AF0500
ARC-FLASH RELAY
REVISION 0-E-120817
TABLE OF CONTENTS
1 KEY FEATURES ...................................................................................................................... 7
1.1 Easy Installation ....................................................................................................................... 7
1.2 Fail-Safe Installation ................................................................................................................. 8
1.3 Fast Error and Fault Location ................................................................................................... 8
1.4 Ethernet Communication .......................................................................................................... 8
1.5 USB Interface ........................................................................................................................... 8
2 ARC-FLASH PROTECTION SYSTEM DESIGN ...................................................................... 9
3 SENSOR PLACEMENT ......................................................................................................... 12
3.1 General Guidelines ................................................................................................................ 12
3.2 Switchgear Protection ............................................................................................................ 12
3.3 Transformer Protection .......................................................................................................... 12
4 OPTICAL SENSORS ............................................................................................................. 13
4.1 PGA-LS10 Photoelectric Point Sensor with Sensor Check .................................................... 14
4.1.1 PGA-LS10 Connection ......................................................................................................... 15
4.1.2 PGA-LS10 Installation .......................................................................................................... 16
4.2 PGA-LS20 and PGA-LS30 Fiber-Optic Sensors with Sensor Check ..................................... 17
4.2.1 Fiber Connection .................................................................................................................. 17
4.2.2 Receiver Wiring Connections ............................................................................................... 17
4.2.3 Transmitter Wiring Connections ........................................................................................... 17
4.2.4 PGA-LS20 and PGA-LS30 Connection................................................................................ 18
4.2.5 Fiber-Optic Sensor Adjustment ............................................................................................ 19
4.2.6 Sensor Adjustment For a Fiber Length Other Than 60 cm (24 in) ....................................... 19
5 APPLICATION EXAMPLES ................................................................................................... 20
5.1 Basic Scenario: One Sensor – One Circuit Breaker .............................................................. 20
5.2 Two Independent Trip Zones ................................................................................................. 21
5.3 Two Zones Combined To One By Cabling ............................................................................. 22
5.4 Several Zones Combined To One By Cabling ....................................................................... 23
5.5 Upstream Circuit Breaker Trip on Local Circuit Breaker Fail ................................................. 24
5.6 Main-Tie-Main using PGA-1100 Logic Diode Unit ................................................................. 24
5.7 Main-Tie-Main from a Dedicated AF0500 Zone ..................................................................... 26
5.8 Total Clearing Time ................................................................................................................ 26
5.8.1 Arc-Detection Delay ............................................................................................................. 26
5.8.2 Circuit Breaker Operating Time............................................................................................ 26
5.8.3 Total Clearing Time Examples ............................................................................................. 27
5.8.4 Total Clearing Time for Upstream Circuit Breakers In Case of a Circuit Breaker Failure .... 27
6 INSTALLATION AND TERMINALS ....................................................................................... 29
6.1 Power Supply ......................................................................................................................... 30
6.1.1 Line AC Supply .................................................................................................................... 30
6.1.2 Station Battery DC Supply ................................................................................................... 30
6.1.3 Auxiliary DC Supply ............................................................................................................. 31
6.1.4 Supply Surveillance.............................................................................................................. 31
6.2 Common I/O Block ................................................................................................................. 31
6.2.1 ERROR Signal Relay ........................................................................................................... 31
6.2.2 TRIPPED Signal Relay ........................................................................................................ 32
6.2.3 C/B Fail Output..................................................................................................................... 32
6.2.4 RESET Input ........................................................................................................................ 32
LIST OF FIGURES
1 AF0500 Default Trip Zones ...................................................................................................... 8
2 AF0500 Typical Wiring Diagram ............................................................................................ 10
3 AF0500 24-Vdc Source Typical Wiring Diagram .................................................................... 11
4 PGA-LS10 Detection Range for a 3 kA Fault ......................................................................... 14
5 PGA-LS10 Connection Diagram ............................................................................................ 15
6 PGA-LS10 Mounting Detail .................................................................................................... 16
7 PGA-LS20 and PGA-LS30 Connection Diagram ................................................................... 18
8 Basic AF0500 Configuration .................................................................................................. 20
9 AF0500 with Two Independent Trip Zones ............................................................................ 21
10 AF0500 with Two Trip Zones Combined ................................................................................ 22
11 AF0500 with Several Trip Zones Combined .......................................................................... 23
12 AF0500 Upstream Circuit Breaker Trip On Local
Circuit Breaker Fail ................................................................................................................. 24
13 PGA-1100 Configuration ........................................................................................................ 25
14 Main-Tie-Main Using PGA-1100 ............................................................................................ 25
15 AF0500 TRIP/TRIPPED Connected to Two AF0500 Units (Three Zone Units) ..................... 26
16 AF0500 Outline And Mounting Details ................................................................................... 29
17 Fail Safe Error Indication using Multiple AF0500’s ................................................................ 31
LIST OF TABLES
1 Circuit Breaker Operating Time .............................................................................................. 27
2 Sample Table for Testing a System ....................................................................................... 50
1 KEY FEATURES
The AF0500 Arc-Flash Relay is a high-speed, arc-detection device for electrical power-distribution
systems. The AF0500 has outputs for two trip coils in two zones, and has inputs for up to four optical
sensors for optimal arc detection. The inputs support both point sensors and fiber-optic line sensors,
which cover a larger area.
Using optical sensors rather than relying strictly on current measurement allows a much faster
detection time than overcurrent relays or a circuit breaker alone can typically provide, as the light
from the arc is unique for the fault, whereas current pulses above the nominal level are part of normal
operation for many systems.
On the occurrence of an arc fault, the AF0500 detects the fault and pulses the trip contact in less
than one millisecond, which trips the circuit breaker(s) supplying the fault. The total arcing time is
effectively reduced to the mechanical opening time of the circuit breaker, typically between 30 and
75 milliseconds. This reduces the energy of the arc fault significantly, increasing worker safety,
reducing fault damage, and improving uptime. Switchgear can often be simply cleaned, inspected,
and put back in service after an arc fault instead of having to be replaced.
