The document provides test results for various components of a high voltage circuit breaker and associated equipment. It tests the circuit breaker nameplate details, insulation resistance, contact resistance, time intervals, coil resistances, control circuits, and current transformers. All test results were found to be within acceptable limits, with no abnormalities noted in any of the components tested.
The document provides test results for various components of a high voltage circuit breaker and associated equipment. It tests the circuit breaker nameplate details, insulation resistance, contact resistance, time intervals, coil resistances, control circuits, and current transformers. All test results were found to be within acceptable limits, with no abnormalities noted in any of the components tested.
The document provides test results for various components of a high voltage circuit breaker and associated equipment. It tests the circuit breaker nameplate details, insulation resistance, contact resistance, time intervals, coil resistances, control circuits, and current transformers. All test results were found to be within acceptable limits, with no abnormalities noted in any of the components tested.
The document provides test results for various components of a high voltage circuit breaker and associated equipment. It tests the circuit breaker nameplate details, insulation resistance, contact resistance, time intervals, coil resistances, control circuits, and current transformers. All test results were found to be within acceptable limits, with no abnormalities noted in any of the components tested.
Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018
Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 01, OUTGOING 01, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2604VC 1.3 Breaker Type : VCB 1.4 Rated Voltage : 33 KV 1.5 Rated Current : 1250 A 1.6 Closing Coil : 110 V DC 1.7 Tripping Coil : 110 V DC 1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation Resistance Close Condition Open Condition Test. Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B Ohms, Ω 1T 1T 1T 800 G 860 G 830 G 1T 1T 1T
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 23 26 22
4. Time Interval Test. Phase Closing Time, Ms Opening Time, mS C/O Time, mS R- Phase 48.3 37.5 28.8 Y- Phase 47.7 37.7 27.9 B- Phase 48.2 37.6 28.5
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 47.8 169.6 22.7
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil Voltage 28.3 V DC 26.5 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark 1 Manual Charging of Spring OK 2 Mechanical closing and tripping OK 3 Mechanical interlocks of breaker OK 4 Charging of spring through motor OK 5 Electrical interlocks of breaker OK 6 Tripping through relays OK Breaker close command blocking when Relays/releases is in operated 7 OK condition 8 Abnormality, if any NONE 7. Maintenance and General Check- up. Sr. No. Description Remark 1 Inspection for physical damage OK 2 Cleaning and tightness of breaker bolts OK 3 Breaker rack-in and rack-out OK 4 Alignment of breaker OK 5 Earthling connection OK 6 Abnormality, if any NONE
8. Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 01, OUTGOING 01, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd Metering Prote. Acc.class of Acc.class of Phase Ratio, Amps Serial No. core VA core VA Mete. Core Protn. Core R 300 / 1-1-1 1612403 15 15/VK 0.5 5P10 / PS Y 300 / 1-1-1 1612404 15 15/VK 0.5 5P10 / PS B 300 / 1-1-1 1612408 15 15/VK 0.5 5P10 / PS
2.0 Insulation Resistance test :
