Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

1

Energy Loss Minimization of Electricity


Networks with Large Wind Generation using
FACTS
X. P. Zhang, Senior Member, IEEE

voltage operating control range. In this situation, new


Abstract - The UK Government is working towards a target of computational tool is required to evaluate the reactive power
providing 10 % of UK electricity from renewable sources by flow and voltage security and their impact on the transmission
2010 with the aspiration that this will rise to 20% by 2020. grid, to which the wind farm is connected.
However, the connection of any wind farm to the grid must This paper reviews the current practice of the grid code for
comply with the Grid Code connection requirements. One of large wind farm connections in the UK. Then analysis of the
the requirements is that the wind farm must have the impact of the grid code arrangements on the reactive power
capabilities to operate within certain reactive power and and voltage security control is presented, and hence the
voltage operating control range. This paper discusses the issue consequence to energy losses of electricity transmission
of energy loss minimization of electricity networks with large networks with large scale integration of on-shore and off-
renewable wind generation. The impact of the special shore wind farms is evaluated. This paper proposes an optimal
operating arrangements of large wind generation on energy power flow (OPF) approach to minimize the electricity
loss of electricity networks is investigated. An optimal power transmission network losses with large wind farms and
flow (OPF) approach is proposed to minimize the energy loss investigate how to use FACTS devices to minimize network
of electricity network with reactive power and FACTS losses while satisfying the grid code connection requirement
control, while satisfying the network operating voltage and for reactive power control and the network operating voltage
thermal limits. and thermal limits. The case studies are carried out on a 30-
bus test network, and results are provided to show the
Index Terms--Reactive power compensation, Voltage control, effectiveness of the OPF approach for electricity network
Optimal power flow, Large on-shore wind farms, Large off-shore planning, design, operation and connection with FACTS
wind farms, Distributed generation, Renewable generation, Grid technologies while satisfying the connection requirements for
Code. reactive power control and the voltage & current operating
limits.
I. INTRODUCTION

T HE UK Government is working towards an ambitious


target of providing 10 % of UK electricity from
renewable sources by 2010, and 15% of UK electricity
II. REVIEW OF REACTIVE POWER CONTROL REQUIREMENT
FOR WIND FARM CONNECTION
Basically, the Grid Code provides specifications of
from renewable energy by 2015 with the aspiration that this procedures for both planning and operational purposes and
will rise to 20% by 2020. A large part of this electricity will covers both normal and exceptional circumstances. For a wind
come from offshore wind farms. There are plans for around 6- farm to be connected to the transmission/distribution network,
7GW of electricity representing nearly 10 per cent of current it must comply with the Grid Code, including the
generating capacity to be developed in the sea around the UK requirements of reactive power range, voltage range and
where most of such a development is focused on offshore control, fault ride through capability, frequency range and
wind farms. It is anticipated that in the future, other frequency control, etc. Among those mentioned above, the
technologies such as wave and tidal power generation may voltage and reactive power control requirements are of great
also be developed. importance.
The connection of any wind farm to the grid must comply
with the UK Grid Code connection requirements. Large scale A. Reactive Power Ranges
on-shore and off-shore wind farms are connected directly with
the British transmission system. For the connection, one of Current Grid Code requirements state that any Medium or
the requirements is that the wind farm must have the Large Wind Farms must provide a reactive power capability
capabilities to operate within certain reactive power and of 0.95 lead / lag at its Grid Entry Point [1]. According to the
current grid code in the UK, wind farms must control the
X. P. Zhang is with the Department of Electronic, Electrical and Computer reactive power at the connection point. For instance, for a
Engineering, University of Birmingham, Edgbaston, Birmingham B15 2TT, UK large on-shore connected with the transmission network, the
(e-mail: x.p.zhang@bham.ac.uk).