The trip contacts are solid-state switches (IGBT’s), and provide fast reaction and sufficient drive
capability for connection directly to circuit-breaker trip coils.
The AF0500 can be used on ac or dc electrical systems and can be powered from either an ac or
dc supply, or both.
1.1 Easy Installation
The AF0500 design philosophy is to configure one or more zone units to provide arc-flash protection.
Each zone unit provides two sensors, one trip coil output, and digital inputs and outputs which make
it possible to combine the zone units into larger zones, or to trip an upstream circuit breaker if a local
circuit breaker has failed to trip. Each AF0500 provides two zone units, which can be combined
freely, with no differences if the zone units are on the same AF0500 or on different physical units.
See Fig. 1. The complete configuration and “programming” of the system can be done by simply
wiring the inputs and outputs marked with green arrows – no external software is needed.
To facilitate this, the zone units are equipped with digital inputs and outputs, which allow a system
with multiple zones and upstream circuit breakers to be wired with no programming required. This
means that in many applications, the switchboard wiring diagram can completely describe how the
arc-flash system works.
The relay will automatically learn which sensors, power supplies and trip coils are connected, and
will indicate an alarm if a previously connected wire breaks or is unplugged. If a configuration change
is needed, the redetection process can be triggered by pressing the Reset button for three seconds.
All changes to the configuration are logged in a non-volatile text log, and if needed, the installation
memory can be locked and password-protected using the USB configuration software.
3 SENSOR PLACEMENT
3.1 General Guidelines
Optical sensors should have line-of-sight to points being monitored. Ensure that the point sensors
and fiber are not blocked by fixed or moveable objects. Areas that will be accessed for maintenance
or with moveable parts (such as draw-out circuit breakers) should be considered a high priority for
installation. Do not place sensors or cables on bare components that will be energized and avoid
sharp bends in the cable, particularly when using the PGA-LS20 and PGA-LS30 fiber-optic sensors.
The electrical cables and sensors should be considered to be at ground potential when determining
electrical clearances.
Sensors should be mounted in a location that will minimize the chance of debris or dust build-up and
with easy access for maintenance if needed. A point sensor mounted at the top of an enclosure and
facing down is optimal for reducing dust build-up. It should be noted that most enclosures are metallic
and the reflectivity combined with the high intensity of an arc mean that even a moderately dusty
sensor will collect adequate light.
In dusty environments, sensor cleaning should be part of a regular maintenance schedule and can
be performed using compressed air or a dry cloth.
3.2 Switchgear Protection
The sensors used for arc-flash detection are optical sensors. Line-of-sight between the points where
an arc could occur and the sensor is optimal, but the reflectivity of metallic compartments will help
in distributing the light from an arc fault in the entire cabinet.
Often one point sensor is sufficient to monitor a complete switchgear compartment. However, if there
are large components such as circuit breakers that cast shadows over wider areas, more than one
point sensor is required.
3.3 Transformer Protection
The AF0500 can also be used for the protection of transformers. Two or more point sensors should
be used per transformer to monitor the primary and secondary connection terminals. For the
placement of the sensors, the same considerations apply as for switchgear protection.
4 OPTICAL SENSORS
The AF0500 has four inputs for optical arc-fault sensors.
Two sensor types are supported:
• PGA-LS10 Photoelectric Point Sensors with sensor check
• PGA-LS20 and PGA-LS30 Fiber-Optic Sensors with sensor check
The sensors can be used together, in any combination.
Both sensor types have LED indication of sensor health and fault location. A sensor-check circuit
tests the sensor to verify that the sensor assembly is functioning correctly. A healthy sensor will
flash its internal red LED every few seconds. A sensor that has detected an arc will indicate solid
red until the trip is reset.
The sensors connect to the AF0500 with shielded three-wire 20 AWG (0.5 mm2) electrical cable.
Each sensor includes 10 m (33 ft) of cable which can be shortened or extended up to 50 m
(164 ft). These cables should be considered to be at ground potential when determining electrical
clearances in the cabinet.
Any connected optical sensor with circuit check will be automatically detected and cause the
AF0500 to report an error if it is subsequently disconnected.
NOTE: Inserting and removing a sensor cable can cause a trip, depending on which terminals make
contact first. To guard against nuisance tripping, remove the trip coil terminal blocks before
connecting and disconnecting sensors, or perform the maintenance while the system is
de-energized.
5 APPLICATION EXAMPLES
5.1 Basic scenario: One Sensor – One Circuit Breaker
No configuration necessary.
NOTE: If several AC-powered units are connected together, ensure that a COM terminal from each
unit are also connected together.
FIGURE 12. AF0500 Upstream Circuit Breaker Trip on Local Circuit Breaker Fail.
NOTE: This could also be achieved through configuration, by assigning ZONE 1 to trip on CB
FAILURE.
An available auxiliary contact in a circuit breaker must be used to provide feedback of the main
contact positions in order to detect that the local circuit breaker did not interrupt the current.
NOTE: The default configuration for C/B ON is a normally-closed signal, but this can be changed
in the Configuration Software via USB.
5.6 Main-Tie-Main using PGA-1100 Diode Logic Unit
When several AF0500 protected zones are used and a common upstream circuit breaker should be
tripped if any of the downstream zones experience a local clearing failure, the upstream circuit
breaker may run out of inputs. The PGA-1100 Diode Logic Unit makes it possible to combine several
trip outputs to the common circuit breaker, both for ground-return and powered circuit breakers.
The PGA-1100 contains six power diodes connected as shown in Fig. 13. Terminals 4 and 8 are
common, and are always connected to the coil on the circuit breaker. If the positive supply is
connected to the coil, and the contacts on AF0500 are ground returned, terminals 5, 6 and 7 are
used for connecting up to three different trip sources to the breaker. If the coil has a fixed ground
return, and the contacts on AF0500 are switching the positive supply, use terminals 1, 2 and 3
instead.
FIGURE 15. AF0500 TRIP/TRIPPED Connected to Two AF0500 Units (Three Zone Units).
