Siemens High Voltage Circuit Breaker

Co., Ltd., Hangzhou (SHVC)


High-Voltage Circuit-Breakers

Copyright© Siemens AG
Energy / Transmission / High Voltage Products
Air Insulated Switchgear

1. Product Introduction

2. Maintenance

Page 2 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
Air Insulated Switchgear

Surge Instrument Circuit Line


Bushings Arresters Transformers Breakers Disconnectors Traps

Page 3 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
Air Insulated Switchgear

GIS
Circuit Breaker
Current Transformer
Voltage Transformer
HYBRID Disconnector
 Circuit Breaker Earthing Switch
 Current Transformer Busbar / Busducts
 Voltage Transformer Exits
 Disconnector
Value Creation

DTB  Earthing Switch


 Circuit Breaker
 Current Transformer

LTB
 Circuit Breaker

Functional Integration
Page 4 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High-Voltage Circuit-Breakers, Disconnectors and Dead
Tank Compact

Live and Dead Tank Circuit- Disconnectors and Compact Switchgear


Breakers for rated voltages Earthing Switches solutions for AIS
from 72.5 up to 550 kV

Double Side Break


3AP1 FI 252 kV 3AP1 DT 145 kV Pantograph 252 kV 252 kV 3AP1 DTC 145 kV

3AP2 FI 550kV Knee Type 550kV 3AP1 DTC 252 kV

Page 5 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
Range of Products Type Definition

3AP1 FI DTC

three pole outdoor circuit-breaker

name of circuit-breaker series (P, Q, T)

interrupter units per pole

spring (F) / hydraulic (E) operated mechanism


G: 1 mechanism + 1 common base
E: 3 mechanisms + 1 common base
I : 3 mechanisms + 3 individual bases
Dead Tank

Compact

Page 6 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
Product Range Live Tank

Rated short-circuit
breaking current [kA]
80

3AT2/3 3AT4/5
63

50

40

31,5

25

3AP1 FG 3AP1 FI 3AP2/3 FI 3AP4/5 FI


0
72,5 123 145 170 245 300 362 420 550 800 Rated voltage [kV]

Page 7 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High-Voltage Circuit-Breaker
Type 3AP1 FG up to 252 kV

Product Characteristics

 For all applications: reliable and economical


 Common stored energy Spring Drive Mechanism
for all 3 poles (FG)
 Self compression arc quenching principle
 Rated voltages up to 252 kV
 Rated short circuit breaking current up to 50 kA
 Type tested according to IEC 62271-100
 Also available for one pole operation (FI)
 Delivered more than 60,000 breakers
to 129 countries

Page 8 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High-Voltage Circuit-Breaker
Type 3AP1 FI up to 300 kV

Product Characteristics

 One stored energy Spring Drive Mechanism per


pole (FI)
 Self compression arc quenching principle
 Rated voltages up to 300 kV
 Rated short circuit breaking current up to 50 kA
 Type tested according to IEC 62271-100
 Economical and durable

Page 9 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High-Voltage Circuit-Breakers
Type 3AP2/3 FI up to 550 kV

Product Characteristics

 Stored energy Spring Drive Mechanism


 Self compression arc quenching principle
 Rated voltages up to 550 kV
 Rated short circuit breaking current up to 63 kA
 Type tested according to IEC 62271-100
 Two cycles breaker
 Also available with closing resistor (3AP3)
 Easy installation and commissioning:
only few subassemblies
 Transportation costs are minimized

Page 10 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Type Centre Break

Product Characteristics
 Rated voltages 126 kV up to 252 kV
 Rated normal current 1250 A up to 4000 A
 Rated short-time withstand current
40 kA up to 50 kA – 3 s
 According to latest IEC Standard 62271-102
 Temperature range from -50 °C to +50 °C
 Operating mechanisms
Disconnector manual/motor
Earthing Switch manual/motor
(three pole operation / single pole operation)
 Arrangement: in line / parallel
 Applicable with 1 or 2 build-on-earthing
switches

Page 11 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.1 General check


The check covers a visual inspection of the circuit-breaker without it having
to be dismantled. The visual inspection contents the following checks:
- check the SF6 filling with the circuit-breaker pressure gauge,
- contamination of insulating parts
- damage to the porcelain body
- number of operating cycles
1.2 Checking the SF6-gas filling
If the measured SF6 pressure lies below the filling curve by not more than
0.3 bar/0.03MPa/4.4 psig (permissible gas loss), refill with SF6.
If the measured value is more than 0.3 bar/0.03 MPa/ 4.4 psi below the
filling curve specified, a leak test must be carried out and the leak must be
repaired. Then the filling must be corrected.