©2008 IEEE.
2

grid may require that over the normal active power operating III. REPRESENTATION OF LARGE WIND FARMS IN ENERGY LOSS
range of the on-shore wind farm, a reactive power capability ANALYSIS OF ELECTRICITY TRANSMISSION NETWORK
of 0.95 power factor lagging to 0.95 power factor leading In the light of the grid code requirement for large wind
(based on full output power) should be available at the farms connected with the electricity transmission network,
connection point. Such a requirement is also extended to the there are three particular situations to be studied for energy
requirement with the connection of off-shore wind farms [1]. loss analysis of the electricity transmission network where the
According to the Grid Code, each Offshore Power Park wind farm at the Grid Entry point is represented by a virtual
Module should be required to be capable of maintaining [1]: power plant who can provide a reactive power capability of
1) unity power factor for LV connections 0.95 lead / lag while the voltage at the Grid Entry point should
2) a power factor equivalent to unity at the LV for HV be within the operating limits. In order to simply the analysis,
connections at the Offshore Grid Entry Point. A tolerance such a virtual power plant model of the wind farm is
of ± 5% of Rated MW in MVAr would be allowed either discussed in three different situations.
side of the specified power factor. The Offshore
Generator will have the option to provide a greater A. Unity Power Factor Control at the Grid Entry Point
reactive capability than the minimum specified under the For this control scheme, the power factor at the Grid Entry
Grid Code. point is controlled to zero. In other words, in this control
B. Voltage Ranges and Control scheme, the reactive power exchange between the wind farm
and transmission network at the Grid Entry point is zero while
Wind farms must remain connected to the transmission the voltage at the connection point is within the permissible
system when the voltage at the connection point is within the limits.
normal and exceptional voltage ranges, for example +/- 5% of
nominal value for normal condition and +/-10% for abnormal B. Lagging Power Factor Control at the Grid Entry Point
condition. While the reactive power output from the wind For this control scheme, the power injection at the Grid
farm should be fully available within the voltage operating Entry point has a lagging power factor. In addition to this
ranges. requirement, the voltage at the Grid Entry point is constrained
C. Reactive Power Control for Wind Farm Connection to the permissible limits.
It is known that most wind farms have installed either the C. Leading Power Factor Control at the Grid Entry Point
fixed speed induction generator (FSIG) or the Doubly Fed For this control scheme, the power injection at the
induction generator (DFIG), and normally they are operated at connection point has a leading power factor. In addition to
the unity power factor. Normally their ability of the voltage this requirement, the voltage at the Grid Entry point is within
and reactive power controls at the connection points may be the permissible limits.
very limited, and installation of additional VARs devices is
required to fulfill the Grid Code requirement for wind farms. IV. ENERGY LOSS MINIMIZATION OF ELECTRICITY
VARs devices such as mechanically switched TRANSMISSION NETWORK WITHOUT/WITH LARGE WIND
capacitors/reactors, SVCs and STATCOM. The VARs FARMS
devices can be either installed at an individual wind turbine
level or at a substation level, depending on economic, A. Energy Loss Minimization of Electricity Transmission
technical and environmental constraints. Network without Large Wind Farms
It has been recognized that in order to meet the connection The objective of an optimal reactive power and voltage
requirements in terms of the control of both reactive control for the minimization of energy losses of the electricity
power/power factor and voltage operation ranges at the transmission network with conventional power plants is to
connection point, there is a requirement of optimal planning minimize the total active power losses through the
and allocation of the reactive power compensation for reactive optimisation of generator active powers, generator reactive
power and voltage control within the wind farm network (and powers, transformer tap ratios while subjecting to various
the off-shore transmission network for the case of off-shore power flow constraints, operating constraints. The optimal
wind farm.). It is assumed in this paper that the reactive reactive power and voltage control for energy loss
power control resources are available to control the reactive minimization may be given by
power in such a way that the power factor at the connection
point or Grid Entry point with the transmission network can Objective: Min ( Ploss ) (1)
be satisfied.
Subject to:
Power flow constraints:
For a power network, the reactive power and voltage controls
Pg i − Pd i − Pi (V ,θ , T ) = DPi ( x) = 0 (2)
can be achieved through the control of the following variables
• Power transformer tap changer Qg i − Qd i − Qi (V , θ , T ) = DQi ( x) = 0 (3)
• Wind turbine generator power factor i = 1,2,…, N
• Reactive power compensation devices such as SVC and Operating and control constraints:
STATCOM. h min
j ≤ h j ( x) ≤ h max
j j = 1, 2,…,Nh (4)
3

where Operating and control constraints:


