in evaporator
SH super heat (K) r,in,c refrigerant, condenser inlet
SC sub cool (K) r,sl refrigerant, saturated liquid
t temperature (8C) w water
U overall heat transfer coefficient (W mK2 KK1) w,out water outlet
Subscripts w,in water inlet
ave average w,sg water at condenser saturated gas
c condenser w,sl water at saturated liquid

loop) ground or rock-coupled heat pump, connected to the is not corrosive in combination with many materials such as
water circulating heating system of the house. Usually, the aluminium, brass, bronze, copper, stainless steel, silver, etc.
heat pump is chosen to cover more than 90% of the annual Therefore it is fully compatible with existing components
heating need of a house and 50–60% of the heating demand such as heat exchangers, expansion valves, compressors,
of the coldest day. The total heating demand covered by heat lubricants and copper tubing, which are commonly used in
pumps in Sweden is estimated to be about 15 TWh/year, current refrigeration systems [3]. Its major drawback,
thus reducing the total energy demands by about 10 TWh/ however, is the flammability.
year. Environmentally adopted and energy effective heat Independently of the chosen refrigerant it is of interest to
pumps can play an important role as replacement of the decrease the total charge of the system, if this can be done
presently dominant energy technology, in Sweden, the without negative influence on the COP of the system. For
direct electric heating. HFC and HCFC systems, reduced charge means less
The ozone depletion potential (ODP) and green house environmental impact in case of leakage. For systems with
warming potential (GWP) of some commonly used flammable refrigerants lower charge is important for safety
refrigerants have led to increased research efforts for reasons. An ongoing project at The Royal Institute of
developing other refrigerants, which are environmentally Technology (KTH), Stockholm, aims to increase the
friendly. Propane is a refrigerant, which has no ODP and existing knowledge about heat pumps and refrigeration
extremely low (!20) GWP [2], compared to many systems designed for the lowest possible refrigerant charge,
currently used refrigerants. Also thermodynamic and with the goal of designing a heat pump system with a charge
transport properties are the same as or better than the most of less than 150 g (with propane) having a heating capacity
popular refrigerants used in refrigeration systems. Propane of the order of 5 kW or more. This should be reached
P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773 763

Fig. 1. The number of heat pumps installed in Sweden from 1986 to August 2003 [1].

without reduction of COP. The level of the heating capacity avoid this collection of liquid refrigerant. In short, the use of
was chosen taking into consideration the Swedish and mini-channel heat exchangers leads to wide possibilities of
eventually cumulative European markets for single-family charge reduction.
house heat pumps. Narrow channel tubes with various diameters and
lengths are manufactured for many industrial applications.
The most common materials are aluminium and copper,
2. Charge minimisation with narrow channel heat which both have high thermal conductivities. New manu-
exchangers facturing methods allow producing tubes with small wall
thickness and even with internal longitudinal fins. This is a
2.1. Narrow channel heat exchangers great advantage when designing heat exchangers with high
heat transfer areas and low internal volumes. The heat
Heat exchangers are the main concern in charge exchangers in heat pumps should be designed for small
minimisation of a heat pump as the high interior volumes temperature differences, which is economical due to long
of the heat exchangers can cause large refrigerant charge. operating hours. Through, narrow channels and rough or
Plate type heat exchangers are widely used in liquid/liquid finned surfaces often lead to higher pressure drops.
applications in refrigeration and air conditioning due to their However, this can be avoided by using a sufficient number
compactness, high heat transfer coefficients and low of parallel channels.
pressure drop. Compared to most other types, the internal
volume is low. However, if very low charges are desired the 2.2. Mini-channel aluminium heat exchangers
amount of refrigerant contained inside during normal
operation is still too high [4]. Experimental investigations Two liquid-cooled heat exchangers have been fabricated
show that using micro-channel heat exchangers in refriger- with multiport aluminium tubes. Fig. 2 shows the cross
ation systems can reduce substantially the refrigerant charge section of the used tube. As shown, the tube had six
[5]. It is obvious that the reduction of channel diameter lead channels. The inner cross section of the four centre channels
to increase in the heat transfer area per unit heat exchanger was 1!2.65 mm2 and of the other two channels 1!
volume. Previous tests done to compare the plate heat 1.45 mm2 with an additional end curvature with 1 mm in
exchangers with mini-channel aluminium heat exchangers diameter each, giving a hydraulic diameters of 1.45 mm for
showed a considerable charge reduction when switching to the centre channels and 1.35 mm for the end channels. The
mini-channel heat exchangers in the same heat pump [6]. wall thickness of the tube was 0.5 mm and the length of each
Especially, the outlet of the condenser and the inlet of the tube was 651 mm (Figs. 3 and 4).
evaporator (headers) of plate heat exchangers contain lots of The evaporator and the condenser consisted of 30 and 36
refrigerant and acts as a liquid pool. The headers of narrow aluminium tubes in two parallel rows, respectively. A shell
(micro or mini) channel heat exchangers can be designed to and 31 baffle plates were made for containing and directing
764 P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773