The wire marked “Note 1” in Fig. 15 allows each side of the switch gear to trip the tie circuit breaker.
The (optional) wire marked “Note 2” disconnects both incoming feeders in case of an arc flash in the
tie circuit breaker itself. It is necessary to have two separate wires for these functions
NOTE: If the zones on each side are larger and made from several discrete zone units, connect only
the wire marked “Note 1”, since the two sides can otherwise trip each other through the shared wire,
or use the scheme with diode logic units detailed in Section 5.6.
5.8 Total Clearing Time
The AF0500 is capable of tripping a circuit breaker in less than 1 ms from when light hits the sensor.
This is not the same as the clearing time for the fault. The arc fault will continue until the current to
the fault has stopped flowing, which happens when the circuit breaker connected to the unit has
reacted.
5.8.1 Arc-Detection Delay
The AF0500’s default arc-flash detection intentional delay time is 1 ms, but can be configured
between 0.5 and 10 ms via the USB configuration software.
5.8.2 Circuit Breaker Operating Time
Circuit breakers have a predetermined operating time, dependent on the type of circuit breaker.
Older circuit breakers have clearing times up to eight cycles, while modern circuit breakers are able
to open in one to five cycles. Refer to the specifications of the installed circuit breaker.
Finally, the upstream circuit breaker must obviously operate, which is added to the total clearing
time.
Example: Total Clearing Time with 3-cycle breakers and a local circuit breaker fault
Two 3-cycle circuit breakers at 50 Hz, with the upstream circuit breaker tripped by connecting the
CB FAIL output on one AF0500 to the TRIP input on another AF0500 zone:
1 + 60 + 1 + 60 ms = 122 ms
Example: Total Clearing Time with two-cycle circuit breakers and a local circuit breaker fault
Two 2-cycle circuit breakers, with the upstream circuit breaker tripped by a zone on the same
AF0500 unit, configured via the USB configuration software:
1 + 40 + 0 + 40 = 81 ms
maximum delay of such a connection is less than 1 ms, which can be safely ignored in relation to
the total clearing time.
The connections marked with a green arrow are not equipped with circuit check. Littelfuse
recommends that the connections are kept within the same cabinet.
6.3.1 INHIBIT Input
The INHIBIT function suppresses the light sensors and TRIP input so that the circuit breaker is not
tripped. The purpose could be to connect an external current sensor module for inhibiting nuisance
trips.
If the INHIBIT input is activated, the AF0500 will indicate on the sensor LED that light above the
threshold is being detected, but will not pulse the TRIP COIL output, nor activate the TRIPPED
output. In the event log available via USB (see section 7.4), logged data will indicate a possible arc
fault was detected, but not tripped due to the inhibit function.
Inhibit blocks all sources of trip from activating the trip coil output, including the TRIP input and all
remote channels.
6.3.2 TRIP Input
The TRIP input is used to remotely trip the AF0500. Once activated, the AF0500 will pulse the TRIP
COIL output in less than 1 ms.
6.3.3 C/B ON Input
Feedback from a circuit breaker auxiliary contact is used with the C/B ON input to detect the circuit
breaker closure status. If a circuit breaker failure is detected, the C/B FAIL signal can be used to trip
an upstream circuit breaker.
The polarity of the input is programmable in the USB configuration software, but in order to be fail-
safe, the default configuration expects the circuit breaker to conduct power to the system when the
input is open circuit. This means that a broken wire will have the AF0500 assume that the circuit
breaker did not open, thus opening the upstream circuit breaker.
6.3.4 TRIPPED Output
The TRIPPED output is used to remotely trip another AF0500. It is pulsed briefly active when a trip
event occurs, and the zone TRIP output is energized. If this output is connected to the TRIP input
on another zone as shown in Fig. 7, zone 1 will trip zone 2 as well. If the reverse connection is made,
the two zones are merged into one – any trip event in one zone will also trip the other zone. This
makes it possible to e.g. extend the number of sensors tripping a single TRIP output.
NOTE: The TRIP COIL output functions as a momentary switch and is protected against thermal
overload. It will gradually lower the time the trip coil is active if the AF0500 is tripped repeatedly.
6.5 Sensors
Each zone in the AF0500 is by default associated with two light sensors
as shown in Fig. 1. In the USB configuration software, this assignment
can be changed if desired. It is also possible to connect the zones
together by wiring the TRIPPED output from one zone to the TRIP input
in the other zone. In this case, the first zone will only trip the second zone.
6.5.1 Zone Association
The zone association can be changed in the USB configuration software,
which allows any sensor to be associated with any output.
It is possible to associate e.g. sensor 4 with trip 1, and sensors 1-3 with
trip 2, but it can easily cause confusion. We recommend keeping the
standard configuration if it is at all possible in the application.
Zones can also be combined by wiring their TRIPPED outputs and TRIP
inputs together. This creates a larger zone with more sensors and
outputs, which will trip together. See application examples in Section 5.
For information on using the USB configuration software, see Section 7.3.
7 USER INTERFACE
7.1 Reset Button
The RESET button on the front panel of the AF0500 has two functions: A
momentary press will reset any trip events, and holding the button for three
seconds will reset and refresh the configuration of the AF0500 with regard to
the sensors, trip coils, and power supplies currently present. Sensors, trip
coils and power supplies can be added at any time, but once a connection is
detected, its removal will cause an alarm.
Pressing the reset button will reset trip indications and error indications for
any existing error. The error indication will remain if the error is still present and cannot be reset, e.g.
if a sensor is missing or a supply voltage is outside the specification.
Holding the reset button for three seconds will reset the current list of connections to the unit. The
AF0500 will then redetect which sensors, trip coils, and power supplies are connected, which will
clear the alarms. Do not do this until the reason for the alarm is known, and has been rectified.
If password protection is enabled in the USB configuration, resetting the list of connections is not
allowed. In this case, use the USB configuration software to reset the alarm.
Holding the reset button for 10 seconds will reset the internal drives to factory defaults. This does
not affect the configuration or the log, but does imply a reset of the connected sensors as detailed
above.