Values in Ω Insulation resistance test between R Y B Primary to Earth, 5 Kv 57.G 64.G 107 G Primary to Secondary (Core – 1), 5 kV 20 G 18 G 28 G Secondary (Core – 1) to Earth, 500 V 1G 1G 1G Primary to Secondary (Core – 2), 5 kV 19 G 25 G 30 G Secondary (Core – 2) to Earth, 500 V 1G 1G 1G Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G 3.0 Ratio, polarity and circuit checks : 3.1.0 Ratio test on 300A 3.1.1 Metering core: Injected primary Measured secondary Current measured Phase Polarity Ratio current, Amps current, Amps at meter, Amps R 150 / 300 0.50 / 1.01 OK OK OK Y 150 / 300 0.51 / 1.05 OK OK OK B 150 / 300 0.50 / 0.99 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary Phase Relay operation Polarity Ratio current, Amps current, Amps R 150 / 300 0.49 / 1.02 OK OK OK Y 150 / 300 0.50 / 0.99 OK OK OK B 150 / 300 0.51 / 0.99 OK OK OK
3.1.3 Protection core:
Injected primary Measured secondary Phase Relay operation Polarity Ratio current, Amps current, Amps R 150 / 300 0.51 / 1.01 OK OK OK Y 150 / 300 0.50 / 1.02 OK OK OK B 150 / 300 0.51 / 1.01 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks 4.1 Inspection for physical damage OK 4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 02, INCOMER 01, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2605VC 1.3 Breaker Type : VCB 1.4 Rated Voltage : 33 KV 1.5 Rated Current : 1250 A 1.6 Closing Coil : 110 V DC 1.7 Tripping Coil : 110 V DC 1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation Resistance Close Condition Open Condition Test. Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B Ohms, Ω 958 G 868 G 930 G 830 G 810 G 841 G 789 G 808 G 768 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 29 27 28
4. Time Interval Test. Phase Closing Time, Ms Opening Time, mS C/O Time, mS R- Phase 43.2 36.2 25.6 Y- Phase 44.3 36.1 25.8 B- Phase 43.6 36.3 25.4
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 46.5 167.4 23.8
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil Voltage 27.6 V DC 27.8 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark 1 Manual Charging of Spring OK 2 Mechanical closing and tripping OK 3 Mechanical interlocks of breaker OK 4 Charging of spring through motor OK 5 Electrical interlocks of breaker OK 6 Tripping through relays OK Breaker close command blocking when Relays/releases is in operated 7 OK condition 8 Abnormality, if any NONE 7.0 Maintenance and General Check- up. Sr. No. Description Remark 1 Inspection for physical damage OK 2 Cleaning and tightness of breaker bolts OK 3 Breaker rack-in and rack-out OK 4 Alignment of breaker OK 5 Earthling connection OK 6 Abnormality, if any NONE
8.0 Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 02, INCOMER 01, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd Metering Prote. Acc.class of Acc.class of Phase Ratio, Amps Serial No. core VA core VA Mete. Core Protn. Core R 600-300 / 1-1 1612336 15 15 0.5 5P10 Y 600-300 / 1-1 1612337 15 15 0.5 5P10 B 600-300 / 1-1 1612338 15 15 0.5 5P10
2.0 Insulation Resistance test :
Values in Ω Insulation resistance test between R Y B Primary to Earth, 5 Kv 65.G 68.G 75 G Primary to Secondary (Core – 1), 5 Kv 26 G 22 G 28 G Secondary (Core – 1) to Earth, 500 V 1G 1G 1G Primary to Secondary (Core – 2), 5 kV 29 G 26 G 27 G Secondary (Core – 2) to Earth, 500 V 1G 1G 1G Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G 3.0 Ratio, polarity and circuit checks : 3.1.0 Ratio test on 600/300A 3.1.1 Metering core: Injected primary Measured secondary Current measured Phase Polarity Ratio current, Amps current, Amps at meter, Amps R 150 / 300 / 450 / 600 0.25 / 0.50 / 0.75 / 1.03 OK OK OK Y 150 / 300 / 450 / 600 0.26 / 0.51 / 0.76 / 1.01 OK OK OK B 150 / 300 / 450 / 600 0.25 / 0.50 / 0.75 / 1.02 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary Phase Relay operation Polarity Ratio current, Amps current, Amps R 150 / 300 / 450 / 600 0.25 / 0.49 / 0.76 / 1.01 OK OK OK Y 150 / 300 / 450 / 600 0.24 / 0.51 / 0.75 / 1.00 OK OK OK B 150 / 300 / 450 / 600 0.25 / 0.49 / 0.76 / 1.01 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks 4.1 Inspection for physical damage OK 4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF POTENTIAL TRANSFORMER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 02, INCOMER 01, 33 KV HT PANEL.
