Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

JHABUA

INPUT AND OUTPUT LIST FOR PLC SYSTEM -


BUCKET WHEEL TYPE STACKER CUM RECLAIMER FLSmidth House,
34, Egatoor,Kelambakkam,
Chennai – 603 103.

FICHTNER CONSULTING ENGINEERS (INDIA) (1 x 600 + 1 x 660) MW JPL SEONI PROJECT


PRIVATE LIMITED.
MADHYA PRADESH
Rev. : 4 Customer Doc.No.: APIL-JPL-PCN-143-G-2514 Date: 22 / Aug / 2014

ITEM : INPUT AND OUTPUT LIST FOR PLC SYSTEM - BUCKET WHEEL TYPE STACKER CUM RECLAIMER
(1 x 600 + 1 x 660) MW JPL SEONI PROJECT
PROJECT:
MADHYA PRADESH
OWNER : JHABUA POWER LIMITED.
OWNER'S CONSULTANT: FICHTNER CONSULTING ENGINEERS (INDIA) PRIVATE LIMITED.

 FLS Doc. No.: 80024774  Ver.: 5.0

Reference Documents:
1. Typical power and control schematics for BWSR (APIL-JPL-PEE-143-G-2506).
2. Field Instrument list for BWSR (APIL-JPL-PEN-143-G-2515).

Rev. 5 Reason for Issue Prepared By Checked By Approved By.


0 25-Oct-11 Preliminary Submission MASL KRP VSE
1 07-Jun-12 Revised As per customer comments KDU KRP VSE
2 27-Aug-12 Revised As per customer comments KDU RASB RTH
3 04-Oct-12 Revised As per customer comments KDU RASB RTH
4 22-Aug-14 For Final Approval KDU KDU RTH

PAGE 1 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

PLC PANEL INSIDE THE E-HOUSE

HT VCB PANEL - 10BBY01GS001

1 1 10BBY01GS001-YB01 HT VCB ON Command - 1 - - - - - BWSR-PLC HT VCB - Hardwire

2 1 10BBY01GS001-YB02 HT VCB OFF Command - 1 - - - - - BWSR-PLC HT VCB - Hardwire

3 1 10BBY01GS001-XB01 HT VCB ON Feedback 1 - - - - - - HT VCB BWSR-PLC - Hardwire

4 1 10BBY01GS001-XB02 HT VCB OFF Feedback 1 - - - - - - HT VCB BWSR-PLC - Hardwire

5 1 10BBY01GS001-XB03 HT VCB SWGR Availble 1 - - - - - - HT VCB BWSR-PLC - Hardwire

6 1 10BBY01GS001-XB48 HT VCB SWGR Disturbed 1 - - - - - - HT VCB BWSR-PLC - Hardwire

7 2 10BBY01GS001-XB43 HT VCB 110V AC Control Supply Fail 1 - - - - - - HT VCB BWSR-PLC - Hardwire

8 1 10BBY01GS001-XQ11 HT VCB Y-Phase Current Feedback - - 1 - - 4-20 mA HT VCB BWSR-PLC - Hardwire

9 2 10BBY01GS001-XQ10 HT VCB RY Line voltage Voltage Feedback - - 1 - - 4-20 mA HT VCB BWSR-PLC - Hardwire

10 2 - HT VCB YB Line Voltage Voltage Feedback - - - - - - - HT VCB BWSR-PLC - Soft signal

11 2 - HT VCB BR Line Voltage Voltage Feedback - - - - - - - HT VCB BWSR-PLC - Soft signal

12 2 - HT VCB W, VAR, WH - - - - - - - HT VCB BWSR-PLC - Soft signal

TRANSFORMER - 10BHT01GT001

13 2 10BHT01GT903-XM01 Transformer Winding Temperature Alarm 1 - - - - - - TRAFO BWSR-PLC - Hardwire

14 2 10BHT01GT903-XM02 Transformer Winding Temperature Trip 1 - - - - - - TRAFO BWSR-PLC - Hardwire

15 2 10BHT01GT903-XQ11 Transformer Winding Temperature Monitoring - - 1 - - 4-20 mA TRAFO BWSR-PLC - Hardwire

MCC INCOMER - 10BHD01GS001 (INSIDE E-HOUSE)

16 1 10BHD01GS001-YB01 ACB ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

17 1 10BHD01GS001-YB02 ACB OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

18 1 10BHD01GS001-XB01 ACB ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

19 1 10BHD01GS001-XB02 ACB OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

20 1 10BHD01GS001-XB03 ACB SWGR Availble Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

21 1 10BHD01GS001-XB48 ACB SWGR Disturbed Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

22 1 10BHD01GS001-XB43 ACB 110V AC Control Supply Fail Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

23 1 10BHD01GS001-XQ11 ACB Y-Phase Current Feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire

24 1 10BHD01GS001-XQ10 ACB RY Line Voltage Voltage Feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire

25 5 10BHD01GS001-XB49 86 Relay Operated 1 - - - - - - MCC BWSR-PLC - Hardwire

26 1 - ACB YB Line Voltage Voltage Feedback - - - - - - - MCC BWSR-PLC - Soft signal

PAGE 2 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

27 1 - ACB BR Line Voltage Voltage Feedback - - - - - - - MCC BWSR-PLC - Soft signal

28 1 - ACB W, VAR, WH - - - - - - - MCC BWSR-PLC - Soft signal

EMERGENCY STOP

29 1 10EAF21GS001-XM02 At E-House Platform 1 - - - - - - MCC BWSR-PLC - Hardwire

30 1 10EAF13GS001-XM02 At Tripper Platform 1 - - - - - - MCC BWSR-PLC - Hardwire

31 1 10EAF07GS001-XM02 At Travel Platform 1 - - - - - - MCC BWSR-PLC - Hardwire

32 1 10EAF02GS001-XM02 At Intermediate Conveyor Platform 1 - - - - - - MCC BWSR-PLC - Hardwire

BOOM CONVEYOR MOTOR - 10EAF03AE001

33 1 10EAF03AE001-YB01 Boom Conveyor Motor Forward ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

34 1 10EAF03AE001-YB11 Boom Conveyor Motor Reverse ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

35 1 10EAF03AE001-YB02 Boom Conveyor Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

36 1 10EAF03AU001-YB01 Boom Conveyor Brake Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

37 1 10EAF03AU001-YB02 Boom Conveyor Brake Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

38 1 10EAF03AE001-XB01 Boom Conveyor Motor Forward ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

39 1 10EAF03AE001-XB11 Boom Conveyor Motor Reverse ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

40 1 10EAF03AE001-XB02 Boom Conveyor Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

41 1 10EAF03AE001-XB03 MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

42 1 10EAF03AU001-XB01 Brake Motor Trip Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