the secondary refrigerant on the shell side of each heat


exchanger. For the calculations, it was assumed that the
baffle plates of the heat exchangers at as fins. The outer areas
(tube areas between baffle plates and areas of the baffle
plates) of the evaporator and the condenser were 0.822 and
0.985 m2, respectively. The two heat exchangers were
mounted in a test rig, simulating typical heat pump
Fig. 2. The tube cross section.
conditions and the test results were compared with results
from corresponding tests with plate type heat exchangers.
The overall heat transfer coefficients of the aluminium mini
channel heat exchangers, working as evaporator and
condenser were 50 and 60% higher, respectively, than
those of the plate heat exchangers. The pressure drop of the
aluminium evaporator was 70% higher than that of the plate
type evaporator, but the pressure drops of both types of
condensers were negligibly small. The total internal
volumes of the aluminium heat exchangers were less than
50% of those of the plate heat exchangers. It was found that
the amount of refrigerant charge in the heat pump with the
plate type heat exchangers was about 300 g, and that with
mini channel heat exchangers about 200 g. The measured
amount of refrigerant in the plate type evaporator was 69 g
and for the mini channels aluminium evaporator 28 g. The
amount of refrigerant in the plate type condenser was 125 g
Fig. 3. Inlet of the heat exchanger showing the tube rows.
and for the mini channels aluminium condenser 96 g [7].

3. Experimental set-up heat pump

Fig. 5 shows a schematic diagram of the experimental


set-up. It consisted of a scroll compressor, mini-channel
aluminium heat exchangers, working as evaporator and
condenser and an electronic expansion valve. Measuring the
temperature and the pressure of the evaporator outlet
controlled the electronic expansion valve. The superheat
was calculated from these readings in a PID controller. The
output signal from the PID controller could also set
manually. Pneumatically operated ball valves were placed
at the inlet and outlet of the heat exchangers. The four ball
valves could be closed simultaneously within 0.25 s, in
order to trap the refrigerant in the different sections during
operation. The condenser was cooled by water and the heat
supply to the evaporator was arranged by an electrically
heated glycol solution. The water flow rate through the
condenser and the glycol flow rate through the evaporator
were measured with electronic flow meters. Pressure
measurements and pressure drop measurements were
taken by two pressure transducers connected at the
evaporator and condenser inlets and two differential
pressure transducers connected between inlet and outlet of
the heat exchangers. Thermo-couples were provided for the
temperature measurements. The thermo-couples were
calibrated by inserting them into an ice-bath (assuming the
temperature of the ice-bath 0 8C). The calibration curves and
Fig. 4. (a) A picture of the exchanger; view inside the shell. (b) A the accuracies of the flow meters were taken as given by the
picture of the heat exchanger. manufacturer. The flow meters were also tested with known
P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773 765

Fig. 5. Schematic diagram of the experimental heat pump.

flow rates, which confirmed the given accuracies. The Ue;tp;r Ae;tp;r C Ue;sh;r Ae;sh;r
pressure transducers were calibrated with standard calibrat- Ue Z (6)
Ae
ing equipment. The measurements accuracies were; tem-
peratures measurements G0.04 at 0 8C, flow measurements The overall energy balance of the two regions are
0.5% of measured value and pressure measurements G
Qe;tp;r Z Ue;tp;r Ae;tp;r LMTDe;tp;r (7)
0.02% of the measured value. All the instruments were
calibrated several times during the test period.
Qe;sh;r Z Ue;sh;r Ae;sh;r LMTDe;sh;r (8)