7.2 LED Indications
Input LED’s follow the input state, and provide no information on the history. Since all digital outputs
are pulsed, the LED’s indicate if the output has been activated since the last reset. Blinking LED’s
on the front panel indicate errors e.g. an expected sensor is missing, etc. To reset the expected
state, use the RESET button.
SUPPLY 1 and 2 (Terminals 1 to 3 and 28 to 30, respectively)
On, green Supply voltage is connected.
Flashing green Supply voltage on this terminal has previously been detected, but is now
missing, or the connected supply is outside the specifications.
Off Supply voltage is not connected.
ERROR Relay (Terminals 4 to 6)
On, red An error has been detected, and the ERROR relay has been de-energized. If
another LED is flashing, use this to localize the error and correct the problem.
The event log or the USB configuration software can also be used to show the
cause for the alarm, see section 7.3.
Off No errors detected.
The LED will not always follow the internal contacts. The ERROR relay will be in the state shown on
the front panel when power is not connected, and will energize if no errors are detected. The relay
will de-energize on errors, and if power is removed. The ERROR relay will furthermore give a one
second pulse if an additional error is detected while errors are already present. Use the event log,
available via USB, to get more information on the errors present. See Section 7.4.
TRIPPED Relay (Terminals 7 to 8)
On, red A TRIP output is or has been active due to an arc-flash event. Press RESET
to clear the trip.
The LED will not always follow the status of the internal contacts. The TRIPPED relay is shown on
the front panel in its de-energized state, and will energize on a trip event, and de-energize on reset.
The TRIPPED relay will also pulse for one second if an additional trip happens before the previous
event was reset. Use the event log, available via USB, to get more information about the history of
the trip. See Section 7.4.
RESET Input (Terminal 9)
On, red RESET input or another reset source (RESET button or MODBUS) is active.
Off RESET input is inactive.
The reset button is blocked during trips. If the RESET input or the MODBUS reset register is
permanently activated, errors and trips will be reset as soon as they are cleared or completed.
C/B FAIL Output (Terminal 10)
On, red A circuit breaker did not trip as expected. The C/B FAIL output is or has been
active. Press RESET to clear the trip.
Off No C/B failure is detected.
INHIBIT input (Terminals 12 and 20)
On, red INHIBIT input is active. The zone will not trip, even if a sensor or a trip input is
activated. The sensor LED’s will turn red on such a trip, and can be reset by
pressing the RESET button.
Off INHIBIT input is inactive
TRIP Input (Terminals 13 and 21)
On, red TRIP input is active.
Off TRIP input is inactive
C/B ON Input (Terminals 14 and 22)
On, green The connected circuit breaker is conducting power.
Off The connected circuit breaker is not conducting power.
TRIPPED Output (Terminals 15 and 23)
On, red The TRIPPED output is or has been active. Press RESET to clear the trip.
Off The TRIPPED output is inactive.
TRIP COIL 1 and 2 (Terminals 18 to 19 and 26 to 27, respectively)
On, green The TRIP output is ready and detects a valid trip voltage in Shunt mode, or is
configured as Undervoltage trip coil.
Flashing red An error has been detected. The connection to the trip coil may be broken. If
this trip coil is not meant to be used, press and hold the RESET button for a
few seconds.
On, red The TRIP output is or has been active. Press RESET to clear the trip.
Off The TRIP output is not configured to trip, and no trip coil has been detected.
Sensors
On, green The sensor input is active and has a functional sensor connected.
On, red The sensor caused a trip event. If no TRIP COIL outputs are red, the trip may
have been inhibited; see the event log. The LED in the sensor will also be solid
red. Press the RESET button to clear the trip.
Flashing red The circuit check of the sensor failed; check the wiring and that fiber sensors
are fully seated in the thumb screws. If possible, the LED in the sensor will
also be flashing red. If a sensor has been removed temporarily or on purpose,
press and hold the RESET button for a few seconds to redetect the state. If
adjustments have been made to the fiber sensitivity, see Section 7.1.
Off The input has not detected a connected sensor. The input will by default still
be active.
PGA-LS10, PGA-LS20 and PGA-LS30
Flashing Red The sensor is operating normally.
On, red The sensor caused a trip event.
Off The sensor is unplugged or faulty, or the AF0500 is without power (check the
wiring and that fiber sensors are fully seated in the thumb screws).
Open the Configuration drive, and double click on the file named ’config.hta’
It is not possible to view live data from the unit via USB. The values shown for e.g. IP address and
sensor state are the values at the moment the USB connector was plugged in. Setting the password
in the USB configuration software will prevent the list of connected devices from being reset via the
reset button on the front panel.
7.3.1 USB Configuration Software – Screen Examples
The USB configuration software also shows the cause of any standing alarms in clear text.
The log is saved on the AF0500_LOG drive, and is a text file called AF0500.LOG.
A tool called log_view.hta allows simple filtering of the log, e.g. to show log lines with relation to
events only.
NOTE: The AF0500 will restart during the firmware upgrade process. Ensure the equipment is in a
safe state prior to starting the upgrade process. Do not interrupt the firmware upgrade process.
Product information, including hardware and firmware details, can be reviewed in the About tab as
shown in Section 7.3.1.
Follow the procedure below to perform a firmware upgrade:
1. Contact Littelfuse at relays@littelfuse.com to obtain the newest firmware file.
2. Connect the AF0500 to a computer using a USB cable. See Section 7.3.
3. Copy the AF0500.bin and AF0500.md5 files to the AF0500 Configuration drive.
4. Disconnect the USB cable. The firmware upgrade will begin. Progress will be shown on the front
panel as progressively-lit green sensor LED’s, starting from Sensor 1 to Sensor 4. The firmware
upgrade can take up to 150 seconds.
5. The AF0500 will restart when the firmware upgrade has been completed.
6. Close the Configuration Software screen (HTA file).
7. Reconnect the AF0500 to the computer as in Step 2.
8. Confirm that the firmware revision shown in the About tab is correct.
8 COMMISSIONING
With no manual configuration, a freshly unpacked and wired AF0500 will work using the factory
default settings. It will trip the TRIP 1 output if any sensors connected to input 1 or 2 exceed the
default setting of 10 klux, even if a circuit check is reporting a cable to be broken. Likewise, the TRIP
2 output will trip if any sensor connected to input 3 or 4 gives an alarm.