43 1 10EAF03FS104-XG01 Pull Cord Switch Activated 1 - - - - - - MCC BWSR-PLC - Hardwire

44 1 10EAF03AE001-XQ11 Boom Conveyor Motor Current Feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire

INTERMEDIATE CONVEYOR MOTOR - 10EAF02AE001

45 1 10EAF02AE001-YB01 Intermediate Conveyor Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

46 1 10EAF02AE001-YB02 Intermediate Conveyor Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

47 1 10EAF02AU001-YB01 Intermediate Conveyor Brake Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

48 1 10EAF02AU001-YB02 Intermediate Conveyor Brake Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

49 1 10EAF02AE001-XB01 Intermediate Conveyor Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

50 1 10EAF02AE001-XB02 Intermediate Conveyor Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

51 1 10EAF02AE001-XB03 Intermediate Conveyor MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

52 1 10EAF02AU001-XB01 Intermediate Conveyor Brake Motor TRIP Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

53 1 10EAF02FS104-XG01 Intermediate Conveyor Pull Chord Switch Activated 1 - - - - - - MCC BWSR-PLC - Hardwire

PAGE 3 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

54 1 10EAF02AE001-XQ11 Intermediate Conveyor Current Feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire

55 1 10EAF02AE001-XB43 Intermediate Conveyor Motor 110V AC Control Supply Fail 1 - - - - - - MCC BWSR-PLC - Hardwire

INTERMEDIATE CONVEYOR FIELD INSTRUMENTS - 10EAF02AE001

56 1 10EAF02FG104-XG01 Intermediate Conveyor Belt Sway Switch Activated 1 - - - - - - FIELD BWSR-PLC - Hardwire

57 1 10EAF02CS101-XG01 Intermediate Conveyor Zero Speed Switch Activated 1 - - - - - - FIELD BWSR-PLC - Hardwire

58 1 10EAF02CG151-XG51 Intermediate Conveyor Brake Released LS Activated 1 - - - - - - FIELD BWSR-PLC - Hardwire


Chute Block Detected Between Boom Conveyor And
59 1 10EAF02CL101-XG01 1 - - - - - - FIELD BWSR-PLC - Hardwire
Intermediate Conveyor
60 1 10EAF02GH001-XB05 Intermediate Conveyor LCS Start Command To PLC 1 - - - - - - FIELD BWSR-PLC - Hardwire

BELT FEEDER MOTOR - 10EAF01AE001

61 1 10EAF01AE001-YB01 Belt Feeder Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

62 1 10EAF01AE001-YB02 Belt Feeder Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

63 1 10EAF01AE001-XB01 Belt Feeder Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

64 1 10EAF01AE001-XB02 Belt Feeder Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

65 1 10EAF01AE001-XB03 MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

66 5 10EAF01FS101-XG01 Belt Feeder Pull chord Switch Activated 1 - - - - - - MCC BWSR-PLC - Hardwire

67 5 10EAF01AE001-XQ11 Belt Feeder Motor Current Feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire

BELT FEEDER FIELD INSTRUMENTS - 10EAF01AE001

68 1 10EAF01FG102-XG01 Belt Feeder Belt Sway Switch Activated 1 - - - - - - FIELD BWSR-PLC - Hardwire

69 1 10EAF01CS101-XG01 Belt Feeder Zero Speed Switch Activated 1 - - - - - - FIELD BWSR-PLC - Hardwire
Chute Block Detected Between Belt Feeder And Intermediate
70 1 10EAF01CL106-XG01 1 - - - - - - FIELD BWSR-PLC - Hardwire
Conveyor
71 1 10EAF01GH001-XB05 Belt Feeder LCS Start Command To PLC 1 - - - - - - FIELD BWSR-PLC - Hardwire

BUCKET WHEEL HYDRAULIC PUMP MOTOR - 10EAF04AE001

72 1 10EAF04AE001-YB01 Bucket Wheel Hydraulic Pump Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

73 1 10EAF04AE001-YB02 Bucket Wheel Hydraulic Pump Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

74 1 10EAF04AE001-XB01 Bucket Wheel Hydraulic Pump Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

75 1 10EAF04AE001-XB02 Bucket Wheel Hydraulic Pump Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire
Bucket Wheel Hydraulic Pump Motor MCC Module Healthy
76 1 10EAF04AE001-XB03 1 - - - - - - MCC BWSR-PLC - Hardwire
Feedback
77 1 10EAF04AE001-XQ11 Bucket Wheel Hydraulic Pump Motor Current feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire
Bucket Wheel Hydraulic Pump Motor 110V AC Control Supply
78 1 10EAF04AE001-XB43 1 - - - - - - MCC BWSR-PLC - Hardwire
Fail
BUCKET WHEEL AND SLEW AIR COOLER - 10EAF04AH001

PAGE 4 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

79 1 10EAF04AH001-YB01 Bucket Wheel and Slew Air Cooler Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

80 1 10EAF04AH001-YB02 Bucket Wheel and Slew Air Cooler Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

81 1 10EAF04AH001-XB01 Bucket Wheel and Slew Air Cooler Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

82 1 10EAF04AH001-XB02 Bucket Wheel and Slew Air Cooler Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

83 1 10EAF04AH001-XB03 Bucket Wheel and Slew Air Cooler MCC Module Healthy FDBK 1 - - - - - - MCC BWSR-PLC - Hardwire

LUFF HYDRAULICS DRIVE - 10EAF06AE001

84 1 10EAF06AE001-YB01 Luff Hyd. Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

85 1 10EAF06AE001-YB02 Luff Hyd. Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

86 1 10EAF06AE001-XB01 Luff Hyd. Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

87 1 10EAF06AE001-XB02 Luff Hyd. Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

88 1 10EAF06AE001-XB03 Luff Hyd. Motor MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

89 1 10EAF06AE001-XQ11 Luff Hyd. Motor Motor Current Feedback - - 1 - - 4-20 mA MCC BWSR-PLC - Hardwire

LUFF DRIVE OIL CIRCULATION PUMP MOTOR - 10EAF06AP001

90 1 10EAF06AP001-YB01 Luff Oil Circulation Pump ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

91 1 10EAF06AP001-YB02 Luff Oil Circulation Pump OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

92 1 10EAF06AP001-XB01 Luff Oil Circulation Pump ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

93 1 10EAF06AP001-XB02 Luff Oil Circulation Pump OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

94 1 10EAF06AP001-XB03 Luff Oil Circulation Pump MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

LUFF DRIVE AIR COOLER - 10EAF06AH001

95 1 10EAF06AH001-YB01 Luff Air Cooler Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

96 1 10EAF06AH001-YB02 Luff Air Cooler Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

97 1 10EAF06AH001-XB01 Luff Air Cooler Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

98 1 10EAF06AH001-XB02 Luff Air Cooler Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

99 1 10EAF06AH001-XB03 Luff Air Cooler MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