The Eqs. (5)–(8) can be summarised as


4. Calculations Qe
LMTDe Z Qe;sh;r Q
e;tp;r
(9)
LMTDe;sh;r C LMTD
The heat transfer rate of the condenser and the e;tp;r

evaporator can be calculated from the temperature change The heat transfer from glycol to refrigerant in the
of the secondary refrigerant, the mass flow rate and the different regions can be calculated as
specific heat of the fluid
Qe;tp;r Z mr ðhe;sg K he;in Þ (10)
Qc Z mw cp;w ðtw;out K tw;in Þ (1)

Qe Z mg cp;g ðtg;in K tg;out Þ (2) Qe;sh;r Z mr ðhe;sh K he;sg Þ (11)

The heat transfer rate of the condenser and evaporator can The LMTDs of the two regions
also be calculated from the enthalpy change of the
refrigerant and the refrigerant mass flow rate
Qc Z mr ðhc;in K hc;out Þ (3)

Qe Z mr ðhe;out K he;in Þ (4)


The overall energy balance of the evaporator is
Qe Z Ue Ae LMTDe (5)
The logarithmic mean temperature difference (LMTD) of
the evaporator was calculated considering a division of the
evaporator into two parts: the evaporation part and the
superheating part [8]. Fig. 6 shows the temperature profile of
the evaporator.
The overall heat transfer coefficient of the evaporator is
defined as Fig. 6. Temperature profile in the evaporator.
766 P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773

ðtg;in K tr;sh Þ K ðtg;sg K tr;sg Þ The LMTDs of different regions can be described as
LMTDe;sh;r Z   (12)
tg;inKtr;sh
ln tg;sg ðtr;in;c K tw;out Þ K ðtr;sg K tw;sg Þ
Ktr;sg LMTDc;dsh;r Z   (23)
t Ktw;out
ln r;in;c
tr;sgKtw;sg
ðtg;sg K tr;sg Þ K ðtg;out K tr;in;e Þ
LMTDe;tp;r Z   (13)
tg;sgKtr;sg
ln tg;out ðtr;sg K tw;sg Þ K ðtr;sl K tw;sl Þ
Ktr;in;e LMTDc;tp;r Z   (24)
t Ktw;sg
ln tr;sg
r;sl Kt w;sl
The overall energy balance of the condenser is
Qc Z Uc Ac LMTDc (14) ðtr;sl K tw;sl Þ K ðtc;sc K tw;in Þ
LMTDc;sc;r Z   (25)
tr;slKtw;sl
The LMTD of the condenser was calculated considering ln tc;sc Ktw;in
division of the condenser into three parts [9]: de-super-
The pressure drop of the evaporator was considered in
heating region, condensing region and sub-cooling region.
calculations of the refrigerant side temperatures, but was not
Fig. 7 shows the temperature profile of the condenser.
considered in the condenser, since the pressure drop of the
condenser was negligibly small.

