PCS-9671S X Selection Guide en Overseas General X R1.03
PCS-9671S X Selection Guide en Overseas General X R1.03
PCS-9671S X Selection Guide en Overseas General X R1.03
NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR
trademarks may be used without written permission. NR products appearing in this document may
be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and
benefits afforded under P.R. China and international copyright and patent laws in its products,
including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is
licensed to use this document as well as all intellectual property rights owned or held by NR
Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how,
trade secrets, trademarks and trade names, service marks, design rights, database rights and
rights in data, utility models, domain names and all similar rights.
The information in this document is provided for informational use only and does not constitute a
legal contract between NR and any person or entity unless otherwise specified. Information in this
document is subject to change without prior notice.
To the extent required the products described herein meet applicable IEC and IEEE standards,
but no such assurance is given with respect to local codes and ordinances because they vary
greatly.
Although every reasonable effort is made to present current and accurate information, this
document does not purport to cover all details or variations in equipment nor provide for every
possible contingency to be met in connection with installation, operation, or maintenance. Should
further information be desired or should particular problems arise which are not covered
sufficiently for your purposes, please do not hesitate to contact us.
Preface
Preface
Warranty
NR can provide up to 10-year warranty for this product. For warranty details, please consult the
manufacturer or agent for warranty information.
Document Structure
This manual is mainly for the overview of the application and functions of the PCS-9671S, and it
provides the configuration of software and hardware information for ordering. An overview of each
manual section and section topics follows.
2 Guide of PCS-Torch
Introduces the main functions of PCS-Torch, including create new project, create new device,
export MOT and Manage MOT library, MOT configuration interface and the structure of the
ordering code.
3 MOT Information
Introduces the meaning and options of each field, and gives a detailed description about the
selection rule for the application, the firmware, the software, the hardware, the chassis structure
and so on.
Corresponding Version
Date Description of change
Document Software
R1.02 R1.12 2020-12-09 Added reactor current differential protection function 87R.
List of Figures
1.1 General
PCS-9671S transformer relay has been designed specifically for the protection of various type
1
power transformers (up to 3 measuring points), including two-winding transformers, three-winding
transformers, auto-transformers, as well as reactors. Ancillary functions of fault diagnostic,
disturbance records, event records and communication function are integrated in the device. With
its modular structure, flexibility and the powerful PCS-Studio engineering tool, PCS-9671S offers
future-oriented system solutions with high investment security and low operating costs.
Self diagnosis
Powerful faults recording (max. buffer for 10,000 sampled points at 1.2 or 9.6 kHz)
Event Recorder including 1024 disturbance records, 1024 binary events, 1024
supervision events, 256 control logs and 1024 device logs.
Disturbance recorder including 64 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Modbus, DNP3.0, IEC 60870-5-103, IEC 61850 Ed.1 & Ed.2, IEC 61850 MMS Server,
IEC 61850-8-1 GOOSE, IEC 62439 Parallel Redundancy Protocol (PRP), IEC 62439
High-availability Seamless Ring (HSR) Redundancy Protocol, IEEE 802.1w Rapid
Spanning Tree Protocol (RSTP).
Two RS-485 serial ports for communication, the second one could be used as a RS-232
Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and
set-point adjustment
Push buttons for open/close, switch for selection between local and remote control, and
user's login and logout authority management
Configuration tool—PCS-Studio
Clock synchronization
IRIG-B: IRIG-B via RS-485 differential level, TTL level, BNC or ST-connector port
PPS: Pulse per second (PPS) via RS-485 differential level, binary input, BNC or
ST-connector port
IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
Cyber security
NERC CIP
IEC 62351
IEC 62443
1 IEEE 1686
HVS
52
*
3CT
64 50/ 50/
87T
REF 51P 51G
1CT
3CT
*
52
LVS
HVS
52
3CT
* 1
64 50/ 50/
87T
REF 51P 51G
MVS
*
52 1CT
*
3CT
3CT
*
52
LVS
HVS
52
*
3CT
64 50/ 50/
MVS 87T
REF 51P 51G
*
52
*
3CT 1CT
3CT
*
52
LVS
Bus
1 52
50/ 50/
87R
51P 51G
*
3 CT
3 CT
*
1 CT
*
2 Guide of PCS-Torch
Table of Contents
List of Figures
2.1 Introduction
The PCS-Torch is an auxiliary ordering tool for the PCS S series products of NR Electric. It is
recommended to run on a MS Windows 7/10 operating system.
This tool helps to create a complete order code with detailed specifications based on the selection
of functional options such as software and hardware. This tool supports engineering methods to
2
create models of various types of the PCS S series protection, measurement and control devices
in power substations, and can view or select device hardware and software configurations before
sales. Meanwhile, it could preview device rear modules, and import or export the device
configuration results in the form of Excel table.