LONG TRAVEL DRIVE MOTORS -10EAF07AE001-016

100 1 10EAF07AE001-16-YB01 Long Travel Motor FWD ON Command - 1 - - - - - BWSR-PLC VFD - Hardwire

101 1 10EAF07AE001-16-YB11 Long Travel Motor REV ON Command - 1 - - - - - BWSR-PLC VFD - Hardwire

102 1 10EAF07AE001-16-YB02 Long Travel Motor Stop Command - 1 - - - - - BWSR-PLC VFD - Hardwire

103 1 10EAF07AU001-16-YB01 Long Travel Brake Motor ON Command - 1 - - - - - BWSR-PLC VFD - Hardwire

104 1 10EAF07AU001-16-YB02 Long Travel Brake Motor OFF Command - 1 - - - - - BWSR-PLC VFD - Hardwire

PAGE 5 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

105 1 10EAF07AE001-16-XB01 Long Travel Motor FWD ON Feedback 1 - - - - - - VFD BWSR-PLC - Hardwire

106 1 10EAF07AE001-16-XB11 Long Travel Motor REV ON Feedback 1 - - - - - - VFD BWSR-PLC - Hardwire

107 1 10EAF07AE001-16-XB02 Long Travel VFD Trip Feedback 1 - - - - - - VFD BWSR-PLC - Hardwire

108 1 10EAF07AE001-16-XB03 Long Travel Motor Ready to Start Feedback 1 - - - - - - VFD BWSR-PLC - Hardwire

109 1 10EAF07AU001-16-XB01 Long Travel Brake ckt not healthy 1 - - - - - - VFD BWSR-PLC - Hardwire

110 1 10EAF07AE001-16-YQ11 Long Travel Motor Speed Reference - - - 1 - 4-20 mA BWSR-PLC VFD - Hardwire

111 1 10EAF07AE001-16-XQ11 Long Travel Motor Speed Feedback - - 1 - - 4-20 mA VFD BWSR-PLC - Hardwire

112 1 10EAF07AE001-16-XQ12 Long Travel Motor Current Feedback - - 1 - - 4-20 mA VFD BWSR-PLC - Hardwire

113 5 10EAF07AE001-16-YB12 Local Permissive from PLC - 1 - - - - - BWSR-PLC VFD - Hardwire

LONG TRAVEL DRIVE FIELD INSTRUMENTS - 10EAF07AE001-016

114 1 10EAF07CG101-XG51 Travel Left - Travel Forward End Switch For Stacking 1 - - - - - FIELD BWSR-PLC - Hardwire

115 1 10EAF07CG102-XG51 Travel Right - Travel Reverse End Switch For Stacking 1 - - - - - FIELD BWSR-PLC - Hardwire

116 1 10EAF07CG103-XG51 Travel Left - Travel Forward End Switch For Reclaiming 1 - - - - - FIELD BWSR-PLC - Hardwire

117 1 10EAF07CG104-XG51 Travel Right -Travel Reverse End Switch For Reclaiming 1 - - - - - FIELD BWSR-PLC - Hardwire

118 1 10EAF07CG105-XG51 Travel Left - Forward End Limit Switch 1 - - - - - FIELD BWSR-PLC - Hardwire

119 1 10EAF07CG106-XG51 Travel Right - Reverse End Limit Switch 1 - - - - - FIELD BWSR-PLC - Hardwire

120 1 10EAF07CG107-XG51 Travel Left - Travel Forward Emg. End Limit Switch 1 - - - - - FIELD MCC - Hardwire

121 1 10EAF07CG108-XG51 Travel Right- Travel Reverse Emg. End Limit Switch 1 - - - - - FIELD MCC - Hardwire

122 1 10EAF07CG001-XQ11 Travel Position Encoder - Travel Frame - - - - 1 - Pulse FIELD BWSR-PLC - Soft signal

123 5 10EAF07CG151-XB05 Brake Release Feedback from VFD 1 - - - - - VFD BWSR-PLC - Hardwire

SLEW DRIVE HYDRAULIC PUMP MOTOR - 10EAF05AE001

124 1 10EAF05AE001-YB01 Slew Motor ON Command - 1 - - - - BWSR-PLC MCC - Hardwire

125 1 10EAF05AE001-YB02 Slew Motor OFF Command - 1 - - - - BWSR-PLC MCC - Hardwire

126 1 10EAF05AE001-XB01 Slew Motor ON Feedback 1 - - - - - MCC BWSR-PLC - Hardwire

127 1 10EAF05AE001-XB02 Slew Motor OFF Feedback 1 - - - - - MCC BWSR-PLC - Hardwire

128 1 10EAF05AE001-XB03 Slew Motor MCC Module Healthy Feedback 1 - - - - - MCC BWSR-PLC - Hardwire

PCRD - 10EAF09AE001

129 1 10EAF09AE001-YB01 PCRD Motor Forward ON Command - 1 - - - - BWSR-PLC MCC - Hardwire

130 1 10EAF09AE001-YB02 PCRD Motor Reverse ON Command - 1 - - - - BWSR-PLC MCC - Hardwire

131 1 10EAF09AE001-XB01 PCRD Motor ON Feedback 1 - - - - - MCC BWSR-PLC - Hardwire

PAGE 6 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

132 1 10EAF09AE001-XB02 PCRD Motor OFF Feedback 1 - - - - - MCC BWSR-PLC - Hardwire

133 1 10EAF09AE001-XB03 PCRD MCC Module Healthy Feedback 1 - - - - - MCC BWSR-PLC - Hardwire

PCRD FIELD INSTRUMENT- 10EAF09AE001

134 5 10EAF09CG102-XG52 PCRD Extra Tension 1 - - - - - MCC BWER-PLC - Hardwire

135 5 10EAF09CG103-XG53 PCRD Slackness 1 - - - - - MCC BWER-PLC - Hardwire

CCRD - 10EAF10AE001
Description
136 1 10EAF10AE001-YB01 CCRD Motor Forward ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire
Change
Description
137 1 10EAF10AE001-YB02 CCRD Motor Reverse ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire
Change
138 1 10EAF10AE001-XB01 CCRD Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

139 1 10EAF10AE001-XB02 CCRD Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

140 1 10EAF10AE001-XB03 CCRD MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

CCRD FIELD INSTRUMENT - 10EAF10AE001

141 5 10EAF10CG102-XG52 CCRD Extra Tension 1 - - - - - - MCC BWER-PLC - Hardwire

142 5 10EAF10CG103-XG53 CCRD Slackness 1 - - - - - - MCC BWER-PLC - Hardwire

RAIL CLAMP HYDRAULIC PUMP MOTOR - 10EAF08AE001-2

143 5 10EAF08AE001-2-YB01 Rail Clamp Motor ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

144 1 10EAF08AE001-2-YB02 Rail Clamp Motor OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