5. The performance of the heat pump with mini-channel


aluminium heat exchangers

5.1. Optimum charge tests

The heat pump was tested with selected heat source


temperatures and with a constant heat sink temperature. The
selected heat source temperatures were K10, K2, 6 and
12 8C, and the heat sink temperature was 40 8C. The cooling
water inlet temperature was kept at 33 8C, to obtain a 7 K
temperature increase of the water. The temperature change
of the glycol was kept at about 3 K for the heat source
Fig. 7. Temperature profile in the condenser.
temperatures of K10 and K2 8C and at about 3.75 and
The overall heat transfer coefficient of the condenser is 4.4 K for the heat source temperatures of 6 and 12 8C,
defined as respectively.
The refrigerant quantity (propane) in the system was
Uc;sc;r Ac;sc;r C Uc;tp;r Ac;tp;r C Uc;dsh;r Ac;dsh;r varied for each heat source and heat sink temperature
Uc Z (15)
Ac combination and the coefficient of performance (COP) of
the system was determined. The superheat at the evaporator
The overall energy balance of the three regions
outlet was slightly increased with decreasing evaporation
Qc;sc;r Z Uc;sc;r Ac;sc;r LMTDc;sc;r (16) temperature for lower charges in order to avoid gas bubbles
in the expansion valve inlet. This was done in order to
Qc;tp;r Z Uc;tp;r Ac;tp;r LMTDc;tp;r (17) simulate the performance of a correctly sized thermostatic
expansion valve. The minimum (desired) superheat was
Qc;dsh;r Z Uc;dsh;r Ac;dsh;r LMTDc;dsh;r (18) maintained around 5 K. The sub-cooling at the condenser
outlet was allowed to increase for higher charges. The heat
The Eqs. (14)–(18) can be summarised as, pump was tested over 1000 h for all heat source/sink
Qc combinations.
LMTDc Z Qc;dsh;r Q
c;tp;r Q
(19) Fig. 8 shows the COP as a function of the refrigerant
c;sc;r
LMTDc;dsh;r C LMTD C LMTD
c;tp;r c;sc;r
charge at different heat source temperatures. For a given
The heat transfer from refrigerant to water in the different heat source temperature, the COP was more or less constant
regions of the condenser can be calculated as when the charge was above a certain minimum level. Below
this level, the COP dropped significantly. The optimum
Qc;sc;r Z mr ðhc;sl K hc;sc Þ (20) refrigerant charges resulting in the highest COP, for the four
tested heat source/sink combinations were170, 200, 240 and
Qc;tp;r Z mr ðhc;sg K hc;sl Þ (21) 265 g, in order from lowest to highest heat source
temperature.
Qc;dsh;r Z mr ðhc;in K hc;sg Þ (22) Fig. 9 shows the variation of the heating capacity with
P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773 767

Fig. 8. COP of the condenser vs refrigerant charge for four heat source temperatures (K10, K2, 6, 12 8C) a constant heat sink temperature
40 8C.

the refrigerant charge. As for the COP the capacity is more and LMTD variation of the condenser and evaporator for the
or less constant as long as the charge is above the optimum selected charges were calculated and the results are plotted
charge. The capacity and COP reduction for lower in Figs. 10 and 11.
refrigerant charges is caused by the decrease of the Fig. 10 shows the LMTD and condenser capacity (Qc)
evaporation temperature. The reason for this decrease is variation with refrigerant charge (at different heat source
the ‘starvation’ of the evaporator, leading to an increase of temperatures). The condensing temperature was increased
the superheat and to an outgoing refrigerant temperature slightly with increasing heat source temperatures, mainly
close to the inlet glycol temperature. due to the increased mass flow resulting more refrigerant
occupation in condenser. That was probably the reason why
5.2. The overall heat transfer coefficients of the evaporator higher LMTDs were recorded at higher heat source
and the condenser temperatures, although the temperature change in the
water was kept about 7 K for all tests. For each heat source
Some refrigerant charges, around the optimum charge temperature the LMTD increased slightly with increasing
for each test condition, were selected. The capacity variation charge due to the increasing of the sub-cool.

Fig. 9. Heat capacity of the condenser vs charge for four heat source temperatures (K10, K2, 6, 12 8C) and a constant heat sink temperature of
40 8C.
768 P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773

Fig. 10. Heat capacity and the LMTD of the condenser vs refrigerant charge in the system.

Fig. 11. Cooling capacity and LMTD of the evaporator vs refrigerant charge in the system.

Fig. 12. Variation of super heat and sub-cooling.


P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773 769

Fig. 13. Overall heat transfer coefficients of evaporator and condenser vs refrigerant charge.

Fig. 11 shows that the LMTD of the evaporator was in coefficients of the evaporator and the condenser for the
the range from 4 to 5 K for all four tests conditions and that selected charges and heat source temperatures. The LMTD
the evaporator capacity was strongly influenced by the heat of the evaporator was almost the same for all test conditions.
source temperature. For each heat source temperature, the The overall heat transfer coefficient of the evaporator
charge had very little influence on the capacity or the LMTD depends significantly on the heat source temperature, which
of the evaporator. influences the heat flux and mass flow of the refrigerant
Fig. 12 shows the variations of the superheat at the through the evaporator. This is in agreement with the
evaporator outlet and the sub-cooling at the condenser outlet following expectations; the boiling heat transfer coefficients
for different heat source temperatures and refrigerant should increase with increasing mass flux, heat flux and
charges close to the optimum. The superheat was kept evaporation temperature. For the condenser, the overall heat
between 4 and 6.5 K and the sub-cooling was depending on transfer coefficient was almost independent of the heat
the system charge, since no receiver was equipped to the source temperatures. This was due to the higher LMTDs at
heat pump. For each heat source temperature the superheat higher heat source temperatures, although the capacity (Qc)
was independent of the refrigerant charge, while the sub- was higher at higher heat source temperatures. It can be
cooling was strongly coupled to the charge. As shown, the observed a decreasing in overall heat transfer coefficient at
optimum charges for each heat source temperature corre- the selected refrigerant charge ranges, since the increasing
spond to a sub-cooling of 4–5 K. of the refrigerant charge leads to a increasing the sub cool
Fig. 13 shows the variation of the overall heat transfer resulting increasing of the LMTD.