The model library of all the types of device could be updated online automatically or offline
manually to facilitate the access of the latest functions of PCS S series devices.
Button Remark
By MOT lib
In the pop-up dialog box, enter the device name, select the device type and MOT version or
firmware version.
Select the main MOT version (R1, R2……) so that PCS-Torch will automatically search
the latest archived firmware version corresponding to such main MOT version, and
create the MOT configuration.
Main MOT version is compatible with all firmware versions that begin with
main MOT version (except disabled firmware version). For example, if
main MOT version is "R1", it is compatible with all firmware version R1.**.
Input the firmware version so that PCS-Torch will create the device MOT configuration
according to such firmware version automatically except that the input firmware version
is disabled or does not exist.
By MOT code
PCS-Torch will automatically search the latest archived firmware version corresponding
to main MOT version, and create the MOT configuration.
PCS-Torch will create the device MOT configuration according to such firmware version
automatically except that the input firmware version is disabled or does not exist.
PCS-Torch can export MOT information of a whole substation, and supports the operations of
copy, paste and rename.
Right-click the menu under the project (substation) node, and select the menu item "Export
station information". An excel file that includes MOT codes and modules configuration
information of all devices in the project will be generated, as shown below.
In the MOT configuration interface, the integral ordering code is displayed at the top. The detailed
MOT information is shown in a row/column format. The first column indicates MOT item, the
second column indicates available options corresponding to each item, the third column indicates
the description about the chosen option, and the fourth column indicates the ordering code
corresponding to the chosen option.
Double-click the cell in the "Option" column to switch the option from drop-down box. When the
contents of the cell in the "Option" column is changed, the corresponding contents of the
"Description" and "Code" columns in the same row are changed synchronously, and the
corresponding bit of ordering code is also changed synchronously. There is possibly a mandatory
binding rule or mutual exclusion rule among MOT items. The option will be chosen fixedly if an
option's mandatory binding rule is activated. The option will be hidden if an option's mutual
exclusion rule is activated. For an option that is not applicable, the row is grey and not selectable.
There is a corresponding relationship between MOT item and the ordering code. When one bit of
the ordering code is chosen, the corresponding MOT item will be highlighted. When one MOT
item is chosen, the corresponding bit of ordering code will be highlighted.
Click the button "Default", all options will be chosen as default value directly. Click the button
"Import Excel" or "Import Code", an existing MOT file (*.xls) or an MOT code can be directly
imported into the corresponding device type of PCS-Torch.
A field: indicates firmware type, which can be standard version or regional version
PWR field: indicates the voltage level of power supply plug-in module
MOT version
H field
PWR field
C field
S field
R field
A field
U field
Device type
After finishing MOT (Market Ordering Table) configuration, click the button “Complete” to display
the currently selected configuration information, including the ordering code and the device′s
hardware configuration, is shown as below:
Button Remark
Export MOT (Market Ordering Table) and device′s hardware configuration in Excel file format
Both MOT and device′s hardware configuration can be exported in Excel file format, as shown in
figures below.
Exported MOT
2
After finishing MOT configuration, the rear view of the device based on selected information can
be displayed. The device′s hardware configuration is displayed graphically (including Slot No.,
Module ID, and total slot numbers), as shown in the figure below.
The latest MOT library is included when PCS-Torch is released. The MOT library contains MOT
templates of each device, which are stored in the directory according to the device type. Each
directory contains all historical versions of the device for the MOT template. The path of MOT
library is "installation directory→PCS-Torch→motLib". There are two methods to upgrade the MOT
Firstly, PCS-Torch reads a list of MOT templates for all devices from the server, and compares
them with local MOT library. The user can select the MOT template that needs to be updated, and
PCS-Torch downloads the corresponding MOT template file from the server.
It takes a long time to update the MOT library by connecting to the server, and the user can
directly import the latest MOT library if the network conditions are not good (The latest MOT
template library can be gained by mail firstly).
3 MOT Information
Table of Contents
3.5.2 Language............................................................................................................................3-2
3.8.2 PRP/HSR..........................................................................................................................3-10
3.5.1 Software
The option is used to select the required protection functions, which is used in conjunction with the
application scenario option. Different options correspond with different combinations of protection
functions, which can be viewed through the button "Software Functions" in PCS-Torch.
3.5.2 Language
The option is used to select other supported language. "Chinese" is supported fixedly. "English",
"English + French", "English + Russian" or "English + Spanish" is available.
3.5.3 Protocol
The option is used to select the supported protocol for communication with SCADA system. There
are several kinds of protocols, including IEC103, DNP3.0, Modbus and IEC61850.