145 1 10EAF08AE001-2-XB01 Rail Clamp Motor ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

146 1 10EAF08AE001-2-XB02 Rail Clamp Motor OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

147 1 10EAF08AE001-2-XB03 Rail Clamp Motor MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

RAIL CLAMP FIELD INSTRUMENTS - 10EAF08AE001-2


DO Module with
148 5 10EAF08AA001-YB01 Rail Clamp Solenoid Valve Open Command - 1 - - - - - BWSR-PLC FIELD - Hardwire
relay board

149 1 10EAF08GH001-XB05 Rail Clamp Start Push Button From LCS 1 - - - - - - FIELD BWSR-PLC - Hardwire -

DRIVE SKIRT LIFTING MOTOR 1 - 10EAF11AE001-002

150 1 10EAF11AE001-YB01 Drive Skirt Motor 1 FWD ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire -

151 1 10EAF11AE001-YB01 Drive Skirt Motor 1 REV ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire -

152 1 10EAF11AE001-YB02 Drive Skirt Motor 1 OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire -

153 1 10EAF11AE001-XB01 Drive Skirt Motor 1 FWD ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire -

154 1 10EAF11AE001-XB01 Drive Skirt Motor 1 REV ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire -

PAGE 7 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

155 1 10EAF11AE001-XB02 Drive Skirt Motor 1 OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire -

156 1 10EAF11AE001-XB03 Drive Skirt Motor 1 MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire -

DRIVE SKIRT LIFTING MOTOR 2 - 10EAF12AE001-002

157 1 10EAF12AE001-YB01 Drive Skirt Motor 2 FWD ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

158 1 10EAF12AE001-YB01 Drive Skirt Motor 2 REV ON Command - 1 - - - - - BWSR-PLC MCC - Hardwire

159 1 10EAF12AE001-YB02 Drive Skirt Motor 2 OFF Command - 1 - - - - - BWSR-PLC MCC - Hardwire

160 1 10EAF12AE001-XB01 Drive Skirt Motor 2 FWD ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

161 1 10EAF12AE001-XB01 Drive Skirt Motor 2 REV ON Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

162 1 10EAF12AE001-XB02 Drive Skirt Motor 2 OFF Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

163 1 10EAF12AE001-XB03 Drive Skirt Motor 2 MCC Module Healthy Feedback 1 - - - - - - MCC BWSR-PLC - Hardwire

UPS-1 & 2 -10BRV40GU001

164 1 10BRV41GU001-XM01 UPS-1 AC source Fail 1 - - - - - - UPS BWSR-PLC - Hardwire

165 1 10BRV41GU001-XM48 UPS-1 Charger Abnormal 1 - - - - - - UPS BWSR-PLC - Hardwire

166 1 10BRV41GU001-XM49 UPS-1 Inverter Abnormal 1 - - - - - - UPS BWSR-PLC - Hardwire

167 1 10BRV42GU001-XM01 UPS-2 AC Source Fail 1 - - - - - - UPS BWSR-PLC - Hardwire

168 1 10BRV42GU001-XM48 UPS-2 Charger Abnormal 1 - - - - - - UPS BWSR-PLC - Hardwire

169 1 10BRV42GU001-XM49 UPS-2 Inverter Abnormal 1 - - - - - - UPS BWSR-PLC - Hardwire

170 1 10BRV43GU001-XM01 SCVS-Bypass Source Fail 1 - - - - - - UPS BWSR-PLC - Hardwire

171 1 10BRV44GU001-XM48 Battery On Load 1 - - - - - - UPS BWSR-PLC - Hardwire

172 1 10BRV44GU001-XM52 Battery Voltage Low 1 - - - - - - UPS BWSR-PLC - Hardwire

LUBRICATION SYSTEM FOR TRAVEL DRIVE - 10EAF07AP001

173 1 10EAF07AP001-YB01 Lub. System Travel Drive ON command - 1 - - - - - BWSR-PLC FIELD - Hardwire

174 1 10EAF07AP001-YB02 Lub. System Travel Drive OFF command - 1 - - - - - BWSR-PLC FIELD - Hardwire

175 1 10EAF07AP001-XB01 Lub. System Travel Drive ON/ OFF Feedback 1 - - - - - - FIELD BWSR-PLC - Hardwire

176 1 10EAF07AP001-XB02 Lub. System Travel Drive Oil Pump On Feedback 1 - - - - - - FIELD BWSR-PLC - Hardwire

177 1 10EAF07AP001-XB03 Lub. System Travel Drive Healthy Feedback 1 - - - - - - FIELD BWSR-PLC - Hardwire

178 1 10EAF07CL101-XG52 Lub. System Travel Drive Grease Level Low 1 - - - - - - FIELD BWSR-PLC - Hardwire

179 4 10EAF07AP001-XB04 Lub. System Remote Selected 1 - - - - - - FIELD BWSR-PLC - Hardwire

180 4 10EAF07AP001-XB05 End of line fault 1 - - - - - - FIELD BWSR-PLC - Hardwire

PAGE 8 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

181 5 10EAF07AP001-XB06 MPCB Trip 1 - - - - - - FIELD BWSR-PLC - Hardwire

TRIPPER CONVEYOR - 10EAF13AF001

182 1 10EAF13FS101-XG01 Tipper Conveyor Pull Chord Switch Activated (Left) 1 - - - - - - FIELD BWSR-PLC - Hardwire

183 2 10EAF13FS102-XG02 Tipper Conveyor Pull Chord Switch Activated (Right) 1 - - - - - - FIELD BWSR-PLC - Hardwire

184 1 10EAF13FG101-XG01 Tipper Conveyor Belt Sway Switch Activated (Left) 1 - - - - - - FIELD BWSR-PLC - Hardwire

185 2 10EAF13FG102-XG02 Tipper Conveyor Belt Sway Switch Activated (Right) 1 - - - - - - FIELD BWSR-PLC - Hardwire

SIREN - 10EAF20AE001

186 3 10EAF20AE001-XG01 Siren - 1 - - - - - BWSR-PLC Field - Hardwire

HARDWIRED SIGNAL EXCHANGE LIST BETWEEN BWSR PLC AND CHP AREA PLC

187 1 EBA25AE001-XB01 Yard Conveyor Running 1 - - - - - - CHP-PLC BWSR-PLC - Hardwire

188 1 EBA25AE001-XB48 Yard Conveyor Stop 1 - - - - - - CHP-PLC BWSR-PLC - Hardwire

189 1 10EAF03AF001-XB01 Boom Conveyor Running - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

190 1 EBA25AE001-XB11 Yard Conveyor Trip Command - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

191 1 10BBY01GS006-XB48 HT VCB Trip Fault Feedback - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

192 1 10EAF02AF001-XB01 Intermediate Conveyor Running - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

