Mayfair LOTS 4 & 10 Buildings 2-6: Building 6 Roof Vent Calculations
Mayfair LOTS 4 & 10 Buildings 2-6: Building 6 Roof Vent Calculations
Mayfair LOTS 4 & 10 Buildings 2-6: Building 6 Roof Vent Calculations
AREA 1 ATTIC CALCULATION AREA 2 ATTIC CALCULATION AREA 1 ATTIC CALCULATION AREA 2 ATTIC CALCULATION AREA 1 ATTIC CALCULATION AREA 1 ATTIC CALCULATION
1149 SQ. FT. ATTIC AREA 193 SQ. FT. ATTIC AREA 623 SQ. FT. ATTIC AREA 193 SQ. FT. ATTIC AREA 623 SQ. FT. ATTIC AREA 889 SQ. FT. ATTIC AREA
X 1/150 SQ. FT. RATIO OF VENTILATION REQUIRED X 1/150 SQ. FT. RATIO OF VENTILATION REQUIRED X 1/150 SQ. FT. RATIO OF VENTILATION REQUIRED X 1/150 SQ. FT. RATIO OF VENTILATION REQUIRED X 1/150 SQ. FT. RATIO OF VENTILATION REQUIRED X 1/150 SQ. FT. RATIO OF VENTILATION REQUIRED
X 144 CONVERSION TO SQUARE INCHES X 144 CONVERSION TO SQUARE INCHES X 144 CONVERSION TO SQUARE INCHES X 144 CONVERSION TO SQUARE INCHES X 144 CONVERSION TO SQUARE INCHES X 144 CONVERSION TO SQUARE INCHES
1103 SQ. INCHES OF VENTILATION REQUIRED 185 SQ. INCHES OF VENTILATION REQUIRED 598 SQ. INCHES OF VENTILATION REQUIRED 185 SQ. INCHES OF VENTILATION REQUIRED 598 SQ. INCHES OF VENTILATION REQUIRED 853 SQ. INCHES OF VENTILATION REQUIRED
VENTILATION PROVIDED: VENTILATION PROVIDED: VENTILATION PROVIDED: VENTILATION PROVIDED: VENTILATION PROVIDED: VENTILATION PROVIDED:
50% OF THE REQUIRED VENTILATION 50% OF THE REQUIRED VENTILATION 50% OF THE REQUIRED VENTILATION 50% OF THE REQUIRED VENTILATION 50% OF THE REQUIRED VENTILATION 50% OF THE REQUIRED VENTILATION
IS LOCATED IN THE UPPER ATTIC IS LOCATED IN THE UPPER ATTIC IS LOCATED IN THE UPPER ATTIC IS LOCATED IN THE UPPER ATTIC IS LOCATED IN THE UPPER ATTIC IS LOCATED IN THE UPPER ATTIC
4 FLAT ROOF VENT 1 FLAT ROOF VENT 2 FLAT ROOF VENT 1 FLAT ROOF VENT 2 FLAT ROOF VENT 3 FLAT ROOF VENT
X 335 SQ. INCHES X 226 SQ. INCHES X 335 SQ. INCHES X 226 SQ. INCHES X 335 SQ. INCHES X 335 SQ. INCHES
1340 SQ. INCHES AT UPPER ATTIC 226 SQ. INCHES AT UPPER ATTIC 670 SQ. INCHES AT UPPER ATTIC 226 SQ. INCHES AT UPPER ATTIC 670 SQ. INCHES AT UPPER ATTIC 1005 SQ. INCHES AT UPPER ATTIC
THE BALANCE OF REQUIRED VENTILATION THE BALANCE OF REQUIRED VENTILATION THE BALANCE OF REQUIRED VENTILATION THE BALANCE OF REQUIRED VENTILATION THE BALANCE OF REQUIRED VENTILATION THE BALANCE OF REQUIRED VENTILATION
IS LOCATED IN THE LOWER ATTIC IS LOCATED IN THE LOWER ATTIC IS LOCATED IN THE LOWER ATTIC IS LOCATED IN THE LOWER ATTIC IS LOCATED IN THE LOWER ATTIC IS LOCATED IN THE LOWER ATTIC
VENT TYPE VENT TYPE VENT TYPE VENT TYPE VENT TYPE VENT TYPE
X SQ. INCHES X SQ. INCHES X SQ. INCHES X SQ. INCHES X SQ. INCHES X SQ. INCHES
SQ. INCHES AT LOWER ATTIC SQ. INCHES AT LOWER ATTIC SQ. INCHES AT LOWER ATTIC SQ. INCHES AT LOWER ATTIC SQ. INCHES AT LOWER ATTIC SQ. INCHES AT LOWER ATTIC
1340 SQ. INCHES OF VENTILATION 226 SQ. INCHES OF VENTILATION 670 SQ. INCHES OF VENTILATION 226 SQ. INCHES OF VENTILATION 670 SQ. INCHES OF VENTILATION 1005 SQ. INCHES OF VENTILATION
SHEET TITLE:
BUILDING 6
ROOF VENT
CALCULATIONS
SHEET NUMBER:
18
A6B3-01.1
PLOT REFERENCE DATE: 10/14/2019