REQUIRED SYSTEM PERFORMANCE - PURCHASER
Note Specified REV Based on case / Flow REV
FLOW PERFORMANCE MIN NORM MAX
1 Enclosed Capacity MSCFD inlet 1 41.9 141.7 681
2 Static Inlet 1 Pressure, PSIG (Note 2) 0 1 2
3 Enclosed Capacity MSCFD inlet 2 12.6 42.5 204.2
4 Static Inlet 2 Pressure, PSIG (Note 2) 0 2 5
5 Peak Burner Exit Velocity, m/s By Vendor
6 Peak Mach Number Max 0.5
7 Design Temperature By Vendor
8 Design
Peak Pressure By Vendor
9 Operating
Pressure due to Flash back By Vendor
Temp. (with
10 Minimum
safety pilot heat release By Vendor
11 factor) By Vendor
12 Pilot ignition system Direct electric ignition
13 Pilot-flame detection system By Vendor
NOISE PERFORMANCE
14 SPL at windfence, dBA 85 dBA at 0.9 m
15 SPL at_______meters from base, dBA
16 SPL at_______meters from base, dBA
17
SMOKELESS PERFORMANCE
18 Total Smokeless Capacity, kg/h
19 Smokeless Definition (R0 / R1 / R2) R1 (Note 1)
20
SMOKELESS STEAM CONSUMPTION
21 Max. Total Steam, kg/h N/A
22 Continuos Steam, kg/h N/A
23 S/HC ratio @ Design Smokeless Rate N/A

SMOKELESS AIR REQUIREMENTS


24 Design Air Capacity, m³/s By Vendor
25 Design Blower Pressure, mm w.c. By Vendor
26 Max Motor Power, kW By Vendor
27
UTILITY CONSUMPTION
28 Purge Gas, lb/h (Continuous) N/A
29 Purge Gas for high pressure inlet, lb/h 5.37
30 Purge Gas for low pressure inlet, lb/h 12.32
31 Pilot Gas, lb/h 80.7
32 Ignition Gas Nm³/h (Intermittent) N/A
33 Ignition Air Nm³/h (Intermittent) N/A
34 Assist Gas Nm³/h /kg/h waste N/A
35 Supplemental Gas, Nm³/h N/A
36 Utility gas pressure By Vendor
37
NOTES
38 1. If this is not complied, indicate the definition of smokeless offered.
39 2. Reference values, must be verified with the final flare size.
40
41
Departamento: #REF!
#REF! Código CPP No. #REF!
Código EP PEC No. #REF!
Código SHAYA N:
#REF! Revisión No.: #REF!
Página No.: 3 de 6
PREDICTED SYSTEM PERFORMANCE - VENDOR
Note Predicted REV Based on Case / Flow REV
FLOW PERFORMANCE
1 Enclosed Capacity, kg/h
2 Static Inlet Pressure, kPa (ga)
3 Peak Burner Exist Velocity, m/s
4 Peak Mach Number
5 Peak Operating Temp. (with safety factor)
6
NOISE PERFORMANCE
7 SPL at windfence, dBA
8 SPL at_______meters from base, dBA
9 SPL at_______meters from base, dBA
10
11
SMOKELESS PERFORMANCE
12 Total Smokeless Capacity, kg/h
13 Smokeless Definition (RO / R1 / R2)
14
15
16
SMOKELESS STEAM CONSUMPTION
17 Max. Total Steam, kg/h
18 Continuos Steam, kg/h
19 S/HC ratio @ Design Smokeless Rate
20
21
SMOKELESS AIR REQUIREMENTS
22 Design Air Capacity, m³/s
23 Design Blower Pressure, mm w.c.
24 Max Motor Power, kW
25
26
UTILITY CONSUMPTION
27 Purge Gas, Nm³/ (Continuous)
28 Purge Gas, Nm³/ (Intermittent)
29 Pilot Gas, Nm³/h
30 Ignition Gas Nm³/h (Intermittent)
31 Ignition Air Nm³/h (Intermittent)
32 Assist Gas Nm³/h /kg/h waste
33 Supplemental Gas, Nm³/h
34
35
36
37
38
39
40
Departamento: #REF!
#REF! Código CPP No. #REF!
Código EP PEC No. #REF!
Código SHAYA N:
#REF! Revisión No.: #REF!
