LOMBOK CFSPP FTP-2 Civil


(2X50 MW) PROJECT Mechanical

Review
Electrical
CONTRACTOR DOCUMENT REVIEW
I&C
Log Date : 12/06/2020 Support
In Comm. No :
A Approved
Contractor
B Approved as Note Record
C Not Approved Working Document
I Information

Distribution
APPROVAL DOES NOT RELIEVE
CONTRACTOR FROM RESPONSIBILITY
FOR ERRORS AND DEVIATIONS FROM
CONTRACT REQUIREMENT

By : Date :
Log Date : 30/06/2020
Out Comm. No : 000211
Owner :
PT. PERUSAHAAN LISTRIK NEGARA (PERSERO)
UNIT INDUK PEMBANGUNAN NUSA TENGGARA
Engineer :
PT. PERUSAHAAN LISTRIK NEGARA (PERSERO)
PUSAT ENJINIRING KETENAGALISTRIKAN
Contract No :
PLN Doc No :
1 0 1 2 2 B - 0 0 - M - 0 9 - Q E A - 0 0 7 - 0 1 - 4

Title :
INSTRUMENT AIR DRYER PACKAGE UNIT DATA SHEET
Purpose :
ISSUE FOR APPROVAL
Rev Description Prepared Checked Approved Date
4 IFA YKA EW TRL/AN 05/06/2020
3 IFA YKA EW TRL/AN 17/10/2019
2 IFA YKA EW TRL/AN 16/07/2019
1 IFA YKA EW TRL/AN 08/01/2019
0 IFA YKA EW TRL/AN 16/11/2018
Contractor : Consortium Of Doc. No :

LPP-30-W4-DS-202-R
Sheet 2 of 3

JOB NO.: 18-1206 REV


INSTRUMENT AIR DRYER PACKAGE UNIT 4
DOC. NO.: LPP-30-W4-DS-202-R
DATA SHEET
DATE BY CHKD APVD
05/06/2020 YKA EW TRL / AN

REVISION HISTORICAL SHEET

Rev. No. Date Description


0 16 Nov 2018 Issued for Approval
1 08 Jan 2019 Re-Issued for Approval
Re-Issued for Approval due to process data update
2 16 Jul 2019 - Revision of Air Dryer Package capacity
- Revision of Compressed air pressure
3 17 Okt 2019 Re-Issued for Approval
4 05 Jun 2020 Re-Issued for Approval due to QC item update
MECHANICAL DATA SHEET FOR AIR DRYER PACKAGE SHEET : 3 OF 3
CLIENT : PT. PERUSAHAAN LISTRIK NEGARA (PERSERO)
PROJECT : LOMBOK CFSPP FTP-2 (2X50 MW) PROJECT
REV 0 1 2 3 4
PRPD YKA YKA YKA YKA YKA
JOB NO. : 18-1206
CHKD EW EW EW EW EW
ITEM NO. : 10QFA1OAHOO1 APPD TRL / AN TRL / AN TRL / AN TRL / AN TRL / AN
DOC. NO. : LPP-30-W4-DS-202-R DATE 16/11/2018 8/01/2019 16/07/2019 17/10/2019 5/06/2020

