System Component Selection Summary

By Trane

Alternative 1

System Description: System - 001


System Type: Fan Coil
Number of Zones: 1
Number of Rooms: 1

Component Sizing Method Location Quantity


Cooling
Main Clg Coil Block Room 1
Primary Clg Fan Peak Room 1
Heating
Main Htg Coil Peak Room 1
Miscellaneous
Return Fan Return Airflow System 1

Coil Location Cooling Coil Selection


Time Sensible Airflow At
Of Peak Total Capacity Capacity Coil Peak Enter DB/ WB/ HR Leave DB/ WB/ HR
System Zone Room Component Mo/Hr ton MBh MBh cfm °F °F gr/lb °F °F gr/lb
CUARTO ELECTRICO Main Clg Coil 6/17 15.0 180.0 177.8 12,107 68.0 56.6 49.3 55.0 51.1 49.0

Coil Location Heating Coil Selection


Entering Leaving
Total Capacity Airflow DB HR DB HR
System Zone Room Component MBh cfm °F gr/lb °F gr/lb
CUARTO ELECTRICO Main Htg Coil -1.6 12,107 65.0 65.1

Component Location Miscellaneous Component Selection


SADB Minimum
Design Airflow Outside Air Clg Htg Airflow
System Zone Room Component cfm Ach/hr % °F °F cfm
System - 001 Return Fan 12,107
CUARTO ELECTRICO Primary Fan 12,107 57.2 0.0 55.0
CUARTO ELECTRICO Diffuser 12,107 57.2 0.0 55.0 65.0

Project Name: AIRE ACONDICIONADO CUARTO TECNICO CCM3 TRACE® 700 v6.2.4 calculated at 10:12 AM on 08/20/2021
Dataset Name: CUARTO ELECTRICO.trc Alternative - 1 System Component Selection Summary Page 1 of 1