Work Sheet For Design of Concrete Mix: Item No.: 400 (23) - Bored Pile
Work Sheet For Design of Concrete Mix: Item No.: 400 (23) - Bored Pile
Work Sheet For Design of Concrete Mix: Item No.: 400 (23) - Bored Pile
NAME OF PROJECT:
PREPARED BY:
ITEM NO.: 400 ( 23 )- BORED PILE
DATA FROM PRELIMINARY TEST: SAND GRAVEL
1. RODDED UNIT WEIGHT 1522 Kg/m³ 1618 kg/m³
2. FINENESS MODULUS 2.82
3. BULK SPECIFIC GRAVITY 2.66 2.70
4. ABSORPTION 2.04 1.07
5. MAXIMUM SIZE 3/8" 20mm
6. KIND Natural Crushed
DESIGN SPECIFICATION REQUIREMENTS:
CLASS OF CONCRETE "A" CEMENT FACTOR 12 Bags/cu.m.
COMPRESSIVE STRENGTH 4000 psi SLUMP 3" -4"
PROPORTION OF MIX:
UNCORRECTED COR
ABS. VOL. SP. GR. UNIT WT. OF WATER WEIGHT (Kg.)
14. CEMENT 0.0127 3.15 1000 40.00
15. FINE AGG. 0.0261 2.66 1000 69.43
16. COARSE AGG. 0.028 2.70 1000 75.60
17. WATER 0.0166 1 1000 16.60
REMARKS/RECOMMENDATION: Actual mix is subject to adjustment based on the actual field condition.
GRAVEL
1618 kg/m³
2.70
1.07
20mm
Crushed
12 Bags/cu.m.
3" -4"
0.1053 m³
0.0127 m³
0.0166 m³
0.0293 m³
0.0541 m³
0.0261 m³
0.0280 m³
UNCORRECTED CORRECTED
WEIGHT (Kg.) WEIGHT
40.00
69.43
75.60
16.60
eld condition.
submitted by:
WORK SHEET FOR DESIGN OF CONCRETE MIX
NAME OF PROJECT:
PREPARED BY:
ITEM NO.: 405- Structural Concrete (MOD, 20.70 Mpa)
DATA FROM PRELIMINARY TEST: SAND GRAVEL
1. RODDED UNIT WEIGHT 1522 Kg/m³ 1618 kg/m³
2. FINENESS MODULUS 2.82
3. BULK SPECIFIC GRAVITY 2.66 2.70
4. ABSORPTION 2.04 1.07
5. MAXIMUM SIZE 3/8" 20mm
6. KIND Natural Crushed
DESIGN SPECIFICATION REQUIREMENTS:
CLASS OF CONCRETE "A" CEMENT FACTOR 10 Bags/cu.m.
COMPRESSIVE STRENGTH 3000 psi SLUMP 3" -4"
PROPORTION OF MIX:
UNCORRECTED COR
ABS. VOL. SP. GR. UNIT WT. OF WATER WEIGHT (Kg.)
14. CEMENT 0.0127 3.15 1000 40.00
15. FINE AGG. 0.0336 2.66 1000 89.38
16. COARSE AGG. 0.0338 2.70 1000 91.26
17. WATER 0.0199 1 1000 19.90
REMARKS/RECOMMENDATION: Actual mix is subject to adjustment based on the actual field condition.
GRAVEL
1618 kg/m³
2.70
1.07
20mm
Crushed
10 Bags/cu.m.
3" -4"
0.1000 m³
0.0127 m³
0.0199 m³
0.0326 m³
0.0674 m³
0.03363 m³
0.03377 m³
UNCORRECTED CORRECTED
WEIGHT (Kg.) WEIGHT
40.00
89.38
91.26
19.90
eld condition.
submitted by:
WORK SHEET FOR DESIGN OF CONCRETE MIX
NAME OF PROJECT:
PREPARED BY:
ITEM NO.: 405- Reinforced Concrete Box Culvert, Class "A"
DATA FROM PRELIMINARY TEST: SAND GRAVEL
1. RODDED UNIT WEIGHT 1,513 Kg/cu.m. 1604 kg/cu.m.
2. FINENESS MODULUS 2.82
3. BULK SPECIFIC GRAVITY 2.60 2.64
4. ABSORPTION 1.83 1.54
5. MAXIMUM SIZE 3/8" 50mm
6. KIND Natural Rounded
DESIGN SPECIFICATION REQUIREMENTS:
CLASS OF CONCRETE "A" CEMENT FACTOR 10 Bags/cu.m.
