White Rust Inhibitor

DR 900 Analytical Procedure AP-146/900

SPECIFICATIONS
Method: Colorimetric (DR 900)
Range: 0.1 to 52.0 ppm
Testing Time: 10 minutes

DESCRIPTION
White Rust Inhibitor is used in many applications
as a corrosion inhibitor for galvanized steel.
Concentration can be determined using this
catalytic UV (ultraviolet) photolysis procedure.

ORDERING INFORMATION
Order all replacement parts and reagents by their
part numbers. To be sure this product is compatible
with your treatment program, contact your local
Nalco representative. Items marked with an “*”
are included with the kit or set. To place your Nalco DR 900 Colorimeter
order, please contact your local customer service
department.
Optional Parts and Reagents
REPLACEMENT PARTS AND REAGENTS Description Size Part No.
Rochelle salt 29 mL
Required Parts and Reagents
Solution DB 460-S0469.70
Description Part No. Sulfuric acid
White Rust 25 mL Reagent Set, Solution, 1.0N 1.7 oz/50 mL 460-S0243.71
100 tests 460-P4334.88 Sulfuric acid
Solution, 1.0N 34.8 oz/1 L 460-S0243.75
Sulfuric acid
Description Part No. Solution, 1.0N 1.06 gal/4 L 460-S0243.77
Nalco DR 900 Colorimeter 400-P0900.88
Sample cells, 10-20-25 mL 500-P2555.88
w/cap, 6/pkg Description Part No.
Cylinder, graduated, glass, 25 mL 500-P1204.88 pH test strips (3 color), 0-14 pH
or (100/box) 500-P3204.88
Cylinder, graduated, plastic, 25 mL 500-P1216.88 pH test strips (3 color), 5-10 pH
(100/box) 500-P3207.88
Depending on line voltage, select one of the Thermometer, -40 to 450°F, digital 500-P2098.88
following: Thermometer, 50 to 550°F, dial 500-P2019.88
UV Lamp (with power supply) Thermometer, 0 to 230°F, glass 500-P2028.88
115 VAC, 60 Hz, with goggles 500-P2553.88 Powder Pillow Snippers 500-P1605.88
UV Lamp (with power supply)
230 VAC, 50 Hz, with goggles 500-P2554.88
SAFETY PRECAUTIONS INTERFERENCES
Refer to Material Safety Data Sheet (MSDS) for The following may interfere when present in
specific reagent personal safety and disposal concentrations exceeding those listed below.
information.
1 mg/L = 1 ppm
SUPPORT Acrylates (as methyl acrylate) 50 mg/L
If you have any questions regarding this procedure, Alum 400 mg/L
please contact your Nalco representative. In North Borate (as sodium tetraborate) 4000 mg/L
America you can also contact the Equipment Help
Desk at 630-305-CHEM. Chlorine (as Cl2) 20 mg/L
Chromium (as chromate) 12 mg/L
Copper 10 mg/L
Hardness (as CaCO3) 500 mg/L
Iron 20 mg/L
Lignosulfonates 40 mg/L
Magnesium (as CaCO3) 300 mg/L
Molybdenum (as molybdate) 200 mg/L
Nitrite 4000 mg/L
Phosphonates (AMP or HEDP) 100 mg/L
Sulfate 200 mg/L
Zinc 80 mg/L

Strong oxidizing or reducing agents present in the


sample will interfere directly with the test.
WHITE RUST INHIBITOR DR 900 PROCEDURE
Special Note: Always wear the goggles (provided with the UV lamp power source) when using UV light.

Start

1 2 3 4
Start Program Fill a sample cell with 25 mL Add the contents of one Insert the ultraviolet lamp
of sample. White Rust Reagent Powder into the sample cell.
779 WR73801 Pillow. Swirl to dissolve
Notes: Sample temperature completely. Note: UV safety goggles
should be between 20 and must be worn while the
25°C (68 and 78°F). Note: If the sample lamp is on.
contains more than
If sample contains nitrite
500 ppm hardness
or borax (sodium borate),
(as CaCO3), add 10 drops
adjust the pH to between
of Rochelle Salt Solution.
4 to 6 with 1 N sulfuric acid.

5 6 7 8
Turn the UV lamp ON and When the timer beeps, Fill another sample cell with Place the blank into the
start TIMER 1 turn the lamp off. Remove 25 mL of sample (the blank). cell holder. Tightly cover
the lamp from the cell (the the sample cell with the
A five-minute reaction period prepared sample). Swirl the instrument cap.
will begin. cell to mix thoroughly.

Notes: A yellow color will


form if triazole is present. Notes: Low results will
occur if photolysis (lamp
ON) takes place for more or
less than five minutes.
Avoid fingerprints on the
quartz surface of the lamp.
Rinse the lamp and wipe
with a soft, clean tissue
between tests.
Zero Read

9 10 11
Press: ZERO Place the prepared sample Press: READ
into the cell holder. Tightly
The curser will move to the cover the sample cell with The curser will move to the
right, then the display will the instrument cap. right then the result in mg/L
show: WR will be displayed.
0 mg/L WR

Nalco, an Ecolab Company


North America: Headquarters – 1601 West Diehl Road • Naperville, Illinois 60563 • USA
Nalco Champion – 7705 Highway 90-A • Sugar Land, Texas 77487 • USA
Europe: Richtistrasse 7 • 8304 Wallisellen • Switzerland
Asia Pacific: 2 International Business Park • #02-20 The Strategy Tower 2 • Singapore 609930
Latin America: Av. das Nações Unidas 17.891 • 6° Andar 04795-100 • São Paulo • SP • Brazil
www.nalco.com

Ecolab, NALCO and the logos are trademarks of Ecolab USA Inc.
©2013 Ecolab USA Inc. All Rights Reserved 8/13

You might also like