x = [V , θ , T , Qg ]T h min
j ≤ h j ( x) ≤ h max
j j = 1, 2,…,Nh (10)
Pg bus active generation where
Qg bus reactive generation x = [V , θ , V FACTS , θ FACTS , T , Qg , Qr , Qc]T
Pd bus active load
Qd bus reactive load Pg bus active generation
V bus voltage magnitude vector Qg bus reactive generation
Pwindi active and reactive power injectionfrom the Wind
θ bus angle vector
Farm connected at the Grid Entry point of bus i.
T tap ratio vector of transformers
Qwindi reactive power injection from the Wind Farm
DPi, bus active power mismatch
connected at the Grid Entry point of bus i
DQi bus reactive power mismatch
Pd bus active load
h(x) include reactive powers of generators, transmission
Qd bus reactive load
line power flows, tap ratios of transformers V bus voltage magnitude vector
h min and h max are lower bound vector and upper bound vector, θ bus angle vector
respectively, for inequality constraints including T tap ratio vector of transformers
reactive generation limits, transmission line thermal DPi, bus active power mismatch
limits, transformer tap ratio limits and bus voltage DQi bus reactive power mismatch
limits, etc. h(x) active and reactive powers of generators,
Ng the total number of generators transmission line power flows, tap ratios
N the total number of buses oftransformers
Nh the total number of double-side inequality constraints min max
h ,h lower bound vector and upper bound vector,
B. Energy Loss Minimization of Electricity Transmission respectively, for inequality constraints including
Network with Large Wind Farms active and reactive generation limits, transmission
With the incorporation of wind farms in the energy loss line thermal limits, transformer tap ratio limits and
minimization of electricity transmission network, the power bus voltage limits, etc.
flow equations in (2) and (3) should be augmented to reflect Ng the total number of generators
the power injections from wind farms: N the total number of buses
Pg i + Pwind i − Pd i − Pi (V , θ , T ) = DPi ( x) = 0 (5) Nh the total number of double-side inequality
constraints
Qg i + Qwind i − Qd i − Qi (V , θ , T ) = DQi ( x ) = 0 (6)
where Pwindi and Qwindi are active and reactive power V. SOLUTION OF ENERGY LOSS MINIMIZATION OF
injections from the Wind Farm connected at the Grid Entry ELECTRICITY TRANSMISSION NETWORK
point of bus i, respectively.
C. Energy Loss Minimization of Electricity Transmission A. Nonlinear Interior Point Methods
Network with Large Wind Farms using FACTS Controls According to the nonlinear interior point methods proposed
The objective of an optimal reactive power compensation in [2], the above problems in Section IV can be solved by the
and voltage control problem may be the minimization of the following sets of linearised Newton equations
total active power losses plus reactive power compensation ⎡− Π l −1 Sl 0 − ∇h 0 ⎤ ⎡ ∆πl ⎤
⎢ ⎥⎢ ⎥
costs through the optimization of generator reactive power
⎢ 0 Π u −1
Su − ∇ h 0 ⎥ ⎢∆πu ⎥
outputs, FACTS devices, transformer tap ratios while ⎢ − ∇h T − ∇h T H − J T ⎥ ⎢ ∆x ⎥
subjecting to various power flow constraints, operating ⎢ ⎥⎢ ⎥

⎣ 0 0 −J 0 ⎥⎦ ⎣ ∆λ ⎦ (11)
constraints. Such an optimal problem may be given by
Objective: Min ( Ploss ) (7) ⎡ − ∇ L − Π l −1∇ L ⎤
πl µ Sl µ
⎢ −1 ⎥
Subject to: ⎢ − ∇ L
πu µ − Π u ∇ Su L µ ⎥
= ⎢ ⎥
Power flow constraints: − ∇ x Lµ
⎢ ⎥
Pg i + Pwind i − Pd i ⎢ − ∇ λ Lµ ⎥
(8) ⎣ ⎦
− Pi (V , θ , V FACTS , θ FACTS , T ) = DPi ( x) = 0
∆sl = Πl −1 (∇ sl Lµ − Sl∆πl ) (12)
−1
Qg i + Qwind i − Qd i ∆su = Πu (−∇ su Lµ − Su∆πu ) (13)
+ Qci (V , θ , VFACTS , θ FACTS ) where sl and su are slack variables for inequalities. πl and πu
(9) are dual variables for inequalities. λ are dual variables for
− Qri (V , θ , V FACTS , θ FACTS )
equalities.
− Qi (V , θ , V FACTS , θ FACTS , T ) = DQi ( x) = 0