APPLICABLE TO : Proposal Purchase As Built


1
2 MANUFACTURER ATLAS COPCO NO. REQUIRED : 1 Package SERVICE COMPRESSED AIR DRYER
3 SERIAL NO. * MODEL : FX 16 SITE LOMBOK, WEST NUSA TENGGARA, INDONESIA
4 TYPE REFRIGERANT TYPE
5 OPERATING CONDITIONS
6 FLUID COMPRESSED AIR OUTLET CONDITION SEE NOTE #2
7 FLOW (Nm3/hr) 800 DEW POINT ( C)
o
3
8 CONTROL l FULLY AUTO ¡ PRESS. (kg/cm2G) MIN. 7 MAX. 7.7
9 INLET CONDITION ALLOW. PRESS. DROP (kg/cm2G) 0.5 (SEE NOTE #3) ACT.
10 PRESS. (kg/cm2G) MIN. 7.5 MAX. 8.2 INSTALLATION ¡ INDOOR l OUTDOOR ¡
o o
11 TEMP. ( C) NOR. 65.66 DES. 82.22 AMB. TEMP. ( C) MIN. 19 MAX. 40
12 HAZARDOUS AREA CLASS.: NON HAZARDOUS
13 CONSTRUCTION
14 ¡ DESICCANT TYPE l REFRIGERANT TYPE REFRIGERANT: R410A
15 DESICCANT QUANTITY.(KG): / CHAMBER l AIR COOLED ¡ WATER COOLED
16 REGENERATION CYCLE TIME (h): NO. OF COMPRESSOR 1
17 ¡ THERMAL SWING ¡ ELECTRIC ¡ STEAM TYPE OF COMPRESSOR Piston
18 ¡ PRESSURE SWING (Heatless) CONDENSER HEAT DUTY (kcal/h) *
19 ¡ AIR FLOW (Nm /h)
3
EVAPORATOR HEAT DUTY (kcal/h) *
20 REGENERATION OTHER
21 ¡ BLOWER
22 ADSORPTION CHAMBER, QUANTITY: l PREFILTER, QUANTITY: 2 set + Diff Press Gauge
23 TYPE: TYPE Dual reverse type with pressure gauge
24 MATERIAL, CHAMBER: REMOVED PARTICLE Water, Oil droplets and Dust
25 INTERNAL ELEMENT: FILTRATION (micron): 0.01 µm EFF 99%
2 o
26 DES. PRESS (kg/cm G) 16.3 AT 66 C
27 DIA. (mm): HEIGHT (mm): ACCESSORIES Drain Trap
28 DES. PRESS (kg/cm G)
2
AT o
C l AFTER FILTER, QUANTITY: 2 set + Diff Press Gauge
29 CORROSION ALLOWANCE (mm): TYPE Dual Type
30 DES. CODE: FILTRATION (micron): 0.01 EFF 99%
2 o
31 DES. PRESS (kg/cm G) 16.3 AT 66 C
32 ACCESSORIES Drain Trap
33 ACCESSORIES OTHERS
34 ¡ AIR HEATER l FILTER BASEPLATE l COMMON ¡ SEPARATE
35 ¡ RELIEF VALVES ¡ DESICCANT INIT. CHARGE WEIGHT (kg): 165 (without filter)
36 l DRAIN TRAPS l DRAIN VALVES MAX. MAINTENANCE WEIGHT (kg): 165 (without filter)
37 ¡ SWITCH-OVER VALVES l REFRIGERANT SPACE REQD: L X W X H (m): 898 x 735 x 1002 (without filter)
38 l LOCAL CONTROL PANEL l INSTRUMENTATION EXP. SOUND LEVEL (dBA @ 1 m): 85
39 l MOISTURE INDICATOR l OTHERS CODE & STANDARD: MFR'S STANDARD
40 l INTERCONNECTING PIPING WITHIN SKID (MFR'S STD) APPLICABLE SPEC.:
41 INSTRUMENTS & CONTROL REQUIREMENTS SHOP INSPECTION
42 ¡ Automatic Regeneration cycle operation Required Witnessed
4
43 l High dew point indication and running indication Leak Test l ¡
44 ¡ Indicator lamp for each tower for operation or regeneration Mechanical Running test ¡ ¡
45 l Connection terminals for running and common alarm signals of dryer Performance Test (SEE NOTE #6) l l
46 ¡ Filter differential pressure high & adsorber tower differential high Complete Unit Test (SEE NOTE #6) l l
47 Dryer function test l l
48
49
50 UTILITY CONDITIONS
51 ELECTRICAL POWER SUPPLY (AT LCP) : 400 V / 3PH / 50 HZ COOLING WATER

52 COMPRESSOR MOTOR RATING 3592 kw CW INLET / OUTLET TEMP. N/A / N/A deg C
53 FAN MOTOR RATING 780 kw CW FLOW N/A m3/h
54 STEAM

55 PRESSURE / TEMP N/A kG/cm2G / deg C


56 FLOW N/A kg/h
57 REMARKS :

58 #1 (*) By Vendor
59 #2 Air quality shall meet ISO 8573.1 Class 1.4.1.
60 #3 Pressure drop for total package include pre-filter and after filter
61 #4 Pipe Flange dimensions for purchaser connection shall conform to ASME B.16.5
62 #5 Refrigrant type shall be environmentally friendly 4
63 #6 Complete Performance and Unit Test shall be done at Site
64