The digital I/O will operate, and if wired to perform upstream circuit breaker tripping or zone merging,
it will work as programmed in the wiring. It is possible to configure these connections in software as
well, if so desired. If both wired and software connections are set up, both will be active, and the
system will perform a logical “OR” between them: if any input, hardware or software, tells a zone to
trip, it will do so.
The INHIBIT input is always active, and will always inhibit a trip from propagating to the TRIPPED
as well as to the TRIP COIL outputs if the input is active.
Littelfuse recommends always doing a full systems test on all sensors and outputs to ensure that
any errors in the cabling or configuration will be detected and can be corrected before the system is
put into normal operation.
CAUTION: Make sure that the area is safe before this test. Ensure that loads and power are
disconnected at the transformers, etc.
8.1 Configuration of Installed Sensors
The AF0500 will auto-detect sensors as they are connected. To reset any errors (shown as blinking
red LED in a position where no sensor is attached), e.g. after moving a sensor to another position
on the unit, press and hold the RESET button for three seconds. This will redetect which sensors,
power supplies, etc. are connected.
8.2 Testing the Sensors
To test the tripping of point sensors, the intensity of light at the sensors needs to rise above 10 klux
(or the defined light immunity setting, if changed). The LED flash on most phones are not sufficient,
nor are most LED flashlights. Most incandescent flashlights (e.g. Mini Maglite with Xenon bulb or
larger) can be used, if the beam can be focused to a very small circle and the flashlight is brought
right next to the sensor. A normal AC light bulb can also be used.
For fiber sensors, the light intensity needs to be above 10 klux on a much larger area, which is not
possible with a flashlight or standard light bulbs. To test fiber sensors, a 300-500 W halogen lamp
or a powerful photo flash with a guide number of at least 15 m (50 ft) is needed. See Section 10.7.
1. Unplug the TRIP outputs to avoid tripping the circuit breakers. If the AF0500 TRIPPED
outputs are connected to other units, unplug these connectors as well.
2. Confirm that there is a solid green LED for each connected optical sensor. This confirms that
sensors are connected and healthy.
3. Confirm that a short red flashing light occurs periodically in each sensor. This indicates that
the sensor circuit is being checked.
4. Point the light source at a sensor and check that the LED on the sensor and the front panel
of the AF0500 turns red continuously. The TRIPPED LED will also turn on. If this does not
happen, the light source may not be powerful enough, especially for fiber sensors.
5. Repeat for the remaining sensors.
6. Check that the indicator LED’s on the front panel of the unit have turned red for all connected
sensors.
9 SUPPORT RESOURCES
The most up-to-date manuals, data sheets, instruction videos, etc. can be found on the AF0500 site
at www.littelfuse.com/AF0500.
The AF0500 is supported through the Littelfuse network of technical sales and distributors. For
installation help and support, please contact your sales representative. Include detailed information
about the installation and application. See Section 2.
9.1 Sending Information For Support
A picture or video of the installation makes it much easier to provide assistance. Also, the
configuration and log files can be very helpful, as is the serial number of the unit.
Attaching the files to the support email can be done like this:
Plug in a USB connector and connect to a computer.
After a few seconds, two new drives appear:
From the LOG drive, select and attach the AF0500.LOG file.
From the CFG drive, select and attach the CONFIG.CFG file.
Provide a single line diagram of the installation with indication of the zone boundaries if possible.
10 SPECIFICATIONS
10.1 AF0500
Supply:
Universal: 20 VA, 100 to 240 Vac (+10%, -15%) 50/60 Hz,
8 W, 110 to 250 Vdc (+10%, -20%)
Low Voltage: 4 W, 24 to 48 Vdc (+10%, -20%)
Optical Settings:
External Sensors: 4 Light sensors
Sensor Types: PGA-LS10, PGA-LS20, and PGA-LS30,
all with sensor check
Immunity Adjustment: Trip above 10 to 25 klux
Intentional Trip Delay Settings: 0.5 to 200 ms
0.5 ms intentional delay results in a
maximum 0.8 ms total delay
TRIP COIL Outputs:
Type: IGBT Switch
Configuration: Normally Open (Form A) isolated contact
UL Rating: 120/240 Vac, 1800 VA, 0.75 A maximum continuous,
125/250 Vdc, 138 VA, 0.75 A maximum continuous
Supplemental Rating:
Make/Carry 0.2 s: 30 A
Voltage Rating: 24 to 300 Vac, 24 to 300 Vdc
Current Rating: 20 A for 2 s, 10 A for 5 s
Control Voltage Alarm: <15 V
Control Voltage Test type: Measurement of current through a 100 k parallel resistor
Operating Mode: Shunt trip or undervoltage trip coil, configurable
Protection: 320 Vac MOV, thermally protected
Isolation: 1,000 Vac
Pulse Duration: 1 to 5 s, configurable
On-State Voltage Drop: 2.5 V at 5 A, 25˚C (77˚F)
4.0 V at 10 A, 25˚C (77˚F)
Output Relays:
ERROR Relay:
Contact Configuration: Change-over (Form C) isolated contact
Normally energized
UL Rating: 5 A resistive, 150 Vac
5 A resistive, 30 Vdc
0.3 A resistive, 50 Vdc
Altitude:
Below 2,000 m (6,500 ft): Normal Operation
Above 2,000 m (6,500 ft): 24 Vdc supply only, shunt trip only
Above 4,000 m (13,000 ft): Contact Littelfuse for further information.
10.2 EMC Tests
Verification tested in accordance with IEC/EN60255-26:2013.
