3-18 Current error / PFC overload error (Error Code : E462, E484)
1. Check items
1) Check the power and restarting after power reset Error CODE Error description Related model
E462 Outdoor unit total current error AM666FXMDCH series
2) Check the outdoor unit installation and environments E484 Outdoor unit PFC overload error AM666FXMDCH series
o Check if the outdoor unit inverter PBA related wires
are disconnected. Check the installation environment
3) Check for indoor unit installation environment
4) Check for open service valve

2. Check procedure

Turn off the power and turn it


on again after 30 seconds

Check the outdoor unit installation and


environment o Check for normal operation o
End service
No 1. Check for wire disconnection related to outdoor
Is the outdoor unit installed correctly? unit inverter PBA
2. Remove the obstacles on outdoor unit air inlet
and secure enough space
3. Remove the obstacles on outdoor unit air outlet
and secure enough space

Yes

[AM666FXMDCH series]

Check the indoor unit installation and


environment o Check for normal operation o
End service
No
Is the indoor unit installed correctly?? 1. Remove obstacles on air inlet and secure
enough space
2. Remove obstacles on air outlet and secure
enough space
Yes

No
Is the service valve completely open? Open the valve

Yes

No
Is the compressor operating normally? Change the compressor

Yes

Change the outdoor unit inverter PBA and check for normal
operation o End service