1.0 Name Plate details of potential transformer :
Make of PT: Crompton Greaves ltd Phase Ratio, Volts Serial No. R 33000/√3/110/√3/110/√3 16/018962 Y 33000/√3/110/√3/110/√3 16/018970 B 33000/√3/110/√3/110/√3 16/018969
Values in Ω Insulation resistance test between R Y B Primary to Earth, 5 kV 70 G 83 G 67 G Primary to Secondary (Core – 1), 5 kV 35 G 40 G 30 G Secondary (Core – 1) to Earth, 500 V 1G 1G 1G Primary to Secondary (Core – 2), 5 kV 31 G 38 G 29 G Secondary (Core – 2) to Earth, 500 V 1G 1G 1G Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G 3.0 Ratio, polarity and circuit checks : Injected primary Measured Metering Measured Protection Phase Polarity Ratio voltage, Volts voltage, P-P Volts voltage, P-N Volts RY 419 1.41 0.809 OK OK YB 420 1.43 0.810 OK OK BR 419 1.41 0.808 OK OK
3.1 Metering core: 1
Injected primary Measured Metering Measured Protection Phase Polarity Ratio voltage, Volts voltage, P-P Volts voltage, P-N Volts RY 419 1.43 0.808 OK OK YB 420 1.42 0.809 OK OK BR 419 1.43 0.807 OK OK
4.0 General check-up :
Sr. No. Description Remarks 4.1 Inspection for physical damage OK 4.2 Continuity check for voltmeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 03, BUS COUPLER, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2606VC 1.3 Breaker Type : VCB 1.4 Rated Voltage : 33 KV 1.5 Rated Current : 1250 A 1.6 Closing Coil : 110 V DC 1.7 Tripping Coil : 110 V DC 1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation Resistance Close Condition Open Condition Test. Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B Ohms, Ω 1T 1T 1T 1T 1T 1T 1T 1T 1T
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 26 24 25
4. Time Interval Test. Phase Closing Time, Ms Opening Time, mS C/O Time, mS R- Phase 39.6 31.8 23.8 Y- Phase 39.5 31.6 24.2 B- Phase 39.7 31.5 23.7
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 43.5 168.2 24.3
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil Voltage 28.3 V DC 27.2 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark 1 Manual Charging of Spring OK 2 Mechanical closing and tripping OK 3 Mechanical interlocks of breaker OK 4 Charging of spring through motor OK 5 Electrical interlocks of breaker OK 6 Tripping through relays OK Breaker close command blocking when Relays/releases is in operated 7 OK condition 8 Abnormality, if any NONE 7. Maintenance and General Check- up. Sr. No. Description Remark 1 Inspection for physical damage OK 2 Cleaning and tightness of breaker bolts OK 3 Breaker rack-in and rack-out OK 4 Alignment of breaker OK 5 Earthling connection OK 6 Abnormality, if any NONE
8. Remark: TESTING AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 04, TRUNKING CHAMBER, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2606AVC 1.3 Breaker Type : VCB 1.4 Rated Voltage : 33 KV 1.5 Rated Current : 1250 A 1.6 Closing Coil : 110 V DC 1.7 Tripping Coil : 110 V DC 1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation Resistance Close Condition Open Condition Test. Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B Ohms, Ω 752 G 762 G 787 G 668 G 687 G 678 G 708 G 723 G 713 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 32 34 31
4. Time Interval Test. Phase Closing Time, Ms Opening Time, mS C/O Time, mS R- Phase 39.5 34.5 27.8 Y- Phase 39.7 34.3 27.6 B- Phase 39.6 34.2 27.9
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 47.5 166.8 24.5
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil Voltage 28.1 V DC 26.3 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark 1 Manual Charging of Spring OK 2 Mechanical closing and tripping OK 3 Mechanical interlocks of breaker OK 4 Charging of spring through motor OK 5 Electrical interlocks of breaker OK 6 Tripping through relays OK Breaker close command blocking when Relays/releases is in operated 7 OK condition 8 Abnormality, if any NONE 7. Maintenance and General Check- up. Sr. No. Description Remark 1 Inspection for physical damage OK 2 Cleaning and tightness of breaker bolts OK 3 Breaker rack-in and rack-out OK 4 Alignment of breaker OK 5 Earthling connection OK 6 Abnormality, if any NONE