193 1 BWSR PLC/UPS-Fault BWSR PLC/ UPS Fault - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

194 1 10EAF03CW001-XQ11 Boom Conveyor Belt Weigher TPH - - - 1 - 4-20 mA BWSR-PLC CHP-PLC - Hardwire

195 1 GPS_TIME STAMPING GPS Time Stamping 1 - - - - - - CHP-PLC BWSR-PLC - Hardwire

196 3 10EAF01AZ001-XW11 BWSR in Stacking Mode - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

197 3 10EAF01AZ001-XW12 BWSR in Reclaiming Mode - 1 - - - - - BWSR-PLC CHP-PLC - Hardwire

DRIVE SKIRT MOTOR - 10EAF11AE001-002 & 10EAF12AE001-002


BWSR-RIO
198 1 10EAF11AE001-002-XB05 Drive Skirt 1 LCS Fwd Start Command To PLC 1 - - - - - Field
PANEL
BWSR-RIO
199 1 10EAF11AE001-002-XB06 Drive Skirt 1 LCS Rev Start Command To PLC 1 - - - - - Field
PANEL
BWSR-RIO
200 1 10EAF12AE001-002-XB05 Drive Skirt 2 LCS Fwd Start Command To PLC 1 - - - - - Field
PANEL
BWSR-RIO
201 1 10EAF12AE001-002-XB06 Drive Skirt 2 LCS Rev Start Command To PLC 1 - - - - - Field
PANEL
DRIVE SKIRT FIELD INSTRUMENTS - 10EAF12AE001-002

202 5 10EAF11CG101-XB51 Drive Skirt Limit Switch 1 activated at Boom Tail 1 - - - - - - MCC BWSR-PLC - Hardwire

203 5 10EAF11CG102-XB51 Drive Skirt Limit Switch 2 activated at Boom Tail 1 - - - - - - MCC BWSR-PLC - Hardwire

204 5 10EAF11CG103-XB51 Drive Skirt Limit Switch 3 activated at Boom Tail 1 - - - - - - MCC BWSR-PLC - Hardwire

PAGE 9 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

205 5 10EAF11CG104-XB51 Drive Skirt Limit Switch 4 activated at Boom Tail 1 - - - - - - MCC BWSR-PLC - Hardwire

206 5 10EAF12CG101-XB51 Drive Skirt Limit Switch 1 activated at Boom Head 1 - - - - - - MCC BWSR-PLC - Hardwire

207 5 10EAF12CG102-XB51 Drive Skirt Limit Switch 2 activated at Boom Head 1 - - - - - - MCC BWSR-PLC - Hardwire

208 5 10EAF12CG103-XB51 Drive Skirt Limit Switch 3 activated at Boom Head 1 - - - - - - MCC BWSR-PLC - Hardwire

209 5 10EAF12CG104-XB51 Drive Skirt Limit Switch 4 activated at Boom Head 1 - - - - - - MCC BWSR-PLC - Hardwire

I/O INTERROGATION POWER SUPPLY SIGNAL


One of The 24V DC Interrogation Power Supply Fail at BWSR
210 2 I/O PSU-INTRG_FAIL 1 - - - - - - PANEL BWSR-PLC - -
I/O Panel
One of The 24V DC Interrogation Power Supply Fail at BWSR BWSR-RIO
211 2 RI/O PSU-INTRG_FAIL 1 - - - - - - PANEL - -
RI/O Panel PANEL
BWSR PLC PANEL IO REQUIREMENTS

DI DO AI AO

Sum of IO Counts 134 56 12 2

Module Counts * * * *

Module Counts With 10% Spare * * * *

REMOTE IO PANEL INSIDE THE OPERATOR CABIN

EMERGENCY STOP
BWSR-RIO
1 1 10EAF03GS001-XM02 At Boom Conveyor Platform 1 - - - - - - MCC - Hardwire
PANEL
BWSR-RIO
2 1 10EAF05GS001-XM02 At Slew Drive Platform 1 - - - - - - MCC - Hardwire
PANEL
ANEMOMETER
BWSR-RIO
3 1 10EAF03CS001-XQ12 Anemometer Feedback For Wind Speed - - 1 - - 4-20 mA FIELD - Hardwire
PANEL
BWSR-RIO
4 1 10EAF03CS002-XQ13 Anemometer Feedback For Wind Direction - - 1 - - 4-20 mA FIELD - Hardwire
PANEL
BOOM CONVEYOR FIELD INSTRUMENTS - 10EAF03AE001
BWSR-RIO
5 1 10EAF03FG104-XG01 Boom Conveyor Belt Sway Switch Activated 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
6 1 10EAF03CS101-XG01 Boom Conveyor Zero Speed Switch Activated 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
7 1 10EAF03CG151-XG51 Boom Conveyor Brake Released LS Activated 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
8 1 10EAF03CL101-XG01 Chute Block Detected Between Boom Conveyor & BCN-7 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
9 1 10EAF03CW001-XB47 Boom Conveyor Belt Weigher Overloaded 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
10 1 10EAF03CW001-XB48 Boom Conveyor Belt Weigher Faulty 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
11 1 10EAF03CW001-XQ01 Boom Conveyor Belt Weigher Actual Feed Rate - - 1 - - 4-20 mA FIELD - Hardwire
PANEL
BWSR-RIO
12 1 10EAF03CW001-XB21 Boom Conveyor Belt Weigher Totalizer Pulse 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
13 1 10EAF03CL001-XQ10 Boom Conveyor Ultrasonic Level Transmitter - - 1 - - 4-20 mA FIELD - Hardwire
PANEL

