Professional Documents
Culture Documents
AAMA 503-03: Voluntary Specification For Field Testing of Storefronts, Curtain Walls and Sloped Glazing Systems
AAMA 503-03: Voluntary Specification For Field Testing of Storefronts, Curtain Walls and Sloped Glazing Systems
AAMA 503-03
Voluntary Specification
For Field Testing Of
Storefronts, Curtain Walls
And Sloped Glazing Systems
M A N U F A C T U R E R S A S S O C I A T I O N
TABLE OF CONTENTS
How To Use The Short Form Specification ....................................1
Glossary Of Terms.....................................................................5
LIST OF FIGURES
Figure 1 Storefront...................................................................6
© 2003
American Architectural Manufacturers Association
1827 Walden Office Square, Suite 550, Schaumburg, IL 60173
PHONE 847/303-5664 FAX 847/303-5774
EMAIL webmaster@aamanet.org WEBSITE www.aamanet.org
All AAMA documents may be ordered at our web site in the “Publications Store”.
** Insert an exact description of the area(s) to be tested. Failure to do so can dramatically affect the cost of the field testing. The
recommended procedure for identification of the test area is to reference an architectural elevation/plan drawing that clearly
shows the intent of the area to be field tested.
AAMA 503-03 specifies water penetration resistance field testing for the above area immediately after installation begins.
Default performance values are specified in Sections 4.5 through 4.7. Any of the following optional paragraphs may be added to
modify the standard specification:
1. Optional air leakage resistance tests shall be conducted at a uniform static test pressure of Pa ( psf).
The maximum allowable rate of air leakage shall not exceed L/s•m2 ( cfm/ft2).
Specifier Note: Field air leakage resistance tests are only recommended for discrete “punched opening” curtain walls,
storefronts and sloped glazing elevations. Field air leakage testing is not recommended for a portion of a continuous system
due to the problems associated with compartmentalization and identification of extraneous air leakage.
4.6 The maximum allowable rates of air leakage for field 5.1.3 Sampling Procedures
testing shall not exceed 1.5 times the project specification If applicable, describe or list the procedures established
rate or 0.5 L/s•m2 (0.09 cfm/ft2), whichever is greater. The from Section 4.
specifier may require project specific air leakage, however
this must be stipulated in Paragraph 2 of the “Short Form 5.1.4 Test Parameters
Field Testing Specification”. List or describe the specified static pressure differential
used in the test, whether the chamber was affixed to the
4.7 The field water penetration resistance tests shall be interior or exterior of the fenestration product and provide a
conducted at a static test pressure of two-thirds of the detailed description (to include sketches showing location,
specified project water penetration test pressure, but not if appropriate) of the chamber attachment to the
less than 300 Pa (6.24 psf). fenestration product. Clearly identify any elements of the
fenestration product that were not tested.
NOTE: The specifier may increase the field water test
pressure to the value specified for the project, however, 5.1.5 Test Results
this must be stipulated in Paragraph 2 of the "Short Form Record the actual and allowable rates of air leakage and
Field Testing Specification." In the event that the project record all points of water penetration. Indicate whether or
does not have a specified water penetration test pressure, not extraneous air leakage was measured. Record unusual
the value will be equal to 20% of the positive design wind weather or test conditions.
load times 0.67.
5.1.6 Compliance Statement
4.8 When testing the specimen, no uncontrolled water shall Make a statement that the tests were conducted in
pass the innermost surface of the specimen as defined by accordance with this method or completely describe any
the face of the vertical or sloped surface of the innermost deviation. Also, state whether or not the results indicate
framing member, or shall enter the wall cavity during the compliance with the field testing specification
water penetration resistance tests. requirements.
FIGURE 1: STOREFRONT
NOTE: The pressure measuring device shall take into account the difference that may exist between the static pressure in the
interior of the building and the static pressure on the exterior. It may be possible to open a window or door in a room to balance
the pressure. If this is not possible, a measurement of the outdoor wind speed and/or indoor building pressure shall be made and
the test pressure adjusted accordingly.
NOTE: The pressure measuring device shall take into account the difference that may exist between the static pressure in the
interior of the building and the static pressure on the exterior. It may be possible to open a window or door in a room to balance
the pressure. If this is not possible, a measurement of the outdoor wind speed and/or indoor building pressure shall be made and
the test pressure adjusted accordingly.
NOTE: The pressure measuring device shall take into account the difference that may exist between the static pressure in the
interior of the building and the static pressure on the exterior. It may be possible to open a window or door in a room to balance
the pressure. If this is not possible, a measurement of the outdoor wind speed and/or indoor building pressure shall be made and
the test pressure adjusted accordingly.