Page 12 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.3 Filling the breaker with SFs


The circuit-breaker may be filled only by or under the supervision of
qualified personnel and in accordance with the SF6 filling curve

Page 13 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.4 Check and Checkout SF6 pressure gauge(integrated density monitor and
pressure gauge)
On-site calibration: first close the pressure gauge valve to segregate the
gauge from gas room of circuit breaker, then full the standard air pressure
across filling connection to checkout the Gas density monitor according to
stated process.
No on-site calibration: make calibration of the Gas density monitor
according to stated process.
Load and unload Gas density monitor as following process
Unload: close the pressure gauge valve --> Gas density monitor
Load: Gas density monitor ⼀> open the pressure gauge valve

Page 14 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

To test the density monitor, close the


pressure gauge valve, The filling
connection is now connected directly with
the density monitor, such that (after
connection of the filling device W424) the
ope「ating points of the density monitor
(Section 3-0080 Technical Data ) can be
checked by regulating the SF6 pressure on
the pressure reducer.

Page 15 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.5 Checks at drive mechanism


1.5.1 Auxiliary switch
The bearings of the auxiliary switch are maintenance-free. Check the linkage
for wear and damage (Fig. 11).
Press the spring lap of the AMP plug if the leads are to be disconnected
from the auxiliary switch. By pulling on the isolation shell of the AMP plug,
the AMP plug with isolation shell will be automatically released.

Page 16 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.5.2 Visual inspection of the


spring drive mechanism
Visually inspect dampers for
closing and opening for any leaks.
Look out for yellowish oil traces
in the vicinity of the lower
damper fastener (Fig. 12).
If you find any yellowish oil traces
at the specified positions (fig. 12),
inform the Siemens
representative responsible and
ask for expert assistence.

Page 17 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.5.3 Check trip coil and latching blocks


Check that the trip coil plate (bolts M6 X 40 with tightning torque of 8⼠1
Nm) and the latching blocks (bolts M 10 X 70 with tightning torque of 40⼠4
Nm) are firmly fixed (Fig. 13).

Page 18 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.6 Electrical connections


Check the terminal connections for firm seating and the terminals for
damage.
1.7 Anti-condensation
Check the effectiveness of the anti-condensation heatng and the function of
the existing monitoring device if applicable.
1.8 Functional checks
1.8.1 Functional check, trip circuits
Check the tripping action of the circuit-breaker via all the existing tripping
paths.
1.8.2 Functional check reclosing lock-out
During the process of charging the closing spring, the effectiveness of the
reclosing lock-out must be checked by means of an electrical "Close"
command. The tripping coil must not trip

Page 19 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.8.3 Functional check SF6


At a level below the operating pressure, check the signal and the
effectiveness of the function lock-out by means of electrical "Close" and
"Open" commands in all tripping paths. The breaker must not operate.
1.8.4 Functional check, anti-pumping feature
Breaker in "Open" state: (Closing spring charged)
- Give electrical "Close" command and keep button pressed in (maintained
command)
The circuit breaker must only open.
1.9 Check of motor control
Check whether after a closing operation the motor is activated by a limit
switch, and, whether after the charging process of the closing spring the
motor is deactivated via a limit switch.

Page 20 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.10 Check SFs gas humidity


Before putting the breaker into operation, the humidity of the SF6-gas must
be checked. For this a commercially available dew point measuring
instrument with °C scale can be used. The maximum permissible dew point
temperatures at operating pressure corresponding to the permissible
humidity are stated below.

If the measured dew point temperature is over-10 °C/ +14 'F, the gas must
be desiccated by means of a SF6 service unit

Page 21 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products
High Voltage Disconnector
Maintenance

1.11 Recommended Procedure in the Event of Irregularities on the


Circuit-Breaker 3AP1 FG

Page 22 SHVC of PTD H 3 Products – 2014 Energy / Transmission / High Voltage Products