PAGE 10 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire
BWSR-RIO
14 1 10EAF03GH001-XB05 Boom Conveyor LCS Forward Start Command To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
15 1 10EAF03GH001-XB06 Boom Conveyor LCS Reverse Start Command To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
16 1 10EAF03CG001-XG51 Boom Conveyor Pile Contact Safety Switch-1 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
17 1 10EAF03CG002-XG51 Boom Conveyor Pile Contact Safety Switch-2 1 - - - - - - FIELD - Hardwire
PANEL
BUCKET WHEEL FIELD INSTRUMENT - 10EAF04AE001
BWSR-RIO
18 1 10EAF04CS101-XG01 Bucket Wheel Zero Speed Switch Activated 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
19 1 10EAF04GH001-XB05 LCS Start Command To PLC 1 - - - - - - FIELD - Hardwire
PANEL
HYDRAULIC POWER CIRCUIT FOR BUCKET WHEEL AND SLEW DRIVE- 10EAF04AU001
Jupiter
BWSR-RIO
20 1 10EAF04CL101-XG52 HPP BW & SD - Level Switch For Oil Level Low 1 - - - - - control - Hardwire
PANEL
panel
Jupiter
BWSR-RIO
21 1 10EAF04CL101-XG54 HPP BW & SD - Level Switch For Oil Level High 1 - - - - - control - Hardwire
PANEL
panel
Jupiter
BWSR-RIO
22 1 10EAF04CG101-XG51 HPP BW & SD - Suction Valve Close LS 1 1 - - - - - control - Hardwire
PANEL
panel
Jupiter BWSR-RIO
23 1 10EAF04CG102-XG51 HPP BW & SD - Suction Valve Close LS 2 1 - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
24 1 10EAF04CG103-XG51 HPP BW & SD - Suction Valve Close LS 3 1 - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
25 1 10EAF04CP111-XG51 HPP BW & SD - Return Line Filter 1 Clogged (DP Switch) 1 - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
26 1 10EAF04CP112-XG51 HPP BW & SD - Return Line Filter 2 Clogged (DP Switch) 1 - - - - - - Hardwire
control PANEL
HPP BW & SD - Pressure Line Filter 1 Clogged - (DP Switch)- Jupiter BWSR-RIO
27 1 10EAF04CP113-XG51 1 - - - - - - Hardwire
Slew control PANEL
Jupiter
HPP BW & SD - Pressure Line Filter 2 Clogged (DP Switch)- BWSR-RIO
28 1 10EAF04CP114-XG51 1 - - - - - control - Hardwire
Bucket Wheel PANEL
panel
Jupiter
HPP BW & SD - Pressure Line Filter 3 Clogged (DP Switch)- BWSR-RIO
29 1 10EAF04CP115-XG51 1 - - - - - control - Hardwire
Bucket Wheel PANEL
panel
Jupiter BWSR-RIO
30 1 10EAF04CP103-XG02 HPP BW & SD - Pressure Switch For Slew 1 - - - - - - Hardwire
control PANEL
Jupiter
BWSR-RIO
31 1 10EAF04CP104-XG02 HPP BW & SD - Pressure Switch For Bucket Wheel 1 - - - - - control - Hardwire
PANEL
panel
BWSR-RIO
32 5 10EAF04CP001-XQ11 HPP BW & SD PT-1 - - 1 - - 4-20 mA FIELD - Hardwire
PANEL
BWSR-RIO
33 5 10EAF04CP002-XQ11 HPP BW & SD PT-2 - - 1 - - 4-20 mA FIELD - Hardwire
PANEL
HPP BW & SD - Temperature Switch- Oil Temperature Alarm BWSR-RIO
34 1 10EAF04CT101-XG51 1 - - - - - FIELD - Hardwire
(Warning) PANEL
HPP BW & SD - Temperature Switch- OilTemperature control BWSR-RIO
35 1 10EAF04CT103-XG51 1 - - - - - FIELD - Hardwire
(Trip) PANEL
BWSR-RIO
36 1 10EAF04AU001-YG51 Enable Command - 1 - - - - FIELD - Hardwire
PANEL
BWSR-RIO
37 1 10EAF04AU001-YG52 Slew Drive Right Command - 1 - - - - FIELD - Hardwire
PANEL
BWSR-RIO
38 1 10EAF04AU001-YG53 Slew Drive Left Command - 1 - - - - FIELD - Hardwire
PANEL

PAGE 11 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire
BWSR-RIO
39 1 10EAF04AU001-YG54 Buckwe Wheel Start/ Stop Command - 1 - - - - FIELD - Hardwire
PANEL
BWSR-RIO
40 1 10EAF04AU001-YG55 Alarm Reset Command - 1 - - - - FIELD - Hardwire
PANEL
Jupiter BWSR-RIO
41 1 10EAF04AU001-XM01 BW & SD Hydraulic system ready to start 1 - - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
42 1 10EAF04AU001-XM02 BW & SD Hydraulic system fault 1 - - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
43 1 10EAF04AU001-XM03 Bucket Wheel Manual Mode 1 - - - - - - - Hardwire
control PANEL
BWSR-RIO
44 1 10EAF04AA002-YQ11 Slew Drive Speed Reference - - - 1 - 4-20 mA FIELD - Hardwire
PANEL
BWSR-RIO
45 1 10EAF04AA003-YQ11 Bucket Wheel Speed Reference - - - 1 - 4-20 mA FIELD - Hardwire
PANEL
Jupiter BWSR-RIO
46 1 10EAF04AU001-XM04 Slew Manual Mode 1 - - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
47 1 10EAF04AU001-XM05 Slew Drive Forward on feedback 1 - - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
48 1 10EAF04AU001-XM06 Slew Drive Reverse on feedback 1 - - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
49 1 10EAF04AU001-XM07 Slew Drive Brake Released 1 - - - - - - - Hardwire
control PANEL
Jupiter BWSR-RIO
50 1 10EAF04AU001-XM08 Bucket Wheel on feedback 1 - - - - - - - Hardwire
control PANEL
LUFF SYSTEM FIELD INSTRUMENTS - 10EAF06AE001
BWSR-RIO
51 1 10EAF06CG111-XG51 Luff Operating UP Sensor Activated 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
52 1 10EAF06CG112-XG51 Luff Operating DOWN Sensor Activated 1 - - - - - - FIELD - Hardwire
PANEL
53 1 10EAF06CG001-XG11 Luff Angle Encoder - - - - 1 - Pulse FIELD BWSR-PLC - Hardwire
BWSR-RIO
54 1 10EAF06CG103-XG51 Luff At Zero Position 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
55 1 10EAF06AE001-XB05 Luff Drive LCS Raise Push Button To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
56 1 10EAF06AE001-XB06 Luff Drive LCS Lower Push Button To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
57 1 10EAF06AE001-XB08 Luff Air cooler LCS Start Command To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
58 1 10EAF06CG101-XG51 Luff Operating UP Emg. End LS Activated 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
59 1 10EAF06CG102-XG51 Luff Operating DOWN Emg. End LS Activated 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
60 1 10EAF06AE001-XB07 Luff Start PB from LPBS for Luff Drive 1 - - - - - FIELD - Hardwire
PANEL
HYDRAULIC POWER SYSTEM - LUFFING - 10EAF06AU001
BWSR-RIO
61 1 10EAF06CP101-XG02 HPP Luffing & Oper. Cabin - Cylinder Line 1 Pressure (PS- 1) 1 - - - - - - HPP JB - Hardwire
PANEL
BWSR-RIO
62 1 10EAF06CP102-XG02 HPP Luffing & Oper. Cabin - Cylinder Line 2 Pressure (PS- 2) 1 - - - - - - HPP JB - Hardwire
PANEL
HPP Luffing & Oper. Cabin - Operator cabin High - Solenoid BWSR-RIO DO Module with
63 1 10EAF06AA001-YG52 - 1 - - - - - HPP JB - Hardwire
operated direction control Valve Open Command PANEL relay board
HPP Luffing & Oper. Cabin - Operator cabin Low - Solenoid BWSR-RIO DO Module with
64 1 10EAF06AA002-YG52 - 1 - - - - - HPP JB - Hardwire
operated directional control Valve Open Command PANEL relay board
HPP Luffing & Oper. Cabin - Unloading Solenoid Valve open BWSR-RIO DO Module with
65 1 10EAF06AA003-YG52 - 1 - - - - - FIELD - Hardwire
command PANEL relay board
HPP Luffing & Oper. Cabin - Proportional directional control BWSR-RIO
66 1 10EAF06AA004-YG52 - - - 1 - 4-20 mA HPP JB - Hardwire
Valve for Luff UP and Down PANEL

