System Psychrometrics For NIVEL PB - Zona 1

You might also like

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 1

System Psychrometrics for NIVEL PB - Zona 1

Project Name: H2N SAN ANTONIO 09/14/2018 


Prepared by: EMI 10:14a.m. 

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet -3,9 0,00243 195 400 -3495 -1745
Vent - Return Mixing Outlet -3,9 0,00243 195 400 - -
Central Heating Coil Outlet 36,2 0,00243 195 400 5731 -
Supply Fan Outlet 36,2 0,00243 195 400 0 -
Humidifier Outlet 36,2 0,00743 195 400 - 1745
Cold Supply Duct Outlet 36,2 0,00743 195 400 - -
Zone Air - 20,6 0,00743 195 400 -2236 0
Return Plenum Outlet 20,6 0,00743 195 400 0 -

    Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 0,733 W/(L/s-K)
    Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 1789,9 W/(L/s)
    Site Altitude = 4013,9 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -2285 Heating -2236 20,6 195 400 0 0

Hourly Analysis Program v.4,4 Page 1 of 1