8. Remark: TESTING AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 05, INCOMER 02, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2607VC 1.3 Breaker Type : VCB 1.4 Rated Voltage : 33 KV 1.5 Rated Current : 1250 A 1.6 Closing Coil : 110 V DC 1.7 Tripping Coil : 110 V DC 1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation Resistance Close Condition Open Condition Test. Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B Ohms, Ω 983 G 976 G 965 G 832 G 851 G 822 G 786 G 768 G 776 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 29 27 30
4. Time Interval Test. Phase Closing Time, Ms Opening Time, mS C/O Time, mS R- Phase 49.8 39.8 28.7 Y- Phase 49.5 39.4 28.6 B- Phase 49.7 39.6 28.7
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 45.6 167.8 21.9
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil Voltage 26.4 V DC 24.3 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark 1 Manual Charging of Spring OK 2 Mechanical closing and tripping OK 3 Mechanical interlocks of breaker OK 4 Charging of spring through motor OK 5 Electrical interlocks of breaker OK 6 Tripping through relays OK Breaker close command blocking when Relays/releases is in operated 7 OK condition 8 Abnormality, if any NONE 7. Maintenance and General Check- up. Sr. No. Description Remark 1 Inspection for physical damage OK 2 Cleaning and tightness of breaker bolts OK 3 Breaker rack-in and rack-out OK 4 Alignment of breaker OK 5 Earthling connection OK 6 Abnormality, if any NONE
Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 05, INCOMER 02, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd Metering Prote. Acc.class of Acc.class of Phase Ratio, Amps Serial No. core VA core VA Mete. Core Protn. Core R 600-300 / 1-1 1612339 15 15 0.5 5P10 Y 600-300 / 1-1 1612334 15 15 0.5 5P10 B 600-300 / 1-1 1612335 15 15 0.5 5P10
2.0 Insulation Resistance test :
Values in Ω Insulation resistance test between R Y B Primary to Earth, 5 Kv 54.G 62.G 56 G Primary to Secondary (Core – 1), 5 Kv 26 G 24 G 27 G Secondary (Core – 1) to Earth, 500 V 1G 1G 1G Primary to Secondary (Core – 2), 5 kV 30 G 28 G 31 G Secondary (Core – 2) to Earth, 500 V 1G 1G 1G Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G 3.0 Ratio, polarity and circuit checks : 3.1.0 Ratio test on 600/300A 3.1.1 Metering core: Injected primary Measured secondary Current measured Phase Polarity Ratio current, Amps current, Amps at meter, Amps R 150 / 300 / 450 / 600 0.24 / 0.51 / 0.74 / 1.00 OK OK OK Y 150 / 300 / 450 / 600 0.25 / 0.50 / 0.75 / 1.03 OK OK OK B 150 / 300 / 450 / 600 0.24 / 0.49 / 0.74 / 1.01 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary Phase Relay operation Polarity Ratio current, Amps current, Amps R 150 / 300 / 450 / 600 0.24 / 0.51 / 0.75 / 1.01 OK OK OK Y 150 / 300 / 450 / 600 0.25 / 0.50 / 0.74 / 0.99 OK OK OK B 150 / 300 / 450 / 600 0.24 / 0.51 / 0.75 / 1.01 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks 4.1 Inspection for physical damage OK 4.2 Continuity check for ammeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF POTENTIAL TRANSFORMER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 05, INCOMER 02, 33 KV HT PANEL.
1.0 Name Plate details of potential transformer :
Make of PT: Crompton Greaves ltd Phase Ratio, Volts Serial No. R 33000/√3/110/√3/110/√3 16/018971 Y 33000/√3/110/√3/110/√3 16/018973 B 33000/√3/110/√3/110/√3 16/018974
Values in Ω Insulation resistance test between R Y B Primary to Earth, 5 kV 65 G 76 G 96 G Primary to Secondary (Core – 1), 5 kV 43 G 46 G 48 G Secondary (Core – 1) to Earth, 500 V 1G 1G 1G Primary to Secondary (Core – 2), 5 kV 34 G 36 G 35 G Secondary (Core – 2) to Earth, 500 V 1G 1G 1G Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G 3.0 Ratio, polarity and circuit checks : Injected primary Measured Metering Measured Protection Phase Polarity Ratio voltage, Volts voltage, P-P Volts voltage, P-N Volts RY 419 1.42 0.810 OK OK YB 420 1.41 0.813 OK OK BR 419 1.43 0.811 OK OK
3.1 Metering core: 1
Injected primary Measured Metering Measured Protection Phase Polarity Ratio voltage, Volts voltage, P-P Volts voltage, P-N Volts RY 419 1.40 0.812 OK OK YB 420 1.42 0.811 OK OK BR 419 1.41 0.812 OK OK
4.0 General check-up :
Sr. No. Description Remarks 4.1 Inspection for physical damage OK 4.2 Continuity check for voltmeter and/or relay circuits OK
5.0 Remarks : TESTED AS ABOVE
TEST CERTIFICATE OF HT CIRCUIT BREAKER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 06, OUT GOING 02, 33 KV HT PANEL.