PAGE 12 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire
BWSR-RIO
67 1 10EAF06CL103-XG52 HPP Luffing & Oper. Cabin - Level Switch For Oil Level Low 1 - - - - - - HPP JB - Hardwire
PANEL
HPP Luffing & Oper. Cabin - Level Switch For Oil Level Low BWSR-RIO
68 1 10EAF06CL104-XG54 1 - - - - - - HPP JB - Hardwire
Low PANEL
BWSR-RIO
69 1 10EAF06CG101-XG51 HPP Luffing & Oper. Cabin - Suction Valve Position LS 1 1 - - - - - - HPP JB - Hardwire
PANEL
HPP Luffing & Oper. Cabin - Thermostat (Temperature BWSR-RIO
70 1 10EAF06CT105-XG51 1 - - - - - - HPP JB - Hardwire
Switch Warning/Trip) PANEL
HPP Luffing & Oper. Cabin - Return Line Filter 1 Clogged (DP BWSR-RIO
71 1 10EAF06CP111-XG51 1 - - - - - - HPP JB - Hardwire
Switch) PANEL
HPP Luffing & Oper. Cabin - Return Line Filter 2 Clogged (DP BWSR-RIO
72 1 10EAF06CP112-XG51 1 - - - - - - HPP JB - Hardwire
Switch) PANEL
HPP Luffing & Oper. Cabin - Return Line Filter 3 Clogged (DP BWSR-RIO
73 1 10EAF06CP113-XG51 1 - - - - - - HPP JB - Hardwire
Switch) PANEL
HPP Luffing & Oper. Cabin - Pressure Line Filter Clogged (DP BWSR-RIO
74 1 10EAF06CP114-XG51 1 - - - - - - HPP JB - Hardwire
Switch) PANEL
BWSR-RIO
75 1 10EAF06CP001-XQ11 HPP Luffing & Oper. Cabin - Cylinder 1 Pressure (PT-1) - - 1 - - 4-20 mA HPP JB - Hardwire
PANEL
BWSR-RIO
76 1 10EAF06CP002-XQ11 HPP Luffing & Oper. Cabin - Cylinder 1 Pressure (PT-2) - - 1 - - 4-20 mA HPP JB - Hardwire
PANEL
BWSR-RIO
77 1 10EAF06CP003-XQ11 HPP Luffing & Oper. Cabin - Cylinder 2 Pressure (PT-3) - - 1 - - 4-20 mA HPP JB - Hardwire
PANEL
BWSR-RIO
78 1 10EAF06CP004-XQ11 HPP Luffing & Oper. Cabin - Cylinder 2 Pressure (PT-4) - - 1 - - 4-20 mA HPP JB - Hardwire
PANEL
BWSR-RIO DO Module with
79 1 10EAF06AA004-YG52 HPP Luffing & Oper. Cabin - Equalizer Solenoid Valve 1 - 1 - - - - - FIELD - Hardwire
PANEL relay board
BWSR-RIO DO Module with
80 1 10EAF06AA005-YG52 HPP Luffing & Oper. Cabin - Equalizer Solenoid Valve 2 - 1 - - - - - FIELD - Hardwire
PANEL relay board
SLEW DRIVE FIELD INSTRUMENTS - 10EAF05AE001
BWSR-RIO
81 1 10EAF05CG101-XG01 Boom At Zero Angle 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
82 1 10EAF05CG102-XG01 Slew Over Travel Left Switch 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
83 1 10EAF05CG103-XG01 Slew Over Travel Right Switch 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
84 1 10EAF05CG106-XG01 Slew Locking Status Limit Switch On Slew Frame 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
85 1 10EAF05CG001-XQ11 Slew Angle Encoder - - - - 1 - Pulse FIELD - Soft signal
PANEL
BWSR-RIO
86 1 10EAF05GH001-XB05 Slew LCS Start Command To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
87 1 10EAF05GH002-XB06 BW & Slew Air Oil Cooler LCS Start Command To PLC 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
88 1 10EAF05CG104-XG01 Slew Over Travel Left Emg. Switch 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
89 1 10EAF05CG105-XG01 Slew Over Travel Right Emg. Switch 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
90 1 10EAF05GH001-XB07 Slew Left PB from LPBS for Slew Drive 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
91 1 10EAF05GH001-XB08 Slew Right PB from LPBS for Slew Drive 1 - - - - - FIELD - Hardwire
PANEL
LUBRICATION SYSTEM FOR SLEW BEARING - 10EAF05AP001
BWSR-RIO
92 1 10EAF05AP001-YB01 Lub. System Slew Bearing ON Command - 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
93 1 10EAF05AP001-YB02 Lub. System Slew Bearing OFF Command - 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
94 1 10EAF05AP001-XB02 Lub. System Slew Bearing Oil Pump on Feedback 1 - - - - - - FIELD - Hardwire
PANEL