i = 1,2,…, N
4

H ( x, λ , πl , πu ) = ∇ 2 f ( x) − λ∇ 2 g ( x) − (πl + πu )∇ 2 h( x) , Based on the IEEE 30-bus system, energy loss analysis will
be carried out over there different scenarios: (a) energy losses
⎡ ∂∆P ( x ) ∂∆Q ( x) ⎤ ⎡ ∆P ( x ) ⎤ ⎡λ p ⎤
⎥ , g ( x ) = ⎢ ∆Q ( x ) ⎥ , λ = ⎢ λ ⎥ ,
J ( x) = ⎢ , of the electricity transmission network without optimal
⎣ ∂x ∂x ⎦ ⎣ ⎦ ⎣ q⎦ reactive control; (b) energy losses of the electricity
Sl = diag ( sl j ) , Su = diag ( su j ) , Π l = diag (πl j ) , transmission network with optimal reactive power control; (c)
the electricity transmission network with optimal reactive
Π u = diag (πu j ) power control and FACTS control. In the following, energy
loss analysis on these three scenarios will be presented.
B. General Procedure of the Solution
Step 0: Select possible locations for FACTS B. Energy Losses of the Electricity Transmission Network
Step 1: Get system data for transmission lines, with Optimal Reactive Power Control
transformers, generators, Wind Farms
In this scenario, there are four cases to be investigated:
Step 2: Solve the problems in Section IV by the nonlinear
interior point method in (11) - (13). Case 1: This is a base case of the electricity network with
Step 3: Output conventional power plants where all the power
(a) Optimal transformer tap settings plants can maintain the terminal voltages to their
(b) Minimized power losses settings of 1.0 p.u.
(c) Optimal VAR location and requirement Case 2: This is a case of the electricity network with
(d) Voltage profile of the system conventional power plants where all the power
(e) Power flow distribution of the system plants can maintain the terminal voltages to their
voltage limits using reactive power and transformer
VI. NUMERICAL EXAMPLES controls.
Case 3: This is similar to case 2 except that the generator at
A. Test Systems bus 2 is replaced by an offshore wind farm where
the power factor at the Grid Entry point is 0.95
leading.
18
1 2 15 Case 4: This is similar to case 2 except that a unity power
factor is maintained at the Grid Entry point.
14 19 Case 5: This is similar to case 2 except that the power
factor at the Grid Entry point is 0.95 lagging.
28 3 4
For Cases 2-5, power losses are minimized through reactive
12 13
8 6 7 5 power control by generators and tap ratio settings of
11 transformers. For Cases 3-5, the total power generation from
9 16 17 the wind farm connected at bus 2 represents around 20% of
the total generation.
10 20
TABLE I
23 ENERGY LOSS RESULTS OF CASES 1-5 WITHOUT/WITH OPTIMAL REACTIVE
26 POWER CONTROL
25 22 21 24 Cases Case 1 Case 2 Case 3 Case 4 Case 5
(Base
Case)
Power Losses 14.35 12.38 12.38 12.48 12.65
29 30 (MW)
27
Power Loss - 13.73% 13.73% 13.03% 11.85%
Reduction with
Fig. 1. Single-line circuit diagram of the IEEE 30-bus system. respect to Base Case
without Optimal
Control
Test cases in this paper are carried out on the IEEE 30-bus
system. The IEEE 30-bus system as shown in Fig. 1 has 6
The energy loss results of Cases 1-5 are presented in Table
generators, 4 OLTC transformers and 37 transmission lines.
I. From Table I, it can be seen that with the coordinated
For all cases in this paper, the convergence tolerances are
optimal control of reactive powers of generators and tap ratios
5.0e-4 for complementary gap and 1.0e-4 (0.01MW/Mvar) for
of transformers, power losses can be reduced significantly by
maximal absolute bus power mismatch, respectively. It is
over 10% with respect to that of base case without optimal
assumed that the total active power generation of the
control. Furthermore, in comparison of Cases 3-5 to Case 2,
generator at bus 2 is 600 MW, the total active power
with the connection of the large scale wind farm into
generation at buses 8, 11 and 13 is equal to 100 MW while the
electricity network, it is likely that power losses will be
rest of the demand is balanced by the generator at bus 1.
increased due to the Grid Code requirement.
5