1 MHz Burst: IEC 60255-22-1
± 1 kV differential mode (line-to-line)
± 2.5 kV common mode
Electrostatic Discharge: IEC 60255-22-2
± 6 kV Contact Discharge (direct and indirect)
± 8 kV Air Discharge
Radiated RF Immunity: IEC 60255-22-3
10 V/m, 80-1,000 MHz, 80% AM (1 kHz)
10 V/m, 1.4 to 2.7 GHz, 80% AM (1 kHz)
Fast Transient: IEC 60255-22-4:
Class A: ± 4 kV (on AC mains)
ANSI/IEEE C37.90.1-2002 (Oscillatory and fast transients on
input terminals)
Surge Immunity: IEC 60255-22-5:
± 4 kV differential mode (on AC lines)
± 2 kV common mode (on AC lines)
± 2 kV differential mode (on DC lines)
± 1 kV common mode (on DC lines)
± 2 kV common mode (on I/O ports)
± 1 kV differential mode (on I/O ports)
Conducted RF Immunity: IEC 60255-22-6
10 Vrms, 0.15-80 MHz, 80% AM (1 kHz)
Power Frequency: IEC 60255-22-7
Magnetic Field Immunity: IEC 61000-4-8
30 A/m and 300 A/m, 50 Hz and 60 Hz
Current Harmonics and Voltage
Fluctuations: IEC 61000-3-2 and IEC 61000-3-3
Class A
Radiated and Conducted
Emissions: CISPR 22:2008-09 / EN55022:2010
Class A
Voltage Interruptions: IEC 60255-11 and IEC 60255-29
100% Interrupts 3 x for
5 ms, 10 ms, 20 ms, 50 ms, 100 ms, 200 ms
10.5 Certification
Certification: CSA
UL Listed
FCC
10.6 Sensors
PGA-LS10 PGA-LS20 and PGA-LS30
Type: Point sensor Fiber-optic sensor
Detection Zone: 180 x 360° (half sphere) 360° along fiber
Output: 0-35 mA 0-35 mA
Electrical Cable: Shielded 3-wire 20 AWG (0.5 Shielded 3-wire 20 AWG (0.5 mm2)
mm2) electrical cable electrical cable
Factory Cable Length: 10 m (33 ft) electrical cable PGA-LS20:
8 m (26 ft) active;10 m (33 ft) total
(2 m (7 ft) shielded),
2 x 10 m electrical cable
PGA-LS30:
18 m (59 ft) active; 20 m (66 ft)
total
(2 m (7 ft) shielded),
2 x 10 m (33 ft) electrical cable
Sensor Check: Built-in LED for visual feedback Built-in LED for visual feedback
Accessories:
PGA-LS10 Point Sensor
PGA-LS20 Fiber-Optic Sensor, 8 m (26 ft) active length
PGA-LS30 Fiber-Optic Sensor, 18 m (59 ft) active length
PGA-0031 DIN-rail mounting brackets
PGA-1100 Diode Logic Unit
PGA-FLSH-00 Photo Flash for commissioning testing
PGA-FLSH-01 Photo Flash, CE and RoHS
10.8 Related Products
PGR-8800 Stand-alone Arc-Flash Relay with 6 sensor inputs, 1 trip coil output, with CT inputs for
current inhibit
10.9 Warranty
The AF0500 Arc-Flash Relay is warranted to be free from defects in material and workmanship for
a period of five years from the date of purchase.
Littelfuse will (at Littelfuse’s option) repair, replace, or refund the original purchase price of a AF0500
that is determined by Littelfuse to be defective if it is returned to the factory, freight prepaid, within
the warranty period. This warranty does not apply to repairs required as a result of misuse,
negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse does not
warrant products repaired or modified by non-Littelfuse personnel.
NOTES:
1
Battery is mounted in an internal socket and should be changed by qualified service personnel
only. Contact your distributor for more information.
2
The AF0500 Arc Flash Relay is currently listed as a protective relay (UL category NRGU) and
complies with the UL508 Industrial Control Equipment standard. UL did not evaluate the functionality
of the arc fault protection afforded by this product. A file review will occur when the requirements for
investigation of arc detection and mitigation systems are developed and additional tests will be
performed if required.
3
AF0500 uses the open source component FreeMODBUS internally. For license, version, and
source-code information please contact opensource@littelfuse.com.
ADDRESS (BASE 1,
PLC MODE) PARAMETER
ACCESS[R/W] DESCRIPTION TERMINAL VALUES
TYPE
DEC HEX
Sensor Input Status (500 - 504)
500 1F4h
500 1F4h Word R Number of light sensors on system. na 4
Bit 0=Not Detected, Bit
1=Detected, Bit2=Tripped,
Bit3= Error (Lost - Has
been detected, but is no
501 1F5h Word R Status of “Sensor 1” 31-34 longer there.)
Bit0=Not Detected,
Bit1=Detected,
Bit2=Tripped, Bit 3= Error
(Lost - Has been detected,
502 1F6h Word R Status of “Sensor 2” 35-38 but is no longer there.)
Bit 0=Not Detected,
Bit1=Detected,
Bit2=Tripped, Bit3= Error
(Lost - Has been detected,
503 1F7h Word R Status of “Sensor 3” 39-42 but is no longer there.)
Bit0=Not Detected,
Bit1=Detected,
Bit2=Tripped, Bit3= Error
(Lost - Has been detected,
504 1F8h Word R Status of “Sensor 4” 43-46 but is no longer there.)