Table 1
Refrigerant charge distribution in various components

Heat source/heat sink K10.22/40.77 K2.09/40.67 6.93/40.77 12.64/40.74


temperatures (8C)
Evaporation/condensing K16.49/39.73 K8.79/40.44 K0.51/41.44 4.55/39.95
temp. (8C)
Evaporator/condenser 2.67/4.00 3.66/5.01 4.90/6.31 5.89/7.23
capacity (kW)
Super heat/sub cool (K) 4.66/3.91 5.30/4.76 5.18/4.56 5.77/3.82
Optimum refrigerant 170 201 240 265
charge (g)
Measured in evaporator 27 23 25 26
(g)
Measured in condenser 69 80 90 93
(g)
Measured in liquid line 24 24 23 24
(g)
Measured in compressor 50 74 102 122
(g)
770 P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773

5.3. Charge distribution tests experiments, will allow further reduction of refrigerant
charge.
The purpose of these tests was to determine the The pneumatically operated ball valves were placed
distribution of the refrigerant charge in the different parts close to the heat exchangers (Fig. 5). The refrigerant
of the system. For each heat source temperature tested, the amounts measured in the heat exchangers were; the total
system was charged with the optimum refrigerant charge. amounts in the heat transfer tubes, two end caps (headers)
Measurements were taken at stable conditions for a given and the tube lengths between ball valves and heat
heat source/sink temperature combinations and the four ball exchangers. The total inside volume between the ball valves
valves of the heat pump were closed simultaneously while surrounding the evaporator is 376 cm3; of this, the top end
the system was in operation. A small cylinder (one litre cap with the tube length between the ball valve and the heat
capacity) was connected to the isolated sections by a flexible exchanger has a volume of 52 cm3, the bottom end cap with
hose and the cylinder was immersed in a larger container, the tube length between the ball valve and the heat
which was filled with liquid air. The cooling of the cylinder exchanger has a volume 42 cm3 and heat transfer tube
caused a low pressure inside and thereby all the refrigerant volume is 279 cm3. The total inside volume between the
in different sections was drained to the cylinder. The valves surrounding the condenser is 437 cm3; of which the
differences between original refrigerant charge and the total top end cap with the tube length between the ball valve and
refrigerant drained were less than 5 g in all tests. The the heat exchanger represents a volume of 53 cm3, the
drained refrigerant was weighed. The accuracy of the bottom end cap with the tube length between the ball valve
measurements was G1 g. and the heat exchanger has the volume of 49 cm3 and the
Table 1 shows the refrigerant charge distribution in the heat transfer tube volume is 335 cm3. The end caps and the
heat pump for the four tested heat source temperatures for extra tube lengths occupy 25% of the total volume. Half of
the optimum charge. The amount of refrigerant in the this 25% volume is in the bottom side of the evaporator and
evaporator was almost same for all four tests, even though condenser where the refrigerant is at least partly in liquid
the evaporation temperature varied from K16.5 to C4.5 8C. phase. Since both, the evaporator and the condenser were
Also, the amount of refrigerant in the liquid line was the placed vertically; a considerable amount of refrigerant was
same in all four experiments. The amount of refrigerant in in the evaporator bottom side end cap and condenser bottom
the condenser varied from 69 to 93 g, showing an increase of side end cap. A redesign of these parts should result in lower
24 g in spite of the fact that the condensing temperature was liquid hold-up. The line between the two ball valves at the
almost constant. The refrigerant amount in the compressor condenser outlet and the evaporator inlet was considered as
was increased from 50 to 122 g, showing an increase of the liquid line. The liquid line consisted of: a sight glass,
72 g. The results of the charge distribution tests indicate that the expansion valve and some extra tubing to facilitate the
a considerable amount of the refrigerant is located in the fitting of the ball valves. The refrigerant amounts in the
compressor. It increases rapidly with increasing evaporation liquid line were consistent for all tests with a total mass of
temperature. This is a problem if, preferably, the system about 24 g. The introduction of smaller ends caps and
should be able to run with the same charge at different exclusion of extended tube lengths for the ball valves may
conditions. The lubrication oil type used in the compressor further reduce the optimum charge at least by 20 g.
was ester type oil (polyol ester). In parallel experiments, the
solubility of propane in different lubrication oils was tested. 5.4. Performance of the heat pump for a given refrigerant
In these experiments, the solubility of propane with two charge
polyol ester (POE) type oils and with one polyalkylene
glycol (PAG) type oil was tested. The solubility was tested In a separate test series, the system was charged with the
at different saturation temperatures and found that increased optimum refrigerant charges determined for the heat source
at higher temperatures and pressures. The solubility of temperatures K10, K2, 6 and 12 8C. For each charge the
propane in ester oil was higher than PAG oil [10]. heat source temperature was varied from K10 to C12 8C,
Solubility of refrigerant in lubrication oil is positive while keeping the heat sink temperature constant at 40 8C.
outside of the compressor as it aids the oil return to the Fig. 14 shows the influence of the heat source
compressor and also keeps the heat transfer surfaces free of temperature on the COP. The minimum sub-cooling of the
oil. Within the compressor high solubility causes a decrease condenser was about 2 K and was increased for lower heat
in lubricant viscosity, which may be harmful for the proper source temperatures due to backup of refrigerant into the
lubrication [11]. The solubility of refrigerant in lubricants condenser. The minimum super heat was kept at 4–6 K but
also depends on the viscosity of the lubricant. A lubricant was allowed to increase at higher heat source temperatures
with higher viscosity has low solubility in a refrigerant by closing the electronic expansion valve, thereby also
compared with the same lubricant type with lower viscosity lowering the evaporation temperature. This was done in
[12]. The selection of less soluble lubricant oil with propane order to prevent uncondensed gas to reach the expansion
or lubricant oil with higher viscosity than that used for these valve inlet.
P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773 771

