List of Quantity for Sub-Station PS2

Item
ID Descriptions Unit Qty.
No.
1 Fire Detecting Equip. Complete Effective Fire Detecting Equip.. [6] No. Set
2 Earthing System Complete Effective Earthing System. [7] No. Set
Power Transformer 11/0.4kV;250 kVA with Thermal
3 T-LPS2 indicator, Buchholz relay and Differential relay with the No. 1
necessary current transformers and accessories.
Main Panel (11 kV) No. 1
Indoor (Bus Coupler + Bus Riser) Type Vacuum or SF6
Metal Clad Switchgear panel (11kV, 1200A, 31.5 kA for
Bus Coupler-CB-PS2-1 1s)[1] with Bus Bars-1200A,Over Load and SC Relays No. Set
(11kV) : to be set in the range (400-600)A for Over
Load and 5*Ir for SC.

Earth Busbar Earth Busbar: 500A No. 1


Indoor Incoming Feeder Type Vacuum or SF6 Metal
Clad Switchgear panel (11kV, 1200A, 31.5 kA for
CB-PS2-1 1s)[1] with one isolator switch, Bus Bars-1200A, HVMU, No. 1
Over Load and SC Relays (11kV) : to be set in the
range (400-600)A for Over Load and 5*Ir for SC.
Indoor Incoming Feeder Type Vacuum or SF6 Metal
Clad Switchgear panel (11kV, 1200A, 31.5 kA for
CB-PS2-2 1s)[1] with one isolator switch, Bus Bars-1200A, HVMU, No. 1
Over Load and SC Relays (11kV) : to be set in the
range (400-600)A for Over Load and 5*Ir for SC.
Indoor Motor Feeder Type Vacuum or SF6 Metal Clad
4 Switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with
CB-PS2-3 one isolator switch, Bus Bars-1200A, HVMU, Over No. 1
Load and SC Relays (11kV) : to be set in the range
(150-255)A for Over Load and 5*Ir for SC.
Indoor Motor Feeder Type Vacuum or SF6 Metal Clad
Switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with
CB-PS2-4 one isolator switch, Bus Bars-1200A, HVMU, Over No. 1
Load and SC Relays (11kV) : to be set in the range
(150-255)A for Over Load and 5*Ir for SC.
Indoor Capacitor Feeder Type Vacuum or SF6 Metal
Clad Switchgear panel (11kV, 630A, 31.5 kA for 1s)[1]
CB-PS2-5 with one isolator switch, Bus Bars-1200A, HVMU, Over No. 1
Load and SC Relays (11kV) : to be set in the range (45-
70)A for Over Load and 5*Ir for SC.
Indoor Capacitor Feeder Type Vacuum or SF6 Metal
Clad Switchgear panel (11kV, 630A, 31.5 kA for 1s)[1]
CB-PS2-6 with one isolator switch, Bus Bars-1200A, HVMU, Over No. 1
Load and SC Relays (11kV) : to be set in the range (45-
70)A for Over Load and 5*Ir for SC.

83
Indoor Motor Feeder Type Vacuum or SF6 Metal Clad
Switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with
CB-PS2-7 one isolator switch, Bus Bars-1200A, HVMU, Over No. 1
Load and SC Relays (11kV) : to be set in the range
(150-255)A for Over Load and 5*Ir for SC.
Indoor Motor Feeder Type Vacuum or SF6 Metal Clad
Switchgear panel (11kV, 630A, 31.5 kA for 1s)[1] with
CB-PS2-8 one isolator switch, Bus Bars-1200A, HVMU, Over No. 1
Load and SC Relays (11kV) : to be set in the range
(150-255)A for Over Load and 5*Ir for SC.
Indoor Auxiliary Transformer Feeder Type Vacuum or
SF6 Metal Clad Switchgear panel (11kV, 630A, 31.5
CB-PS2-9 kA for 1s)[1] with one isolator switch, Bus Bars-1200A, No. 1
HVMU, Over Load and SC Relays (11kV) : to be set in
the range (6-14)A for Over Load and 5*Ir for SC.

R Multi-Function Protection Relay (Optional) No. 4


SST Solid State Tripe Relay to be used with ZSCT. No. 4
ZSCT Zero sequence current transformer. No. 4
Main Panel ( 0.4kV ) consists of: No. 1
Bus-LPS2 Bus Bars: 3phase, 0.4kV,800A No. Set
Indoor Load Feeder Type Air Circuit Breaker ( 0.4kV,
CB-PS2-10 500A,100 kA ) [2]. No. 1
5
Low Voltage Measuring Unit (0.4kV): A; V; W; Wh;
LVMU P.F.; and f with all CTs, VTs and indicators No. Set

LUMP-PS2 Low Voltage Panel for Substation PS2 Services. No. 1


Earth Busbar Earth Busbar: 500A No. 1
6 Cable-PS2-1 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 5
7 Cable-PS2-2 XLPE, 1-3/C, 11kV 150 mm2, Cu m.l. 20
8 Cable-PS2-3 XLPE, 1-3/C, 11kV,50 mm2, Cu m.l. 5
9 Cable-PS2-4 XLPE, 1-3/C, 11kV,50 mm2, Cu m.l. 5
10 Cable-PS2-5 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 5
11 Cable-PS2-6 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 5
12 Cable-PS2-7 XLPE, 1-3/C, 11kV,50 mm2, Cu m.l. 20
13 Cable-PS2-8 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 30
14 Cable-PS2-9 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 30
15 Cable-PS2-10 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 30
16 Cable-PS2-11 XLPE, 1-3/C, 11kV,150 mm2, Cu m.l. 30
17 Cable-PS2-11 XLPE, 1-3/C, 0.4kV,150 mm2, Cu m.l. 20
17 CAP-PS2-1 Variable Capacitor Bank (800kVAR 11 kV) No. 1
18 CAP-PS2-2 Variable Capacitor Bank (800kVAR 11 kV) No. 1
19 PS2-1-SS Soft-Starter with Operation Contactor& Phase Failure No. 1
20 PS2-2-SS Soft-Starter with Operation Contactor& Phase Failure No. 1
21 PS2-3-SS Soft-Starter with Operation Contactor& Phase Failure No. 1
22 PS2-4-SS Soft-Starter with Operation Contactor& Phase Failure No. 1
23 PS2-1 High Voltage Induction Motor,2240kW,11kV, 1500rpm No. 1
24 PS2-2 High Voltage Induction Motor,2240kW,11kV, 1500rpm No. 1

84
25 PS2-3 High Voltage Induction Motor,2240kW,11kV, 1500rpm No. 1
26 PS2-4 High Voltage Induction Motor,2240kW,11kV, 1500rpm No. 1

Note: The sub-station must be in accordance with IEC standards; the enclosed single
line diagram; [1-3] description given in Appendix[ C ]; [4-7] description given in
Appendix[ B ] and RMU specifications given in Appendix [ D ].