COMPRESSIVE STRENGTH 3000 psi SLUMP 2" -4"
PROPORTION OF MIX:
UNCORRECTED COR
ABS. VOL. SP. GR. UNIT WT. OF WATER WEIGHT (Kg.)
14. CEMENT 0.0129 3.09 1000 39.86
15. FINE AGG. 0.0215 2.60 1000 55.90
16. COARSE AGG. 0.0499 2.64 1000 131.74
17. WATER 0.0157 1 1000 15.70
REMARKS/RECOMMENDATION: Actual mix is subject to adjustment based on the actual field condition.
GRAVEL
1604 kg/cu.m.
2.64
1.54
50mm
Rounded
10 Bags/cu.m.
2" -4"
0.1000 cu.m
0.0129 cu.m
0.0157 cu.m
0.0286 cu.m
0.0714 cu.m
0.0215 cu.m
0.0499 cu.m
UNCORRECTED CORRECTED
WEIGHT (Kg.) WEIGHT
39.86
55.90
131.74
15.70
eld condition.
submitted by:
TRIMLUV BUILDERS & SUPPLY AND LEGACY
CONSTRUCTION JOINT VENTURE
WORK SHEET FOR DESIGN OF CONCRETE MIX
NAME OF PROJECT: Improvement/ Widening of Bacolod North Road Including RROW (S0040BNR)K0092+450-K0095+(-18.50)
Escalante City, Negros Occidental (17RO0006)
PREPARED BY: Esmael L. Chua III-Materials Engineer-Trimluv Builders and Supply/Legacy Construction(Joint Venture)
ITEM NO.: 311 Portland Cement Concrete Pavement
DATA FROM PRELIMINARY TEST: SAND GRAVEL
1. RODDED UNIT WEIGHT 1530 Kg/cu.m. 1435kg/cu.m.
2. FINENESS MODULUS 2.66
3. BULK SPECIFIC GRAVITY 2.62 2.6
4. ABSORPTION 3.94 1.14
5. MAXIMUM SIZE 75 mm
6. KIND Natural Angular
DESIGN SPECIFICATION REQUIREMENTS:
CLASS OF CONCRETE "A" CEMENT FACTOR 9.5 Bags/cu.m.
FLEXURAL STRENGTH 550 psi SLUMP 3"-4"
PROPORTION OF MIX:
UNCORRECTED CORRECTED
ABS. VOL. SP. GR. UNIT WT. OF WATER WEIGHT (Kg.) WEIGHT
14. CEMENT 0.01280 3.12 1000 40.00
15. FINE AGG. 0.0223 2.62 1000 58.43
16. COARSE AGG. 0.05350 2.600 1000 139.10
17. WATER 0.01670 1.00 1000 16.70
REMARKS/RECOMMENDATION: Actual mix is subject to adjustment based on the actual field condition.
PROPORTION OF MIX:
UNCORRECTED CORRECTED
ABS. VOL. SP. GR. UNIT WT. OF WATER WEIGHT (Kg.) WEIGHT
14. CEMENT 0.0127 3.15 1000 40
15. FINE AGG. 0.0240 2.56 1000 61.40
16. COARSE AGG. 0.0313 2.67 1000 83.60
17. WATER 0.0153 1 1000 15.30
REMARKS/RECOMMENDATION: Actual mix is subject to adjustment based on the actual field condition.
PROPORTION OF MIX:
UNCORRECTED CORRECTED
ABS. VOL. SP. GR. UNIT WT. OF WATER WEIGHT (Kg.) WEIGHT
14. CEMENT 0.0127 3.15 1000 40
15. FINE AGG. 0.0282 2.56 1000 72.19
16. COARSE AGG. 0.0368 2.67 1000 98.26
17. WATER 0.0175 1 1000 17.50
REMARKS/RECOMMENDATION: Actual mix is subject to adjustment based on the actual field condition.