C. Energy Losses of the Electricity Transmission Network power plant with integrated advanced communication and
with Coordinated Control of Reactive Power Generation, control technologies.
Transformers and FACTS
Based on Cases 2-5, it has been found that there are the VII. CONCLUSIONS
largest sensitivities at buses 23, 24, 26, 30. Cases 6-9 are This paper has reviewed the current practice of the grid code
carried out with FACTS control, which are corresponding to for large wind farm connection in the UK. Then analysis of
Cases 2-5, respectively where FACTS devices - STATCOMs the impact of the grid code arrangements on the reactive
or SVCs are placed at buses 23, 24, 26, 30. The results are power and voltage security control has been presented. This
presented in Table II. paper has proposed an optimal power flow (OPF) approach to
minimize the electricity transmission network losses with
TABLE II
ENERGY LOSS RESULTS OF CASES 6-9 WITH OPTIMAL REACTIVE POWER AND large wind farms and investigate how to use FACTS devices
FACTS CONTROL to minimize network losses while satisfying the grid code
connection requirement for reactive power control and the
Case 6 Case 7 Case 8 Case 9 network operating voltage and thermal limits. The
FACTS Buses 23, Buses 23, Buses 23, Buses 23, consequence to energy losses of electricity transmission
locations 24, 26, 30 24, 26, 30 24, 26, 30 24, 26, 30
networks with large scale integration of large wind farms has
Power 12.13 12.13 12.22 12.39
Losses
been evaluated. The case studies have been carried out on a
(MW) 30-bus test network, and results have been provided to show
Power 2.0% 2.0% 2.1% 2.1% the effectiveness of the OPF approach for electricity network
Loss operation with FACTS technologies while satisfying the
Reduction connection requirements for reactive power control and the
with respect voltage & current operating limits. With the connection of
to that
without
large scale wind farms into electricity network in the
FACTS replacement of conventional power plants, it is likely that
power losses will be increased due to the Grid Code
From Table II, it can be seen clearly that the reactive requirement. However, with the advance in communication
compensation by shunt FACTS devices is useful in the power and control technologies, it is possible to operate a large wind
loss minimization. Comparing the results of Table II with that farm like a conventional power plant.
of Table I, it is obvious that the reactive power control of
VIII. REFERENCES
generators plays a very important role in power loss
[1] OFGEM Grid Code Subgroup, "Recommendations for the application of
minimization where such a control is very effective. However,
Grid Code technical requirements to offshore electricity transmission
the reactive power control for power loss minimization with networks," OFGEM, London, UK. 7th Nov. 2007.
generators in deregulated environments becomes difficult. It [2] X.-P. Zhang, E. Handschin, and M. M. Yao, “Modeling of the generalized
is now at a stage for power engineers to re-think the role of unified power flow controller (GUPFC) in a nonlinear interior point OPF,”
IEEE Trans. on Power Systems, vol. 16, no. 3, pp.367-373, Aug. 2001
reactive power control by generators in power loss
minimization as CO2 reduction becomes a worldwide IX. BIOGRAPHIES
concern. In light of this, the reactive control for power loss
minimization should be reflected in electricity market design Xiao-Ping Zhang (M’95, SM’06) received the BEng., MSc. and PhD degrees in
and hence market efficiency. electrical engineering from Southeast University in 1988, 1990, 1993,
In comparison of Cases 6-9, with the connection of the respectively. He worked at NARI, Ministry of Electric Power, China on
EMS/DMS advanced application software research and development between
large scale wind farm into electricity network, it is likely that 1993 and 1998. He was visiting UMIST from 1998 to 1999. He was an
power losses will be increased due to the Grid Code Alexander-von-Humboldt Research Fellow with the University of Dortmund,
requirement. Due to the fact that large offshore wind farms Germany from 1999 to 2000. He was a lecturer, senior lecturer and then an
associate professor at the University of Warwick, UK till early 2007. Currently
are equipped with advanced FACTS devices for reactive
he is a Reader at the University of Birmingham, England, UK. He is also
control and wind turbines have also reactive control Director of the Institute for Energy Research and Policy. He is a coauthor of the
capability, it is possible that in the future a large offshore monograph "Flexible AC Transmission Systems: Modelling and Control"
wind farm can be operated very much like a conventional published in 2006. He is a senior member of the IEEE and a member of CIGRE.

You might also like