PAGE 13 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire
BWSR-RIO
95 1 10EAF05AP001-XB03 Lub. System Slew Bearing Healthy FDBK 1 - - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
96 1 10EAF05CL101-XG52 Lub. System Slew Bearing Grease Level Low 1 - - - - - - FIELD - Hardwire
PANEL
Pressure Switch-1 For Discharge Pressure Low Monitoring At BWSR-RIO
97 1 10EAF05CP101-XG02 1 - - - - - FIELD - Hardwire
Line-1 PANEL
Pressure Switch-2 For Discharge Pressure Low Monitoring At BWSR-RIO
98 1 10EAF05CP102-XG02 1 - - - - - FIELD - Hardwire
Line-2 PANEL
BWSR-RIO
99 1 10EAF05AP001-XB05 Lub. System Remote Selected 1 - - - - - - FIELD - Hardwire
PANEL
LUBRICATION SYSTEM FOR BUCKET WHEEL - 10EAF04AP001
BWSR-RIO
100 1 10EAF04AP001-YB01 Lub. System Bucket Wheel ON Command - 1 - - - - FIELD - Hardwire
PANEL
BWSR-RIO
101 1 10EAF04AP001-YB02 Lub. System Bucket Wheel OFF Command - 1 - - - - FIELD - Hardwire
PANEL
BWSR-RIO
102 1 10EAF04AP001-XB02 Lub. System Bucket Wheel Oil Pump on Feedback 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
103 1 10EAE04AP001-XB03 Lub. System Bucket Wheel MCC Module Healthy FDBK 1 - - - - - FIELD - Hardwire
PANEL
BWSR-RIO
104 1 10EAF04CL101-XG52 Lub. System Bucket Wheel Grease Level Low 1 - - - - - FIELD - Hardwire
PANEL
Pressure Switch-1 For Discharge Pressure Low Monitoring At BWSR-RIO
105 1 10EAF04CP101-XG02 1 - - - - - FIELD - Hardwire
Line-1 PANEL
Pressure Switch-2 For Discharge Pressure Low Monitoring At BWSR-RIO
106 1 10EAF04CP102-XG02 1 - - - - - FIELD - Hardwire
Line-2 PANEL
BWSR-RIO
107 5 10EAE04AP001-XB04 Lub. System Remote Selected 1 - - - - - - FIELD - Hardwire
PANEL
OPERATOR STATION - 10CSA01GC001
BWSR-RIO
108 1 10CSA01GC001-XL01 Auto / Manual Selection 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
109 1 10CSA01GC001-XL02 Local / Remote Selection 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
110 1 10CSA01GC001-XL03 Fault Accept Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
111 1 10CSA01GC001-XL04 Fault Reset Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
112 1 10CSA01GC001-XL05 Emergency Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
113 1 10CSA01GC001-XL06 Power ON Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
114 1 10CSA01GC001-XL07 Power OFF Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
115 1 10CSA01GC001-XL08 Lights On/Off Selection 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
116 1 10CSA01GC001-XL09 Bucket Wheel Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
117 1 10CSA01GC001-XL10 Bucket Wheel Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
118 1 10CSA01GC001-XL11 Boom Conveyor FWD Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
119 1 10CSA01GC001-XL12 Boom Conveyor REV Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
120 1 10CSA01GC001-XL13 Boom Conveyor Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
121 1 10CSA01GC001-XL14 Cabin Raise Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
122 1 10CSA01GC001-XL15 Cabin Lower Push Button 1 - - - - - CD - Hardwire
PANEL

PAGE 14 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire
BWSR-RIO
123 1 10CSA01GC001-XL16 Belt Feeder Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
124 1 10CSA01GC001-XL17 Belt Feeder Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
125 1 10CSA01GC001-XL18 Travel Drive Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
126 1 10CSA01GC001-XL19 Travel Drive Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
127 1 10CSA01GC001-XL20 Slew Drive Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
128 1 10CSA01GC001-XL21 Slew Drive Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
129 1 10CSA01GC001-XL22 Intermediate Conveyor Start Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
130 1 10CSA01GC001-XL23 Intermediate Conveyor Stop Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
131 1 10CSA01GC001-YL01 Control Supply ON Lamp - 1 - - - - CD - Hardwire
PANEL
BWSR-RIO
132 1 10CSA01GC001-YL02 Power Supply ON Lamp - 1 - - - - CD - Hardwire
PANEL
BWSR-RIO
133 1 10CSA01GC001-YL03 Hooter ON Lamp - 1 - - - - CD - Hardwire
PANEL
BWSR-RIO
134 1 10CSA01GC001-XL24 Hooter ON Push Button 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
135 1 10CSA01GC001-XQ01 Travel - Speed Reference Joystick - - 1 - - 4-20 mA CD - Hardwire
PANEL
BWSR-RIO
136 1 10CSA01GC001-XL25 Travel Joystick Forward Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
137 1 10CSA01GC001-XL26 Travel Joystick Reverse Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
138 1 10CSA01GC001-XL27 Travel Joystick Deadband Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
139 1 10CSA01GC001-XQ02 Slew Speed Reference Joystick - - 1 - - 4-20 mA CD - Hardwire
PANEL
BWSR-RIO
140 1 10CSA01GC001-XQ03 Luffing Position Reference Joystick - - 1 - - 4-20 mA CD - Hardwire
PANEL
BWSR-RIO
141 5 10CSA01GC001-XL28 Luff Joystick Up Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
142 5 10CSA01GC001-XL29 Luff Joystick Down Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
143 5 10CSA01GC001-XL30 Slew Joystick Left Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
144 5 10CSA01GC001-XL31 Slew Joystick Right Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
145 5 10CSA01GC001-XL32 Luff and Slew Joystick Deadband Contact 1 - - - - - CD - Hardwire
PANEL
BWSR-RIO
146 5 10CSA01GC001-XL33 Stacking/ Reclaiming Selection 1 - - - - - - CD - Hardwire
PANEL

BWSR PLC RIO PANEL IO REQUIREMENTS

DI DO AI AO

Sum of IO Counts 111 17 13 3

Module Counts * * * *

Module Counts With 10% Spare * * * *

PAGE 15 OF 16
Project : (1 x 600 + 1 x 660)MW JPL SEONI PROJECT,
Prepared By : KDU
MADHYA PRADESH Consultant: Fichtner Consulting Engineers (India) Private Ltd.,
Contractor : FLSmidth Pvt. Ltd., Customer: Jhabua Power Limited
Scope: COAL HANDLING PLANT Checked By : KDU

Document No : 80024774 Approved By : RTH

Version: 5.0

Date : 22.08.2014

TYPE OF SIGNALS SOURCE. ALARM Softsigna


ENGG
SR. NO. VER. PLC TAG NUMBER TAG DESCRIPTION RANGE PRIOR l/ REMARKS
UNITS
DI DO AI AO DP FROM TO ITY Hardwire

NOTE:

ABBREVIATION

1 THE MAIN PLC SHALL BE LOCATED INSIDE THE E-HOUSE. PLC PROGRAMMABLE LOGIC CONTROLLER

2 THE RIO PANEL AND CONTROL DESK SHALL BE LOCATED IN THE OPERATOR CABIN. RIO PANEL REMOTE PLC IO PANEL

3 THE BWSR PLC COMMUNICATION WITH THE CHP PLC THROUGH THE CCRD ONLY. CD CONTROL DESK

4 A DEDICATED CONTROL PANEL IS PROVIDED FOR BUCKET WHEEL AND SLEW DRIVE HPP. COMMUNICATION CHP COAL HANDLING PACKAGE

BETWEEN THE CONTROL PANEL AND PLC IS THROUGH HARDWIRE COMMUNICATION VIA HPP JB ONLY. UPS UNINTERRUPTABLE POWER SUPPLY

LDB LIGHTING DISTRIBUTION BOARD

TRAFO DRY TYPE TRANSFORMER

HT VCB HT VACCUM CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

PANEL LOCAL FIELD MOUNTED JUNCTION BOX

DP DIGITAL PULSE

PAGE 16 OF 16

You might also like