System Status (1100 - 1104)
1100 44Ch
1100 44Ch Word R Number of user-reading status. na 4
Reading: 0=Inactive;
1101 44Dh Word R Supply 1 Present 1-3 1=Active;
Reading: 0=Inactive;
1102 44Eh Word R Supply 2 Present 28-30 1=Active;
DC Supply Voltage (In
1103 44Fh Word R DC Supply Voltage 28-30 Integer Volts)
Reading: 0=No errors;
1=Error - Refer To Error
1104 450h Word R Error na Flags Bitmap
Digital Inputs (1200 - 1207)
Inputs with (optional) cable
1200 4B0h monitoring
1200 4B0h word R Number of Inputs na 7
Reading: 0=Inactive;
1201 4B1h word R Status of Input “RESET” 9-11 1=Active;
Reading: 0=Inactive;
1202 4B2h word R Status of Input “INHIBIT 1” 12-16 1=Active;
Reading: 0=Inactive;
1203 4B3h word R Status of Input “TRIP 1” 13-16 1=Active;
Reading: 0=Inactive;
1204 4B4h word R Status of Input “C/B ON 1” 14-16 1=Active;
Reading: 0=Inactive;
1205 4B5h word R Status of Input “INHIBIT 2” 20-24 1=Active;
Reading: 0=Inactive;
1206 4B6h word R Status of Input “TRIP 2” 21-24 1=Active;
Reading: 0=Inactive;
1207 4B7h word R Status of Input “C/B ON 2” 22-24 1=Active;
ADDRESS (BASE 1,
PLC MODE) PARAMETER
ACCESS[R/W] DESCRIPTION TERMINAL VALUES
TYPE
DEC HEX
Digital and Relay Outputs (1300 - 1307)
1300 514h Status of Physical Outputs
1300 514h Word R Number of Outputs NA 7
Reading: 0=Open;
1301 515h Word R Status on Relay “ERROR” 4-5-6 1=Closed;
Reading: 0=Open;
1302 516h Word R Status on Relay “TRIPPED” 7-8 1=Closed;
Reading: 0=Open;
1303 517h Word R Status of Output “C/B FAIL” 10-11 1=Closed;
Reading: 0=Open;
1304 518h Word R Status of Output “TRIPPED 1” 15-16 1=Closed;
Reading: 0=Open;
1305 519h Word R Status of “IGBT TRIP 1” 18-19 1=Closed;
Reading: 0=Open;
1306 51Ah Word R Status of Output “TRIPPED 2” 23-24 1=Closed;
Reading: 0=Open;
1307 51Bh Word R Status of “IGBT TRIP 2” 26-27 1=Closed;
LED Status (1400 - 1426)
1400 578h Status of LED
1400 578h Word R Number of LED`s NA 26
Bit 0=Off, Bit 1=On, Bit
1401 579h Word R Supply 1 1-2 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1402 57Ah Word R Error 4-5-6 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1403 57Bh Word R Tripped 7-8 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1404 57Ch Word R Reset 9 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1405 57Dh Word R C/B Fault 10 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1406 57Eh Word R Inhibit 1 12 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1407 57Fh Word R Trip 1 13 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1408 580h Word R C/B On 1 14 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1409 581h Word R Tripped 1 15 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1410 582h Word R Trip 1 Red 18-19 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1411 583h Word R Trip 1 Green 18-19 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1412 584h Word R Inhibit 2 20 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1413 585h Word R Trip 2 21 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1414 586h Word R C/B On 2 22 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1415 587h Word R Tripped 2 23 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1416 588h Word R Trip 2 Red 26-27 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1417 589h Word R Trip 2 Green 26-27 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1418 58Ah Word R Supply 2 29-30 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1419 58Bh Word R Sensor 1 Red 31-34 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1420 58Ch Word R Sensor 1 Green 31-34 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1421 58Dh Word R Sensor 2 Red 35-38 2=Flashing
ADDRESS (BASE 1,
PLC MODE) PARAMETER
ACCESS[R/W] DESCRIPTION TERMINAL VALUES
TYPE
DEC HEX
Bit 0=Off, Bit 1=On, Bit
1422 58Eh Word R Sensor 2 Green 35-38 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1423 58Fh Word R Sensor 3 Red 39-42 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1424 590h Word R Sensor 3 Green 39-42 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1425 591h Word R Sensor 4 Red 43-46 2=Flashing
Bit 0=Off, Bit 1=On, Bit
1426 592h Word R Sensor 4 Green 43-46 2=Flashing
Alarms (1500 - 1526)
Internal flags from the last
event - describes where a
1500 5DCh trip came from.
1500 5DCh Word R Number of status flags available. NA 26
Reading: 0=Inactive,
1501 5DDh Word R Sensor 1 Fault 31-34 1=Active
Reading: 0=Inactive,
1502 5DEh Word R Sensor 2 Fault 35-38 1=Active
Reading: 0=Inactive,
1503 5DFh Word R Sensor 3 Fault 39-42 1=Active
Reading: 0=Inactive,
1504 5E0h Word R Sensor 4 Fault 43-46 1=Active
Reading: 0=Inactive,
1505 5E1h Word R Supply 1 Off 1-3 1=Active
Reading: 0=Inactive,
1506 5E2h Word R Supply 2 Off 28-30 1=Active
Reading: 0=Inactive,
1507 5E3h Word R Supply 1 Out Of Spec 1-3 1=Active
Reading: 0=Inactive,
1508 5E4h Word R Supply 2 Out Of Spec 28-30 1=Active
Reading: 0=Inactive,
1509 5E5h Word R Internal I/O supply Error NA 1=Active
Reading: 0=Inactive,
1510 5E6h Word R Internal Sensor Supply Error NA 1=Active
Reading: 0=Inactive,
1511 5E7h Word R CB 1 Feedback Error 14 1=Active
Reading: 0=Inactive,
1512 5E8h Word R CB 2 Feedback Error 22 1=Active
Reading: 0=Inactive,
1513 5E9h Word R Trip Coil 1 Fault 18-19 1=Active