Fig. 14. Variations of COP with heat source temperature for different refrigerant charges.

6. Heat source temperature Sweden. A borehole with 83 m active length was used the
heat source. The measurements were taken during a period
It is obvious that of higher heat source temperatures are of eight months, from 1st of October 2001 to 24th May
more favourable in heat pumps. The ground heat source is 2002.
the dominant heat source for heat pumps in the range above Fig. 15 shows the averaged (24 h) outdoor temperature
5 kW in Sweden. The most common method of extracting (A-ut) variation and the average temperature variation in the
heat from the ground is the circulation of brine in an 80– borehole at 25 m (A-BH-25) and 55 m (A-BH-55) depth on
150 m deep borehole. These boreholes provide excellent each day. The minimum and maximum average values of
working conditions and high reliability, but at relatively the outdoor temperature were K21 and 17 8C. The
high cost [13]. Figs. 15 and 16 show the monitored minimum and maximum average values of temperatures
temperature measurements in a single-family heat pump in the borehole at 25 m depth were K0.2 and 5.6 8C and at
located in Katrineholm (170 km south-west of Stockholm), 55 m depth 0.7 and 5.6 8C.

Fig. 15. Monitored (24 h) average temperature variations (three locations; outdoor, and at two levels in the bore hole, 25 m deep, 55 m deep) in
Katrineholm, Sweden in October 2001 to May 2002.
772 P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773

Fig. 16. Monitored minimum temperature variation (four locations; outdoor, at two levels in bore hole, 25 m deep ground, 55 m deep and brine
inlet temperature to a heat pump) on each day in Katrineholm, Sweden in October 2001 to May 2002.