Página No.: 4 de 6
MECHANICAL DESING DATA (COMBUSTION EQUIPMENT)
Note Purchaser - Specified REV Vendor - Proposed /Actual REV
FLARE BURNER BODY
1 Tip Type / Model By Vendor
2 Quantity of Burners By Vendor
3 Quantity of pilots By Vendor
4 Pilot ignition system By Vendor
5 Flare Burner Outlet Diameter By Vendor
6 Smokeless Method By Vendor
7 Overall Length, m By Vendor
8 Tip Material By Vendor
9 Exist Section Length, m By Vendor
10 Material /Size, mm /Sched. By Vendor
11 Inlet Section Length, m By Vendor
12 Material /Size,mm /Sched. By Vendor
13 Connection Type /Size, mm By Vendor
14 Flame Retention, (Y/N) / Material Yes / By Vendor
15
STEAM ASSIST EQUIPMENT
16 Steam Injector, Material N/A
17 Connection Mat'l / Type / Size, mm N/A
18
AIR ASSIST EQUIPMENT
19 Air Plenum Length, m By vendor
20 Air Plenum Diameter, m By vendor
21 Connection Type /Size, mm By vendor
22 Required airflow rate By vendor
23
FIREBOX EQUIPMENT
24 Overall Height, m By Vendor
25 Firebox Outside Dimensions, m By Vendor
26 Rectangular - Length / Width By Vendor
27 Round - Diameter Yes / By Vendor
28 Polygonal - No. Sides / Width By Vendor
29 Windfence Outside Dimensions, m By Vendor
30 Rectangular - Length / Width By Vendor
31 Round - Diameter Yes / By Vendor
32 Polygonal - No. Sides / Width By Vendor
33 Refractory Material
Woven Ceramic Fiber and/or
refractory bricks
34 Internal protective coating material By Vendor
35 Thickness, mm By Vendor
36 Max. Allowable Oper. Temp., °C By Vendor
37 Max. Shell Temperature °C By Vendor
38 Anchor Type /Material By Vendor
39 Max. Flue Gas Temperature, °C By Vendor
40 Flue Gas velocity out By Vendor
41 Stack T/C (Y/N) By Vendor
42 Stack Sample Conn. (Y/N) By Vendor
43 Connection Type / Size, mm By Vendor
44 Max. Personnel Exposure Temp., °C By Vendor (not exceed 160 °F)
45
Departamento: #REF!
#REF! Código CPP No. #REF!
Código EP PEC No. #REF!
Código SHAYA N:
#REF! Revisión No.: #REF!
Página No.: 5 de 6
MECHANICAL DESING DATA (PIPING)
Note Purchaser - Specifield REV Vendor - Proposed /Actual REV
PIPING TO BURNERS
1 Waste Gas Piping - Material Note 1
2 Steam Piping - Material Note 1
3 Air Piping - Material Note 1
4 Heat Shielding - Material By Vendor
5 External coating material By Vendor
6
7 Pilot Gas Lines - Quantity By Vendor
8 Material /Size (mm) /Schedule Note 1
9 Ignition Lines - Quantity By Vendor
10 Material /Size (mm) /Schedule Note 1
11 Assist Gas Line - Mat'l / Size / Sched. Note 1
12 T/C Conduit - Mat'l /Size, mm By Vendor
13 Ignition/Power Conduit - Mat'l /Size, mm By Vendor
14
15
16 Stage 1 - Burner Count
17 Wase Gas Valve Size, mm / Type By Vendor
18 Steam Valve Size, mm / Type By Vendor
19 Air Valve Size, mm / Type By Vendor
20
21
22 Stage 2 - Burner Count
23 Wase Gas Valve Size, mm / Type By Vendor
24 Steam Valve Size, mm / Type By Vendor
25 Air Valve Size, mm / Type By Vendor
26
27
28 Stage 3 - Burner Count
29 Wase Gas Valve Size, mm / Type By Vendor
30 Steam Valve Size, mm / Type By Vendor
31 Air Valve Size, mm / Type By Vendor
32
33
34 Stage 4 - Burner Count
35 Wase Gas Valve Size, mm / Type By Vendor
36 Steam Valve Size, mm / Type By Vendor
37 Air Valve Size, mm / Type By Vendor
38
39
40
41 NOTES
42 1. According to 61G2158-ACP-50-SP-001-3 "Clases de Tuberías"
43
44
Departamento: #REF!
#REF! Código CPP No. #REF!
Código EP PEC No. #REF!
Código SHAYA N:
#REF! Revisión No.: #REF!
Página No.: 6 de 6
MECHANICAL DESING DATA (ANCILLARIES)
Note Purchaser - Specifield REV Vendor - Proposed /Actual REV
AIR ASSIST BLOWER SYSTEM
1 Fan Quantity By Vendor
2 Fan Type / Material By Vendor
3 Fan Location By Vendor
4 Damper Quantity By Vendor
5 Damper Control Required / Included By Vendor
6 Motor Type / Speed By Vendor
7 Motor Enclosure TEFC
8 Motor Nameplate, kW By Vendor
9 Motor / Fan - Lubrication By Vendor
10 Max. Motor Current - Winter, amps By Vendor
11 Supplemental Requirements IEEE 841
12 Insulation Type F
13 Hazardous Location By Vendor (Ref API 500)
14 Variable Speed Driver Application Inverter Duty
15 Wind fence Enclosure material Steel
16 Fuel train of enclosed flame shutdown By Vendor
17
18
19
LADDERS & PLATFORMS (Note 2)
20 Top Platform, Deg. / Size, m By Vendor
21 Step-Off Platforms, Quantity By Vendor
22 Instrument Access, Quantity Two (2), By Vendor
23 Ladders Type By Vendor
24 Material / Finish By Vendor
25 L&P Specification By Vendor
26
27
28
EST. EQUIPMENT WEIGHTS, kg
29 Firebox Outside Dimensions, m By Vendor
30 Flare Burners By Vendor
31 Piping By Vendor
32 Control Valves By Vendor (Note 1)
33 Windfence Outside Dimensions, m By Vendor
34 Ladders & Platforms By Vendor
35 Liquid Seal By Vendor
36 Knockout Drum N/A
37 Control Panels By Vendor (Note 1)
38
39
40 NOTES
41 1. For control panel, instruments and valves information see: 3808-E538-M-SP-100-005 (61KFC0504-CBP-20-SP-010)
42 2. The vendor shall install the required platforms and ladders so that all valves and instruments are easy to operate.