1. Name Plate details of circuit breaker.
1.1 Make : Crompton Greaves ltd
1.2 Serial No : 2608VC 1.3 Breaker Type : VCB 1.4 Rated Voltage : 33 KV 1.5 Rated Current : 1250 A 1.6 Closing Coil : 110 V DC 1.7 Tripping Coil : 110 V DC 1.8 Motor Coil : 230 V AC
2. Insulation Resistance Test.
Insulation Resistance Close Condition Open Condition Test. Values in G R-Y Y-B B-R R-E Y-E B-E R-R Y-Y B-B Ohms, Ω 869 G 875 G 863 G 786 G 768 G 765 G 806 G 814 G 803 G
3. Contact Resistance Measurement.
Contact Resistance of R- Phase Y- Phase B- Phase
Values in Micro Ohms, Ω 27 26 28
4. Time Interval Test. Phase Closing Time, Ms Opening Time, mS C/O Time, mS R- Phase 46.2 38.4 29.4 Y- Phase 46.8 37.3 28.7 B- Phase 46.5 37.5 29.5
5. Coil Resistance Measurement.
Coil Resistance of Closing Coil Opening Coil Motor Coil
Values in Ohms 47.3 168.2 23.7
5.1 Pickup voltage Test:
Coil designation Closing Coil Tripping Coil Voltage 28.6 V DC 26.8 V DC
6. Control Circuit and Operational Checks.
Sr. No. Description Remark 1 Manual Charging of Spring OK 2 Mechanical closing and tripping OK 3 Mechanical interlocks of breaker OK 4 Charging of spring through motor OK 5 Electrical interlocks of breaker OK 6 Tripping through relays OK Breaker close command blocking when Relays/releases is in operated 7 OK condition 8 Abnormality, if any NONE 7. Maintenance and General Check- up. Sr. No. Description Remark 1 Inspection for physical damage OK 2 Cleaning and tightness of breaker bolts OK 3 Breaker rack-in and rack-out OK 4 Alignment of breaker OK 5 Earthling connection OK 6 Abnormality, if any NONE
Remark: TESTING AS ABOVE
TEST CERTIFICATE OF CURRENT TRANSFORMER Client EAGLE CONSTRUCTION, LUCKNOW Tested on 20.01.2018 Plant SUB STATION, HT PANEL Tested by RAHUL SINGH Location PANEL: - 06, OUT GOING 02, 33 KV HT PANEL.
1.0 Name Plate details of current transformer :
Make of CT: Crompton Greaves ltd Metering Prote. Acc.class of Acc.class of Phase Ratio, Amps Serial No. core VA core VA Mete. Core Protn. Core R 300 / 1-1-1 1612406 15 15/VK 0.5 5P10 / PS Y 300 / 1-1-1 1612405 15 15/VK 0.5 5P10 / PS B 300 / 1-1-1 1612407 15 15/VK 0.5 5P10 / PS
2.0 Insulation Resistance test :
Values in Ω Insulation resistance test between R Y B Primary to Earth, 5 Kv 68.G 62.G 67 G Primary to Secondary (Core – 1), 5 kV 29 G 31 G 27 G Secondary (Core – 1) to Earth, 500 V 1G 1G 1G Primary to Secondary (Core – 2), 5 kV 32 G 30 G 33 G Secondary (Core – 2) to Earth, 500 V 1G 1G 1G Secondary (Core – 1) to Secondary (Core – 2), 500 V 1G 1G 1G 3.0 Ratio, polarity and circuit checks : 3.1.0 Ratio test on 300A 3.1.1 Metering core: Injected primary Measured secondary Current measured Phase Polarity Ratio current, Amps current, Amps at meter, Amps R 150 / 300 0.49 / 0.99 OK OK OK Y 150 / 300 0.50 / 1.01 OK OK OK B 150 / 300 0.51 / 1.02 OK OK OK
3.1.2 Protection core:
Injected primary Measured secondary Phase Relay operation Polarity Ratio current, Amps current, Amps R 150 / 300 0.52 / 1.02 OK OK OK Y 150 / 300 0.51 / 1.04 OK OK OK B 150 / 300 0.52 / 0.99 OK OK OK
3.1.3 Protection core:
Injected primary Measured secondary Phase Relay operation Polarity Ratio current, Amps current, Amps R 150 / 300 0.49 / 0.99 OK OK OK Y 150 / 300 0.51 / 1.01 OK OK OK B 150 / 300 0.50 / 0.99 OK OK OK
4.0 General check-up :
Sr. No. Description Remarks 4.1 Inspection for physical damage OK 4.2 Continuity check for ammeter and/or relay circuits OK