Fig. 16 shows the minimum outdoor temperature (M-ut); exchangers are high, indicating that the reduction of
the minimum temperatures at the two locations of the borehole charge can be reached without loss of COP.
(M-BH-25 and M-BH-55) and the minimum brine inlet 3. Careful selection of compressor lubrication oil would
temperatures (M-BR-in) to the heat pump on each day. The further decrease the refrigerant charge of the heat pump.
range of minimum and maximum values of these outdoor 4. Reduction of the tube lengths and exclusion of ball
temperatures were K23 to 12 8C, borehole temperature at valves would give an optimum charge for the 5 kW
25 m depth, K2 to 5.2 8C, borehole temperature at 55 m depth, propane heat pump with ground heat source or other
0.5–5 8C and brine inlet temperature to the heat pump, K2.2 to liquid to liquid type applications of less than 200 g.
3.8 8C.
Although the outdoor temperature varied very much
during the period of the eight months, the ground
temperature variation was small. Fig. 16 shows that most
of the time the minimum ground temperature was higher Acknowledgements
than the minimum outdoor temperature. These conditions
are favourable for stable operation and high coefficients of Financial support from The Swedish National Energy
performances of the heat pump. Administration, aluminium tube supply from Hydro Alu-
The minimum brine inlet temperature range from K2.2 minium and compressor supply from Copeland is gratefully
to 3.8 8C suggests a best refrigerant charge to the proposed acknowledged. The authors express their gratitude to
propane heat pump. Fig. 14 shows that a charge of about Joachim Claesson and Martin Forsén, KTH, for their kind
200 g is the best choice for the heat pump providing a COP cooperation.
between 3.5 and 4.

References
7. Conclusions
[1] Swedish heat pump association.
The following conclusions are drawn from the tested [2] Calm J. Ferret Database; 1997.
laboratory heat pump and the temperature measurements [3] Pelletier O. Propane as refrigerant in residential heat pumps.
from the field heat pump Engineering Licentiate Thesis. Royal Institute of Technology,
Sweden; 1998.
1. Use of mini-channel heat exchangers reduces consider- [4] Primal WDF, Samoteeva O, Palm B, Lundqvist P. Charge
ably the refrigerant charge in heat pumps and refriger- distribution in a 5 kW heat pump using propane as working
ation systems. fluid. 16 Nordiske KØlemØde og 9, Nordiske Varmepumpe-
2. The heat transfer coefficients of mini-channel heat dage 29–31. KØbenhvn; 2001. p. 299.
P. Fernando et al. / International Journal of Refrigeration 27 (2004) 761–773 773

[5] Hrnjak P. Micro-channel heat exchangers as a design option [10] Primal WDF, Palm B, Granryd E, Houde H, Lundqvist P. The
for charge reduction in NH3 and HC systems Zero leakage- solubility of propane (R290) with commonly used compressor
minimum charge, IIR/IIF, Stockholm 2002 p. 91. lubrication oils. International Conference on compressors and
[6] Primal WDF, Palm B, Granryd E, Samoteeva O, Anderson K. their systems IMECHE Conference Transactions 2003–4.:
The behaviour of small capacity (5 kW) heat pump with Professional Engineering Publishing, ISSN; 2004 p. 1356–
micro-channel flat tube heat exchangers Zero leakage- 448.
minimum charge, IIR/IIF, Stockholm 2002 p. 179. [11] ASHRAE handbook. Refrigeration systems and applications,
[7] Primal WDF, Palm B, Granryd E, Andersson K. Mini-channel SI edition 1994 chapter 7; ISBN 1 883413 16 8.
aluminium heat exchangers with small inside volumes. [12] Spauschus HO, Henderson DR, Grasshoff HD. Lubricants for
Washington, DC: 21st IIR International Congress of refriger- hydrocarbon refrigerants Proceedings of the IIF-IIR Con-
ation; 2003. August 17–22. ference, new applications of natural working fluids in
[8] Dutto T, Blaise JC, Benedic T. Performance of brazed plate refrigeration and air conditioning, Hanover, Germany 1994
heat exchanger set in heat pump Proceedings of the 18th
p. 153; ISBN 2 903 633 68 1.
International Congress of Refrigeration, new challenges in
[13] Forsén M, Lundqvist P. Field measurements on a single-
refrigeration, Montreal, Quebec, Canada, vol. 3 1991. August
family house in Sweden supplied with a ground source heat
10–17.
pump for heating and passive cooling Fourth International
[9] Kedzierski MA. Effect of inclination on the performance of a
Conference on heat pumps in cold climates Quebec 17–18
compact brazed plate heat condenser and evaporator. Heat
August 2000.
Transfer Engng 1997;18(3):25–38.

You might also like