"Basic (IEC 60870-5-103 + DNP3.0 + Modbus)": includes IEC 60870-5-103, DNP3.0 and
Modbus.
"Basic + IEC 61850 (Edition 1.0 or Edition 2.0)": includes IEC 60870-5-103, DNP3.0, Modbus
and IEC 61850, and full compatibility between IEC 61850 Edition 1.0 and 2.0.
The option is used to select the case size. The device supports one of case size: "6U 1/3 19" (6U
The 6U 1/3 chassis supports 15 configurable LEDs, and it provides 3 slots (Slot2~Slot4) for
analogue input (AI) module and extended input/output (I/O) modules, the CPU module is fixed at
slot 1, and the power supply (PWR) module is fixed at slot P1.
When the installation mode chooses "Rack", please communicate with the
manufacturer to confirm the different installation accessories.
1. Flush Mounting
2. Semi-flush Mounting
3. Rack Mounting
4. Wall Mounting
5. Surface Mounting
The option is used to select whether or not the harsh environment conformal coating treatment is
needed. If "Required" is selected, the harsh environment conformal coating treatment for the
whole device will be done before delivery.
"0.8~4mm2 lead (26-pin connector, ring ferrule, IP10)": 0.8~4mm2 lead, 26-pin screw
terminal with protection class IP10
"0.8~4mm2 lead (26-pin connector, ring ferrule, IP20)": 0.8~4mm2 lead, 26-pin screw
terminal with protection class IP20
"0.8~2.5mm2 lead (36-pin connector, pin ferrule, IP20)": 0.8~2.5mm2 lead, 36-pin (two
18-pin) screw terminal with protection class IP20 3
The appearance of the terminals are as below.
IP20 (0.8~2.5mm2)
The power supply module supports external power supply input of 110Vdc~250Vdc /
100Vac~250Vac or 24Vdc~60Vdc, and provides 9 binary inputs and 6 binary outputs (5NO+1NC,
NC contact is output contact of the device failure).
communication ports, the number of binary inputs and outputs, the number of AC analogs, and so
on. Different case size can support different hardware resources.
3.8.2 PRP/HSR
The option is used to determine whether or not PRP/HSR networking mode is supported.
3.8.3 Slot02
The option is used to select the I/O module located in slot No.2, and is chosen as "12CT (1A/5A)"
fixedly, meaning 12 AC current inputs, the secondary rated current is adaptive between 1A and
5A.
3.8.4 Slot03
Currently, the option is used as reserved bit and it is chosen as "Not required" fixedly.
3.8.5 Slot04
This option is used to select the extended I/O module located in slot No.4.
3
"Not required": the extended I/O module located in slot No.4 is not required.
"25 BI (Common negative supply)": 25 binary inputs share the common negative input of
power supply, and the rated voltage of binary input can be 24Vdc, 48Vdc, 110Vdc, 125Vdc,
220Vdc, 250Vdc, 110Vac or 220Vac, which can be set through the settings.
"13 BO (Normal, NO)":13 normal binary outputs, normally open contact (NO).
"13 BO (Normal, 11 NO + 2 NC)":13 normal binary outputs, 11 normally open contacts (NO)
and 2 normally closed contacts (NC).
"13 BI (Independent negative supply, settable conducting mode by high power with
constant current drain)": 13 binary inputs with independent negative supply terminals and
the rated voltage of binary input can be 24Vdc, 48Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc,
110Vac or 220Vac, which can be set through the settings. The conducting mode by high
power with constant current drain of binary inputs could be enabled by setting. The
instantaneous active power rises along with the voltage during such mode, so as to avoid
mistaken signal.
"32 BI (2 groups, each group share 1 common negative supply)": 32 binary inputs with
two 18-pin connectors, BI01~BI16 share one common negative input of power supply and
BI17~BI32 share another common negative input of power supply.
"17 BO (Normal, 15 NO + 2 NC/NO)": 17 normal binary outputs, the first 15 BOs are normally
open contact. The last 2 BOs are normally closed/open contacts, and each BO has 3
terminals, and the normally open contact and normally closed contact share one common
terminal.
"14 BI (Independent negative supply, settable conducting mode by high power with
constant current drain)": 14 binary inputs with independent negative supply terminals and
the rated voltage of binary input can be 24Vdc, 48Vdc, 110Vdc, 125Vdc, 220Vdc, 250Vdc,
110Vac or 220Vac, which can be set through the settings. The conducting mode by high
power with constant current drain of binary inputs could be enabled by setting. The
3 instantaneous active power rises along with the voltage during such mode, so as to avoid
mistaken signal.