Professional Documents
Culture Documents
Figure For Question No. 1
Figure For Question No. 1
1. A fault occurs at bus 3 of the power system shown in the figure. Find
positive sequence component of current in phase ‘a’ with (i) Z f = 0.0 and (ii)
Zf = j0.1 p.u for
(I) single line to ground,
(II) double line and
(III) double line to ground fault.
Given: Generators 1 and 2: Xd// = X1 =X2 = 20%, X0 = 4% and Xn = 5%
Transformers T1 and T2: X = 8%
Transmission line: X1 = X2 = 15%, X0 = 50%
Vf = 1.0 p.u.
Page 1 of 4
would limit the subtransient line current for a single line to ground fault to
that for a 3φ symmetrical fault. Given: X// = X2 = j0.15 P.U. and X0 = j0.05
P.U.
(b) Three identical Y connected resistors of three phase rating 2300 volt and
500 KVA consumes Ia1 = 0.9857<43.60 p.u., Ia2 = 0.2346<250.30 p.u. and Ia0
= 0.0. The voltage components at the load terminals are V an0 = 0.0, Van1 =
0.9857<43.60 p.u and Van2 = 0.2346<250.30 p.u. Find the total power
absorbed by the resistors in KW.
(b) Draw the reactance diagram for the following power system. Consider a
base of 13.8 KV and 50 MVA in the circuit of generator 1.
G1: 20 MVA, 13.8 KV, X// = 20%
G2: 30 MVA, 18 KV, X// = 20%
T1: 25 MVA, 220Y/13.8Δ KV, x = 10%
T2: 10 MVA, 127/18 KV, x = 10% (single phase bank)
5. What are the information obtained and what are the data required for load
flow study. Using Gauss-Seidal method obtain load flow solution (one
Page 2 of 4
iteration) of the system shown in the figure. The reactances are given in per
unit on a base of 100 MVA. Consider V 1 = 1.2<00 p.u., V2 = 1.0 p.u, P2 =
60.0 MW, P3 = -80.0 MW and Q3 = - 60.0 MVAR. Neglect the generator
reactance.
Consider that both the units are operating at all times and the total load
varies from 250 MW to 1250 MW. The maximum and minimum loads on
each unit are 625 and 100 MW, respectively. Find the incremental fuel cost
of the plant and the allocation of loads between the units for the minimum
cost of various total lodas (at an interval of 50 MW).
7. (a) What is a critical clearing angle? Explain how equal area criterion can
be used to find the critical clearing angle.
(b) A three phase fault occurs in one of the twoparallel lines as shown in the
figure. Find the critical clearing angle for clearing fault with the
simultaneous opening of breakers ‘C’ and ‘D’. Consider that the generator
was delivering 1.0 P.U. power just before the fault.
Page 3 of 4
Figure for Q.7(b)
Page 4 of 4