Reading: 0=Inactive,
1514 5Eah Word R Trip Coil 2 Fault 26-27 1=Active
Reading: 0=Inactive,
1515 5EBh Word R Trip Coil 1 Unpowered 18-19 1=Active
Reading: 0=Inactive,
1516 5ECh Word R Trip Coil 2 Unpowered 26-27 1=Active
Reading: 0=Inactive,
1517 5EDh Word R FW Unspecified Fault NA 1=Active
Reading: 0=Inactive,
1518 5EEh Word R FW Drive Not Ready NA 1=Active
Reading: 0=Inactive,
1519 5EFh Word R FW File Not Found NA 1=Active
Reading: 0=Inactive,
1520 5F0h Word R FW Image Wrong Product Name NA 1=Active
Reading: 0=Inactive,
1521 5F1h Word R FW Image No signature Found NA 1=Active
Reading: 0=Inactive,
1522 5F2h Word R FW Image Wrong Size NA 1=Active
Reading: 0=Inactive,
1523 5F3h Word R FW MD5 File Not Found NA 1=Active
ADDRESS (BASE 1,
PLC MODE) PARAMETER
ACCESS[R/W] DESCRIPTION TERMINAL VALUES
TYPE
DEC HEX
Reading: 0=Inactive,
1524 5F4h Word R FW Error MD5 Fault NA 1=Active
Reading: 0=Inactive,
1525 5F5h Word R Ethernet Peer To Peer Alarm NA 1=Active
Reading: 0=Inactive,
1526 5F6h Word R Trip Condition While Inhibited NA 1=Active
0
Arc Detection Time Before Tripping (Effective 1 20,000 ms _________ ms
0.8)
Light Sensor 1
q Sensor Present
q No Sensor Detected
Sensor Status
q Sensor Missing
q Sensor Tripped
Sensor Description Sensor 1 ___________________
q No Change
Change Configuration No Change q No Sensor Expected
q Sensor Expected
Light Sensor 2
q Sensor Present
q No Sensor Detected
Sensor Status
q Sensor Missing
q Sensor Tripped
Sensor Description Sensor 2 ___________________
q No Change
Change Configuration No Change q No Sensor Expected
q Sensor Expected
Light Sensor 3
q Sensor Present
q No Sensor Detected
Sensor Status
q Sensor Missing
q Sensor Tripped
Sensor Description Sensor 3 ___________________
q No Change
Change Configuration No Change q No Sensor Expected
q Sensor Expected
Light Sensor 4
q Sensor Present
q No Sensor Detected
Sensor Status
q Sensor Missing
q Sensor Tripped
Sensor Description Sensor 4 ___________________
q No Change
Change Configuration No Change q No Sensor Expected
q Sensor Expected
GENERAL INSTALLATION
MIN DEFAULT MAX UNIT COMMENTS
SETTINGS
COMMON CONTROL BLOCK
Nothing To Configure
ZONE 1
þ Light Sensor 1 ¨ Light Sensor 1
þ Light Sensor 2 ¨ Light Sensor 2
Zone 1 / TRIP 1 Trips On ¨ Light Sensor 3 ¨ Light Sensor 3
¨ Light Sensor 4 ¨ Light Sensor 4
¨ CB Feedback Failure ¨ CB Feedback Failure
Trip Input
Enabled Enabled q Enabled q Disabled
CB ON Input
Enabled Enabled q Enabled q Disabled
q CB is conducting power when
CB is conducting power when input is pulled low.
Function
input is floating. q CB is conducting power when
input is floating.
Trip Output
q Shunt Coil (Trips When
Shunt Coil (Trips When Powered)
Circuit Breaker Type
Powered) q Undervoltage Coil (Closed
While Powered)
Circuit Breaker Pulse Time 1 1 5 seconds
Report An Error If Trip Coil Is Not
Enabled q Enabled q Disabled
Detected
ZONE 2
¨ Light Sensor 1 ¨ Light Sensor 1
¨ Light Sensor 2 ¨ Light Sensor 2
Zone 2 / TRIP 2 Trips On þ Light Sensor 3 ¨ Light Sensor 3
þ Light Sensor 4 ¨ Light Sensor 4
¨ CB Feedback Failure ¨ CB Feedback Failure
Trip Input
Enabled Enabled q Enabled q Disabled
CB ON Input
Enabled Enabled q Enabled q Disabled
¨ CB is conducting power when
CB is conducting power when input is pulled low.
Function
input is floating. ¨ CB is conducting power when
input is floating.
Trip Output
¨ Shunt Coil (Trips When
Shunt Coil (Trips When Powered)
Circuit Breaker Type
Powered) ¨ Undervoltage Coil (Closed
While Powered)
Circuit Breaker Pulse Time 1 1 5 seconds
Report An Error If Trip Coil Is Not
þ Enabled q Enabled q Disabled
Detected
COMMUNICATION
¨ Manual Fixed IP
TCP IP Address þ Manual Fixed IP ¨ Automatic (DHCP)
¨ Automatic (AUTO IP)
Manual IP Address 192.168.0.99 ___.___.___.___
TCP/IP Subnet Mask 255.0.0.0 ___.___.___.___
TCP/IP Default Gateway 192.168.0.1 ___.___.___.___
GENERAL INSTALLATION
MIN DEFAULT MAX UNIT COMMENTS
SETTINGS
ADVANCED
Possibility To Reset Configuration
And Drives – No Setup Parameters
ALARMS
Shows Currently Standing Alarms
Tripping from light and inputs signals will work due to the redundant hardware, but with a simpler
setup according to the table below. The ERROR relay will be in the correct state, indicating a unit
error. Greyed out inputs and outputs are not read or driven.
Output TRIP COIL 1 TRIPPED TRIP COIL 2 TRIPPED TRIPPED C/B FAIL ERROR
Input (NOTE 1) Output 1 (NOTE 1) Output 2 Relay Output Relay
INHIBIT 1 X
TRIP 1 X X X
C/B FB 1 X
INHIBIT 2 X
TRIP 2 X X X
C/B FB 2 X
RESET X
RESET Button X
SENSOR 1 X X X X X
SENSOR 2 X X X X X
SENSOR 3 X X X X X
SENSOR 4 X X X X X
NOTE 1: When SW runs these outputs are pulsed – When controlled via redundant HW, they are
held statically as long as the sensor reports light over the threshold, only protected by a thermal
protection circuit (IGBT will disable when too hot).
NOTE 2: All light sensor inputs trip both TRIP COILS – normal zone setup is not respected.
APPENDIX D
AF0500 REVISION HISTORY
HARDWARE REVISION
MANUAL RELEASE
MANUAL REVISION (REVISION NUMBER ON FIRMWARE REVISION
DATE
PRODUCT LABEL)
December 8, 2017 0-E-120817
April 8, 2016 0-D-040816
1 1.00.01
September 16, 2015 0-C-091615
June 1, 2015 0-B-060115
March 2, 2015 0-A-030215 0 1.00.00